Fronius Oversizing Fronius Primo GEN24 and GEN24 Plus 3.0 - 6.0 Certificate [EN]

OVERSIZING FRONIUS PRIMO GEN24
Fronius International GmbH
Wels, December 28th, 2021
Fronius Primo GEN24 3.0 (Plus)
Fronius Primo GEN24 3.6 (Plus)
Fronius Primo GEN24 4.0 (Plus)
Fronius Primo GEN24 4.6 (Plus)
Fronius Primo GEN24 5.0 (Plus)
Fronius Primo GEN24 6.0 (Plus)
can be oversized above the rated nameplate capacity without voiding the manufacturer’s warranty, provided that the following conditions are always adhered to:
The string and array configuration do not exceed the sizing limits of the inverter (Isc_max, Ppv_max, Udc_max)
stated in the official datasheets and in this document. This includes, but is not limited to conditions like, low
temperatures, high irradiances, bifacial gain, etc.
Exceeding any of these limits can damage the inverter or even cause harm or injury.
INPUT DATA
DC input voltage range (U
Usable M PP input current (M PPT1/MPPT2/total) (I
Max. PV gen erator short circuit current (MPPT1/M PPT2/total) (I
Max. u sable DC power (MPPT1/M PPT2/total) (P
Max. PV gen erator power (MPPT1/M PPT2/total) (P
dc min
- U
dc_ma x
sc_max
dc_ma x
PRIMO GEN24
3.0 (PLUS)
)
dc max
22 / 12 / 34 A 22 / 12 / 34 A 22 / 12 / 34 A 22 / 12 / 34 A 22 / 12 / 34 A 22 / 12 / 34 A
)
33 / 18 / 51 A 33 / 18 / 51 A 33 / 18 / 51 A 33 / 18 / 51 A 33 / 18 / 51 A 33 / 18 / 51 A
)
3.11 / 3.11 / 3.11 kW 3.81 / 3.81 / 3.81 kW 4.1 / 4.1 / 4.1 kW 4.75 / 4.75 / 4.75 kW 5.17 / 5.17 / 5.17 kW 6.2 / 5.76 / 6.2 kW
)
3.75 / 3.11 / 4.5 kWpeak 4.6 / 3.81 / 5.52 kWpeak 5 / 4.14 / 6 kWpeak 5.75 / 4.75 / 6.9 kWpe ak 6.25 / 5.17 / 7.5 kWpeak 7.5 / 5.76 / 9 kWpeak
)
pv_max
PRIMO GEN24
3.6 (PLUS)
PRIMO GEN24
4.0 (PLUS)
65 - 600 V (U
PRIMO GEN24
of the PV array ≤ 600 V)
oc max
4.6 (PLUS)
PRIMO GEN24
5.0 (PLUS)
PRIMO GEN24
6.0 (PLUS)
reduc ed DC input vol tage range (U
Max. PV genera tor power @ reduced DC in put voltage range ***
(MPPT1 /MPPT2/total) (P
dc min
- U
)
dc max
4.5 / 4.5 / 6 kWpeak 5.5 / 4.5 / 7.36 kWpeak 6 / 4.5 / 8 kWpeak 6.9 / 5.75 / 9 kWpeak 7 / 5.75 / 9 kWpea k 7.5 / 5.76 / 9 kWpeak
)
pv_max
65 - 450 V (U
of the PV array ≤ 450 V)
oc max
***Note - the oversizing values in the table vary depending on the PV array max. voltage Uoc_max.
Fronius International GmbH
Business Unit Solar Energy Froniusplatz 1 A-4600 Wels
Bernhard Kossak, MSc Head of Solution Management
02/2017
1/1