Fronius Fronius Symo Advanced UL - Installation (Online) Installation Instruction [EN]

Installation Instructions
Fronius Symo Advanced - Installation
10.0-3 208-240
12.0-3 208-240
15.0-3 480
20.0-3 480
22.7-3 480
24.0-3 480
EN-US
Installation instructions
Table of contents
Safety 5
General 5 Electrical installations 5 Rapid shutdown 5
Installation location and position 7
Explanation of safety instructions 7 Safety 7 Intended Use 8 Location Selection 9 Installation position of the inverter 10 General Location Selection 11 Example: Installation of several inverters 12 Do not ground the solar modules. 12 Power Line Communication (PLC) transmitter 13
Preparation 15
Attaching the Mounting Bracket 17
Safety 17 Selecting Dowels and Screws 17 Screw recommendation 17 Opening the Inverter 17 Installing the Mounting Bracket on a Wall 18 Attaching the mounting bracket to a metal carrier 19 Do not warp or deform the mounting bracket 19
Knockouts 21
Safety 21 General 21 Knocking or Drilling Out Knockouts 22
EN-US
AC~ 25
Suitable Grids 27 Connecting the inverter to the public grid (AC side) 28
Safety 28 Permitted cables 29 Preparing Aluminum Cables for Connection 31 Monitoring the grid 31 Connecting the Inverter to the Public Grid (AC) 32 Maximum AC Fuse Protection 33 Additional external AC and/or DC disconnect 34
DC= 35
Connecting solar module strings to the inverter 37
Safety 37 String fuses 38 Permitted cables 39 General Information about Solar Modules 41 Connecting Aluminum Cables 42 Connecting Solar Module Strings to the Inverter 43
Laying Solar.Net Cables 45
Data communication 47
Lay data communication cables 47 Installing Datamanager in the Inverter 48
Finally... 51
Seal Conduits 53 Clipping the Inverter onto the Mounting Bracket 54
3
Clipping the Inverter onto the Mounting Bracket 54
Using for the first time 57
Using the Inverter for the First Time 57
Options 59
USB Stick as a Data Logger and for Updating Inverter Software 61
USB Flash Drive as a Data Logger 61 Data on the USB thumb drive 61 Data Amount and Memory Capacity 62 Buffer Memory 63 Suitable USB Thumb Drives 63 USB Stick for Updating Inverter Software 64 Removing the USB Stick 64
Options 65
Options 65 OPTION 'ShadeCover' 65
Care and maintenance 67
Notes on Maintenance 69
Maintenance 69 Cleaning 69
4
Safety
SOLAR PV SYSTEM IS EQUIPPED
WITH RAPID SHUTDOWN.
TURN RAPID SHUTDOWN SWITCH TO
THE „OFF“ POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE SHOCK
HAZARD IN ARRAY.
SOLAR ELECTRIC
PV PANELS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
General This manual contains important instructions for the inverter that must be fol-
lowed during installation and maintenance of the inverter.
The inverter is designed and tested according to international safety require­ments. Due to its electrical and electronic components, certain precautions must be taken when installing and operating the inverter. In order to reduce the risk of injury to persons and to ensure safe installation and operation of the inverter, be sure to read these Operating Instructions carefully and follow all instructions and safety instructions.
Failure to observe the Operating Instructions and safety instructions can void the warranty and/or cause damage to the inverters or other property damage!
EN-US
Electrical in­stallations
Rapid shutdown The rapid shutdown (RSD) can be triggered via loss of the grid connection: If the
All electrical installations must be carried out in accordance with the National Electrical Code, ANSI/NFPA 70, and any other codes and regulations applicable to the installation site.
For installations in Canada, the installations must be done in accordance with applicable Canadian standards.
AC connection is lost, a rapid shutdown can be performed automatically. The in­verter detects a loss of the AC connection and the lines are discharged to < 30 VDC / 8 A / 240 VA and < 15 VAC / 8 A / 240 VA. The inverter also interrupts the
communication to the PV modules if they comply with the SunSpec standard for Rapid Shutdown.
In case a module-level shutdown equipment within the PV array is used in combination with the inverter, this labeling has to be used according to NEC (Section 690.12), CEC (64-218):
5
In case a string-level shutdown equipment at the PV array is used in combina-
SOLAR PV SYSTEM IS EQUIPPED
WITH RAPID SHUTDOWN.
TURN RAPID SHUTDOWN SWITCH TO
THE „OFF“ POSITION TO SHUT DOWN
CONDUCTORS OUTSIDE THE ARRAY.
CONDUCTORS IN ARRAY REMAIN
ENERGIZED IN SUNLIGHT.
SOLAR ELECTRIC
PV PANELS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
tion with the inverter, this labeling has to be used according to NEC (Section
690.12), CEC (64-218).
Warning! The installer is responsible for the correct labeling of the PV system. The rapid shutdown requirement of the inverter is not affected by the FRT (fault ride through) capability, so the inverter is „Grid support interactive compatible“
Warning! This photovoltaic rapid shutdown equipment (PVRSE) does not per­form all of the functions of a complete photovoltaic rapid shutdown system (PVRSS). This PVRSE must be installed with other equipment to from a com­plete PVRSS that meets the requirements of NEC (NFPA 70) section 690.12, CEC 6 section 4-218 for controlled conductors outside the array. Other equip­ment installed in or on this PV system may adversly affect the operation of the PVRSS. It is the responsibility of the installer to ensure that the completed PV system meets the rapid shutdown functional requirements. This equipment must be installed according to the manufacturer´s installation instructions Warning! Risk due to unsuitable location of the inverter. Failure or limited opera­tion of the inverter can be the result
Location according to the information in the user manual.
Observe national regulations and guidelines for the installation of the inverter.
Self-test
A self-test of the RSD function can be performed manually or automatically. The self-test only affects the discharge circuit of the RSD function. All other RSD circuit components are implemented in a single-failure-proof manner.
Automatic self-test sequence: At each start - before switching on to the public network - the discharge circuit is activated for 10 ms if the DC voltage (40 V) is sufficient and the feedback pin is checked before and during charging.
Manual self-test sequence: A manual self-test can be triggered by an interruption of the AC connection (e.g.: AC breaker).
The discharge must be measured and checked using a multimeter.
6
Self-test error automatic: AC_SystemFailure
Installation location and position
EN-US
Explanation of safety instruc­tions
Safety
WARNING!
Indicates a potentially dangerous situation.
Death or serious injury may result if appropriate precautions are not taken.
CAUTION!
Indicates a potentially harmful situation.
Minor injury or damage to property may result if appropriate precautions are
not taken.
NOTE!
Indicates a possibility of flawed work results and possible damage to the equip­ment.
Please pay special attention when one of the symbols from the "Safety rules" chapter appears in these instructions.
WARNING!
Danger from incorrect operation and work that is not carried out properly.
This can result in severe personal injury and damage to property.
Only qualified staff are authorized to commission the inverter and only with-
in the scope of the respective technical regulations. Read the Installation Instructions and Operating Instructions before install-
ation and commissioning.
WARNING!
Danger from work that is not carried out properly.
This can result in damage to property and severe personal injury.
The surge protection device should only be installed and connected by li-
censed electricians. Observe the safety rules!
Prior to all installation and connection work, disconnect the AC and DC sup-
ply to the inverter.
7
Fire Prevention
CAUTION!
Danger due to faulty or incorrect installation.
This may result in damage to inverters and other current-carrying parts of a photovoltaic system. Faulty or improper installation may cause overheating of cables and terminals as well as the formation of arcs. This could cause thermal damage, which in turn may lead to fires.
Please note the following when connecting the AC and DC cables:
Securely tighten all terminals using the proper torque listed in the Operating
Instructions Securely tighten all grounding terminals (PE/GND) using the proper torque
listed in the Operating Instructions, even for free grounding terminals Do not overload cables
Check cables for damage and correct wiring
Follow all safety instructions, Operating Instructions, and any local connec-
tion regulations
Always secure the inverter to the mounting bracket with fixing screws using
the torque specified in the Operating Instructions. Only put the inverter into operation with the fixing screws securely tightened.
Notice! Fronius will not bear any costs for production downtimes, or for installa­tions, etc., which may arise due to a detected electric arc and its consequences. Fronius accepts no liability for fires which may break out despite integrated arc detection/interruption (e.g., due to a parallel arc).
Notice! Before an inverter can be reset following a detected electric arc, check the entire affected photovoltaic system for any damage.
The manufacturer's specifications for connection, installation, and operation must be observed. You must carefully follow all installation steps and make all connections in accordance with specifications and regulations to minimize any risk of danger. The tightening torques for the respective terminals are listed in the Installation Instructions for the devices.
Intended Use The inverter is designed exclusively to convert direct current from solar modules
into alternating current and feed this power into the public grid. The following are deemed to be not in conformity with its intended purpose:
Utilization for any other purpose, or in any other manner
-
Alternations to the inverter are not expressly recommended by Fronius
-
Installation of components that are not expressly recommended or sold by
-
Fronius.
The manufacturer is not responsible for any damage resulting from improper use. All warranty claims are considered void in such cases.
Proper use also means
carefully reading and obeying the instructions and all the safety and danger
-
notices in the Operating and Installation Instructions compliance with the maintenance operations
-
installation as specified in the Installation Instructions
-
8
When configuring the photovoltaic system, make sure that all components are
10.0-3 - 12.0-3 208-240
U
DC max
0 - 11154 ft. (0 - 3400 m)
ft. (m)
600 V
1000 V
0 - 6561 ft. (0 - 2000 m)
> 8202 - 9842 ft. (> 2500 - 3000 m) > 6561 - 8202 ft. (> 2000 - 2500 m)
> 9842 - 11154 ft. (> 3000 - 3400 m)
950 V
900 V
850 V
U
DC max
ft. (m)
15.0-3 - 24.0-3 480
> 11154 ft. > 3400 m
NH
3
operating completely within their permitted operating range.
Location Selec­tion
All measures recommended by the solar module manufacturer for maintaining solar module properties must be followed.
Follow all grid operator regulations regarding grid power feed and connection methods.
Please note the following criteria when choosing a location for the inverter:
The inverter is suitable for indoor installation.
The inverter is suitable for outdoor installation.
Because of its NEMA 4X protection class, the inverter is not sus­ceptible to hose water on any side and can also be operated in moist environments. However:
EN-US
In order to keep inverter heating as low as possible, do not ex­pose the inverter to direct sunlight. The inverter should be in­stalled in a protected location, e.g., near the solar modules or under an overhanging roof.
IMPORTANT! The inverter must not be installed or operated above an altitude of 11,154 ft. (3400 m).
The maximum permissible DC voltage of the inverter depends on the altitude.
U
at an altitude of:
DCmax
Symo Advanced 10.0-3–12.0-3 208–240
0 to 11,154 ft ( 0 to 3400 m). = 600 V
Symo Advanced 15.0-3–24.0-3 480
0 to 6561 ft ( 0 to 2000 m). = 1000 V 6531 to 8202 ft (2000 to 2500 m). = 950 V 8202 to 9842 ft (2500 to 3000 m). = 900 V 9842 to 11,154 ft (3000 to 3400 m). = 850 V
The output power reduces when the device temperature is too
high, and this may occur earlier than normal at increased alti­tudes.
Do not install the inverter:
where it may be exposed to ammonia, corrosive gases, acids,
-
or salts (e.g., fertilizer storage areas, vent openings for livestock stables, chemical plants, tanneries)
9
During certain operating phases the inverter may produce a slight noise. For this reason, it should not be installed in an oc­cupied living area.
Do not install the inverter in:
areas where there is an increased risk of accidents from
-
farm animals (horses, cattle, sheep, pigs, etc.) Stables or adjoining areas
-
storage areas for hay, straw, chaff, animal feed, fertilizers,
-
etc.
The inverter is designed to be dustproof in principle. However, in areas of high dust accumulation, the cooling surfaces can be­come dusty, which can impair the thermal performance. In this case, the dust must be removed regularly. We therefore recom­mend that installation is not carried out in areas and environ­ments with high dust accumulation (e.g., iron filings) as this can cause damage to the inverter.
Do not install the inverter in:
Greenhouses
-
Storage or processing areas for fruit, vegetables, or viticul-
-
ture products Areas used in the preparation of grain, green fodder, or an-
-
imal feeds
Installation posi­tion of the in­verter
The inverter is suitable for vertical installation on a vertical wall or column.
The inverter is suitable for a horizontal installation position.
The inverter is suitable for installation on a sloping surface.
Do not install the inverter on a sloping surface with the connec­tions upwards.
10
4 i
n.
100 m
m
4 i
n.
100 m
m
8 i
n.
200 m
m
-40 °F ­+
1
40 °F
-4
0 °C - +60 °C
0 -
100 %
Do not install the inverter in a sloping position on a vertical wall or column.
Do not install the inverter in a horizontal position on a vertical wall or column.
Do not install the inverter with the connections upwards on a vertical wall or column.
Do not install the inverter overhanging with the connections up­wards.
EN-US
General Location Selection
Do not install the inverter overhanging with the connections downwards.
Do not install the inverter on the ceiling.
Please note the following criteria when choosing a location for the inverter:
11
Example: Install-
+
-
+
-
ation of several inverters
Only install on a solid, non-flammable surface
Max. ambient temperatures: -40 °F/+140 °F (-40 °C/+60 °C)
Relative humidity: 0–100%
The air flow direction within the inverter is from right to top (cold air intake on the right, hot air outflow at the top). The waste air may reach a temperature of up to 70 °C.
When installing the inverter in a switch cabinet or similar closed environment, it is necessary to make sure that the hot air that develops will be dissipated by forced-air ventilation
If you wish to install the inverter on the outer walls of cattle stables, it is im­portant to keep a minimum clearance of 2 m between all sides of the inverter and air vents and other openings. The place of installation should not be exposed to ammonia, corrosive gases, salts, or acids.
Do not ground the solar mod­ules.
The inverter is designed exclusively for connection to and use with non-groun­ded solar modules. The solar modules must not be grounded at either the positive or negative pole.
12
Power Line Com­munication (PLC) transmit­ter
The inverter is equipped with a Power Line Communication (PLC) transmitter on the DC side. Its function is to ensure rapid shutdown in accordance with US safety standard NEC 2017 Art. 690.12. The PLC is implemented according to the specification "Communication Signal for Rapid Shutdown – SunSpec Interoperability Spe­cification". Please visit www.sunspec.org for details.
To ensure compliance with all applicable regulations in your country and to en­sure optimal reception among all recipients, please follow the recommendations below:
Keep the distance between the DC+ and DC- conductors as small as possible
-
Avoid cable loops caused by cables that are too long (coil effect)
-
Use metal cable ducts where possible
-
Do not place DC cables from different inverters in the same cable duct or
-
cable tray
EN-US
13
14
Preparation
15
16
Attaching the Mounting Bracket
EN-US
Safety
WARNING!
Danger of residual voltage from capacitors.
An electric shock can be fatal.
Wait until the capacitors have discharged. Discharge takes 5 minutes.
CAUTION!
Danger due to soiling or water on the terminals and contacts in the connection area.
This may result in damage to the inverter.
When drilling, make sure that terminals and contacts in the connection area
do not become soiled or wet. The mounting bracket without integrated inverter does not correspond to the
degree of protection according to the data sheet. For this reason do not leave the mounting bracket exposed to environmental influences without the inserted inverter. Protect the mounting bracket from soiling and moisture during installation.
NOTE!
Protection class NEMA4X is only ensured when the inverter is mounted and firmly screwed into the mounting bracket.
The mounting bracket without inverter and ventilation channel has no NEMA pro­tection.
Selecting Dowels and Screws
Screw recom­mendation
Opening the In­verter
Important! Depending on the surface, different mounting materials may be re-
quired for installing the mounting bracket. These mounting materials are not part of the scope of delivery for the inverter. The installer is responsible for selecting the proper mounting materials.
For the installation of the inverter we recommend steel or aluminum screws with a diameter of 0.2–0.3 in. (6–8 mm).
WARNING!
Danger due to inadequate ground conductor connection.
This can result in severe personal injury and damage to property.
The housing screws provide an adequate ground conductor connection for
grounding the housing and should not be replaced under any circumstances by other screws that do not provide a reliable ground conductor connection.
17
ON
OFF
Lock
1 2
lb
NO NEMA ENCLOSURE TYPE
Installing the Mounting Brack­et on a Wall
3
4
The mounting bracket must be secured in at least four places.
1 2
18
3
EN-US
Attaching the mounting brack­et to a metal car­rier
NOTE!
When mounted on metal supports, the inverter must not be exposed to rainwa­ter or splashing water from the rear.
Provide suitable rainwater protection or splash water protection.
The mounting bracket must be secured in at least four places.
1
Do not warp or deform the mounting brack­et
Notice! When attaching the mounting bracket to the wall or to a column, make
sure that the mounting bracket is not warped or deformed.
19
20
Knockouts
1 1/4 in. 1 1/4 in. 1 in. 1 in.
Conduit size 1/2 in. / 3/4 in. / 1 in.
*
Conduit size 1/2 in. / 3/4 in. / 1 in. / 1 1/4 in.
**
1/2 in. ... DATCOM
3/4 in. - 1 1/4 in. ... AC ~ / DC =
*
*
** **
*
*
*
*
METAL EMPOSSING Remove parts fallen into the connection area before hanging the inverter to the wall bracket!
** **
METAL EMPOSSING Remove parts fallen into the connection area before hanging the inverter to the wall bracket!
EN-US
Safety
General
CAUTION!
Danger of short circuit from loose metal parts from knockouts.
Loose metal parts in the inverter may cause short circuits when the inverter is powered up. When removing knockouts, make sure that
no loose metal parts fall into the connection area of the inverter,
any metal pieces that do fall into the connection area are removed immedi-
ately.
NOTE!
When using the cable inlets at the back, take care to seal them according to pro­tection class NEMA4X before operating outdoors.
NOTE!
When installing outdoors, only use waterproof conduit fittings and conduits.
Conduit fittings and conduits are not part of the scope of supply for the inverter.
The wall bracket contains several knockouts of different sizes. When knocked out, the openings are used for the inputs of various wires.
21
1/2 in. for data communication cable (DATCOM)
*
3/4 in.
for AC and DC cables
- 1 1/4 in. * A grounding electrode terminal (GET) may be required depending on local
regulations. The cable for the grounding electrode terminal can be fed through the designated opening on the underside of the wall bracket.
IMPORTANT! The knockouts on the rear of the wall bracket are made of metal.
Knocking or Drilling Out Knockouts
IMPORTANT! The knockouts on the underside of the mounting bracket may be
knocked out using a hammer or screwdriver, drilled out using a step drill, or opened using a hole punch. The side knockouts and the knockouts at the back may only be drilled out with a step drill or opened with a hole punch.
IMPORTANT! You should only remove the minimum number of knockouts re­quired for the available cables.
Use suitable eye protection when knocking/drilling out the knockouts.
Only knock out knockouts using a hammer or screwdriver from the inside outwards.
Only use suitable step drills to drill out the knockouts. Do not use spiral drills for drilling out!
Only drill out knockouts using a step drill from the outside inwards.
When drilling out using a step drill, ensure that the inside of device (e.g. connection block) is not damaged.
When drilling out the knockouts at the back, place the mounting bracket on an even surface with the back upwards so that shavings and pieces of metal can fall out of the mounting bracket.
Attach appropriate conduits to all knocked/drilled out knock­outs. In the event of installation outside, only use watertight con­duits and conduit fittings. Conduits and conduit fittings are not included with the in­verter.
If necessary, deburr the number of knockouts required with a suitable tool.
22
Loading...
+ 50 hidden pages