ENA Engineering Recommendation G98
All Micro-generators connected to the DNO Distribution Network shall be Fully Type Tested. This form
is the Manufacturer’s declaration of compliance with the requirements of G98.
This form should be used when making a Type Test submission to the Energy Networks Association
(ENA).
If the Micro-generator is Fully Type Tested and already registered with the ENA Type Test Verification
Report Register, the Installation Document should include the Manufacturer’s Reference Number (the
Product ID), and this form does not need to be submitted.
Where the Micro-generator is Fully Type Tested and not registered with the ENA Type Test
Verification Report Register this form needs to be completed and provided to the DNO, to confirm that
the Micro-generator has been tested to satisfy the requirements of this EREC G98.
Manufacturer´s reference number
Micro-generator technology
Fronius International GmbH
Guenter Fronius Str 1
4600 Wels-Thalheim, Austria
Registered Capacity,
use separate sheet if
more than one
connection option.
kW single phase, single, split or three phase system
kW two phases in three phase system
kW two phases split phase system
Manufacturer Type Test declaration. - I certify that all products supplied by the company with the above
Fully Type Tested reference number will be manufactured and tested to ensure that they perform as
stated in this document, prior to shipment to site and that no site modifications are required to ensure that
the product meets all the requirements of EREC G98.
Fronius International GmbH
Note that testing can be done by the Manufacturer of an individual component or by an external test
house.
Where parts of the testing are carried out by persons or organisations other than the Manufacturer then
that person or organisation shall keep copies of all test records and results supplied to them to verify that
the testing has been carried out by people with sufficient technical competency to carry out the tests.
Issue 1 – Amendment 4 2019
MATERIALS & SAFETY - R&D TR 2 9 79 1 page 1 of 18
FORM C TYPE TEST VERIFICATION REPORT
@BCL@DC0AE06F.doc
Backup: Fronius Symo GEN24 G98

ENA Engineering Recommendation G98
Operating Range: This test should be carried out as specified in EN 50438 D.3.1.
Active Power shall be recorded every second. The tests will verify that the Micro-generator
can operate within the required ranges for the specified period of time.
The Interface Protection shall be disabled during the tests.
In case of a PV Micro-generator the PV primary source may be replaced by a DC source.
In case of a full converter Micro-generator (e.g. wind) the primary source and the prime
mover Inverter/rectifier may be replaced by a DC source.
In case of a DFIG Micro-generator the mechanical drive system may be replaced by a test
bench motor.
Test 1
Voltage = 85% of nominal (195.5 V)
Frequency = 47.5 Hz
Power factor = 1
Period of test 90 minutes
Test 2
Voltage = 110% of nominal (253 V).
Frequency = 51.5 Hz
Power factor = 1
Period of test 90 minutes
Test 3
Voltage = 110% of nominal (253 V).
Frequency = 52.0 Hz
Power factor = 1
Period of test 15 minutes
Remark: During the tests 1, 2 and 3 the unit does not disconnect, tests have been passed.
Issue 1 – Amendment 4 2019
MATERIALS & SAFETY - R&D TR 2 9 79 1 page 2 of 18
@BCL@DC0AE06F.doc
Backup: Fronius Symo GEN24 G98

ENA Engineering Recommendation G98
Power Quality – Harmonics: These tests should be carried out as specified in BS EN
61000-3-2. The chosen test should be undertaken with a fixed source of energy at two power
levels a) between 45 and 55% and b) at 100% of Registered Capacity. The test
requirements are specified in Annex A1 A.1.3.1 (Inverter connected) or Annex A2 A.2.3.1
(Synchronous).
Micro-generator tested to BS EN 61000-3-2 Phase 1
Micro-generator rating per phase (rpp)
At 45-55% of Registered
Capacity
100% of Registered
Capacity
Measured
Value MV in
Amps
Measured
Value MV in
Amps
Limit in
BS EN
610003-2 in
Amps
Higher limit for
odd harmonics
21 and above
Issue 1 – Amendment 4 2019
MATERIALS & SAFETY - R&D TR 2 9 79 1 page 3 of 18
@BCL@DC0AE06F.doc
Backup: Fronius Symo GEN24 G98

ENA Engineering Recommendation G98
Issue 1 – Amendment 4 2019
MATERIALS & SAFETY - R&D TR 2 9 79 1 page 4 of 18
@BCL@DC0AE06F.doc
Backup: Fronius Symo GEN24 G98

ENA Engineering Recommendation G98
Note the higher limits for odd harmonics 21 and above are only allowable
under certain conditions, if these higher limits are utilised please state the
exemption used as detailed in part 6.2.3.4 of BS EN 61000-3-2 in the box
below.
Issue 1 – Amendment 4 2019
MATERIALS & SAFETY - R&D TR 2 9 79 1 page 5 of 18
@BCL@DC0AE06F.doc
Backup: Fronius Symo GEN24 G98

ENA Engineering Recommendation G98
Power Quality – Harmonics: These tests should be carried out as specified in
BS EN 61000-3-2. The chosen test should be undertaken with a fixed source of
energy at two power levels a) between 45 and 55% and b) at 100% of
Registered Capacity. The test requirements are specified in Annex A1 A.1.3.1
(Inverter connected) or Annex A2 A.2.3.1 (Synchronous).
Micro-generator tested to BS EN 61000-3-2 Phase 2
Micro-generator rating per
phase (rpp)
At 45-55% of
Registered Capacity
100% of Registered
Capacity
Measured
Value MV
in Amps
Measured
Value MV
in Amps
Limit
in BS
EN
610003-2 in
Amps
Higher limit
for odd
harmonics
21 and
above
Issue 1 – Amendment 4 2019
MATERIALS & SAFETY - R&D TR 2 9 79 1 page 6 of 18
@BCL@DC0AE06F.doc
Backup: Fronius Symo GEN24 G98