Fronius Oversizing Fronius Primo 10.0-1 - 15.0-1 US Certificate [EN]

Wels, April 14th 2016
OVERSIZING FRONIUS PRIMO 10.0-1 208-240 – 15.0-1 208-240
Fronius International GmbH
hereby confirms that the inverters
/ Fronius Primo 10.0-1 208-240
can be oversized 50% above the rated nameplate capacity without voiding the manufacturer’s warranty, always provided that
/ The string configuration adheres to the voltage and current window guidelines published in the operation
manual.
/ The open circuit voltage of a module string does not exceed the maximum input voltage of the inverter under
any circumstances (temperature, irradiance). Excess voltage above this threshold will damage the inverter and negate the standard terms of warranty.
/ The maximum DC array short circuit current shall not exceed 1.5 times the maximum usable input currents
(MPPT 1 / MPPT 2) or 1.5 times the total maximum DC current (MPPT 1 + MPPT 2) of the inverter.
/ Reverse polarity of solar module strings can lead to an unacceptable overload condition. This can cause a
strong arc, which can lead to an inverter fire. When using string fuses or combiner DC bus bars, always make sure that the polarity is correct before connecting the individual solar module strings.
Fronius International GmbH
Solar Energy Division Froniusplatz 1 A-4600 Wels
DI Thomas Mühlberger Head of Solution Management