/ Perfect Welding / Solar Energy / Perfect Charging
N
W
S
E
FRONIUS SYMO ADVANCED UL
Powering three-phase projects that last now with integrated SunSpec PLC
PC board
replacement
concept
SnapINverter
Technology
Integrated Data
Communication
Smart Grid
Ready
SuperFlex
Design
Power Line
Communication
Featuring ten models ranging from 10 kW to 24 kW, the Fronius Symo Advanced is the ideal inverter for commercial applications.
The new Advanced versions combine the benefits of the Fronius Symo with additional value for states with Module Level
Shutdown requirements including integrated PLC transmitter for SunSpec Rapid Shutdown communication standard, com-
pliance with NEC pre-2014, 2014 and 2017, zero tilt mounting, light weight and field serviceability.
TECHNICAL DATA FRONIUS SYMO ADVANCED (208-240 V VERSIONS)
Max. continuous output current 27.7 A24 A33.3 A28.9 A
OCPD/AC breaker size 35 A30 A45 A40 A
min - fmax) 45 - 60 Hz
)0-1 ind. / cap.
ac,r
208 V240 V208 V240 V
peak
18 kW
peak
208 V240 V208 V240 V
EFFICIENCYSYMO 10.0-3 208-240SYMO 12.0-3 208-240
208 V240 V208 V240 V
Max. Eciency97.0 %
CEC Eciency 96.5 %96.5 %
TECHNICAL DATA FRONIUS SYMO (208-240 V VERSIONS)
GENERAL DATASYMO 10.0-3 208-240SYMO 12.0-3 208-240
Dimensions (height x width x depth)510 x 725 x 225 mm (20.1 x 28.5 x 8.9 inches)
Weight41.7 kg (91.9 lbs)
Protection ClassNEMA 4X
Night time consumption< 1 W
Inverter topologyTransformerless
CoolingRegulated air cooling
InstallationIndoor and outdoor installation, tilt from 0 - 90 degrees
DIN rail (length x width x depth)max. 106 x 90 x 66 mm (max. 4.2 x 3.5 x 2.6 inches)
Ambient operating temperature range-40 - +60 °C (-40 - +140 °F)
Permitted humidity0 - 100 % (non-condensing)
Elevation max. input voltage of 600 V up to 3,400 m (11.155 ft)
DC connection technology6x DC+ and 6x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)
AC connection technologyScrew terminals 14-6 AWG
Certificates and compliance with standards
UL 1741-2010 Second Edition (incl. U L1741 Supplement SA 2016-09 for California Rule 21 and Hawaiian Ele ctric Code Rule 14H), UL1998 (for
functions: AF CI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547a-2014, IEEE 1547.1-2003, ANSI/IEEE C62.41, FCC Part 15 A & B,
NEC 2017 Article 690, C22. 2 No. 107.1-16, UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
1
Fronius Shade Cover required for installation angles less than 15 degree
/ Perfect Welding / Solar Energy / Perfect Charging
THREE BUSINESS UNITS, ONE GOAL: TO SET THE STANDARD THROUGH TECHNOLOGICAL ADVANCEMENT.
What began in 1945 as a one-man operation now sets technological standards in the fields of welding technology, photovoltaics and battery charging. Today, the
company has around 5,660 employees worldwide and 1,321 patents for product development show the innovative spirit within the company. Sustainable
development means for us to implement environmentally relevant and social aspects equally with economic factors. Our goal has remained constant throughout:
to be the innovation leader.
Further information about all Fronius products and our global sales partners and representatives can be found at www.fronius.com
Fronius USA LLC
6797 Fronius Drive
Portage, IN 46368
USA
pv-support-usa@fronius.com
www.fronius.us/pv
Fronius International GmbH
Froniusplatz 1
4600 Wels
Austria
pv-sales@fronius.com
www.fronius.com
EN v02 Apr 2023
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.