Fronius prints on elemental chlorine free paper (ECF) sourced from certified sustainable forests (FSC).
/ Perfect Charging / Perfect Welding / Solar Energy
Fronius Symo Hybrid
Wiring examples emergency
power switchover
Installation instructions
EN
Grid-connected inverter
42,0426,0209,EN 015-22092020
Page 2
Page 3
Contents
General4
General4
Cabling variants including emergency power circuits and 3-pin separation e.g. Austria or Australia5
Circuit diagram5
Functions5
Cabling for emergency power circuit and non-emergency power circuits5
Transition from feeding energy into the grid to emergency power mode6
Transition from emergency power mode to feeding energy into the grid 6
Cabling variants including emergency power circuits with grid and system protection and 3-pin separation e.g. Austria
Circuit diagram7
Functions7
Cabling for emergency power circuits and non-emergency power circuits7
Transition from feeding energy into the grid to emergency power mode8
Transition from emergency power mode to feeding energy into the grid 9
Cabling variants including emergency power circuits and 4-pin separation e.g. Germany10
Circuit diagram10
Functions10
Cabling for emergency power circuits and non-emergency power circuits10
Transition from feeding energy into the grid to emergency power mode11
Transition from emergency power mode to feeding energy into the grid 12
Cabling variants including emergency power circuits with grid and system production and 4-pin separation e.g. Germany
Circuit diagram13
Functions13
Cabling for emergency power circuits and non-emergency power circuits13
Transition from feeding energy into the grid to emergency power mode14
Transition from emergency power mode to feeding energy into the grid 15
Cabling variants including emergency power circuits with grid and system protection and 4-pin separation, e.g. Italy
Circuit diagram16
Functions16
Cabling for emergency power circuits and non-emergency power circuits16
Transitioning from feeding energy into the grid to backup power mode18
Transition from emergency power mode to feeding energy into the grid 18
Description of components19
Description of components for full version19
Emergency power configuration21
Requirements21
Emergency power configuration - overview21
Accessing the CONFIG menu21
Selecting alternative (emergency power) setup22
Configuring the digital I/Os on the Fronius Datamanager22
Configuring the system overview on the Fronius Datamanager 23
Configuring the energy management on the Fronius Datamanager (option) 23
EN
7
13
16
Appendix25
3-pin separation Austria with Solar Battery26
3-pin separation Australia with Solar Battery27
3-pin separation Austria with BYD28
3-pin separation Australia with BYD29
3-pin separation with grid and system protection Austria with Solar Battery30
4-pin separation Germany with Solar Battery31
4-pin separation Germany with BYD32
4-pin separation with grid and system protection Germany with Solar Battery33
4-pin seperation with grid and system protection Italy with Solar Battery34
Fronius Symo Hybrid and BYD Battery-Box Premium HV35
3
Page 4
General
GeneralThe examples given in this document (in particular cabling variants and Circuit Dia-
grams) are suggestions only. These examples have been carefully developed and
tested. They can therefore be used as a basis for real-life installation. Anyone following
or using these examples does so at their own risk.
IMPORTANT!
The applicable national laws, standards and regulations as well as the specifications of
the respective grid operator must be taken into account and applied.
It is strongly recommended to coordinate the concrete examples implemented and in
particular the specific installation with the grid operator to obtain their explicit approval.
This obligation applies to system constructors in particular (e.g. installers).
The examples suggested here show a backup power supply with or without an external
protection relay (external grid and system protection unit). Whether an external protection relay must be used or not is the decision of the respective grid operator.
IMPORTANT!
No uninterruptible power supply (UPS) must be operated in the backup power circuit.
The Installation and Operating Instructions must be read carefully prior to use. If anything
is unclear, contact your vendor immediately.
WARNING!
Any incorrect installation, commissioning, operation or usage can cause serious
personal injury and/or property damage.
Only trained and qualified personnel are authorised to install and commission the system, and only within the scope of the technical regulations.
4
Page 5
Cabling variants including emergency power circuits and 3-pin separation e.g. Austria or Australia
Circuit diagramThe circuit diagram for the cabling variant „3-pin separation Austria with Solar Bat-
tery“ can be found in the appendix to this document on page 26.
The circuit diagram for the cabling variant „3-pin separation Australia with Solar Bat-
tery“ can be found in the appendix to this document on page 27.
The circuit diagram Fronius Symo Hybrid and BYD Battery-Box Premium HV can be
found in the appendix to this document on page 35.
The circuit diagram for the cabling variant „3-pin separation Austria with BYD“ can be
found in the appendix to this document on page 28 .
The circuit diagram for the cabling variant „3-pin separation Australia with BYD“ can
be found in the appendix to this document on page 29.
Functions-Measuring and transferring the required parameters for energy management and
Solar.web by the Fronius Smart Meter
-Disconnecting from the public grid to enable operation in emergency power mode if
the grid parameters are outside the country-specific standards.
-Reconnecting to the public grid when the grid parameters are within the limits specified by the country-specific standards.
-Option of having a separate emergency power circuit or several emergency power
circuits that are supplied even during failure of the public grid. The total load of the
emergency power circuits must not exceed the nominal output of the inverter. Furthermore, the performance of the attached battery must also be considered. The
other circuits are not supplied in the event of a power failure.
EN
Cabling for emergency power circuit and nonemergency power
circuits
The use of contactor K2 is optional in Australia.
If not all the consumers in the home need to be supplied in an emergency power situation, the circuits need to be divided into emergency power circuits and non-emergency
power circuits.
The total load of the emergency power circuits must not exceed the nominal output of the
inverter.
The emergency power circuits and non-emergency power circuits must be fused separately according to the required safety measures (residual-current circuit breaker, automatic circuit breaker, etc.).
In emergency power mode, only the emergency power circuits are disconnected from the
grid by contactors K1 and K2 3-pin (L1, L2 and L3). The rest of the home network is not
supplied with power in this case
5
Page 6
The following points regarding cabling must be considered:
-The main contacts of contactors K1 and K2 must be installed between the Fronius
Smart Meter and the residual-current circuit breaker of the inverter or the residualcurrent circuit breaker of the emergency power circuits.
-The supply voltage for contactors K1 and K2 is provided by the public grid and must
be connected to phase 1 (L1) after the Fronius Smart Meter and fused accordingly.
-An NC contact for relay K3 interrupts the supply voltage to contactors K1 and K2.
This prevents the emergency power network of the inverter from being switched to
the public grid.
-The NO contact of relay K3 gives feedback to the inverter on whether the locking
was successfully performed by relay K3.
-Additional inverters or other AC sources can be installed in the emergency power
circuit after the main contacts of K1 and K2. The sources are not synchronised to
the network of the Fronius Symo Hybrid because this emergency power network has
a frequency of 53 Hz.
Transition from
feeding energy
into the grid to
emergency power
mode
Transition from
emergency power
mode to feeding
energy into the
grid
1.The public grid is monitored by the inverter's internal grid and system protection unit
and by the Fronius Smart Meter connected to it.
2.Failure of the public grid
3.The inverter carries out the necessary measures according to the country standard
and then switches off.
Contactors K1 and K2 drop out. This disconnects the emergency power circuits and
the inverter from the rest of the home network and from the public grid, as the main
contacts of the contactors K1 and K2 3-pin open.The NC auxiliary contacts of contactors K1 and K2 send feedback to the inverter that the contactors are open (a condition for starting the emergency power mode).
4.The inverter activates relay K3, which interrupts the supply to contactors K1 and K2.
This prevents unintentional activation of contactors K1 and K2 and thus a grid connection when voltage is restored in the grid.
5.The NO contact of relay K3 gives optional feedback to the inverter on whether the
locking was successfully performed by relay K3.
6.Based on the feedback from the contactors and the measurements at the inverter
terminals and at the Smart Meter, the inverter decides that emergency power mode
can be started.
7.The inverter starts emergency power mode after a defined checking period
8.All loads in the emergency power circuits are supplied with power. The remaining
loads are not supplied with power and are safely isolated.
1.The inverter is operating in emergency power mode. The contactors K1 and K2 to
the public grid are open.
2.Public grid available again
3.The Fronius Smart Meter monitors the grid parameters on the public grid and
passes this information to the inverter.
4.After a defined measuring period, the restored public grid is deemed to be stable.
5.The inverter ends emergency power mode and disconnects the outputs.
6.The inverter deactivates K3. The contactors K1 and K2 are reactivated.
7.All circuits are reconnected to the public grid and are supplied by the grid. The
inverter, therefore, does not feed anything into the grid.
8.The inverter can start feeding energy into the grid again after performing the grid
checks required by the country standard.
6
Page 7
Cabling variants including emergency power circuits with grid and system protection and 3-pin
separation e.g. Austria
Circuit diagramThe circuit diagram "3-pin separation with grid and system protection Austria with
Solar Battery" can be found in the appendix to this document on page 30.
Functions-Measuring and transferring the required parameters for energy management and
Solar.web by the Fronius Smart Meter.
-Monitoring of the voltage and frequency grid parameters by the grid and system protection unit.
-Disconnecting from the public grid to enable operation in emergency power mode if
the grid parameters are outside the country-specific standards.
-Reconnecting to the public grid when the grid parameters are within the limits specified by the country-specific standards.
-Option of having a separate emergency power circuit or several emergency power
circuits that are supplied even during failure of the public grid. The total load of the
emergency power circuits must not exceed the nominal output of the inverter. Furthermore, the performance of the attached battery must also be considered. The
other circuits are not supplied in the event of a power failure.
EN
Cabling for emergency power circuits and nonemergency power
circuits
If not all the consumers in the home need to be supplied in an emergency power situation, the circuits need to be divided into emergency power circuits and non-emergency
power circuits.
The total load of the emergency power circuits must not exceed the nominal output of the
inverter.
The emergency power circuits and non-emergency power circuits must be fused separately according to the required safety measures (residual-current circuit breaker, automatic circuit breaker, etc.).
In emergency power mode, only the emergency power circuits are disconnected from the
grid by contactors K1 and K2 3-pin (L1, L2 and L3). The rest of the home network is not
supplied with power in this case.
7
Page 8
The following points regarding cabling must be considered:
-The main contacts of contactors K1 and K2 must be installed between the Fronius
Smart Meter and the residual-current circuit breaker of the inverter or the residualcurrent circuit breaker of the emergency power circuits.
-The supply voltage for contactors K1 and K2 is provided by the public grid and must
be connected to phase 1 (L1) after the Fronius Smart Meter and fused accordingly.
-Actuation of contactors K1 and K2 is carried out by the external grid and system protection unit.
-The external grid and system protection unit must be installed after the Fronius
Smart Meter. Precise installation and cabling notes for the external grid and system
protection unit can be found in its separate Operating Instructions.
-The remote trip input of the external grid and system protection unit must be set to
NC according to the manufacturer's Operating Instructions.
-An NC contact for relay K3, which activates the remote input of the external grid and
system protection unit, interrupts the supply voltage to contactors K1 and K2. This
prevents the emergency power network of the inverter from being switched to the
public grid.
-The NO contact of relay K3 gives feedback to the inverter on whether the locking
was successfully performed by relay K3.
-Additional inverters or other AC sources can be installed in the emergency power
circuit after the main contacts of K1 and K2. The sources are not synchronised to
the network of the Fronius Symo Hybrid because this emergency power network has
a frequency of 53 Hz.
Transition from
feeding energy
into the grid to
emergency power
mode
1.The public grid is monitored by the inverter's internal grid and system protection unit
and by an external grid and system protection unit.
2.Failure of the public grid
3.The inverter carries out the measures necessary according to the country standard
and then switches off.
4.The external grid and system protection unit opens contactors K1 and K2 for grid
monitoring. This disconnects the emergency power circuits and the inverter from the
rest of the home network and from the public grid, as the main contacts of the contactors K1 and K2 3-pin open. To ensure that the public grid has definitely been disconnected, the NC auxiliary contacts of contactors K1 and K2 give feedback to the
external grid and system protection unit.
5.The NC main contact of contactor K4 gives feedback to the inverter that the grid was
disconnected by the external ENS.
6.The inverter activates relay K3, which activates the remote input of the external grid
and system protection unit via an NC contact. This prevents a connection to the public grid when power returns.
7.The NO contact of relay K3 gives optional feedback to the inverter on whether the
locking was successfully performed by relay K3.
8.The inverter decides based on the contactor's feedback as well as the measurement
on the inverter terminals and the Smart Meter that the emergency power mode can
be activated.
9.The inverter starts emergency power mode after a defined checking period.
10. All loads in the emergency power circuits are supplied with power. The remaining
loads are not supplied with power and are safely isolated.
8
Page 9
Transition from
emergency power
mode to feeding
energy into the
grid
1.The inverter is operating in emergency power mode. The contactors K1 and K2 to
the public grid are open.
2.Public grid available again
3.The Fronius Smart Meter monitors the grid parameters on the public grid and
passes this information to the inverter.
4.After a defined measuring period, the restored public grid is deemed to be stable.
5.On the basis of adjustments that have been carried out, the inverter ends emergency power mode and disconnects the outputs.
6.The inverter deactivates K3. The external grid and system protection unit switches
the contactors K1 and K2 after performing the grid checks required by the applicable
standards.
7.All circuits are reconnected to the public grid and are supplied by the grid.
8.The inverter can start feeding energy into the grid again after performing the grid
checks required by the country standard.
EN
9
Page 10
Cabling variants including emergency power circuits and 4-pin separation e.g. Germany
Circuit diagramThe circuit diagram for the cabling variant "4-pin separation Germany with Solar Bat-
tery" can be found in the appendix to this document on page 31.
The circuit diagram Fronius Symo Hybrid and BYD Battery-Box Premium HV can be
found in the appendix to this document on page 35.
The circuit diagram for the cabling variant "4-pin separation Germany with BYD" can
be found in the appendix to this document on page 32.
Functions-Measuring and transferring the required parameters for energy management and
Solar.web by the Fronius Smart Meter.
-Disconnecting from the public grid to enable operation in emergency power mode if
the grid parameters are outside the country-specific standards.
-Reconnecting to the public grid when the grid parameters are within the limits specified by the country-specific standards.
-Establishing a proper ground connection for emergency power mode to ensure the
protection devices function correctly.
-Option of having a separate emergency power circuit or several emergency power
circuits that are supplied even during failure of the public grid. The total load of the
emergency power circuits must not exceed the nominal output of the inverter. Furthermore, the performance of the attached battery must also be considered. The
other circuits are not supplied in the event of a power failure.
Cabling for emergency power circuits and nonemergency power
circuits
If not all the consumers in the home need to be supplied in an emergency power situation, the circuits need to be divided into emergency power circuits and non-emergency
power circuits.
The total load of the emergency power circuits must not exceed the nominal output of the
inverter.
The emergency power circuits and non-emergency power circuits must be fused separately according to the required safety measures (residual-current circuit breaker, automatic circuit breaker, etc.).
In emergency power mode, only the emergency power circuits are disconnected at all
pins from the grid by contactors K1 and K2; a ground connection is only established for
these circuits. The rest of the home network is not supplied with power in this case.
10
Page 11
The following points regarding cabling must be considered:
-The main contacts of contactors K1 and K2 must be installed between the Fronius
Smart Meter and the residual-current circuit breaker of the inverter or the residualcurrent circuit breaker of the emergency power circuits.
-The supply voltage for contactors K1 and K2 is provided by the public grid and must
be connected to phase 1 (L1) after the Fronius Smart Meter and fused accordingly.
-To ensure residual-current circuit breakers function in emergency power mode, the
connection between the neutral conductor and the ground conductor must be established as close as possible to the inverter, but in any case before the first residualcurrent circuit breaker. An NC contact is used for this purpose for each of the main
contacts of contactors K4 and K5. This ensures that the ground connection is established as soon as the public grid connection is no longer available.
-As with contactor K1, the supply voltage for contactors K4 and K5 is provided via
phase 1 (L1) of the public grid.
-An NC contact for the relay K3 interrupts the supply voltage to contactors K1, K2, K4
and K5. This prevents the ground connection from being immediately disconnected
again when power returns to the public grid and the emergency power network of
the inverter from being switched to the public grid.
-The NO contact of relay K3 gives feedback to the inverter on whether the locking
was successfully performed by relay K3.
-Additional inverters or other AC sources can be installed in the emergency power
circuit after the main contacts of K1 and K2. The sources are not synchronised to
the network of the Fronius Symo Hybrid because this emergency power network has
a frequency of 53 Hz.
EN
Transition from
feeding energy
into the grid to
emergency power
mode
1.The public grid is monitored by the inverter's internal grid and system protection unit
and by the Fronius Smart Meter connected to it.
2.Failure of the public grid
3.The inverter carries out the necessary measures according to the country standard
and then switches off.
Contactors K1 and K2, as well as K4 and K5, drop out. This disconnects the emergency power circuits and the inverter from the rest of the home network and from the
public grid, as the main contacts of the contactors K1 and K2 open at all pins. The
NC auxiliary contacts of contactors K1 and K2 send feedback to the inverter that the
contactors are open (a condition for starting the emergency power mode).
4.The NC main contacts of contactors K4 and K5 are closed, establishing a connection between the neutral conductor and the ground conductor. The two other NC
main contacts of contactors K4 and K5 give feedback to the inverter that the ground
connection has been established correctly (a condition for starting the emergency
power mode).
5.The inverter activates relay K3, which interrupts the supply to contactors K1, K2, K4
and K5. This prevents unintentional activation of contactors K1, K2, K4 and K5 and
thus a grid connection when voltage is restored in the grid.
6.The NO contact of relay K3 gives additional feedback to the inverter on whether the
locking was successfully performed by relay K3.
7.The inverter decides based on the contactors' feedback as well as the measurements on the inverter terminals and the Smart Meter that the emergency power
mode can be activated.
8.The inverter starts emergency power mode after a defined checking period
9.All loads in the emergency power circuits are supplied with power. The remaining
loads are not supplied with power and are safely isolated.
11
Page 12
Transition from
emergency power
mode to feeding
energy into the
grid
1.The inverter is operating in emergency power mode. The contactors K1 and K2 to
the public grid are open.
2.Public grid available again
3.The Fronius Smart Meter monitors the grid parameters on the public grid and
passes this information to the inverter.
4.After a defined measuring period, the restored public grid is deemed to be stable.
5.The inverter ends emergency power mode and disconnects the outputs.
6.The inverter deactivates K3. The contactors K1, K2, K4 and K5 are reactivated.
7.All circuits are reconnected to the public grid and are supplied by the grid. The
inverter, therefore, does not feed anything into the grid.
8.The inverter can start feeding energy into the grid again after performing the grid
checks required by the country standard.
12
Page 13
Cabling variants including emergency power circuits with grid and system production and 4-pin
separation e.g. Germany
Circuit diagramThe circuit diagram "4-pin separation with grid and system protection Germany
with Solar Battery" can be found in the appendix to this document on page 33.
Functions-Measuring and transferring the required parameters for energy management and
Solar.web by the Fronius Smart Meter.
-Monitoring of the voltage and frequency grid parameters by the grid and system protection unit.
-Disconnecting from the public grid to enable operation in emergency power mode if
the grid parameters are outside the country-specific standards.
-Reconnecting to the public grid when the grid parameters are within the limits specified by the country-specific standards.
-Establishing a proper ground connection for emergency power mode to ensure the
protection devices function correctly.
-Option of having a separate emergency power circuit or several emergency power
circuits that are supplied even during failure of the public grid. The total load of the
emergency power circuits must not exceed the nominal output of the inverter. Furthermore, the performance of the attached battery must also be considered. The
other circuits are not supplied in the event of a power failure.
EN
Cabling for emergency power circuits and nonemergency power
circuits
If not all the consumers in the home need to be supplied in an emergency power situation, the circuits need to be divided into emergency power circuits and non-emergency
power circuits.
The total load of the emergency power circuits must not exceed the nominal output of the
inverter.
The emergency power circuits and non-emergency power circuits must be fused separately according to the required safety measures (residual-current circuit breaker, automatic circuit breaker, etc.).
In emergency power mode, only the emergency power circuits are disconnected from the
grid by contactors K1 and K2; a ground connection is only established for these circuits.
The rest of the home network is not supplied with power in this case.
13
Page 14
The following points regarding cabling must be considered:
-The main contacts of contactors K1 and K2 must be installed between the Fronius
Smart Meter and the residual-current circuit breaker of the inverter or the residualcurrent circuit breaker of the emergency power circuits.
-The supply voltage for contactors K1 and K2 is provided by the public grid and must
be connected to phase 1 (L1) after the Fronius Smart Meter and fused accordingly.
-Actuation of contactors K1 and K2 is carried out by the external grid and system protection unit.
-The external grid and system protection unit must be installed after the Fronius
Smart Meter. Precise installation and cabling notes for the external grid and system
protection unit can be found in its separate Operating Instructions
-The remote trip input of the external grid and system protection unit must be set to
NC according to the manufacturer's Operating Instructions.
-To ensure residual-current circuit breakers function in emergency power mode, the
connection between the neutral conductor and the ground conductor must be established as close as possible to the inverter, but in any case before the first residualcurrent circuit breaker. An NC contact is used for this purpose for each of the main
contacts of contactors K4 and K5. This ensures that the ground connection is established as soon as the public grid connection is no longer available.
-As with contactor K1, the supply voltage for contactors K4 and K5 is provided via
phase 1 (L1) of the public grid and is switched via the grid and system protection.
-An NC contact for relay K3, which activates the remote input of the external grid and
system protection unit, interrupts the supply voltage to contactors K1, K2, K4 and
K5. This prevents the ground connection from being immediately disconnected
again when power returns to the public grid and the emergency power network of
the inverter from being switched to the public grid.
-The NO contact of relay K3 gives feedback to the inverter on whether the locking
was successfully performed by relay K3.
-Additional inverters or other AC sources can be installed in the emergency power
circuit after the main contacts of K1 and K2. The sources are not synchronised to
the network of the Fronius Symo Hybrid because this emergency power network has
a frequency of 53 Hz.
Transition from
feeding energy
into the grid to
emergency power
mode
1.The public grid is monitored by the inverter's internal grid and system protection unit
and by an external grid and system protection unit.
2.Failure of the public grid
3.The inverter carries out the measures necessary according to the country standard
and then switches off.
4.The external grid and system protection unit opens contactors K1 and K2 for grid
monitoring. This disconnects the emergency power circuits and the inverter from the
rest of the home network and from the public grid, as the main contacts of the contactors K1 and K2 open at all pins. To ensure that the public grid has definitely been
disconnected, the NC auxiliary contacts of contactors K1 and K2 give feedback to
the external grid and system protection unit.
5.The NC main contacts of contactors K4 and K5 are closed, establishing a connection between the neutral conductor and the ground conductor. The two other NC
main contacts of contactors K4 and K5 give feedback to the inverter that the ground
connection has been established correctly (a condition for starting the emergency
power mode).
6.The inverter activates relay K3, which activates the remote input of the external ENS
via an NC contact. This prevents a connection to the public grid when power returns.
7.The NO contact of relay K3 gives optional feedback to the inverter on whether the
locking was successfully performed by relay K3.
8.The inverter decides based on the contactor's feedback as well as the measurements on the inverter terminals and the Smart Meter that the emergency power
mode can be activated.
9.The inverter starts emergency power mode after a defined checking period.
10. All loads in the emergency power circuits are supplied with power. The remaining
loads are not supplied with power and are safely isolated.
14
Page 15
Transition from
emergency power
mode to feeding
energy into the
grid
1.The inverter is operating in emergency power mode. The contactors K1 and K2 to
the public grid are open.
2.Public grid available again
3.The Fronius Smart Meter monitors the grid parameters on the public grid and
passes this information to the inverter.
4.After a defined measuring period, the restored public grid is deemed to be stable.
5.On the basis of adjustments that have been carried out, the inverter ends emergency power mode and disconnects the outputs.
6.The inverter deactivates K3. The external grid and system protection unit switches
the contactors K1, K2, K4 and K5 after performing the grid checks required by the
applicable standards.
7.All circuits are reconnected to the public grid and are supplied by the grid.
8.The inverter can start feeding energy into the grid again after performing the grid
checks required by the country standard.
EN
15
Page 16
Cabling variants including emergency power circuits with grid and system protection and 4-pin
separation, e.g. Italy
Circuit diagramThe circuit diagram "4-pin seperation with grid and system protection Italy with
Solar Battery" can be found in the appendix to this document on page 34.
Functions-Measuring and transferring the required parameters for energy management and
Solar.web by the Fronius Smart Meter.
-Monitoring of the voltage and frequency grid parameters by the grid and system protection unit.
-Disconnecting from the public grid to enable operation in emergency power mode if
the grid parameters are outside the country-specific standards.
-Reconnecting to the public grid when the grid parameters are within the limits specified by the country-specific standards.
-Establishing a proper ground connection for emergency power mode to ensure the
protection devices function correctly.
-Option of having a separate emergency power circuit or several emergency power
circuits that are supplied even during failure of the public grid. The total load of the
emergency power circuits must not exceed the nominal output of the inverter. Furthermore, the performance of the attached battery must also be considered. The
other circuits are not supplied in the event of a power failure.
Cabling for emergency power circuits and nonemergency power
circuits
If not all the consumers in the home need to be supplied in an emergency power situation, the circuits need to be divided into emergency power circuits and non-emergency
power circuits.
The total load of the emergency power circuits must not exceed the nominal output of the
inverter.
The emergency power circuits and non-emergency power circuits must be fused separately according to the required safety measures (residual-current circuit breaker, automatic circuit breaker, etc.).
In emergency power mode, only the emergency power circuits are disconnected at all
pins from the grid by contactors K1 and K2; a ground connection is only established for
these circuits. The rest of the home network is not supplied with power in this case.
16
Page 17
The following points regarding cabling must be considered:
-The main contacts of contactors K1 and K2 must be installed between the Fronius
Smart Meter and the residual-current circuit breaker of the inverter or the residualcurrent circuit breaker of the emergency power circuits.
-The supply voltage for contactors K1 and K2 is provided by the public grid and must
be connected to phase 1 (L1) after the Fronius Smart Meter and fused accordingly.
-Actuation of contactors K1 and K2 is carried out by the external grid and system protection unit.
-The external grid and system protection unit must be installed after the Fronius
Smart Meter. Precise installation and cabling notes for the external grid and system
protection unit can be found in its separate Operating Instructions
-The remote trip input of the external grid and system protection unit must be set to
NC according to the manufacturer's Operating Instructions.
-To ensure residual-current circuit breakers function in emergency power mode, the
connection between the neutral conductor and the ground conductor must be established as close as possible to the inverter, but in any case before the first residualcurrent circuit breaker. An NC contact is used for this purpose for each of the main
contacts of contactors K4 and K5. This ensures that the ground connection is established as soon as the public grid connection is no longer available.
-As with contactor K1, the supply voltage for contactors K4 and K5 is provided via
phase 1 (L1) of the public grid and is switched via the external grid and system protection unit.
-An NC contact for relay K3, which activates the remote input of the external grid and
system protection unit, interrupts the supply voltage to contactors K1, K2, K4 and
K5. This prevents the ground connection from being immediately disconnected
again when power returns to the public grid and the emergency power network of
the inverter from being switched to the public grid.
-The NO contact of relay K3 gives additional feedback to the inverter on whether the
locking was successfully performed by relay K3.
-Additional inverters or other AC sources can be installed in the emergency power
circuit after the main contacts of K1 and K2. The sources are not synchronised to
the network of the Fronius Symo Hybrid because this emergency power network has
a frequency of 53 Hz.
EN
17
Page 18
Transitioning
from feeding
energy into the
grid to backup
power mode
1.The public grid is monitored by the inverter's internal grid and system protection unit
and by an external grid and system protection unit.
2.Failure of the public grid
3.The inverter carries out the measures necessary according to the country standard
and then switches off.
4.The external grid and system protection unit opens contactors K1 and K2 for grid
monitoring. This disconnects the backup power circuits and the inverter from the rest
of the home network and from the public grid, as the main contacts of the contactors
K1 and K2 open at all pins. To ensure that the public grid has definitely been disconnected, the NC auxiliary contacts of contactor K1 give feedback to the external grid
and system protection unit.
5.The NC main contact of contactors K4 and K5 is closed, establishing a connection
between the neutral conductor and the ground conductor. The two other NC main
contacts of contactors K4 and K5 give feedback to the inverter that the ground connection has been established correctly.
6.The inverter activates relay K3, which activates the remote input of the external grid
and system protection unit via an NC contact. This prevents a connection to the public grid when voltage is restored in the grid.
7.The NO contact of relay K3 gives additional feedback to the inverter on whether the
locking was successfully performed by relay K3.
8.The inverter decides based on the contactors' feedback as well as the measurement
on the inverter terminals and the Smart Meter that backup power mode can be started.
9.The inverter starts backup power mode after a defined checking period.
10. All loads in the backup power circuits are supplied with power. The remaining loads
are not supplied with power and are safely isolated.
Transition from
emergency power
mode to feeding
energy into the
grid
1.The inverter is operating in emergency power mode. The contactors K1 and K2 to
the public grid are open.
2.Public grid available again
3.The Fronius Smart Meter monitors the grid parameters on the public grid and
passes this information to the inverter.
4.After a defined measuring period, the restored public grid is deemed to be stable.
5.On the basis of adjustments that have been carried out, the inverter ends emergency power mode and disconnects the outputs.
6.The inverter deactivates K3. The external grid and system protection unit switches
the contactors K1, K2, K4 and K5 after performing the grid checks required by the
applicable standards.
7.All circuits are reconnected to the public grid and are supplied by the grid.
8.The inverter can start feeding energy into the grid again after performing the grid
checks required by the country standard.
18
Page 19
Description of components
EN
Description of
components for
full version
Fronius Smart Meter
-Type: Fronius Smart Meter 63 A
-Fronius item number: 43,0001,1473
-230 (400) V - 240 (415) V
-10 (63) A / 50 Hz - 60 Hz
-Modbus RTU communication
or
-Type: Fronius Smart Meter 50kA-3
-Fronius item number: 43,0001,1478
-230 (400) V - 240 (415) V
-10 (63) A / 50 Hz - 60 Hz
-Modbus RTU communication
Grid and system protection
Other types and manufacturers are permitted if they are technically and functionally
identical to the following type, e.g.:
-manufacturer: Bendner
-type: VMD460-NA-D-2
Fuse protection, grid and system protection or coupling relays
-3-pin or 1-pin
-6 A
K1 and K2 - installation contactor with auxiliary contact
-3-pin or 4-pin (depending on cabling variant)
-25 A or 63 A (depending on house connection)
-Coil voltage, 230 V AC
-Auxiliary contact
•1 NO
•Switching voltage 12 - 230 V @ 50/60 Hz
•Short circuit current min. 1 kA
K3 - modular relay
-2 changeover contacts
-Coil voltage: 12 V DC
K4 and K5 - installation contactor
-2 NCs 20 A
-Coil voltage, 230 V AC (2P)
-20 A
-Nominal frequency 50/60 Hz
-Short circuit current = min. 3 kA (Working contacts)
19
Page 20
Further requirements
Contactors K1, K2, K4 and K5 must be certified to IEC 60947-4-1. Examples of contactors / relays that meet these requirements are
RequirementsIn order to use the hybrid inverter's emergency power function, the following prerequis-
ites must be fulfilled:
-Correct wiring of the emergency power system in the electrical installation (according to this document) - Check wiring
-Attach the emergency power sticker supplied with the inverter to the electrical distributor.
-The meter (Fronius Smart Meter) must be installed at the feed-in point and configured
-Current system monitoring firmware on the inverter: V 1.3.2-3 or higher.
Update the firmware if necessary.
EN
Emergency
power configuration - overview
Accessing the
CONFIG menu
-Accessing the CONFIG menu
-Selecting alternative (emergency power) setup
-Configuring the digital I/Os on the Fronius Datamanager
-Configuring the system overview on the Fronius Datamanager
-Configuring the energy management on the Fronius Datamanager (option)
Press the "Menu" key
1
The menu level appears.
Press the unassigned "Menu / Esc"
2
key
5 times
'Access Code' is displayed in the
'CODE' menu; the first digit starts flashing.
The access code for the CONFIG menu
is: 39872
Enter the access code for the CON-
3
FIG menu: Use the 'Up' and 'Down'
keys to select a value for the first
digit of the code
Press the 'Enter' key
4
The second digit flashes.
Repeat steps 3 and 4 for the second,
5
third, fourth and fifth digits of the
access code until...
21
Page 22
Access Code
the selected code starts flashing.
Select Altern. Config
(1)
(2)
(3)
Press the 'Enter' key
6
The first parameter of the CONFIG
menu is displayed
Selecting alternative (emergency
power) setup
Configuring the
digital I/Os on the
Fronius Datamanager
The setups with the designation "EmergencyPower" are available as "Alternative (emergency power) setups":
-EmergencyPower 50Hz: for all countries with a nominal frequency of 50 Hz
-EmergencyPower 60Hz: for all countries with a nominal frequency of 60 Hz
Use the 'Up' and 'Down' keys to
1
select the Alternative (emergency
power) setup
Press the 'Enter' key
2
Open the Fronius system monitoring web page (= Fronius Datamanager)
1
Select settings
2
Sign in as "Service"
3
Select IO mapping from the menu
4
Switch user
5
Activate and open "Emergency power"
6
22
Page 23
After installing the wiring, configure the pins under "Emergency power" (1)
(1)
(2)
(1)
(2)
7
Configuring the
system overview
on the Fronius
Datamanager
The default values for the pins correspond to the settings used in the document
entitled "Fronius Energy Package - Examples of emergency power switchover".
Check the wiring again
8
Configure the locking feedback (optional) (2)
9
Click the "save" button (3) to apply the entries
10
Under "Settings" on the Fronius system monitoring (= Fronius Datamanager) web
1
page, select "System overview" from the menu
Set the emergency power operating mode (1) to "Auto"
2
EN
Configuring the
energy management on the
Fronius Datamanager (option)
Click the "save" button (2) to apply the entries
3
Under "Settings" on the Fronius system monitoring (= Fronius Datamanager) web
1
page, select "Energy management" from the menu
The remaining battery capacity (1) and SoC warning level (2) can be set under
"Energy management".
Click the "save" button (3) to apply the entries
2
23
Page 24
TASKTESTCONFIRMATION
The inverter, battery, and all other necessary components have been installed and assembled correctly.
The backup power changeover unit has been installed
and commissioned in accordance with the country-specic installation guidelines and as outlined in the documentation.
The software settings have been carried out in accor-
dance with the „Backup power conguration“ chapter in
the documentation.
A warning notice has been put on the switch cabinet to
warn that a backup power supply has been installed.
Start the inverter in grid power feed operation.Check whether the inverter starts in grid power feed
operation and a power shift takes place. (Test duration
6 minutes).
Disconnect the PV system from the public grid. This
can be eected using a disconnecting device in the
upstream AC path or the disconnecting devices (e.g. NH
fuse) of the building connection. The disconnection must
occur before the Smart Meter (grid side).
Check whether the inverter starts in stand-alone operation. The changeover can take more than 1 minute.
Measure the voltage/frequency in the established standalone operation.
Set value: 230 V / ± 10 % / 53 Hz
USA: 120 V / ± 10 % / 63 Hz
Reconnect the PV system to the public grid.The time taken from the end of stand-alone operation
until the subsequent connection of the contactors in
the backup power changeover unit must be at least 10
seconds. The changeover can take more than 1 minute.
Only then may the inverter resume grid power feed operation. This may take several minutes due to national
requirements (test duration 6 minutes).
/ Perfect Welding/Solar Energy / Perfect Charging
CHECKLIST - BACKUP POWER
Once installation, conguration, and commissioning have been successfully completed, this checklist must be worked through to ensure the backup power changeover function and backup power mode are operating correctly.
I hereby conrm that the backup power changeover function and backup power mode are operating correctly.
Signature
Place, date
42,0426,0365,EA 002-07042020
FRONIUS INTERNATIONAL GMBH www.fronius.com
24
Page 25
Appendix
25
Page 26
3-pin separation Austria with Solar Battery
26
Page 27
3-pin separation Australia with Solar Battery
27
Page 28
3-pin separation Austria with BYD
28
Page 29
3-pin separation Australia with BYD
29
Page 30
3-pin separation with grid and system protection
Austria with Solar Battery
30
Page 31
4-pin separation Germany with Solar Battery
31
Page 32
4-pin separation Germany with BYD
32
Page 33
4-pin separation with grid and system protection
Germany with Solar Battery
33
Page 34
4-pin seperation with grid and system protection
Italy with Solar Battery
34
Page 35
Fronius Symo Hybrid and BYD Battery-Box
Premium HV
35
Page 36
FRONIUS INTERNATIONAL GMBH
Froniusstraße 1
A-4643 Pettenbach
AUSTRIA
contact@fronius.com
www.fronius.com
Under www.fronius.com/contact you will find the addresses
of all Fronius Sales & Service Partners and locations.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.