Perfect Welding / Solar Energy / Perfect Charging
SURGE PROTECTIVE DEVICE
FOR DIRECT INSTALLATION IN
/ Fronius Primo 3.0 – 8.2 kW,
/ Fronius Symo 3.0 – 8.2 kW und
/ Fronius Symo Hybrid
The surge protection device type 1+2 for direct and indirect
lightning strikes is suitable for use with the Fronius Symo 3.0
- 8.2 1), Fronius Primo 3.0 - 8.2
1)
and Fronius Symo Hybrid
1)
inverters and therefore fulfils the standard requirement of
installing a DC fuse near the inverter 3).
The surge protective device is equally applicable for all devices,
regardless of whether 1 or 2 trackers are being used. When only
one tracker is in operation (such as with the Symo Hybrid), one
input on the surge protective device remains unassigned (for
further information see the Quick Start Guide).
Thanks to the adjustable, integrated remote signalling function, the
system operator is notified automatically via the Fronius Solar.
web2) online portal whenever the surge protective device trips).
The surge protective device comes as an upgrade kit and can be
installed into the inverter connection area in a few minutes.
TECHNICAL DATA
Item designation DC SPD 8.2 TYP 1+2 M
Item number 4,240,335,CK
Nominal voltage 1000 VDC
Fault indicator mechanical, red
Remote message signal integrated
Standards DIN EN 50539-11, UTE C61-740-51, EN 50539-11, UL1449 ed.3
1)
Please be aware that a surge protective device can only be installed from the following serial numbers onwards:
Fronius Primo: 30408866
Fonius Symo: 30408866
Fronius Symo Hybrid: 30408866
2)
A Fronius Solar.web account is required.
3)
Since April 2019, DIN VDE 0100-712 requires that a DC fuse be installed on PV systems. In DIN VDE Appendix ZB Section
712.534 DE, it is stipulated that the surge protective devices be fitted on the DC side as close to the inverter as possible.
By installing the DC SPD 8.2 type 1+2 M surge protective device, these standard requirements are fulfilled.
Fronius International GmbH
Froniusplatz 1
4600 Wels
Österreich
Telefon +43 7242 241-0
pv-sales@fronius.com
www.fronius.com
Text and images correspond to t he current state of technology at the t ime of printing. Subject to modifications.
All information is without gua rantee in spite of carefu l editing - liability excluded. C opyright © 2011 Fronius™. All rights reserved.
as17