Fronius Type verification test sheet G98 NI Fronius Symo GEN24 6.0 Certificate [EN]

ENA Engineering Recommendation G98/NI
Manufacturer´s reference number
Fronius Symo GEN24
Micro-generator technology
transformerless
Manufacturer name
Fronius International GmbH
Address
Guenter Fronius Str 1 4600 Wels-Thalheim, Austria
Tel
+43-7242-241-0
Fax
+43-7242-241-224
E:mail
pv@fronius.com
Web site
www.fronius.com
Registered Capacity, use separate sheet if more than one connection option.
Connection Option
--
kW single phase, single, split or three phase system
6
kW three phase
--
kW two phases in three phase system
--
kW two phases split phase system
Signed
On behalf of
Fronius International GmbH
Issue 1 – 2019
MATERIALS & SAFETY - R&D TR 3 1 3 1 5 page 1 of 18
FORM C TYPE TEST VERIFICATION REPORT
@BCL@FC088B8B.doc Backup: Fronius Symo GEN24 G98/NI
ENA Engineering Recommendation G98/NI
Operating Range: This test should be carried out as specified in EN 50438 D.3.1. Active Power shall be recorded every second. The tests will verify that the Micro-generator
can operate within the required ranges for the specified period of time. The Interface Protection shall be disabled during the tests. In case of a PV Micro-generator the PV primary source may be replaced by a DC source. In case of a full converter Micro-generator (e.g. wind) the primary source and the prime
mover Inverter/rectifier may be replaced by a DC source. In case of a DFIG Micro-generator the mechanical drive system may be replaced by a test
bench motor.
Test 1 Voltage = 85% of nominal (195.5 V) Frequency = 47.5 Hz Power factor = 1 Period of test 90 minutes
Test 2 Voltage = 110% of nominal (253 V). Frequency = 51.5 Hz Power factor = 1 Period of test 90 minutes
Test 3 Voltage = 110% of nominal (253 V). Frequency = 52.0 Hz Power factor = 1 Period of test 15 minutes
Remark: During the tests 1, 2 and 3 the unit does not disconnect, tests have been passed.
Issue 1 – 2019
MATERIALS & SAFETY - R&D TR 3 1 3 1 5 page 2 of 18
@BCL@FC088B8B.doc Backup: Fronius Symo GEN24 G98/NI
ENA Engineering Recommendation G98/NI
Power Quality – Harmonics: These tests should be carried out as specified in BS EN
61000-3-2. The chosen test should be undertaken with a fixed source of energy at two power levels a) between 45 and 55% and b) at 100% of Registered Capacity. The test requirements are specified in Annex A1 A.1.3.1 (Inverter connected) or Annex A2 A.2.3.1 (Synchronous).
Micro-generator tested to BS EN 61000-3-2 Phase 1
Micro-generator rating per phase (rpp)
2,074
kW
Harmonic
At 45-55% of Registered
Capacity
100% of Registered
Capacity
Measured Value MV in Amps
Measured Value MV in Amps
Limit in BS EN 61000­3-2 in Amps
Higher limit for odd harmonics 21 and above
2
0.000
0.003
1.080
3
0.001
0.001
2.300
4
0.002
0.002
0.430
5
0.002
0.001
1.140
6
0.001
0.001
0.300
7
0.003
0.003
0.770
8
0.000
0.001
0.230
9
0.001
0.000
0.400
10
0.000
0.001
0.184
11
0.017
0.013
0.330
12
0.000
0.000
0.153
13
0.014
0.013
0.210
14
0.000
0.000
0.131
15
0.000
0.000
0.150
16
0.000
0.000
0.115
17
0.008
0.012
0.132
18
0.000
0.000
0.102
19
0.006
0.012
0.118
Issue 1 – 2019
MATERIALS & SAFETY - R&D TR 3 1 3 1 5 page 3 of 18
@BCL@FC088B8B.doc Backup: Fronius Symo GEN24 G98/NI
ENA Engineering Recommendation G98/NI
20
0.000
0.000
0.092
21
0.001
0.000
0.107
0.160
Issue 1 – 2019
MATERIALS & SAFETY - R&D TR 3 1 3 1 5 page 4 of 18
@BCL@FC088B8B.doc Backup: Fronius Symo GEN24 G98/NI
ENA Engineering Recommendation G98/NI
22
0.000
0.000
23
0.004
0.011
0.147
24
0.000
0.000
25
0.003
0.011
0.135
26
0.000
0.001
27
0.001
0.000
0.124
28
0.000
0.000
29
0.005
0.011
0.117
30
0.000
0.000
31
0.006
0.010
0.109
32
0.000
0.001
33
0.000
0.000
0.102
34
0.000
0.000
35
0.005
0.010
0.096
36
0.000
0.000
37
0.006
0.009
0.091
38
0.000
0.000
39
0.000
0.001
0.087
40
0.000
0.000
Note the higher limits for odd harmonics 21 and above are only allowable under certain conditions, if these higher limits are utilised please state the exemption used as detailed in part 6.2.3.4 of BS EN 61000-3-2 in the box below.
Issue 1 – 2019
MATERIALS & SAFETY - R&D TR 3 1 3 1 5 page 5 of 18
@BCL@FC088B8B.doc Backup: Fronius Symo GEN24 G98/NI
ENA Engineering Recommendation G98/NI
Power Quality – Harmonics: These tests should be carried out as specified in BS EN
61000-3-2. The chosen test should be undertaken with a fixed source of energy at two power levels a) between 45 and 55% and b) at 100% of Registered Capacity. The test requirements are specified in Annex A1 A.1.3.1 (Inverter connected) or Annex A2 A.2.3.1 (Synchronous).
Micro-generator tested to BS EN 61000-3-2 Phase 2
Micro-generator rating per phase (rpp)
2,046
kW
Harmonic
At 45-55% of Registered
Capacity
100% of Registered
Capacity
Measured Value MV in Amps
Measured Value MV in Amps
Limit in BS EN 61000­3-2 in Amps
Higher limit for odd harmonics 21 and above
2
0.00
0.002
1.080
3
0.01
0.003
2.300
4
0.00
0.000
0.430
5
0.00
0.001
1.140
6
0.00
0.000
0.300
7
0.00
0.002
0.770
8
0.00
0.001
0.230
9
0.00
0.001
0.400
10
0.00
0.000
0.184
11
0.02
0.014
0.330
12
0.00
0.000
0.153
13
0.01
0.013
0.210
14
0.00
0.000
0.131
15
0.00
0.000
0.150
16
0.00
0.000
0.115
17
0.01
0.013
0.132
18
0.00
0.000
0.102
19
0.01
0.013
0.118
Issue 1 – 2019
MATERIALS & SAFETY - R&D TR 3 1 3 1 5 page 6 of 18
@BCL@FC088B8B.doc Backup: Fronius Symo GEN24 G98/NI