Fronius Type Test result sheet CER/06/190 Fronius IG Plus 35 V-1 Certificate [EN]

CONSULTATION PAPER CER/06/190
Manufacturer:
Fronius International GmbH
Tel: +43-7242-241-0
Address:
Guenter Fronius Str 1 4600 Wels-Thalheim, Austria
Fax: +43-7242-241-224
Name and address of test house
Fronius R&D Laboratories, Fronius International GmbH, Guenter Fronius Str 1, A-4600 Wels-Thalheim, Austria
Telephone number
+43-7242-241-0
Facsimile number
+43-7242-241-224
E-mail address
pv@fronius.com
MATERIALS & SAFETY - R&D TR12028 page 1 of 3
APPENDIX 2 Type Test Certification Test Result Sheet Micro-generator details
Test house details
Type test certification test result sheet for Fronius IG Plus 35V-1_TR12028.doc Backup: Fronius IG Plus V IE
CONSULTATION PAPER CER/06/190
Harmonic
2nd
3rd
5th
7th
9th
11th
13th
15th – 39th
Limit
1,08
2,3
1,14
0,77
0,4
0,33
0,21
0,15x(15/n)
Test value
at 15,3A/phase
(max value of Phase1)
0,012
0,225
0,101
0,071
0,053
0,012
0,012
See TR
LF_10024
Starting
Stopping
Running
Limit*
3,3%
3,3%
Pst = 1.0
Plt = 0.65
Test value
NA**
NA**
NA**
NA**
Power factor
Protection Limit
+0.95 lag–0,95 at three voltage levels
210 V
230 V
250 V
Test value
0,99
0,99
0,99
MATERIALS & SAFETY - R&D TR12028 page 2 of 3
POWER QUALITY
*Maximum permissible voltage fluctuation (expressed as a percentage of nominal voltage at 100% power) and flicker. As per BS EN 61000-3-3.
** The EUT itself does not produce flicker relevant variations of the line current, start-up is made using a ramp function and does therefore not create relevant d
values.
MAX
Solar power variations naturally lead to variations of the electric power fed into the grid, however these variations are not significant for PST and PLT.
Type test certification test result sheet for Fronius IG Plus 35V-1_TR12028.doc Backup: Fronius IG Plus V IE
Loading...
+ 1 hidden pages