Country setup4
Access code4
Adjusting parameters with the Fronius Solar.start app5
Adjusting parameters with the browser5
Country setup7
Country setup selection9
Country setup selection9
General10
Startup and Reconnection10
Ramp Rates11
Safety14
Unintentional Islanding Detection14
Isolation monitoring14
DC Arc Fault Protection16
RCMU18
DC Shutdown Communication19
Interface Protection20
Voltage20
Frequency23
DC Injection27
Grid Support Functions29
Voltage Fault Ride Through (VFRT)29
Active Power41
Reactive Power63
EN
3
General
Country setupThe "Country Setup" menu area is intended exclusively for installers/service
technicians from authorised specialist companies. The access code must be requested from the national/international Fronius point of contact using an application form.
CAUTION!
Risk due to unauthorised access.
Incorrectly set parameters can negatively influence the public grid and/or the inverter feeding energy into the grid, and lead to a loss of conformity with the
standard.
The parameters may only be adjusted by installers/service technicians from
▶
authorised specialist companies.
Do not give the access code to third parties and/or unauthorised persons.
▶
WARNING!
Danger due to unauthorised error analyses and repair work.
This can result in serious injury and damage to property.
Fault analyses and repair work on the photovoltaic system may only be car-
▶
ried out by installers/service technicians from authorized specialist companies in accordance with national standards and guidelines.
The selected country setup for the respective country contains preset parameters according to the nationally applicable standards and requirements. Depending on local grid conditions and the specifications of the energy provider, adjustments to the selected country setup may be necessary.
CAUTION!
Risk due to incorrectly set parameters.
Incorrectly set parameters can negatively influence the public grid and/or cause
faults and failures on the inverter, and lead to the loss of standard conformity.
The parameters may only be adjusted by installers/service technicians from
▶
authorised specialist companies.
The parameters may only be adjusted if the energy provider permits or re-
▶
quires this.
Only adjust the parameters taking into account the nationally applicable
▶
standards and/or directives and the specifications of the energy provider.
Access codeThe "Country setup" menu area is intended exclusively for installers/service tech-
nicians from authorised specialist companies. The access code must be requested from the national/international Fronius point of contact using an application
form.
4
CAUTION!
12
open access point
Setup your PV system in a few minutes.
START INSTALLATION
LOGIN
Log in with your Fronius credentials (email adress
& password) in order to get the most out of the
PV System. Installing a new product does not
require a Login.
Imprint & ContactTerms & ConditionsData Privacy
Fronius Solar.start
open access point
1
FRONIUS_PILOTxxx
Secured
Password:
12345678
2
192.168.250.181
Adjusting parameters with the
Fronius Solar.start app
Risk due to unauthorised access.
Incorrectly set parameters can negatively influence the public grid and/or the inverter feeding energy into the grid, and lead to a loss of conformity with the
standard.
The parameters may only be adjusted by installers/service technicians from
▶
authorised specialist companies.
Do not give the access code to third parties and/or unauthorised persons.
▶
The "Fronius Solar.start" app is needed for registration. Depending on the end
device, the app is available on the respective platform.
EN
Adjusting parameters with the
browser
Start the installation in the app.
1
Select the product to which the connection should be established.
2
3
Open the access point by touching the sensor once → Communication LED:
flashes blue.
Select the "Technician" user in the "User menu" and enter and confirm the
4
password for the "Technician" user.
Call up the "Safety and grid regulations" → "Country setup" menu area.
5
Enter the requested access code (see chapter Access code on page 4) in the
6
input field "Access code country setup" and click the button "Activate".
Adjust the parameters in the individual menu areas taking into account the
7
nationally applicable standards and/or the specifications of the energy provider.
WLAN:
1
Open the access point by touching the sensor once → Communication LED:
flashes blue.
5
Establish the connection to the inverter in the network settings (the inverter
169.254.0.180
21
open access point
2
is displayed with the name "FRONIUS_PILOT" and the serial number of the
device).
Password: enter 12345678 and confirm.
3
IMPORTANT!
To enter the password on a Windows 10 operating system, the link "Connect
using a security key instead" must first be activated to establish a connection
with the password: 12345678.
In the browser address bar, enter and confirm the IP address
4
192.168.250.181.
Select the "Technician" user in the "User menu" and enter and confirm the
5
password for the "Technician" user.
Call up the "Safety and grid regulations" → "Country setup" menu area.
6
Enter the requested access code (see chapter Access code on page 4) in the
7
input field "Access code country setup" and click the button "Activate".
Adjust the parameters in the individual menu areas taking into account the
8
nationally applicable standards and/or the specifications of the grid operator.
Ethernet:
Establish a connection to the inverter (LAN1) with a network cable (CAT5
1
STP or higher).
2
Open the access point by touching the sensor once → Communication LED:
flashes blue.
In the browser address bar, enter and confirm IP address 169.254.0.180.
3
Select the "Technician" user in the "User menu" and enter and confirm the
4
password for the "Technician" user.
Call up the "Safety and grid regulations" → "Country setup" menu area.
5
Enter the requested access code (see chapter Access code on page 4) in the
6
input field "Access code country setup" and click the button "Activate".
Adjust the parameters in the individual menu areas taking into account the
7
nationally applicable standards and/or the specifications of the grid operator.
6
Country setup
7
8
Country setup selection
EN
Country setup
selection
Predefined setups can be selected in the "Country setup selection" menu. The
selected country setup for the respective country contains preset parameters
according to the nationally applicable standards and requirements. Depending
on local grid conditions and the specifications of the energy provider, adjustments to the selected country setup may be necessary.
ParameterDescription
"Country / Region"Selecting the respective country or region limits/
displays the available country setups for the inverter.
"Country setup"Displays the available setups per country/region.
A setup is a device configuration predefined by
Fronius. The selection of the country setup must be
made in consideration of the applicable standards
or in coordination with the grid operator.
"Rated Frequency (Hz)"The rated frequency is predetermined by the coun-
try setup selection. Changing this parameter affects
the stable operation of the inverter and is therefore
only permitted in consultation with Fronius.
"Rated Voltage (V)"The rated voltage is predetermined by the choice of
the country setup. Changing this parameter affects
the stable operation of the inverter and is therefore
only permitted in consultation with Fronius.
9
General
Startup and Reconnection
These parameters can be used to set the grid monitoring times before the inverter is switched on.
For the set time, both the mains voltage and the grid frequency must be within
the permissible range before connection is allowed.
The permissible range for the mains voltage is defined in the menu area
-
"Grid and system protection" → "Voltage" → "Startup and reconnection"
(see chapter Voltage).
The permissible range for the grid frequency is defined in the menu area
-
"Grid and system protection " → " Frequency " → " Startup and reconnection" (see chapter Frequency).
ParameterRange of valuesDescription
"Grid Monitoring
Time Startup"
ParameterRange of valuesDescription
"Grid Monitoring
Time Reconnection"
1 - 900 [s]Grid monitoring time before the invert-
er is switched on during a normal startup process in seconds (e.g. at sunrise).
1 - 900 [s]Grid monitoring time before the invert-
er is switched back on after a grid fault
(see table "Grid faults") in seconds
(e.g. if a fault occurs in the AC grid during the day which causes the inverter to
shut down).
The following errors are defined by the inverter as grid errors for this functionality:
NameDescription"StateCode"
name
"Overvoltage"Mains voltage exceeds an
overvoltage limit ("Inner,
Middle, or Outer Limit
Overvoltage").
"Undervoltage"Mains voltage falls below
an undervoltage limit ("In-
ner, Middle or Outer Limit
Undervoltage").
"Overfrequency"Grid frequency exceeds an
overfrequency limit ("In-
ner, Outer or Alternative
Limit Overfrequency").
"Underfrequency"
Grid frequency falls below
an underfrequency limit
("Inner, Outer or Alternat-
ive Limit Underfrequency").
"AC voltage
too high"
"AC voltage
too low"
"AC frequency too
high"
"AC frequency too
low"
"StateCode"
number
1114
1119
1035
1037
10
"Fast Overvoltage Disconnect"
Triggering of the fast surge
protection (> 135%).
"Grid voltage
too high (fast
overvoltage
cut-out)"
1115, 1116
NameDescription"StateCode"
name
"Long Time Average Overvoltage
Limit"
Mains voltage exceeds the
long-term overvoltage limit ("Long Time Average
Limit").
"Long-term
mains
voltage limit
exceeded"
"StateCode"
number
1117
EN
"Unintentional Islanding Detection."
Ramp RatesRamp rates limit the maximum rate of change of effective power in special situ-
ations. Rising ramps ("Ramp-Up") limit the increase in effective power at the inverter AC output. Falling ramps ("Ramp-Down") limit the reduction of effective
power at the AC output of the inverter.
Note that the lowest rate of change is applied if there are multiple rate of change
specifications. An "Irradiation Ramp" can thus be rendered ineffective by, for ex-
ample, a lower "Startup Ramp" or another function affecting the rate of change
(e. g., P(U) or P(F)).
"Ramp-Up at Startup and Reconnection"
When connecting the inverter, the maximum rate of change of the effective
power can be limited by a rising ramp with a defined gradient. As soon as the effective power increase is influenced due to the available PV power or another
control, the ramp is terminated.
ParameterRange of valuesDescription
Unintentional islanding
was detected.
"Islanding
detected"
1004
"Ramp-Up at
Startup and Reconnection"
"Ramp-Up at
Startup and Reconnection Rate."
"Ramp-Up/Down Irradiation"
The "Irradiation Ramp" is a permanent limitation of the rate of change for the ef-
fective power. If the PV power changes rapidly due to passing clouds, the rate of
change of the inverter output power is limited with the "Ramp-Up Irradiation
Rate" or the "Ramp-Down Irradiation Rate".
ParameterRange of valuesDescription
"Ramp-Up Irradiation"
"Ramp-Up Irradiation Rate"
OnThe effective power is limited at the
"Startup" or a "Reconnection" with a
rate of change of "Ramp-Up at Startup
and Reconnection Rate".
OffThe function is deactivated.
0.001 ‑ 100
[%/s]
OnThe effective power increase is limited
OffThe function is deactivated.
0.001 - 200
[%/s]
Permitted rate of change of the effective power at "Startup" or "Reconnec-
tion".
with a rate of change of "Ramp-Up Ir-
radiation Rate".
Permitted rate of change during power
increase.
11
ParameterRange of valuesDescription
"Ramp-Down Irradiation"
Note: This func-
tion only has an
effect on inverters with storage.
"Ramp-Down Irradiation Rate"
Example: Effective power limitation by "Irradiation-Ramp-Up/Down", which was
caused by a change in the available PV power.
OnThe effective power reduction is limited
with a rate of change of "Ramp-Down
Irradiation Rate".
OffThe function is deactivated.
0.001 - 200
[%/s]
Permitted rate of change of effective
power.
"Ramp-Up/Down Communication"
This is a limitation of the effective power rate of change when changing external
specifications for effective power. These can be, for example, power limitations
via I/Os or Modbus commands. If smaller rates of change are specified via Modbus command, these are applied. Larger rates are limited by the parameter
"Ramp-Up Communication Rate" or "Ramp-Down Communication Rate".
ParameterRange of valuesDescription
"Ramp-Up Communication"
"Ramp-Up Communication Rate"
"Ramp-Down
Communication"
OnThe limitation of the rate of change
(corresponding to "Ramp-Up Commu-
nication Rate") in case of effective
power increase due to an external specification is activated.
OffThe function is deactivated.
0.001 ‑ 100
[%/s]
OnThe limitation of the rate of change
OffThe function is deactivated.
Permitted rate of change during power
increase.
(corresponding to "Ramp-Down Com-
munication Rate") in the event of ef-
fective power reduction due to an external specification is activated.
12
ParameterRange of valuesDescription
"Ramp-Down
Communication
Rate"
0.001 ‑ 100
[%/s]
Permitted rate of change for power reduction.
EN
13
Safety
Unintentional Islanding Detection
Unintentional islanding
In the event of a grid failure or disconnection of a small part of the grid from the
higher-level utility grid, it is possible under special conditions for local loads and
inverters to establish unintentional islanding. If the generation and load (of both
active and reactive power) are balanced, the AC voltage and frequency can remain within the allowable limits. In this case, the inverter (without additional islanding detection) will continue feeding energy into the grid, will not automatically shut down, and will supply power to the local loads. This is an unwanted condition. To prevent these situations, active or passive islanding detection methods
can be used.
Active islanding detection
The inverter's active islanding detection function detects unwanted islanding
situations, the inverter stops feeding energy into the grid and disconnects from
the AC grid at all poles.
The detection process is carried out using a grid frequency shift method (Active
Frequency Drift): In the event of short-term grid frequency changes, the inverter
feeds in an alternating current with a changed frequency (frequency shift). In the
event of an interruption to the grid, the AC voltage will also change its frequency.
There is a co-feedback effect, whereby the frequency is shifted so much that it
exceeds or falls below the permissible limits. This causes the inverter to stop
feeding energy into the grid.
In the case of three-phase inverters, the method is also able to detect islanding
on any individual phases. This function is an active islanding detection method,
since the inverter specifically changes its feed-in behaviour during the detection
process.
Standard
ParameterRange of values
"Unintentional
Islanding Detection."
"Quality Factor"0.1 ‑ 10.01.0The higher this value, the
In contrast, there are passive methods that detect islanding based only on the
measurement of AC network variables. This group includes, for example, "Rate of
Change of Frequency (RoCoF) Protection".
OnActive islanding detection
OffOffActive islanding detection
valueDescription
is activated.
is deactivated.
stronger/more aggressive
the frequency shift of the
island detection.
Higher values therefore
result in shorter island detection times. However,
values that are too high
can also have a negative
effect on the voltage quality.
Isolation monitoring
14
Isolation monitoring ("Iso Monitoring")
The inverter performs an isolation measurement at the DC terminals of the PV
generator before each connection (at least once a day). Isolation monitoring
must be activated for both the isolation warning and the isolation error.
Isolation Warning
The measured value of the isolation monitoring is used for an isolation warning.
Status code 1083 is displayed if the measured value falls below an adjustable
limit value.
Isolation Error
The measured value of the isolation monitoring is also used for isolation error
monitoring. If the measured isolation value is below the limit value "Isolation Er-
ror Threshold", feeding energy into the grid is prevented and status code 1082 is
displayed.
IMPORTANT!
For the "Isolation Monitoring" function, the parameters in the two menu sections described must be configured accordingly.
The parameters below in the menu item "Safety and grid regulations" →
1
"Country setup" → "Safety" → "Isolation monitoring" are used to configure
the parameters for the isolation measurement:
ParameterRange of valuesDescription
"Iso Monitoring
Mode"
OnThe function is activated.
OffThe function is deactivated.
Off (with Warning)
Isolation monitoring is deactivated and
status code 1189 is permanently displayed on the user interface of the inverter.
EN
"Isolation Error
Threshold"
0.1 ‑ 10 MOhmIf the measured isolation value is lower
than this value, feeding energy into the
grid is prevented (if isolation monitoring
is activated) and status code 1182 is
displayed on the user interface of the
inverter.
The parameters below in the menu item "Device configuration" → "Inverter"
2
→ "Iso warning" are used to configure the parameters for the isolation warning:
ParameterRange of valuesDescription
"Iso Warning"
OnThe isolation warning is activated.
If the isolation warning threshold is undershot, a warning occurs but not a
shutdown.
OffThe function is deactivated.
"Isolation measurement mode"
PreciseIsolation monitoring is performed with
the highest accuracy and the measured
insulation resistance is displayed on the
user interface of the inverter.
QuickIsolation monitoring is performed with
lower accuracy, which shortens the duration of the isolation measurement and
the isolation value is not displayed.
15
ParameterRange of valuesDescription
DC Arc Fault
Protection
"Isolation Warning Threshold"
These parameters can be used to set the behaviour of the arc detection at the
DC terminals of the inverter. The DC Arc Fault Protection function protects
against arc faults and contact faults. Any faults that occur in the current and
voltage curve are constantly evaluated and the current circuit is switched off if a
contact fault is detected. This prevents overheating on defective contacts and
possible fires.
Parameter
"Arc Fault Detection (AFD)"
0.1 ‑ 10 MOhmIf this value is undershot, status code
1183 is displayed on the user interface
of the inverter.
Range of valuesDescription
For activating and deactivating the arc
fault detection. The parameters "Arc logging" and "Automatic reconnects" are
only considered with activated "Arc Fault
Detection (AFD)".
OffArcs are not detected.
Off (with
Warning)
Arcs are not detected and status code
1184 is permanently displayed on the user
interface of the inverter.
"Arc-Fault Circuit Interrupter
(CI)"
OnThe arc detection is active.
Describes the behaviour in the event of a
detected arc and simultaneously activates/deactivates the integrated self-test.
OffThe detection of an arc does not cause the
inverter to shut down and is not displayed
on the user interface of the inverter.
Off (with
Warning)
OnIf an arc is detected, the inverter inter-
The detection of an arc does not cause the
inverter to shut down. The status code
1185 is permanently displayed on the user
interface of the inverter.
rupts feeding energy into the grid and the
status code 1006 is displayed on the user
interface of the inverter.
Depending on the configuration of the
parameter "Automatic Reconnects", the
inverter will attempt to restart feeding energy into the grid after 5 minutes. Furthermore, an integrated self-test is active,
which is executed at regular intervals. If
this fails, the inverter stops feeding energy
into the grid and status code 1009 is displayed.
16
Parameter
"Automatic Reconnects"
Range of valuesDescription
If more arcs have been detected within 24
hours than are defined in "Automatic Re-
connects", the inverter will not make any
further attempt to start feeding energy into the grid. The status code 1006 is displayed on the user interface of the inverter after each detection and must be acknowledged manually.
UnlimitedThe 24 hour counter is deactivated. The in-
verter restarts feeding energy into the grid
5 minutes after each arc detected.
EN
0 - No Reconnection
1 ‑ 4After a shutdown by an arc, 1, 2, 3 or 4 at-
"Arc Logging"Enables or disables the recording of arc
OffArc signatures are not recorded.
OnArc signatures are recorded, uploaded to
After an arc has been detected, no further
attempt is made to start feeding energy
into the grid and status code 1173 is displayed on the user interface of the inverter.
tempts are made within 24 hours to restart feeding energy into the grid. After
this number of attempts, no further attempt is made to start feeding energy into
the grid and status code 1173 is displayed
on the user interface of the inverter.
signatures. The data is uploaded to the
cloud and used to continuously improve
the interference immunity and fault tolerance of arc detection.
the cloud, and used to continuously improve the interference immunity and fault
tolerance of arc detection.
"Automatic Signal Recording"
Activates or deactivates recording of the
inverter's signal characteristics to continuously improve arc detection.
OffRecording is deactivated.
OnRecording is activated. With a probability
in accordance with the "Recording Prob-
ability" parameter, data is recorded and
uploaded to the cloud every 10 minutes.
17
Parameter
Range of valuesDescription
"Recording
Probability"
RCMUThe inverter is equipped with a universal current-sensitive residual current monit-
oring unit (RCMU) in accordance with IEC 62109-2. This unit monitors residual
currents from the PV module to the AC output of the inverter and disconnects
the inverter from the grid in the event of unauthorised residual current.
Parameter
If "Automatic Signal Recording (ASR)" is
activated, the frequency for a recording
can be set here.
0No signal characteristics are recorded.
0.0 ‑ 1.0Every 10 minutes, data is uploaded to the
cloud with a frequency in accordance with
the "Recording Probability".
Example:
With a setting value of 0.1, data is uploaded on average every 100 minutes.
1Data is recorded every 10 minutes.
Range of valuesDescription
"RCMU"OffThe protective function is deactivated.
Off (with
Warning)
OnThe protective function is activated.
The protective function is deactivated. The
status code 1188 is permanently displayed
on the user interface of the inverter.
18
Parameter
"Automatic Reconnects"
Range of valuesDescription
If more fault currents have been detected
within 24 hours than are defined in "Automatic Reconnects", the inverter will not
make any further attempt to start feeding
energy into the grid. The status code 1076
is displayed on the user interface of the inverter and must be acknowledged manually.
0No fault current above 300 mA is toler-
ated. After each detected fault current,
feeding energy into the grid is interrupted
and the status code must be acknowledged manually on the user interface of
the inverter.
1 ‑ 4After a shutdown due to a fault current ex-
ceeding 300 mA, 1, 2, 3 or 4 attempts are
made within 24 hours to restart feeding
energy into the grid. After this number of
attempts, no further attempt is made to
start feeding energy into the grid and the
status code must be acknowledged manually on the user interface of the inverter.
EN
DC Shutdown
Communication
UnlimitedThe 24 hour counter is deactivated. The in-
verter restarts feeding energy into the grid
after each detected fault current above
300 mA.
Devices for shutdown within the DC generator (e.g. in or on the module or within
a string) can be controlled by the inverter. The condition for this is compatibility,
especially with the communication of the inverter.
Range of val-
Parameter
"Powerline
Communication"
uesDescription
Activates and deactivates DC Powerline
Communication (PLC) on the inverter.
PLC OffDC Powerline Communication is deactiv-
ated on the inverter. There are no shutdown devices installed in the PV system,
or if shutdown devices are installed in the
PV system that are waiting for an enable
signal, then this signal must come from
another device (transmitter) (otherwise
the system will not function).
SunSpec PLCThe inverter communicates with DC-
Powerline Communication according to
the "SunSpec Rapid Shutdown Standard".
Compatible shutdown devices must be
used for the correct functioning of the PV
system.
19
Interface Protection
VoltageThis chapter deals with the protection settings for overvoltage and undervoltage.
Mains voltage limits are defined for this purpose. These depend on the country
setup and can be adjusted as described below.
Each mains voltage limit is defined by:
an undervoltage with associated protection time, or
-
an overvoltage with associated protection time.
-
The protection time describes the duration for which the voltage may be outside
the respective voltage limit value before the inverter switches off with an error
message.
Three overvoltage and three undervoltage limit values can be used. The "Inner
Limits" (U< for undervoltage; U>for overvoltage) refer to those limit values which
are closer to the nominal voltage. The "Middle Limits" (U< for undervoltage;
U>for overvoltage) have a greater distance to the nominal voltage. The greatest
distance between the nominal voltage and the limit value is for the "Outer Lim-
its" (U<< for undervoltage; U>> for overvoltage).
For expedient use of the "Inner Limits" and "Outer Limits", the respective "In-
ner Limit" must be linked to a greater time than the "Outer Limit". If the "Middle
Limits" are also used, their time between "Inner Limit" and "Outer Limit" must
value
OL"Outer limit" - outer limit value
(1)Trip range
OVOvervoltage
UVUndervoltage
t
Graphic illustrating the limits
These voltage limit values are not active in backup power mode. Under "Device
configuration" → " Inverter" → "Backup power", the voltage limits that apply in
backup power mode can be configured.
"Inner Limits"
Protection time
x
20
ParameterDescription
"Undervoltage U<"Setting value for undervoltage protection U< in [V]
"Undervoltage Time U<"Setting value of time for undervoltage protection
U< in [s]
"Overvoltage U>"Setting value for surge protection U> in [V]
"Overvoltage Time U>"Setting value of time for surge protection U> in [s]
"Middle Limits"
ParameterDescription
"Voltage Middle Limits"Activate / deactivate the middle voltage limit values
"On" / "Off"
"Undervoltage U<"Setting value for undervoltage protection U< in [V]
"Undervoltage Time U<"Setting value of time for undervoltage protection
U< in [s]
"Overvoltage U>"Setting value for surge protection U> in [V]
"Overvoltage Time U>"Setting value of time for surge protection U> in [s]
"Outer Limits"
ParameterDescription
"Voltage Outer Limits"Activate / deactivate the outer voltage limit values
"On" / "Off"
"Undervoltage U<<"Setting value for undervoltage protection U<< in [V]
"Undervoltage Time
U<<"
"Overvoltage U>>"Setting value for surge protection U>> in [V]
Setting value of time for undervoltage protection
U<< in [s]
EN
"Overvoltage Time U>>"Setting value of time for surge protection U>> in [s]
"Long Time Average Limit"
This function calculates a moving average voltage value over the set time and
compares it with the set overvoltage protection value. If the overvoltage protection value is exceeded, a disconnect occurs.
ParameterDescription
"Long Time Average
Limit"
"Overvoltage Averaging
Time U>"
"Overvoltage U>"Setting value of the surge protection with average
"Fast Overvoltage Disconnect"
Fast overvoltage disconnect for voltage spikes that can respond within one period.
ParameterDescription
Activate / deactivate the voltage average limit value
"On" / "Off"
Time period over which the average value is calculated in [s]. (If 0 s is set, the check is not active)
value formation U> in [V]
"Fast Overvoltage Disconnect"
"Fast Overvoltage Disconnect Time"
"Startup and Reconnection"
Before the inverter is allowed to connect, the connection conditions for voltage
Activate / deactivate fast RMS overvoltage disconnect (exceeding 135 % of rated voltage) "On" / "Off"
Setting value of time for fast surge protection (peak
value exceeded by 35 %) in [s]. This disconnect can
be configured in the time range of microseconds.
21
and frequency must be fulfilled for a certain time.
A distinction is made between:
"Startup": switching on the inverter during a normal startup process (e. g. at
-
sunrise) and
"Reconnection": the reconnection of the inverter after a grid fault (see table
-
"Grid faults") (e. g. if a fault occurs in the AC grid during the day which
causes the inverter to disconnect).
Which limit values are used when checking the connection conditions depends
on whether a mains fault has occurred and which "Mode" is defined. The "Mode"
only influences the limit values and not the monitoring time. The monitoring time
is determined by the parameters described in "General" / "Startup and Recon-
nection". The monitoring time used depends on whether it is "Startup" or "Reconnection" and applies equally to frequency and voltage limits. After the grid
monitoring has expired, the previously mentioned "Interface Protection" values
are active. In backup power mode these "Startup and Reconnection" parameters
are not active.
ParameterDescription
"Mode"The following modes are available:
"Startup Values are used for Startup / Recon-
-
nection Values are used for Reconnection": In
a normal startup process, the startup values
are used as connection conditions. When reconnecting after a mains fault, the reconnection values are used as connection conditions.
"Startup Values are used for Startup and Re-
-
connection": Regardless of the type of con-
nection, the startup values are always used as
connection conditions.
"Reconnection Minimum Voltage"
"Reconnection Maximum Voltage"
"Startup Minimum
Voltage"
"Startup Maximum
Voltage"
The following errors are defined by the inverter as grid errors for this functionality:
NameDescription"StateCode"
"Overvoltage"Mains voltage exceeds an
overvoltage limit ("Inner,
Middle, or Outer Limit
Overvoltage").
"Undervoltage"Mains voltage falls below
an undervoltage limit ("In-
ner, Middle or Outer Limit
Undervoltage").
Lower value of the voltage for reconnection in [V]
Upper value of the voltage for reconnection in [V]
Lower value of the voltage for the normal start process in [V]
Upper value of the voltage for the normal start process in [V]
"StateCode"
name
"AC voltage
too high"
"AC voltage
too low"
number
1114
1119
22
NameDescription"StateCode"
name
"Overfrequency"Grid frequency exceeds an
overfrequency limit ("In-
ner, Outer or Alternative
Limit Overfrequency").
"AC frequency too
high"
"StateCode"
number
1035
EN
"Underfrequency"
"Fast Overvoltage Disconnect"
"Long Time Average Overvoltage
Limit"
"Unintentional Islanding Detection."
FrequencyThis chapter deals with the protection settings for overfrequencies and underfre-
quencies. Grid frequency limit values are defined for this purpose. These depend
on the country setup and can be adjusted as described below.
Grid frequency falls below
an underfrequency limit
("Inner, Outer or Alternat-
ive Limit Underfrequency").
Triggering of the fast surge
protection (> 135%).
Mains voltage exceeds the
long-term overvoltage limit ("Long Time Average
Limit").
Unintentional islanding
was detected.
"AC frequency too
low"
"Grid voltage
too high (fast
overvoltage
cut-out)"
"Long-term
mains
voltage limit
exceeded"
"Islanding
detected"
1037
1115, 1116
1117
1004
Each frequency limit value is defined by:
an underfrequency with associated protection time, or
-
an overfrequency with associated protection time.
-
The protection time describes the duration for which the frequency may be outside the respective frequency limit value before the inverter switches off with an
error message. Two overfrequency and two underfrequency limit values can be
used. The "Inner Limits" (f< for underfrequency; f>for overfrequency) are those
limit values which are closer to the rated frequency than the "Outer Limits" (f<<
for underfrequency; f>> for overfrequency). For the sensible use of both ranges,
the respective "Inner Limit" must be linked to a larger time than the "Outer Lim-
it".
23
IL"Inner limit" - inner limit value
OL"Outer limit" - outer limit value
(1)Trip range
OFOverfrequency
UFUnderfrequency
Graphic illustrating the limits
In backup power mode, the inverter itself determines the frequency and the frequency limits are therefore not active.
"Inner Limits"
ParameterDescription
"Underfrequency f<"Setting value of underfrequency protection f< in
[Hz]
"Underfrequency Time
f<"
Setting value of time for underfrequency protection
f< in [s]
"Overfrequency f>"Setting value of overfrequency protection f> in [Hz]
"Overfrequency Time
f>"
Setting value of time for overfrequency protection
f> in [s]
"Outer Limits"
ParameterDescription
"Frequency Outer Limits"
Activate / deactivate the outer frequency limits
"On" / "Off"
"Underfrequency f<<"Setting value of underfrequency protection f<< in
[Hz]
"Underfrequency Time
f<<"
Setting value of time for underfrequency protection
f<< in [s]
"Overfrequency f>>"Setting value of overfrequency protection f<< in
[Hz]
24
"Overfrequency Time
f>>"
Setting value of time for the overfrequency protection f>> in [s]
"Alternative Limits"
For the inner frequency limit values there is an additional second parameter set,
which is only relevant for Italy. In order to activate this second parameter set, the
alternative frequency limit value must be set to "On" on the user interface of the
inverter and activated/deactivated via an external signal as follows: