Dear reader,
Introduction Thank you for the trust you have placed in our company and congratulations on buying this
high-quality Fronius product. These instructions will help you familiarise yourself with the product. Reading the instructions carefully will enable you to learn about the many different features it has to offer. This will allow you to make full use of its advantages.
Please also note the safety rules to ensure greater safety when using the product. Careful handling of the product will repay you with years of safe and reliable operation. These are essential prerequisites for excellent results.
The latest version of the operating instructions can be found on the Fronius website www.fronius.com.
Explanation of safety symbols
DANGER!
Indicates immediate and real danger.
If it is not avoided, death or serious injury will result.
WARNING!
Indicates a potentially dangerous situation.
Death or serious injury may result if appropriate precautions are not taken.
CAUTION!
Indicates a situation where damage or injury could occur.
If it is not avoided, minor injury and/or damage to property may result.
NOTE!
Indicates a risk of flawed results and possible damage to the equipment.
IMPORTANT!
Indicates tips for correct operation and other particularly useful information.
It does not indicate a potentially damaging or dangerous situation.
If you see any of the symbols depicted in the "Safety rules" chapter, special care is re­quired.
Page 4
4
Page 5
5
EN
Contents
Safety rules ................................................................................................................................................ 7
General ................................................................................................................................................. 7
Proper use ............................................................................................................................................ 7
Environmental conditions...................................................................................................................... 7
Mains connection.................................................................................................................................. 7
Dangers from mains current and charging current ............................................................................... 8
Dangers from acid, gases and vapours ................................................................................................ 8
General information regarding the handling of batteries....................................................................... 8
Protecting yourself and others .............................................................................................................. 9
Safety measures in normal operation ................................................................................................... 9
EMC Device Classifications.................................................................................................................. 9
EMC measures ..................................................................................................................................... 9
Data protection...................................................................................................................................... 9
Maintenance and repair ........................................................................................................................ 10
Obligations of the operator.................................................................................................................... 10
Safety inspection................................................................................................................................... 10
Safety symbols...................................................................................................................................... 10
Disposal ................................................................................................................................................ 10
Copyright............................................................................................................................................... 11
General information ................................................................................................................................... 12
Device concept ..................................................................................................................................... 12
Correct battery configuration................................................................................................................. 12
Mains connection.................................................................................................................................. 12
Charging leads...................................................................................................................................... 12
Warning notices on the device.............................................................................................................. 13
Warning notices inside the charger....................................................................................................... 14
Setup regulations.................................................................................................................................. 14
Wall bracket .......................................................................................................................................... 16
Correct arrangement of the mains/charging leads................................................................................19
Control elements and connections............................................................................................................. 20
Controls and connections ..................................................................................................................... 20
Control panel......................................................................................................................................... 22
Charging the battery .................................................................................................................................. 24
Charging ............................................................................................................................................... 24
Interrupting charging............................................................................................................................. 25
Stopping charging................................................................................................................................. 26
Display ....................................................................................................................................................... 28
Overview of modes ............................................................................................................................... 28
Standard mode ..................................................................................................................................... 28
Menu selection...................................................................................................................................... 29
Statistics mode...................................................................................................................................... 29
History mode......................................................................................................................................... 30
Configuration mode............................................................................................................................... 30
Settings................................................................................................................................................. 34
Additional functions............................................................................................................................... 40
General options..................................................................................................................................... 43
Reset settings ....................................................................................................................................... 44
USB mode............................................................................................................................................. 44
Status codes ......................................................................................................................................... 46
Options....................................................................................................................................................... 49
Safety.................................................................................................................................................... 49
Electrolyte circulation (not available on Selectiva 220 V variant).......................................................... 49
External start/stop................................................................................................................................. 51
Charging lights...................................................................................................................................... 51
Temperature-controlled charging.......................................................................................................... 52
CAN card .............................................................................................................................................. 52
Relay board........................................................................................................................................... 52
Aquamatic control ................................................................................................................................. 53
Charging ............................................................................................................................................... 53
Charge 50%.......................................................................................................................................... 53
Page 6
6
Charge 80%.......................................................................................................................................... 53
Charging not complete.......................................................................................................................... 53
Charge finish......................................................................................................................................... 53
Main charge finished............................................................................................................................. 53
Common error message ....................................................................................................................... 53
Common error + warning ...................................................................................................................... 54
Signal lamp ........................................................................................................................................... 54
Immobiliser............................................................................................................................................ 54
Battery cooled down ............................................................................................................................. 54
External air pump - electrolyte circulation............................................................................................. 54
Wall bracket .......................................................................................................................................... 54
Floor bracket......................................................................................................................................... 54
LED strip ............................................................................................................................................... 54
IP 23...................................................................................................................................................... 54
Air filter.................................................................................................................................................. 55
"Mobile" kit ............................................................................................................................................ 55
RCS 3.0 remote indication.................................................................................................................... 55
Technical data............................................................................................................................................ 56
Selectiva 8 kW 220 V............................................................................................................................ 56
Selectiva 8 kW 400 V............................................................................................................................ 58
Selectiva 16 kW 400 V.......................................................................................................................... 60
Page 7
7
EN
Safety rules
General The device is manufactured using state-of-the-art technology and according to recognised
safety standards. If used incorrectly or misused, however, it can cause:
- Injury or death to the operator or a third party
- Damage to the device and other material assets belonging to the operator
- Inefficient operation of the device
All persons involved in commissioning, operating, maintaining and servicing the device must:
- Be suitably qualified
- Read and follow these Operating Instructions carefully
The Operating Instructions must always be at hand wherever the device is being used. In addition to the Operating Instructions, attention must also be paid to any generally appli­cable and local regulations regarding accident prevention and environmental protection.
All safety and danger notices on the device:
- Must be in a legible state
- Must not be damaged
- Must not be removed
- Must not be covered, pasted or painted over
For the location of the safety and danger notices on the device, refer to the section headed "General information" in the Operating Instructions for the device. Before switching on the device, rectify any faults that could compromise safety.
This is for your personal safety!
Proper use The device is to be used exclusively for its intended purpose. Any use above and beyond
this purpose is deemed improper. The manufacturer is not liable for any damage, or unex­pected or incorrect results arising out of such misuse.
Proper use includes:
- carefully reading and obeying all operating instructions and safety and danger notices
- performing all stipulated inspection and maintenance work
- following all instructions from the battery and vehicle manufacturers
Proper handling of the device is essential for it to function correctly. The device must never be pulled around by the cable.
Environmental conditions
Operation or storage of the device outside the stipulated area will be deemed as not in ac­cordance with the intended purpose. The manufacturer shall not be held liable for any dam­age arising from such usage.
For exact information on permitted environmental conditions, please refer to the "Technical data" section.
Mains connection Devices with a higher rating may affect the energy quality of the mains due to their current
consumption.
This may affect a number of types of device in terms of:
- connection restrictions
- criteria with regard to the maximum permissible mains impedance
*)
- criteria with regard to the minimum short-circuit power requirement
*)
Page 8
8
*)
at the interface with the public grid
see Technical Data
In this case, the plant operator or the person using the device should check whether the device may be connected, where appropriate by discussing the matter with the power sup­ply company.
NOTE! Ensure that the mains connection is earthed properly
Dangers from mains current and charging cur­rent
Anyone working with chargers exposes themselves to numerous dangers e.g.:
- Risk of electrocution from mains current and charging current
- Hazardous electromagnetic fields, which can risk the lives of those using cardiac pacemakers
An electric shock can be fatal. Every electric shock is potentially life threatening. To avoid electric shocks while using the charger:
- Do not touch any live parts inside or on the outside of the charger.
- Under no circumstances touch the battery poles
- Do not short-circuit the charging lead or charging terminals
All cables and leads must be secured, undamaged, insulated and adequately dimen­sioned. Loose connections, scorched, damaged or inadequately dimensioned cables and leads must be immediately repaired by authorised personnel.
Dangers from ac­id, gases and va­pours
Batteries contain acid which is harmful to the eyes and skin. During charging, gases and vapours are released that can harm health and are highly explosive in certain circumstanc­es.
- Only use the chargers in well ventilated areas to prevent the accumulation of explosive gases. Battery areas are not deemed to be hazardous areas provided that a concen­tration of hydrogen of less than 4 % can be guaranteed by the use of natural or forced ventilation.
- Maintain a distance of at least 0.5 m (19.69 in.) between battery and charger during the charging procedure. Possible sources of ignition, such as fire and naked lights, must be kept away from the battery
- The battery connection (e.g. charging terminals) must not be disconnected for any reason during charging
- On no account inhale any of the gases and vapours released
- Make sure the area is well ventilated.
- To prevent short circuits, do not place any tools or conductive metals on the battery
- Battery acid must not get into the eyes, onto the skin or clothes. Wear protective gog­gles and suitable protective clothing. Rinse any acid splashes thoroughly with clean water, and seek medical advice if necessary.
General informa­tion regarding the handling of bat­teries
- Protect batteries from dirt and mechanical damage.
- Store charged batteries in a cool place. Self discharge is kept to a minimum at approx. +2 °C (35.6 °F).
- Every week, perform a visual inspection to ensure that the acid (electrolyte) level in the battery is at the Max. mark.
- If any of the following occurs, do not start the device (or stop immediately if already in use) and have the battery checked by an authorised workshop:
- uneven acid levels and/or high water consumption in individual cells caused by a
possible fault.
- heating of the battery over 55 °C (131 °F).
Page 9
9
EN
Protecting your­self and others
While the charger is in operation, keep all persons, especially children, out of the working area. If, however, there are people in the vicinity,
- warn them about all the dangers (hazardous acids and gases, danger from mains and charging current, etc.),
- provide suitable protective equipment.
Before leaving the work area, ensure that people or property cannot come to any harm in your absence.
Safety measures in normal opera­tion
- Chargers with a ground conductor must only be operated on a mains supply with a ground conductor and a socket with a ground conductor contact. If the charger is op­erated on a mains supply without a ground conductor or in a socket without a ground conductor contact, this will be deemed gross negligence. The manufacturer shall not be held liable for any damage arising from such usage.
- Only operate the charger in accordance with the degree of protection shown on the rating plate.
- Never operate the charger if there is any evidence of damage.
- Arrange for the mains cable to be checked regularly by a qualified electrician to ensure the ground conductor is functioning properly.
- Any safety devices and parts that are not functioning properly or are in imperfect con­dition must be repaired by a qualified technician before switching on the charger.
- Never bypass or disable protection devices.
- After installation, an accessible mains plug is required.
EMC Device Clas­sifications
Devices in emission class A:
- Are only designed for use in industrial settings
- Can cause line-bound and radiated interference in other areas
Devices in emission class B:
- Satisfy the emissions criteria for residential and industrial areas. This is also true for residential areas in which the energy is supplied from the public low-voltage mains.
EMC device classification as per the rating plate or technical data.
EMC measures In certain cases, even though a device complies with the standard limit values for emis-
sions, it may affect the application area for which it was designed (e.g. when there is sen­sitive equipment at the same location, or if the site where the device is installed is close to either radio or television receivers). If this is the case, then the operating company is obliged to take appropriate action to rectify the situation.
Data protection The user is responsible for the safekeeping of any changes made to the factory settings.
The manufacturer accepts no liability for any deleted personal settings.
Page 10
10
Maintenance and repair
Under normal operating conditions, the device requires only a minimum of care and main­tenance. However, it is vital to observe some important points to ensure it remains in a us­able condition for many years.
- Before switching on, always check the mains plug and cable as well as charger leads and charging terminals for any signs of damage.
- If the surface of the device housing is dirty, clean with a soft cloth and solvent-free cleaning agent only
Maintenance and repair work must only be carried out by authorised personnel. Use only original replacement and wearing parts (also applies to standard parts). It is impossible to guarantee that bought-in parts are designed and manufactured to meet the demands made on them, or that they satisfy safety requirements.
Do not carry out any modifications, alterations, etc. to the device without the manufactur­er's consent.
Obligations of the operator
The operator must only allow persons to work with the device who:
- are familiar with the fundamental instructions regarding safety at work and accident prevention and have been instructed in how to use the device
- have read and understood these operating instructions, especially the section "safety rules", and have confirmed as much with their signatures
- are trained to produce the required results.
Checks must be carried out at regular intervals to ensure that operators are working in a safety-conscious manner.
Safety inspection The manufacturer recommends that a safety inspection of the device is performed at least
once every 12 months.
A safety inspection should be carried out by a qualified electrician
- After any changes are made
- After any additional parts are installed, or after any conversions
- After repair, care and maintenance has been carried out
- At least every twelve months
For safety inspections, follow the appropriate national and international standards and di­rectives.
Further details on safety inspections can be obtained from your service centre. They will provide you, on request, with any documents you may require.
Safety symbols Devices with the CE mark satisfy the essential requirements of the low-voltage and elec-
tromagnetic compatibility directives.
Devices with the TÜV test mark satisfy the requirements of the relevant standards in Can­ada, USA, Australia and Japan.
Devices with the EAC mark of conformity satisfy the requirements of the relevant standards in Russia, Belarus, Kazakhstan, Armenia and Kyrgyzstan.
Disposal Do not dispose of this device with normal domestic waste! To comply with the European
Directive on Waste Electrical and Electronic Equipment and its implementation as national law, electrical equipment that has reached the end of its life must be collected separately and returned to an approved recycling facility. Any device that you no longer require must
Page 11
11
EN
either be returned to your dealer or given to one of the approved collection and recycling facilities in your area. Ignoring this European Directive may have potentially adverse af­fects on the environment and your health!
Copyright Copyright of these operating instructions remains with the manufacturer.
The text and illustrations are all technically correct at the time of printing. We reserve the right to make changes. The contents of the operating instructions shall not provide the ba­sis for any claims whatsoever on the part of the purchaser. If you have any suggestions for improvement, or can point out any mistakes that you have found in the instructions, we will be most grateful for your comments.
Page 12
12
General information
Device concept The three-phase battery charging systems for 24 V, 48 V and 80 V batteries are fitted with
intelligent charging technology. The successful Active Inverter Technology with the revo­lutionary Ri charging process adapts itself to the requirements of the battery and only charges the battery with the current that it actually needs.
The technology is embedded in a robust industry-standard housing. The exceptionally compact design complies with all safety standards, requires less installation space and protects the components to ensure a long service life.
Fitted with a graphical display, an integrated datalogger, new interfaces and additional op­tions, the device is perfectly equipped for the future.
Correct battery configuration
WARNING!
If an unsuitable battery is connected to the charger, there is a danger of serious in­jury or damage from escaping gases, fire or explosion.
Never connect a battery to the charger unless it is compatible in terms of its type, voltage and capacity and corresponds to the charger settings.
Mains connection
WARNING!
An electric shock due to a fault current can be fatal.
If required, nothing other than a type B residual current circuit breaker should ever be used for connecting the device to the mains.
WARNING!
Operating the equipment incorrectly can cause serious injury and damage.
Do not use the functions described here until you have fully read and understood the fol­lowing documents: ► Operating Instructions ► All the Operating Instructions for the system components, especially the safety rules ► Battery and vehicle manufacturer's Operating Instructions and safety rules
WARNING!
Risk of serious injury and damage due to faulty or insufficient power supply.
The power supply requirements detailed in "Technical data" must be met.
Charging leads
WARNING!
There is a risk of very serious injury and damage if charging leads are left lying around.
People may become entangled in or trip over loose, unwound cables. Lay the charging leads so that no one can trip over or become entangled in them.
Page 13
13
EN
WARNING!
There is a high risk of very serious injury and damage if the charging plug is pulled out during the charging process.
The sparks caused by this can ignite the charging gases that build up during the charging process, causing a fire or an explosion. After the charging process has completed, wind up the charging leads, or if available, place them on the cable holder.
Warning notices on the device
A number of safety symbols can be seen on the charger's rating plate. The safety symbols must not be removed or painted over.
An electric shock can be fatal. The housing must never be opened by anyone other than a service technician trained by the manufacturer. The device must be disconnected from the mains before starting any work with the housing open. A suitable measuring instrument must be used to ensure that electrically charged components (e.g. capacitors) are fully discharged. Ensure that the device re­mains disconnected from the mains until all work has been completed.
Do not use the functions until you have read all the Operating Instructions.
Possible sources of ignition, such as fire, sparks and naked flames, must be kept away from the battery.
Risk of explosion! Oxyhydrogen is generated in the battery during charging.
Battery acid is corrosive and MUST be kept away from eyes, skin and clothes.
Ensure an adequate supply of fresh air during charging. Maintain a distance of at least 0.5 m (19.69 in.) between battery and charger during the charging pro­cedure.
The charger can cause DC fault currents in the ground conductor. If a fault cur­rent protection device (RCD) is used on the mains side to protect against electric shock, it must conform to Type B.
Do not dispose of used devices with domestic waste. Dispose of them according to the safety rules.
Ser.No.: xxxxxxxx
Part No.: 4,010,xxx
U
DC nom.
I
DC max.
Protective class I
WARNING
Explosive gases. Prevent flames and sparks. Provide adequate ventilation during charge!
Always stop charging before you disconnect the charging cable!
I
AC max.
U
AC nom.
P
AC max.
IP20
xxV
xxxA
xxA
3~ NPE xxxV 50/60Hz
xxxxW
www.fronius.com
xxxxxxxx
Selectiva xxxx
Page 14
14
Warning notices inside the charger
WARNING!
An electric shock can be fatal.
The housing must never be opened by anyone other than a service technician trained by the manufacturer. The device must be disconnected from the mains before starting any work with the housing open. A suitable measuring instrument must be used to ensure that electrically charged components (e.g. capacitors) are fully discharged. Use an easily legi­ble and understandable warning sign to ensure that the charger is not reconnected to the mains supply before all the work has been completed.
Inside the device:
Setup regulations
WARNING!
Toppling or falling devices can cause life-threatening injuries.
Make sure that all system components are securely in position when setting them up. If using a floor bracket or wall bracket, always make sure that all the securing elements are seated securely.
Devices weighing more than 25 kg (55.12 lb.) must be carried by at least two people.
If mounting on shelves, the shelf must be capable of supporting the weight of the device.
(4) (5)
(+) (-)
(1) (2) (3)
RCS 3.0 Lights
1 2 3 4
12V GREEN YELLOW RED BLUE
Temp. Sensor Ext. Start/Stop
WARNING
Hazardous Voltage
Kondensator Entladezeit < 2 min. Capacitor discharge time < 2 min. Décharge de condensateur < 2 min. Condensador tiempo de descarga < 2 min. Condensatore tempo di scaricamento < 2 min.
Risk of Electric Shock! Do not operate at circuits more than 250 V to ground!
0... 30V DC/4A
0... 250V AC/4A
Use Copper Conductors Only!
C Common NC Normally Closed NO Normally Opened L Line N Neutral Wire
max. 1A
AC Output!
42,0409,0008
C NC NO C NC NO C NC NO
L/C NC NO N
WARNING!
  
Page 15
15
EN
The device is tested to IP20 protection, meaning:
- Protection against penetration by solid foreign bodies with diameters exceeding 12.5 mm (0.49 in.)
- No protection against water
The device can be set up and operated in dry, closed areas that comply with degree of pro­tection IP20. Exposure to wet conditions should be avoided.
The device may only be operated in a hori­zontal position.
The air surrounding the charger must be kept free from battery acid vapour as far as pos­sible. You should therefore avoid mounting the device directly above the battery that is to be charged.
Cooling air
The charger must be set up in such a way that the cooling air can flow unimpeded through the vents in the housing that are provided for that purpose. Ensure that there is always a minimum clearance of f 0.2 m (7.874 in.) around the air inlets and outlets. The surrounding air must be free from
- excessive dust
- electrically conductive particles (carbon black or swarf)
- heat sources
Cooling air is drawn in and flows out as indicated by the arrows in the following illustrations.
NOTE!
Air inlets and outlets must never be covered, not even partially.
If several chargers are set up one behind the other, they should be offset.
16 kW: 60 cm (1 ft. 11.62 in.)
8 kW: 30 cm (11.81 in.)
Page 16
16
If the chargers are arranged in a line one behind the other without being offset, the space between the chargers must be as follows:
- Selectiva 8 kW: Minimum distance 30 cm (11.81 in)
- Selectiva 16 kW: Minimum distance 60 cm (1 ft. 11.62 in.)
Wall bracket
WARNING!
Work that is carried out incorrectly and falling chargers can cause serious injury and damage.
This installation must only be carried out by trained and qualified personnel. Take note of the safety rules in the charger Operating Instructions.
Different wall plugs and screws will be required depending on the supporting surface. Wall plugs and screws are therefore not included in the scope of supply. The installer is respon­sible for selecting the right wall plugs and screws.
WARNING!
Risk of serious damage or injury from objects being dropped or falling over.
► Ensure that all screw connections are secure ► Must only be used with a Fronius Selectiva 8/16 kW charger ► Ensure the device is level when mounting
1 2
1
312
32
62
62
2
Page 17
17
EN
633 (24.92)
mm (in.)
13 (.51)
180 (7.09)
193 (7.6)
595,5 (23.44)
179 (7.05)
453 (17.83)
344 (13.54)
109
(4.29)
8 kW (400 V)
8 kW 220 V
392 (15.43)
502 (19.76)
647 (25.47)
267 (10.51)
247 (9.72)
241 (9.49)
585 (23.03)
20 (.79)
110
(4.33)
mm (in.)
Page 18
18
Drilling template
16 kW 400 V
392 (15.43)
502 (19.76)
647 (25.47)
267 (10.51)
247 (9.72)
241 (9.49)
585 (23.03)
20 (.79)
110
(4.33)
mm (in.)
342 (13.46)
418 (16.46)
494 (19.45)
500 (19.69)
492 (19.37)
450 (17.72)
400 (15.75)
300 (11.81)
200 (7.87)
20 (.79)
8.3
(.79)
6 (.24)
7 (.28)
8.5
(.33)
6
(.24)
25
(.98)
76 (2.99)
60
(2.36)
mm (in.)
Weight of wall bracket:
8 kW 400 V 1,8 kg (3.97 lb.) 8 kW 220 V 3,15 kg (6.49 lb.) 16 kW 400 V 3,15 kg (6.49 lb.)
Page 19
19
EN
Correct arrange­ment of the mains/charging leads
CAUTION!
Risk of damage to components due to overheating caused by laying the mains/ charging leads incorrectly.
► Lay mains/charging lead without loops ► Do not cover mains/charging lead
Page 20
20
Control elements and connections
Controls and con­nections
No. Function
(1) Position for internal electrolyte
circulation option
Compressed air outlet
(2) Position for internal electrolyte
circulation option
Air intake with air filter (12)
(3) (+) Charging lead
(4) (-) Charging lead
No. Function
(5) Position for external start/stop option or temperature-controlled charging
option
(6) Position for the remote control system or 12 V charging lights options
(7) USB port
The USB port allows a USB flash drive to be used to update the device and also to log the charging parameters while charging is in progress. The maximum supply current is 0.5 A.
(8) CAN connection area option *
(9) Positions for relay-related options
(e.g. Aquamatic control) More information can be found in the "Options" section
(3)
(4)
(5)
(6)
(2)
(8)
(9)
(1)
(7)
(10)
(11)
(12)
Page 21
21
EN
(10) Mains cable
(11) Control panel
(12) Optional LED strip
lights up in different colours depending on the state of charge, as explained in the "Control panel" section
WARNING!
An electric shock can be fatal.
Only trained service technicians may open the housing. This includes removing the con­nection plate. The device must be disconnected from the mains before starting any work with the housing open. A suitable measuring instrument must be used to ensure that elec­trically charged components (e.g. capacitors) are fully discharged. Use an easily legible and understandable warning sign to ensure that the charger is not reconnected to the mains supply before all the work has been completed.
WARNING!
Work that is carried out improperly can cause serious injury or damage.
Connection work on the device must only be carried out by qualified specialist technicians. If there are Installation Instructions or User Information for the optional component con­cerned, then all warning notices and instructions therein must be obeyed. Once the connection work is complete, a safety inspection must be carried out in accord­ance with relevant national and international standards and directives. Further details on safety inspections can be obtained from your authorised service centre. They will provide you with any documents you may require on request.
* The CAN connection area can only be accessed by removing the connection plate on
the front of the device. The following warning notices must be obeyed:
The figure shows the connections in the CAN connection area.
The CAN connection area is located be­hind the connection plate on the front of the device. The warning notices listed above apply to the CAN connection area.
(2) Control voltage - white (3) External start/stop - black
(5) Not assigned (6) CAN High - green (7) CAN Low - yellow (8) CAN GND - brown
(2)
Control Supply
white
Ext. Start/Stop
black
Not connected
CAN High
green
CAN Low
yellow
CAN GND
brown
(3)
(5) (6) (7) (8)
only for 48V/80V Batteries (2)
Page 22
22
Control panel
No. Function
(1) Display
Displays the current charging parameters Displays settings
(2) "Menu" key
Selects the desired menu Selects the appropriate symbol to return to the previous display
(3) "Up/Down" keys
Selects the desired menu item Sets the desired value
(4) "Stop/Start" key
For interrupting and resuming the charging process Confirms a menu item or setting
(5) "Battery cooled down" indicator (blue)
Indicates that a battery has cooled down and is ready for use On steady: After charging has finished, the set cooling time or optionally the bat-
tery temperature has been reached. Flashes every second: The water refill indicator has also tripped. More information can be found under "Additional functions" in the "Display" section.
(6) "Fault" indicator (red)
On steady: The charger outputs an error. The current conditions do not allow prop-
er charge. While the red indicator is on, charging cannot take place (charging in­terrupted). The relevant status code appears in the display.
Flashes briefly every 3 seconds: The charger outputs a warning. Charging is continued despite the adverse charging parameters. The relevant status code and the state of charge appear alternately on the display.
(1) (8)
(7)
(6)
(5)
(4)(3)(2)
Page 23
23
EN
(7) "Charge" indicator (orange)
Lit: during charging Flashes: If charging has been interrupted
(8) "Battery charged" indicator (green)
On steady: Charging ended Flashes every second: Charging ended. The water refill indicator has also
tripped.
Page 24
24
Charging the battery
Charging
WARNING!
Risk of serious injury or damage from escaping battery acid or explosion if faulty batteries are charged.
Before charging, ensure that the battery to be charged is fully functional.
WARNING!
Risk of serious injury and damage from incorrect charging settings or a defective battery.
Before beginning the charging process, ensure that the settings on the charger for the bat­tery to be charged are correct and that the battery is functioning properly.
NOTE!
The device may be damaged if the charging plug contacts are very dirty.
The resulting increase in contact resistance can lead to overheating and subsequent de­struction of the charging plug. Keep the charging plug contacts free from impurities and clean them if necessary.
Plug the charger into the electrical mains supply
The display appears in standard mode. The display shows the charger parameters:
- Type of battery (e.g. wet)
- Charging characteristic (e.g. IUI)
- Nominal voltage (e.g. 48 V)
- Capacity (e.g. 300 Ah)
- Day of the week, date and time
The charger parameters can be set individually. More information on the charger parame­ters can be found under "Configuration mode" in the "Display functions" chapter. Ensure that the battery to be charged matches the configuration of the battery charging system.
Connect the charging plug or connect the (+) charging lead to the positive pole of the battery and the (-) charging lead to the negative pole of the battery
The charger detects that the battery is connected and starts charging. If start-up delay is activated, then charging will start at the end of the set delay time. For more information, see "Configuration mode" in the "Display" section.
During the charging process the display shows the following values:
- Current charging current (A)
- Current charging voltage (V)
- The charge already input (Ah)
- Battery temperature with the "temperature-controlled charging" option
- The time (hh:mm) since charging started
1
2
Page 25
25
EN
The battery symbol indicates the current state of charge. The greater the number of bars that are displayed, the further advanced the charging process is. As soon as the battery is fully charged, a minute counter will appear (see figure on right). This counts the minutes since the end of charging; when a number of chargers are being used, this makes it easier to decide which battery will have already cooled down most.
When the battery is fully charged all 4 bars of the battery symbol appear black. As soon as the battery is fully charged, the charger begins conservation charging.
Interrupting charging
If, however, the standard display is still to be shown rather than the minute counter:
Use the "Up/Down" keys to toggle between the minute counter and standard display
- All bars are displayed
- The green "Battery charged" indicator is on
- The battery is always ready to use
- The battery can remain connected to the charger for as long as required
- Conservation charging counteracts battery self-discharge
1
To interrupt the charging process:
Press the "Stop/Start" key
1
Page 26
26
As long as a battery is connected to the charger, only the charging process can be inter­rupted and resumed using the "Stop/Start" key. Display modes can be changed using the "Menu" key as described in the "Display" section, but this is only possible when there is no battery connected to the charger.
Stopping charg­ing
WARNING!
Risk of serious injury or damage from ignition of oxyhydrogen through sparks gen­erated when the charging leads are disconnected.
Before disconnecting or unplugging the charging plug, first stop the charging process by pressing the "Stop/Start" key.
NOTE!
The battery may be damaged if it is disconnected from the charger before the charg­ing process is complete.
Only disconnect the battery from the charger when it is fully charged (green "Battery charged" indicator lights up).
While the charging progress is interrupted:
The "Charge" indicator (yellow) flashes
To resume the charging process:
Press the "Stop/Start" key again
2
As soon as the battery is fully charged and has cooled down, the following indicators light up:
- "Battery charged" indicator (green)
- "Battery cooled down" indicator (blue)
Page 27
27
EN
Unplug the charging plug or disconnect the (-) charging lead from the negative pole of the battery and the (+) charging lead from the positive pole of the battery
For an optimal battery life, only disconnect the battery from the battery charging sys­tem when the blue "Battery cooled" indica­tor is showing in addition to the green indicator, in accordance with the explana­tion below. If several battery charging sys­tems are in use, first disconnect the battery which has been fully charged for the longest (the coolest).
To stop the charging process:
Press the "Stop/Start" key
1
2
Page 28
28
Display
Overview of modes
The device has the following modes:
As long as a battery is connected to the battery charging system, the charging process can only be interrupted and resumed using the "Stop/Start" key. Display modes can be changed using the "Menu" key as described in the following sections that explain the indi­vidual modes, but this is only possible when there is no battery connected to the battery charging system.
During a pause in the charging process the menu selection is available, however only in a limited form. In this case the modes described below are available as follows:
Statistics mode and history mode remain unrestricted.
In configuration mode the following data is available:
- Date and time
- Device serial number
- Hardware version and serial number
- Software: main software, secondary software, primary software and characteristic block version
In USB mode all options except for "Update" and "Load configuration" are available.
Standard mode Once the mains plug has been connected to the electrical mains supply, the display will
automatically operate in standard mode.
In standard mode, the display shows the following charger parameters:
- Type of battery (e.g. wet)
- Charging characteristic (e.g. IUI)
- Nominal voltage (e.g. 48 V)
- Capacity (e.g. 300 Ah)
- Day of the week, date and time
Standard mode In standard mode the display shows the charging parameters
Statistics mode Visualises the frequency of the device operating modes and shows the total number of charging actions. Also shows an overview of the total and average Ah produced and energy consumed per charge
History mode Provides information about the parameters for all the stored charging processes
Configuration mode Configuration mode enables all the settings for the device and the charging pro­cess to be adjusted
USB mode USB mode enables a device to be updated, device configurations to be saved and loaded, and the charging parameters to be recorded during the charging process - all using a USB flash drive
Page 29
29
EN
The charger parameters can be set individually. More information can be found in the "Configuration mode" section.
Menu selection
Change from standard mode to the menu selection as follows:
Statistics mode In statistics mode, horizontal bars display
the frequency of the following device opera­ting statuses:
- Idle
- Charging
- Floatingcharge
- Cooldown
- Error
Page 2/2 shows the following values:
- Total number of charges
- Total Ah output
- Average Ah output per charge
- Total energy consumed (kWh)
- Average energy consumed (kWh) per charge
The consumed energy display is a standard value and can deviate by up to 5% from the actual amount of energy. At lower power levels the deviation may be higher.
Press and hold the "Menu" key for approx. 5 seconds
1
Change from all other modes to the menu selection as follows:
Press the "Menu" key briefly
To select the desired mode:
Use the "Up/Down" keys to select the symbol for the desired mode
- e.g. the battery symbol for standard mode
Use the "Stop/Start" key to confirm the "Tick" symbol
1
2
3
Use the "Up/Down" keys to toggle between page 1/2 and page 2/2
1
Page 30
30
History mode History mode provides information about the parameters for all the stored charging pro-
cesses. In order to show changing or different displays, two versions of the display window are shown below:
Text content of the display window:
- Start date of charge, e.g. Thursday 19.06.14
- Start time of charge, e.g. 19:29 or charging period, e.g. 8h28min
- Voltage at charge start, e.g. 45.9 V
- Voltage after 5 minutes, e.g. 47.9 V
- Voltage at charge end, e.g. 48.0 V
- Consumed Ah, e.g. 397 Ah
- Consumed kWh, e.g. 19 kWh
- Charging characteristic, e.g. 6 RI
- Set charging period, e.g. 8-9 h or set Ah, e.g. 400 Ah or set charge end time (not shown)
Configuration mode
Configuration mode provides the following setting options:
- "Charging settings": settings for the battery
- Type of battery, e.g. "Wet"
- Charging characteristic, e.g. "IU"
- Capacity (Ah) or charging time (h) depending on the charging characteristic
Use the "Up/Down" keys to scroll between the pages for each stored charging process
Symbols shown:
- Full battery: Charging has been completed
- Empty battery: Charging has not been completed
- Exclamation mark with number: Warning has been output with the corresponding status code. More informa­tion can be found in the "Status codes" section.
- Symbol with number: Error has been output with the corresponding status code. More information can be found in the "Status codes" section.
- Key symbol with a tick: Charging was stopped properly using the "Stop/Start" key
- Key symbol with a cross: Charging was stopped without using the "Stop/Start" key
- Charging details - Display of certain battery data at the beginning and end of the charging process: Number of cells Ah Characteristic Type of battery
1
Page 31
31
EN
- Cells: voltage (V) and number of battery cells or automatic setting of the number of cells
CAUTION!
Risk of damage to the battery.
Only use the automatic number of cells selection function with batteries with the following nominal voltage values: 12 V and 24 V with 24 V devices 24 V and 48 V with 48 V devices The automatic selection function must not be used with deep discharged batteries.
- "Additional functions": for individual adaptation options for the charging characteristic
- "Additional functions": Additional functions
- Blue LED
- External start/stop
- Refill indicator
- "General options": General options
- Language
- Contrast
- Time (hh:mm:ss) Time zone Daylight saving time/normal time
- Date (dd:mm:yy)
- AC current limiter
- Length of charging lead (m)
- Charging lead cross section (mm2)
- Code for accessing the configuration menu activated/deactivated
- Time interval for the parameter recorded on the USB flash drive (s)
- "Reset Factory Settings": resets settings to those when the charger left the factory or optionally to the manufacturer's defaults
- includes a double-check prompt ("OK?") that requires the operator to reconfirm
that this step is intended
First the screen will appear in its initial for­mat, showing the date, time and software version.
The "Up/Down" keys can be used to retrieve the following informa­tion:
- Serial number of the device plus serial number and version of the configuration memory
- PC board for controller/power electronics: hardware version and serial number
- Software: main software, secondary software, primary soft­ware and characteristic block version
The procedure for opening the configuration menu is as follows:
Press the "Stop/Start" key
1
1
Page 32
32
You will be prompted to enter a code:
The code required is "1511", and is entered as follows:
Using the "Up/Down" keys, enter the first digit of the code
Press the "Menu" key to move to the next digit of the code Continue to follow the procedure described above until the com-
plete code has been entered Use the "Stop/Start" key to confirm the code entered
You will now be prompted to select one of the main menu items for the configuration mode:
When you select a menu item you may be presented with a symbol prompting you to read the Operating Instructions. Confirm this prompt by pressing the "Stop/Start" key again.
1
2
3
4
Page 33
33
EN
The procedure for navigating the configuration menu and its submenus is as follows:
Use the "Up/Down" keys to select the desired menu item
Use the "Stop/Start" key to confirm the menu item, and reconfirm any double-check prompt (e.g. "OK?")
Use the "Up/Down" keys as necessary to choose an item e.g. "Off/ On" or enter a value
Use the "Stop/Start" key to confirm what you have entered
If the cursor should move to another setting or position after con­firmation of the previous setting, then the procedure described in points (3) and (4) should be repeated
To exit the current menu:
Press the "Menu" key to return to the higher-level menu
For an example, see the explanation below of how to set the charging parameters:
Use the "Up/Down" keys to select the "Charging settings" menu item
Use the "Stop/Start" key to confirm this menu item
1
2
3
4
5
6
1
2
Page 34
34
the display may vary depending on the selection made. If the "Pb-Wet" type of battery has been selected in combination with the "RI" characteristic ("Curve") as in the example here, then the title "Ah" is replaced by the "Charging time" setting.
Both the start and end time can be set for this charging time period. The starting time can be deselected as required; the charging time then bases itself exclusively on the specified charge end time following a manual charge start.
When applying the settings, the user will be guided through the menu in much the same way as a wizard function.
Settings Below is a detailed description of the "Settings" menu item for the "Charging settings"
menu item discussed above. Navigation is performed as described in the "Configuration mode" section.
The choice of settings for the "Charging settings" menu item will now be displayed:
Use the "Up/Down" keys to select the desired parameter (e.g. "Cells")
Use the "Stop/Start" key to confirm the parameter
Use the "Up/Down" keys to set the desired value (e.g. "24" for the number of battery cells)
Use the "Stop/Start" key to confirm what you have entered
3
4
5
6
A list appears with the following selection options:
Page 35
35
EN
The individual selection options are explained in greater detail below:
The electrolyte circulation cycle is controlled by the charger's control system. A number of selection options are available for this purpose.
The following settings are available for electrolyte circulation:
- Off:
- Electrolyte circulation switched off
- Continuous operation ("continuous"):
- Electrolyte circulation permanently on
- Program 1 to 5:
- Default electrolyte circulation programs and their relevant parameters can be found in the table under "Settings" in the "Display" chapter.
- Automatic:
- Automatic adjustment of electrolyte circulation flow rate based on the set battery parameters
- "User" - "On"/"Off":
- Individual setting of the electrolyte circulation
- The settings for "On" and "Off" determine the pulse/pause ratio of the air flow in­tervals
Default electrolyte circulation programs and their relevant parameters can be found in the table below:
In each of these programs, the solenoid valve opens for a time "ON 1" and closes for a time "OFF 1". This process is repeated for the number of times specified under "Repeat". After this number of repetitions has been completed, the process continues with the "ON 2" and "OFF 2" times until charging is completed.
"Air Pump" electrolyte circulation (not available on Selectiva 220 V variant):
Program ON 1 OFF 1 Repeat ON 2 OFF 2
1 30 min 25 min 1 x 5 min 25 min 2 3 min 10 min 4 x 3 min 20 min 3 3 min 12 min 1 x 3 min 12 min 4 5 min 10 min 3 x 5 min 20 min 5 2.5 min 7.5 min 1 x 2.5 min 7.5 min
Temperature-controlled charging:
Page 36
36
The following settings are available for temperature-controlled charging:
- automatic/OFF/required:
- automatic ... Temperature-dependent adjustment of the charging characteristic
- OFF ... The measured battery temperature is not taken into account
- required ... Charging only starts when a temperature sensor is connected
- Error overtemperature ON/OFF:
- ON ... Error message in the event of battery overtemperature Charging process stops and can only be continued once the battery has cooled down and been reconnected
- OFF ... No error message in the event of battery overtemperature
- Warning overtemperature ON/OFF:
- ON ... Warning in the event of battery overtemperature
- OFF ... No battery overtemperature warning
Equalising charge:
- OFF: There is no equalising charge.
- Delay: If the battery remains connected to the charger for the duration of the equalising charge delay ("equalize charge delay"), then a special type of charging takes place. This prevents acid stratification. The parameters for the current (ampere / 100 ampere hours), voltage (volt / cell) and duration of the equalising charge may all be changed.
- Weekday: Specify the weekday on which the equalising charge is to take place. The parameters for the current (ampere / 100 ampere hours), voltage (volt / cell) and duration of the equalising charge may all be changed.
- Manual equalising charge ("Manual"): An equalising charge can be started manually by pressing the relevant key on the dis­play. The equalising charge starts after a set delay time has been observed. The charge parameters that have been set are followed. The parameters for the current (ampere / 100 ampere hours), voltage (volt / cell) and duration of the equalising charge may all be changed. This function is only available for Pb-Wet characteristics.
If a setting for the equalising charge has been enabled, a symbol on the homescreen next to the set ampere hours or charging time shows whether an equalising charge is being car­ried out or may be started.
Delay:
charge start delay: Delay time (minutes) of actual start of charging relative to the moment when charge start was initiated
charge end delay: Delay time (minutes) before charge end is signalled (e.g. green indicator) relative to the moment when charging actually stopped
at mains failure restart charging: If this option is chosen, the charging process is restarted automatically as soon as the mains supply becomes available again after a disruption to the electrical mains supply.
Page 37
37
EN
Calendar:
The calendar function allows charging to be started automatically according to the follow­ing criteria:
- Time window in which charging may not be started if a battery is connected
- Time window in which charging is to be started using a defined characteristic 1 if a bat­tery is connected
- Time window in which charging is to be started using a defined characteristic 2 if a bat­tery is connected
To activate the calendar function, select the "ON" setting and confirm
The first menu item "Charging settings" al­lows three characteristics to be defined:
- Type of battery for every characteristic: e.g. Pb-Wet
- Curve settings when selecting the rele­vant characteristic
- Symbol for characteristic 1: Time window in which charging is to be started using characteristic 1 (e.g. 0:00-6:00)
- Stop: Time window in which charging must not take place (e.g. 06:00-20:00)
- Symbol for characteristic 2: Time window in which charging is to be started using characteristic 2 (e.g. 20:00-24:00)
1
Additional settings can be found under the "Calendar" function:
Day Setting 1-5:
The day settings allow up to five different charging start time profiles to be defined with the following settings:
Page 38
38
NOTE!
Ongoing charging operations are unaffected by the set time windows. If in the ex­ample above a battery is connected at 05:45, the charge end time is governed ac­cording to need and is not interrupted by the end time specified for the set time window (06:00 in the example).
If the battery is connected during the "stop" time window, charging is started automatically during the next time window. If charging is started manually during the "stop" time window, charging will always take place using characteristic 1.
Additional settings:
- Change the allocated characteristic: characteristics symbol
- Remove the selected characteristic: "remove"
Week Setting:
- Three different week settings can be defined.
A previously created day setting can be as­signed to any day of the week.
Year Setting:
- Multiple periods throughout the year may be defined, each containing a single week setting (e.g. 1/1 - 7/1).
When the calendar function is active, a ca­lendar symbol (shown here with the number "4" as the current date) appears on the dis­play.
Page 39
39
EN
Special Charges:
Selecting "Special Charges" allows one or more of the alternative charging types to be performed temporarily:
- ON: Function activated
- OFF: Function deactivated
The "repeat" setting defines how often the alternative charging mode should be performed until the device reverts to the original charging parameters again:
- Setting range: 1 to 99 repetitions
Disable Start Button:
- ON: The charging process cannot be started using the "Stop/Start" key; one reason for this is to prevent unauthorised intervention.
- OFF: The charging process can be started using the "Stop/Start" key.
The following settings are also possible:
- Characteristic: e.g. "Deep discharge 10"
- Number of battery cells: "Cells" - e.g. 12x
- Battery capacity in Ah: e.g. 375 Ah
The following curve settings are available:
- Curve - e.g. RI - Pb-Wet
- Charging time - e.g. 5-6 h
Special function "Opportunity Charge":
To extend the usage interval of a battery, it is possible to re-charge it at a time when it will not be needed, e.g. during sched­uled plant shutdowns.
- ON: Function activated
- OFF: Function deactivated
Page 40
40
- Figure on left: display when RI characteristic is selected
- Figure on right: display for other characteristics (e.g. IUI)
- Figure on left: "Runner symbol" (1)
- Figure on right: indication when opportunity charging starts
Additional func­tions
The following contains a detailed description of the "additional functions" menu item in con­figuration mode. Navigation is performed as described in the "Configuration mode" section.
Select the "additional functions" menu item
The individual selection options are explained in greater detail below:
Setting the "Blue LED" indicator: Time (minutes) that must be allowed to pass before the blue "battery cooled down" indica­tor should come on to indicate that a battery has cooled down sufficiently. The time from the end of charging is used as the setting.
When opportunity charging is "ON" and a battery is connected, the following appears:
To start opportunity charging:
- Use the "Up" key to select the runner symbol (1)
(1)
1
A list appears with the following selection options:
Page 41
41
EN
In conjunction with the "Temperature-controlled charging" option, a temperature value can be set here. The blue "battery cooled down" indicator will light up to signal a sufficiently­cooled battery once the temperature drops below this value.
The following settings are available when external start/stop is selected:
- Start: normal ON:
- Charging starts when an external switch is closed and a battery is detected
- Or when the charging plug is connected by closing the auxiliary contacts and a
battery is detected
normal OFF:
- Charging starts when a battery is connected
- Stop: normal ON:
- Charging is interrupted when an external switch is opened
- Or when the charging plug is disconnected by opening the auxiliary contacts normal OFF:
- Opening of an external switch or the auxiliary contacts is ignored
- Button: The function of the "OK/STOP" key can be simulated using an external button
Refill Indicator: The refill indicator is a message that appears as soon as the battery needs topping up with distilled water. The time at which refilling is deemed necessary can be defined as follows:
- Every nth week and weekday
- e.g. top up with water every fortnight on a Friday
- If set to "off", the refilling request does not have to be confirmed
External start/stop:
Relay board ("Relays"):
Page 42
42
When a relay board has been selected, one of the following functions can be set for each of the 4 terminals (-> 1) to (-> 4), viewed from left to right:
- Aquamatic
- Signal to activate a solenoid valve, for example
- "Standard" program with preconfigured factory settings
- "User" with user-defined settings
- More information about the Aquamatic control can be found under "Aquamatic
control" in the "Options" section.
- Charging
- Charge 50 %
- Charge 80 %
- Charge Finish
- Main Charge Finished
- Signal to indicate that the main charge phase has finished
- Charging not complete
- Signal if the battery is prematurely disconnected from the charger
- Can be set from 1 to 10 s
- Charge OK
- Battery is being charged or is already fully charged
- Common error ("Cumulative Error"):
- Signal in the event of an error
- A power failure can also be displayed as an error if required (setting "ON")
- Freely-defined text, which could for example include the contact details of the
dealer, can be displayed if the device is in an error state. More information can be found in the "USB mode" section.
- Cumulative error + warning
- In the same way as for the "Cumulative Error" function, the corresponding relay
trips as soon as an error or warning is detected
- Signal Lamp:
- One or more suitable lamps can be connected to the relay board to indicate the
state of charge or operating status of the charger.
- More information can be found under "Signal lamp" in the "Options" section.
- Immobiliser
- ON:
- The relay picks up permanently as soon as the charger is connected to the mains.
- Refill Indicator:
- Signals that the battery needs topping up with distilled water.
- More information can be found under "Additional functions" in the "Display" sec-
tion.
- Battery Cold
- External Air pump for electrolyte circulation ("External Air Pump")
- The settings are applied as described under "-> Settings" for the electrolyte circu-
lation (Air Pump)
More information on the relay board can be found in the "Options" section.
External lamp setting ("External lamp"): as described under "Charging Lights" in the "Options" section, suitable signal lamps can be connected to indicate the state of charge or operating status of the charger. The follow­ing settings are available:
- normal (conventional signal lamps)
- RGB (LED strips)
Page 43
43
EN
The contrast for the remote control system can be adjusted.
at mains failure restart charging: If this option is chosen, the charging process is restarted automatically as soon as the mains supply becomes available again after a disruption to the electrical mains supply.
General options A detailed explanation of the "general options" menu item in configuration mode can be
found below. Navigation is performed as described in the "Configuration mode" section.
Select the "general options" menu item
A list appears with the following selection options:
- Language
- Display settings
- Contrast
- LED brightness
- Show Ah at charge end ON/OFF
- Time and Date
- daylight saving time / normal time
- Predefined time zones
- User-defined time zones
- Basic length of charging cable in m (Charging Cable)
- Cable cross section (mm²)
- Code entry required / not required to access configuration mode (Code ON / OFF)
Remote control system:
1
Page 44
44
- Time interval (s) for recording charging parameters on the USB stick (USB Logging Time)
- Reset statistics
- Reset history
For more detailed information on the statistics and history, please refer to the "Statistics mode" and "History mode" sections.
Reset settings The menu item below "General options" offers two alternative ways of resetting all the set-
tings:
Reset Factory Settings:
- Resets to factory settings
Reset Default Settings:
- Resets settings to the manufacturer's defaults
USB mode
In USB mode, the display shows whether or not a USB flash drive is connected.
The USB flash drive must conform to the following specifications:
- Formatting: FAT32
- 32 Gigabyte maximum
- No multiple partitioning
The I-SPoT VIEWER software supports the visualisation and evaluation of data on the USB flash drive. The I-SPoT VIEWER software can be found online at the following ad­dress: http://www.fronius.com/i-spot.
Only insert the USB flash drive when charging is not in progress or if the charging process has been interrupted.
If the charging process is only interrupted, not completed, it is only possible to read out da­ta. A new update or configuration cannot be loaded.
Use the "Stop/Start" key to access the following settings
Use the "Up/Down" keys to scroll between the settings
Use the "Stop/Start" key to confirm the desired setting
1
2
3
Page 45
45
EN
A USB flash drive may be connected while charging is in progress, after the "Stop/Start" key has been pressed. However, this can only be to read out data. An update or new con­figuration cannot be loaded.
- Safely remove Safely remove the USB flash drive as soon as the desired action has been completed.
- Update A list of the suitable update files stored on the USB flash drive opens. Select and confirm the desired file in the same way as scrolling through the settings. Do not change the automatically assigned file names of the update file!
- Download The data relating to the logged charging parameters stored in the device's datalogger is saved to the USB flash drive for the I-SPoT VIEWER. Additionally, events - such as the device settings and user curves (configuration) - are saved. The following time ranges can be selected for the datalogger:
- 1 month
- 3 months
- All
- Since the last save
- Download optional The following options are available:
- I-SPoT VIEWER
The logged data is saved in the same way as for the "Download" function, but sav­ing only the I-SPoT VIEWER data.
- Save datalogger
The logged data is saved in the same way as for the "Download" function, but is saved not in the I-SPoT VIEWER format, but as ".csv" files (Automatic folder structure for the ".csv" files: * Fronius\<device serial number>\Charges\<yyyymmdd>\<hhmmss.csv>
- Save events
Events are saved to the USB flash drive.
- Save configuration
The device settings are saved to the USB flash drive.
- Load configuration Loads onto the device one of the suitable device configurations stored on the USB flash drive
- Load dealer text A text file can be loaded from the USB flash drive that is displayed as soon as the de­vice enters an error state. The text file can, for example, contain the contact details of
Page 46
46
the dealer. The file must be saved on the USB flash drive as a ".txt" file in "unicode" format. The file name must be "dealer.txt". The number of characters is restricted to
99.
Status codes
If a fault occurs during operation, specific status codes may be displayed. Faults can result from the following:
- Battery fault
- The voltage of the connected battery is unsuitable
- The device has overheated
- There is a software or hardware fault
Battery fault: If the battery signals a fault, the battery charging system displays this fault as a battery fault including the corresponding fault number for the battery. The respective fault is explained in the battery's Operating Instructions.
If an error message appears on the display and if you cannot resolve the error yourself:
Note the displayed status code: e.g. "Statecode (31)" Note the configuration of the device Contact your authorised service centre
Freely-defined text, which could for example include the contact details of the dealer, can be displayed if the device is in an error state.
* If a USB flash drive is connected while charging is in progress, the .csv files are
saved directly to the USB flash drive. The folder structure here is also created auto­matically and differs due to the presence of the "Datalog" folder instead of the "Charges" folder.
Status codes caused by external factors Number Cause
(11) Check mains voltage (12) Check mains (phase failure) (13) External temperature sensor faulty (14) Electrolyte circulation faulty (pressure switch not switching) (15) Control voltage not detected (16) External start/stop is not closed (17) Open circuit voltage detection triggered more than once during charging
(e.g. worn charging contacts)
Status codes in the event of a battery fault Number Cause
(22) Battery undervoltage (23) Battery overvoltage (24) Battery too hot (with external temperature sensor only) (25) Battery too cold (with external temperature sensor only)
1
2
3
Page 47
47
EN
(26) Cell fault detected (27) Battery not supported (28) Battery heavily discharged - safety charging is being carried out (29) Battery is connected with reverse polarity (100) - (400)General battery fault
Status codes in the event of a CAN fault Number Cause
(51) Battery not responding (52) Battery data cannot be requested (53) Battery voltage not supported (54) Communication fault (55) Battery fault (56) Battery does not switch on (57) Message time limit exceeded (58) Registration failed
Status codes in the event of a charging error Number Cause
(31) Timeout in I1 phase (32) Timeout in U1 phase (33) Battery overvoltage in the I2 phase (34) Ah limit exceed (35) Timeout in I2 phase (36) Target voltage in I2 phase not reached (with format characteristic only) (37) Problem with RI charge (38) Set charging time cannot be reached
Status codes in the event of a fault in the primary circuit Number Cause
(500) Module 1 (top) temperature sensor faulty (501) Module 2 (bottom) temperature sensor faulty (502) PCB temperature sensor faulty (503) Primary overtemperature (504) Fan blocked/faulty (505) Intermediate circuit over/undervoltage (506) Intermediate circuit imbalance (507) Primary supply voltage outside the tolerance (508) Power failure (509) Wrong device configuration (510) Primary EEPROM faulty (527) Phase shifter overcurrent (528) Charging relay switched off during charging process (530) Communication error (532) Microcontroller error (e.g. Division by 0) (533) Reference voltage outside the tolerance (534) Start-up error (535) PFC overcurrent (536) Phase shifter or PFC faulty
Status codes in the event of a fault in the secondary circuit Number Cause
(520) Secondary temperature sensor faulty (521) Secondary overtemperature (522) Output fuse faulty (523) Secondary supply voltage outside the tolerance (524) Secondary reference voltage outside the tolerance (525) Current offset (526) Current offset outside the tolerance (527) Power module overcurrent (primary) (529) No secondary communication
Status codes in the event of a battery fault Number Cause
Page 48
48
(530) No primary communication (531) Secondary EEPROM faulty (532) Microcontroller fault (537) Voltage measurement faulty (570) Secondary relay cannot be switched (571) ADC/SPI error
Status codes in the event of a fault in the controller Number Cause
(540) Configuration memory chip missing/faulty (541) No secondary communication (542) Secondary initialisation failed (543) Program/memory fault in characteristic control (544) Program/memory fault in characteristic control (545) Primary initialisation failed (546) Update failed (547) Load/save settings failed (548) Load/save characteristic settings failed (549) Charging could not be resumed after a power failure (550) Time not set (551) Hardware change detected (552) Configuration memory chip invalid
Status codes in the event of a fault in the secondary circuit Number Cause
Page 49
49
EN
Options
Safety In order to connect optional components, it may be necessary to open the housing. The
following warning notices must be obeyed:
WARNING!
An electric shock can be fatal.
The housing must never be opened by anyone other than a service technician trained by the manufacturer. The device must be disconnected from the mains before starting any work with the housing open. A suitable measuring instrument must be used to ensure that electrically charged components (e.g. capacitors) are fully discharged. Use an easily legi­ble and understandable warning sign to ensure that the charger is not reconnected to the mains supply before all the work has been completed.
WARNING!
Work that is carried out incorrectly can cause serious injury or damage.
All work involved with connecting optional components must only be carried out by quali­fied specialist technicians. If there are Installation Instructions or User Information for the optional component concerned, then all warning notices and instructions therein must be obeyed. In the case of all optional components with electrical connections, once the connection work is complete, a safety inspection must be carried out in accordance with relevant na­tional and international standards and directives. Further details on safety inspections can be obtained from your authorised service centre. They will provide you with any documents you may require on request.
WARNING!
Toppling or falling devices can cause life-threatening injuries.
Due to its weight, the device must be secured using suitable fittings to prevent it from top­pling or falling over. The wall and floor brackets provided by the manufacturer must be used.
Electrolyte circu­lation (not availa­ble on Selectiva 220 V variant)
NOTE!
Risk of damage to air pump from the ingress of electrolyte from the battery or from operation without any back pressure.
Always set up the charger at least 0.5 m (1 ft. 7.69 in.) above the battery to be charged. Always use an undamaged connecting hose provided specifically for this purpose to con­nect the charger's compressed air outlet to the battery.
NOTE!
Failure to observe the permitted mains voltage tolerance can cause malfunctions and damage.
For the electrolyte circulation option, a restricted mains voltage tolerance vis-à-vis the charger of 207 V to 250 V applies.
Page 50
50
The electrolyte circulation option features an air pump integrated in the charger. This intro­duces air into the battery through capillary tubes that are provided specifically for this pur­pose. This allows intensive mixing of the electrolyte to take place. The benefit is reduced heating of the battery, and consequently longer battery-life, plus reduced water loss during charging.
If a pump fault or leaks in the connection with the battery result in a fault being detected, then the status code "Statecode 14" will appear on the display. One way in which this fault can be indicated is by using an external indicator lamp to show a common error.
The electrolyte circulation cycle is controlled by the charger's control system. A number of selection options are available for this purpose in the configuration menu. More information can be found under "Additional functions" in the "Display" section.
The default preconfigured programs 1 to 5 are among these selection options. The relevant parameters for these programs are listed in the table below together with a subsequent ex­planation.
In each of these programs, the solenoid valve opens for a time "ON 1" and closes for a time "OFF 1". This process is repeated for the number of times specified under "Repeat". After this number of repetitions has been completed, the process continues with the "ON 2" and "OFF 2" times until charging is completed.
Cleaning the air filter insert
The air filter insert for the integrated air pump should be cleaned once a year. In dusty en­vironments, the cleaning interval should be shortened accordingly. The air filter insert (2) must be removed for cleaning. Remove the air filter (1) by pulling it out and then refit it as follows:
1 2
Program ON 1 OFF 1 Repeat ON 2 OFF 2 1 30 min 25 min 1 x 5 min 25 min 2 3 min 10 min 4 x 3 min 20 min 3 3 min 12 min 1 x 3 min 12 min 4 5 min 10 min 3 x 5 min 20 min 5 2.5 min 7.5 min 1 x 2.5 min 7.5 min
(1)
1
(2)
2
Page 51
51
EN
1
External start/ stop
The external start/stop option prevents sparking if the charging plug is disconnected during charging. Dedicated auxiliary contacts inside the plug detect the removal of a shorting jumper in the counterpart before the main contacts have even become separated. This trig­gers an immediate stop to charging. As a result there is no wear to the main contacts, and this arrangement safeguards more effectively against an oxyhydrogen explosion.
Charging lights
Suitable signal lamps can be connected to the connections inside the device as illustrated in order to indicate the state of charge or operating status of the charger. Each signal lamp must have a working voltage of 12 V, and the total current drawn by all the lamps must not exceed 0.5 A. Connections (1) to (5) in the Figure are assigned as shown below. It is ad­visable to use the lamp colours shown below:
If the RGB setting (LED strip) is set in the menu, then connection 3 (YELLOW) is not sup­ported. The normal setting (conventional signal lamp) or RGB (LED strip) for the "External Lamp" function is explained under "Additional functions" in the "Display" section.
(1)
3
Connection Function Colour
(1) 12 V power supply (2) Battery is fully charged green (3) On: battery is being charged
Flashing: charging has been interrupted
yellow
(4) An error has occurred (common error) red (5) The battery has already cooled down and is ready for use blue
(4) (5)
(+) (-)
(1) (2) (3)
RCS 3.0 Lights
1 2 3 4
12V GREEN YELLOW RED BLUE
Temp. Sensor Ext. Start/Stop
WARNING
Hazardous Voltage
Kondensator Entladezeit < 2 min. Capacitor discharge time < 2 min. Décharge de condensateur < 2 min. Condensador tiempo de descarga < 2 min. Condensatore tempo di scaricamento < 2 min.
Page 52
52
Temperature-con­trolled charging
The temperature-controlled charging option always adjusts the charging voltage according to the current temperature of the battery. This results in considerably longer battery-life, es­pecially where batteries are used in cold stores.
CAN card
WARNING!
Risk of serious injury and damage from using the CAN card for safety-critical func­tions.
Do not use the CAN card for safety-critical functions.
The optional CAN card enables the charger's operating statuses and the connected bat­tery's state of charge to be evaluated externally.
More information on the CAN card can be found in the instructions supplied with the CAN card option.
Relay board
WARNING!
Risk of serious injury and damage from using the relay board for safety-critical func­tions.
Do not use the relay board for safety-critical functions.
NOTE!
Failure to observe the permitted mains voltage tolerance can cause malfunctions and damage.
For the relay board option, a restricted mains voltage tolerance vis-à-vis the charger of 207 V to 250 V applies.
The optional relay board enables the charger's operating statuses and the connected bat­tery's state of charge to be evaluated externally. One or more external consumers can also be supplied with input voltage L-N. A neutral conductor in the electrical mains supply is a prerequisite for this. The configuration of the relay board outputs is explained in the Oper­ating Instructions for the charger: "Additional functions" in the "Display" section.
More information on the relay board can be found in the instructions supplied with the relay board option.
There follows an overview of the options that are directly connected with the relay board. These relay-connected options are activated through the relay board outputs:
- Aquamatic
- Charging
- Charge 50%
- Charge 80 %
- Charge Finish
- Main Charge Finished
- Charge OK
Page 53
53
EN
- Charging not complete
- Signal if the battery is prematurely disconnected from the charger
- Cumulative error
- Cumulative error + warning
- Signal Lamp
- Immobiliser device
-ON
- Refill indicator
- Battery Cold
- External air pump (electrolyte circulation)
Aquamatic con­trol
The Aquamatic control contains the controller for a solenoid valve that automatically tops up the water in the battery to be charged.
- Standard setting:
- At the start of the recharging phase, the solenoid valve opens for 12 seconds and
then closes for 4 seconds
- This cycle is repeated 26 times
- USER setting:
- Configurable "ON" time (solenoid valve opens) after the end of the main charge
phase
Charging The "Charging" option is suitable for actuating a signal lamp for instance. While charging
is in progress, the corresponding relay picks up automatically.
Charge 50% Like the "Main charge finished" function, the relevant relay switches as soon as the battery
is 50% charged.
Charge 80% Like the "Main charge finished" function, the relevant relay switches as soon as the battery
is 80% charged.
Charging not complete
The "Charging not complete" option lends itself to the actuation of an audible alarm device, for example. If the battery is disconnected from the charger before the charging process is complete, the relay switches for an adjustable time of 1 to 10 seconds.
Charge finish The "Charge finish" option is suitable for actuating a signal lamp for instance. Once the
configured charging characteristic is fully completed, the corresponding relay picks up au­tomatically.
Main charge fin­ished
The "Main charge finished" option is suitable for actuating a signal lamp for instance. When the main charge phase finishes, the corresponding relay picks up automatically.
Common error message
The "Common error message" option is suitable for actuating a signal lamp for instance. Each time an error is detected, the relevant relay picks up automatically.
Page 54
54
Common error + warning
In the same way as for the "Common error" function, the corresponding relay trips as soon as an error or warning is detected.
Signal lamp As an alternative to the charging lights, one or more suitable lamps can be connected to
the relay board to indicate the state of charge or operating status of the charger. These lamps can be designed for a voltage of up to 30 V DC or up to 250 V AC on a starpoint­earthed network.
If the lamp circuit is potential-free, then the switching current must not exceed 4 A. A lamp that is actuated by the 230 V supply relay must be operated with an output current of max. 1 A.
Immobiliser If the charger is built into the vehicle as an on-board device, then the optional immobiliser
will prevent the vehicle from being started unintentionally whilst charging is taking place. This protects the vehicle, the battery and the charger leads from damage.
As soon as the vehicle is connected up to the mains supply, the corresponding relay picks up and blocks the ignition signal for instance. Another example is the actuation of a suitable signal lamp to convey the message visually that charging is currently in progress.
Battery cooled down
The corresponding relay switches automatically once the time set in the menu has passed.
External air pump
- electrolyte circu­lation
This option enables an external air pump to be activated by a relay contact in the sense of the "electrolyte circulation" option.
Wall bracket The robust wall bracket ensures safe fitting on site. More information can be found in the
corresponding Installation Instructions.
Floor bracket The robust floor bracket ensures safe fitting on site. More information can be found in the
corresponding Installation Instructions.
LED strip The LED strip acts as a status indicator and lights up in the same colours as the display
elements on the control panel. An LED strip including a diffuser is installed in the gap be­tween the front wall and upper part of the housing.
IP 23 The IP 23 option increases the IP protection rating of the device from IP 20 to IP 23. More
detailed information can be found in the corresponding User Information.
Page 55
55
EN
Air filter In dusty environments, the air filter prevents the inside of device from becoming dirty. This
avoids a possible reduction in power or other problem. More detailed information can be found in the corresponding User Information.
"Mobile" kit A carrying strap and handle improve the mobility of the device.
RCS 3.0 remote indication
The remote indication allows the device to be fully controlled from a distance of up to 30 m (98 ft., 5.1 in.). This option includes a full control panel in an aluminium housing that pro­vides IP42 protection.
Page 56
56
Technical data
Selectiva 8 kW 220 V
WARNING!
An electric shock due to a fault current can be fatal.
Nothing other than a type B residual current circuit breaker should ever be used for con­necting the device to the mains.
Cable lengths must not exceed 30 m (98 ft. 5.1 in.).
Mains voltage (-10% / +30%)
1)
Optional:
3~ NPE 220 V / 50/60 Hz 3~ PE 220 V / 50/60 Hz
2)
32 A
Minimum mains lead cross section Selectiva 4120 Selectiva 4140 / 4160
4 mm² (0.0062 in²)
6 mm² (0.0093 in²) Duty cycle 100% EMC device class B Protection class 1 Max. permitted mains impedance Z
max
at PCC 3) According to the "Device-specific
data" table below Degree of protection
4)
IP 20 Overvoltage category III Operating temperature
5)
-20 °C to +40 °C
(-4 °F to 104 °F) Storage temperature -25 °C to +80 °C
(-13 °F to 176 °F) Relative humidity maximum 85% Maximum altitude above sea level 3000 m (9842 ft.) Marks of conformity according to rating plate Product standard EN62477-1 Dimensions l x w x h 647 x 247 x 392 mm
(25.47 x 9.72 x 15.43 in.) Weight (with standard mains and charging leads) 34,84 kg (76.81 lb) Pollution level 3
1) The device is approved for operation on neutral-earthed mains networks with a maximum outer conductor nominal voltage of 220 V. A mains voltage tolerance of 207 V to 250 V applies for the relay board options.
2) The earth leakage current is less than 3.5 mA.
3) Interface to a 127/220 V, 50 Hz public grid
4) For indoor use only, do not expose to rain or snow
5) A high ambient temperature may result in power degradation (derating).
Page 57
57
EN
Device-specific data
Device Max. AC
current
Max. AC power
Nominal volt­age
Max. charg­ing current
Z
max
Selectiva 4120 28,5 A 9070 W 48 V 120 A 72 mOhm Selectiva 4140 29,6 A 9390 W 48 V 140 A 65 mOhm Selectiva 4160 29,9 A 9490 W 48 V 160 A 55 mOhm
Page 58
58
Selectiva 8 kW 400 V
WARNING!
An electric shock due to a fault current can be fatal.
Nothing other than a type B residual current circuit breaker should ever be used for con­necting the device to the mains.
Cable lengths must not exceed 30 m (98 ft. 5.1 in.).
Mains voltage (-10% / +30%)
1)
Optional:
3~ NPE 400 V / 50/60 Hz 3~ PE 400 V / 50/60 Hz
2)
16 A Minimum mains lead cross section 2.5 mm² (0.003875 in²) Duty cycle 100% EMC device class B Protection class 1 Max. permitted mains impedance Z
max
at PCC 3) none
Degree of protection
4)
IP 20 Overvoltage category III Operating temperature
5)
-20 °C to +40 °C
(-4 °F to 104 °F) Storage temperature -25 °C to +80 °C
(-13 °F to 176 °F) Relative humidity maximum 85% Maximum altitude above sea level 2000 m (6561 ft.) Marks of conformity according to rating plate Product standard EN62477-1 Dimensions l x w x h 633 x 180 x 344 mm
(24.92 x 7.09 x 13.54 in.) Weight (with standard mains and charging leads) 23 kg (50.71 lb) Pollution level 3
1) The device is approved for operation on neutral-earthed mains networks with a maximum outer conductor nominal voltage of 400 V. A mains voltage tolerance of 207 V to 250 V applies for the electrolyte circulation and relay board options.
2) If the charger is protected by a 32 A fuse, the thermal stress of the automatic circuit breaker must not exceed 82000 A²s. The earth leakage current is less than 3.5 mA.
3) Interface to a 230/400 V, 50 Hz public grid
4) For indoor use only, do not expose to rain or snow
5) A high ambient temperature may result in power degradation (derating).
Page 59
59
EN
Device-specific data
Device Max. AC cur-
rent
Max. AC power Nominal volt-
age
Max. charging current
Selectiva 2100 11 A 3900 W 24 V 100 A Selectiva 2120 12.5 A 4600 W 24 V 120 A Selectiva 2140 14.5 A 5400 W 24 V 140 A Selectiva 2160 10 A 6100 W 24 V 160 A Selectiva 2180 11 A 6800 W 24 V 180 A Selectiva 2200 11 A 6900 W 24 V 200 A Selectiva 4060 12.5 A 4600 W 48 V 60 A Selectiva 4075 15 A 5700 W 48 V 75 A Selectiva 4090 11 A 6800 W 48 V 90 A Selectiva 4120 14 A 8800 W 48 V 120 A Selectiva 4140 15 A 9500 W 48 V 140 A Selectiva 4160 15.5 A 9600 W 48 V 160 A Selectiva 8040 8.5 A 5000 W 80 V 40 A Selectiva 8060 12 A 7500 W 80 V 60 A Selectiva 8075 14.5 A 9100 W 80 V 75 A Selectiva 8090 14.5 A 9200 W 80 V 90 A
Page 60
60
Selectiva 16 kW 400 V
WARNING!
An electric shock due to a fault current can be fatal.
Nothing other than a type B residual current circuit breaker should ever be used for con­necting the device to the mains.
Cable lengths must not exceed 30 m (98 ft. 5.1 in.).
Mains voltage (-10% / +30%)
1)
Optional:
3~ NPE 400 V / 50/60 Hz 3~ PE 400 V / 50/60 Hz
2)
32 A
Minimum mains lead cross section Selectiva 8120 / 8140 Selectiva 8160 / 8180
4 mm² (0.0062 in²)
6 mm² (0.0093 in²) Duty cycle 100% EMC device class B Protection class 1 Max. permitted mains impedance Z
max
at PCC 3) According to the "Device-specific
data" table below Degree of protection
4)
IP 20 Overvoltage category III Operating temperature
5)
-20 °C to +40 °C
(-4 °F to 104 °F) Storage temperature -25 °C to +80 °C
(-13 °F to 176 °F) Relative humidity maximum 85% Maximum altitude above sea level 2000 m (6561 ft.) Marks of conformity according to rating plate Product standard EN62477-1 Dimensions l x w x h 647 x 247 x 392 mm
(25.47 x 9.72 x 15.43 in.) Weight (with standard mains and charging leads) 36.8 kg (81.13 lb) Pollution level 3
1) The device is approved for operation on neutral-earthed mains networks with a maximum outer conductor nominal voltage of 400 V. A mains voltage tolerance of 207 V to 250 V applies for the electrolyte circulation and relay board options.
2) The earth leakage current is less than 3.5 mA.
3) Interface to a 230/400 V, 50 Hz public grid
4) For indoor use only, do not expose to rain or snow
5) A high ambient temperature may result in power degradation (derating).
Page 61
61
EN
Device-specific data
Device Max. AC
current
Max. AC power
Nominal volt­age
Max. charg­ing current
Z
max
Selectiva 8120 24.5 A 14800 W 80 V 120 A 96 mOhm Selectiva 8140 28 A 17200 W 80 V 140 A 82 mOhm Selectiva 8160 29.5 A 18200 W 80 V 160 A 74 mOhm Selectiva 8180 29.5 A 18300 W 80 V 180 A 67 mOhm