Fronius Fronius String Control 250/25 USA Operating Instruction [EN]

Page 1
/ Battery Charging Systems / Welding Technology / Solar Electronics
Fronius String Control 250/25
Operating Instructions
Data Communication
EN-US
42,0426,0082,EA 005-12042012
Page 2
Page 3
Dear Fronius Customer,
Introduction
Please also note the safety information and the safety precautions for the product installation location. Following all product instructions will ensure long-lasting quality and reliability. And these are the essential ingredients for outstanding results.
EN-US
ud_fr_st_et_01382 012012
Page 4
ud_fr_st_et_01382 012008
Page 5
IMPORTANT SAFETY
INSTRUCTIONS
SAVE THESE INSTRUCTIONS
General This manual contains important instructions for the Fronius String Control
250/25, that must be followed during installation and maintenance.
The Fronius String Control 250/25 is designed and tested according to international safety requirements, but as with all electrical and electronic equipment, certain precautions must be observed when installing and/or operating the Fronius String Control 250/25. To reduce the risk of personal injury and to ensure the safe installation and operation of the Fronius String Control 250/25, you must carefully read and follow all instructions and safety instructions in this manual.
EN-US
Safety Instruc­tions
Electrical installations
The following section “Safety Instructions“ contains different warnings. A warning describes a hazard to equipment or personnel. It calls attention to a procedure or practice, which, if not correctly performed or adhered to, could result in damage to or destruction of part or all of the Fronius string Control 250/25 and/or other equipment connected to the Fronius String Control 250/25 or personal injury.
All electrical installations must be made in accordance with the National Electrical Code, ANSI/NFPA 70, and any other codes and regulations applicable to the installation site.
For installations in Canada the installations must be done in accordance with applicable Canadian standards.
Page 6
2
Page 7
Safety Instructions
Explanation of Safety Warnings!
General
„DANGER!“ Indicates an immediate danger. Death or serious injury may
result if appropriate precautions are not taken.
EN-US
„WARNING!“ indicates a potentially dangerous situation. Death or serious injury may result if appropriate precautions are not taken.
„CAUTION!“ Indicates a situation where damage or injury could occur. Minor injury or damage to property may result if appropriate precautions are not taken.
NOTE! Indicates a situation which could adversely affect work results and may cause damage to equipment.
„Important“ Highlights tips for correct operation and other particularly useful information. It does not indicate a potentially damaging or dangerous situation.
If you see any of the symbols depicted in the „Safety Rules,“ special care is required.
This equipment has been manufactured using state-of-the-art technology and in accordance with general safety regulations. However, incorrect operation or misuse may endanger:
- the life and well-being of the operator or third parties
- the equipment and other property of the owner/operator
- the efficient operation of the equipment.
All persons involved with equipment startup, service and maintenance must:
- be suitably qualified
- be familiar with electrical installations
- have completely read and followed these operating instructions
The operating instructions must be available at the equipment location at all times. In addition to the operating instructions, all applicable local rules and regulations regarding accident prevention and environmental protection must also be followed.
All safety instructions and warning signs on the equipment itself:
- must be maintained in legible condition
- must not be damaged
- must not be removed
- must not be covered or painted over
For information about where the safety instructions and warning signs are located on the equipment, please refer to the “General“ section of your equipment’s operating instructions.
Any equipment malfunctions which might impair safety must be remedied immediately before the device is turned on.
Your safety is at stake.
I
ud_fr_se_sv_01381 012012
Page 8
Intended Use
The equipment may only be operated in compliance with its intended use.
Any other purpose does not constitute intended use. The manufacturer is not responsible for any damages resulting from unintended use.
Intended use also includes:
- reading and complying with all general information as well as safety information and warnings from the operating instructions
- compliance with all inspection and maintenance requirements
- installation as per operating instructions
Where appropriate, the following guidelines should also be applied:
- Utility company regulations regarding grid feed-in
- Information from solar module manufacturer
Ambient Conditi­ons
Qualified Person­nel
Operation and/or storage of the device outside of the stipulated range does not constitute intended use. The manufacturer is not responsible for any damages resulting from unintended use.
Please refer to the technical data in your operating instructions for informati­on about permitted ambient conditions.
The servicing information contained in these operating instructions is intended only for the use of qualified service engineers. An electric shock can be fatal. Please do not perform any actions other than those described in the docu­mentation. This also applies to qualified personnel.
All cables and wires must be secured, undamaged, insulated and adequately dimensioned. Loose connections, scorched, damaged or under-dimensioned cables and wires must be repaired immediately by an authorized specialist.
Maintenance and repair may only be carried out by an authorized specialist.
The use of third-party parts does not guarantee that they were designed and manufactured according to operational demands and safety requirements. Use only original spare parts (also applies to standard parts).
Safety Precauti­ons at Equipment Location
ud_fr_se_sv_01381 012012
Do not carry out any alterations, installations or modifications to the device without first obtaining the manufacturer’s permission.
Immediately replace any components that are not in perfect condition.
When installing devices with air vents, make sure that cool air can flow freely through the vents unobstructed. The device should only be operated in accordance with the protec­tion class listed on the rating plate.
II
Page 9
Information on Noise Emission Values
The inverter generates a maximum sound power level of <80dB(A) (ref. 1pW) at full-load operation according to IEC 62109-1.
The cooling of the device takes place via an electronic temperature control system at the lowest possible noise level and depends on the power used, ambient temperature and the soiling level of the device, etc.
A workplace-related emissions value cannot be provided for this device because the actual noise level that occurs depends strongly on the installati­on situation, the grid quality, the surrounding walls and the general properties of the space.
EMC Device Classifications
Devices in emission class A:
- Are only designed for use in industrial settings
- Can cause grid-bound and radiated interference in other areas
Devices in emission class B:
- Satisfy the emissions criteria for residential and industrial areas. This is also true for residential areas in which the energy is supplied from the public low-voltage grid.
EMC device classification as per the rating plate or technical data
EMC Precautions In special cases, there may still be interference for the specified application
area despite maintaining standardized emission limit values (e.g. when sensitive equipment is located at the setup location or when the setup location is near radio or television receivers). In this case, the operator is obliged to take proper action to rectify the situation.
EN-US
Grid connection
Devices with a high output (> 16 A) can influence the voltage quality of the grid due to a high current input into the main supply. This can affect several device types in the form of:
- Connection limitations
- Requirements regarding permitted mains impedance
- Requirements regarding minimum required short circuit power
*)
for each interface to the public grid
*)
*)
See technical data
In this case, the operator or the user of the device must make sure whether or not the device may be connected, if necessary by contacting the power supply company.
III
ud_fr_se_sv_01381 012012
Page 10
Electrical Installa­tions
Electrical installations may only be carried out in accordance with relevant national and local standards and regulations.
ESD Precautions
Safety Precauti­ons in Normal­Operation
Safety Markings
Danger of damage to electronic components due to electrostatic discharge. Take appropriate ESD precautions when replacing and installing compon­ents.
The device should only be operated when all safety equipment is fully func­tional. If safety equipment is not fully functional, there is a danger to:
- the life and well-being of the operator or third parties
- the equipment and other property of the owner/operator
- the efficient operation of the equipment
Safety equipment that is not fully functional must be repaired by an authori­zed specialist before the device is turned on.
Never bypass or disable safety equipment.
Equipment with the CE marking fulfils the basic requirements of the Guideli­ne Governing Low-Voltage and Electromagnetic Compatibility. (For more information, please see the attachment and/or the “Technical Data“ section in your documentation).
Disposal
Data Security
Copyright
This device should not be disposed of in residential waste. To comply with European Directive 2002/96/EC on Waste Electrical and Electronic Equipment and its implementation as national law, electrical equipment that has reached the end of its life must be collected separately and returned to an approved recycling facility. Any device that you no longer require must be returned to your dealer or you must find an approved collec­tion and recycling facility in your area. Ignoring this EU Directive may have adverse affects on the environment and your health.
The user is responsible for backing up data relating to changes made to factory settings. The manufacturer will not accept liability if personal settings are deleted.
The manufacturer maintains the copyright to these operating instructions.
Text and illustrations are technically correct at the time of going to print. The right to make modifications is reserved. The contents of the operating in­structions shall not provide the basis for any claims whatsoever on the part of the purchaser. We would be grateful for any comments or suggestions regarding improvements and/or error corrections for the operating instruc­tions.
ud_fr_se_sv_01381 012012
IV
Page 11
Contents
General ............................................................................................................................... 3
Functional Principle ........................................................................................................ 3
Other System Requirements ........................................................................................... 3
Device Concept .............................................................................................................. 3
FCC Compliance ........................................................................................................... 4
Standards and Regulations ............................................................................................. 4
Intended Use .................................................................................................................. 4
Abbreviations and Descriptions Used ............................................................................. 4
Product listings and compliance ..................................................................................... 4
Components Supplied .................................................................................................... 4
Product Description ............................................................................................................ 5
Safety ............................................................................................................................. 5
Fronius String Control 250/25 - Housing.......................................................................... 5
Fronius String Control 250/25 - Connection Area ............................................................ 6
Selecting a Location ....................................................................................................... 8
Fronius String Control 250/25 Installation ............................................................................. 8
Wall anchors and Screws ................................................................................................ 8
Recommended Screws for Mounting .............................................................................. 8
Installation Position ......................................................................................................... 8
Safety ............................................................................................................................. 8
Drilling Pattern ................................................................................................................9
Attaching the Fronius String Control 250/25 to a Concrete or Brick Wall .......................... 9
Attaching the Fronius String Control 250/25 to a Wooden Wall ...................................... 10
Attaching the Fronius String Control 250/25 to a Metal Carrier ..................................... 10
Knocking out Cable Input Openings and Mounting Conduits on the Fronius String Control
250/25 ............................................................................................................................... 11
General ......................................................................................................................... 11
Cable Input Areas .......................................................................................................... 11
Maximum Conduit Size ................................................................................................. 12
Recommendation for Inserting Cables .......................................................................... 12
Preparation .................................................................................................................. 12
Knocking out Cabel Input Openings on the Fonius String Control 250/25 ....................... 13
Mounting Conduits on the Fronius String Control 250/25 .............................................. 13
Connecting Solar Module Strings to the Fronius String Control 250/25 .............................. 14
General Information About Solar Modules ..................................................................... 14
Safety ........................................................................................................................... 14
Necessary Inside Cable Length of the Fronius String Control 250/25............................. 15
Notes for Connecting Solar Module Strings to the Fronius String Control 250/25 ........... 16
Terminal Assignment with Grounded Solar Modules ...................................................... 16
Connecting Solar Module Strings to the Fronius String Control 250/25 .......................... 17
Connecting the Fronius String Control 250/25 to the Inverter .............................................. 18
Safety ........................................................................................................................... 18
Cable Lugs for DC Cable ‘OUT’ ................................................................................... 19
Preparation .................................................................................................................. 19
Connecting DC Cable ‘OUT’ to the Fronius String Control 250/25 ................................. 20
Connecting the Fronius String Control 250/25 to the Inverter.......................................... 20
EN-US
1
Page 12
Criteria for the Proper Selection of String Fuses................................................................ 22
General ........................................................................................................................ 22
Criteria for the Proper Selection of String Fuses ........................................................... 22
Effects of Using Underrated Fuses ............................................................................... 22
Fuse Recommendations ............................................................................................... 22
Fuses ...........................................................................................................................23
Application Example ..................................................................................................... 23
Inserting String Fuses........................................................................................................ 24
Selecting String Fuses .................................................................................................. 24
Inserting String Fuses ................................................................................................... 24
Safety ........................................................................................................................... 24
Connecting Data Communication Cables to the Fronius String Control 250/25.................. 25
Connection Options ...................................................................................................... 25
Additional Insulation for Data Communication Cables ................................................... 25
Configuration example .................................................................................................. 26
Safety ........................................................................................................................... 26
Connecting RJ 45 Data Communication Cables to the Fronius String Control 250/25 ... 27
Connecting Unterminated Multi-core Data Communication Cables to the Fronius String
Control 250/25 .............................................................................................................. 27
Terminal assignments ................................................................................................... 28
Connecting an External Power Supply ............................................................................... 29
General ........................................................................................................................ 29
Safety ........................................................................................................................... 29
Connecting an External Power Supply........................................................................... 29
Setting the Address........................................................................................................... 30
Safety ........................................................................................................................... 30
General ........................................................................................................................ 30
Setting the Address - Examples .................................................................................... 30
Installing the Protection Against Contact and Closing the Fronius String Control 250/25 .... 31
Safety ........................................................................................................................... 31
Installing Protection Against Contact ............................................................................. 31
Closing the Fronius String Control 250/25 ..................................................................... 31
Settings ............................................................................................................................ 32
General ........................................................................................................................ 32
Initial Steps ...................................................................................................................32
Possible Settings for the Fronius String Control 250/25................................................. 32
Strings per Measuring Channel ..................................................................................... 33
Max. Energy Deviation .................................................................................................. 33
Threshold...................................................................................................................... 33
Display of Data and Status Messages ............................................................................... 34
Data Display................................................................................................................. 34
Status Messages .......................................................................................................... 34
Replacing String Fuses ..................................................................................................... 35
Safety ........................................................................................................................... 35
Preparation .................................................................................................................. 35
Replacing String Fuses................................................................................................. 35
Finally... ........................................................................................................................ 36
Technical Data ..................................................................................................................37
Input data ...................................................................................................................... 37
Output data (to the inverter) ........................................................................................... 37
General Data ................................................................................................................ 38
2
Page 13
General
Device Con­cept
The Fronius String Control 250/25 is designed for use in grid-con­nected photovoltaic systems with several solar module strings.
Up to 25 solar module strings can be integrated at the input of the Fronius String Control 250/25 to reduce these at the output to one DC+ and DC- main line. The Fronius String Control 250/25 monitors the incoming solar module strings to detect errors in the solar
Fronius String Control 250/25 (open)
Status messages can be sent via e-mail or SMS when using the “Fronius Solar.access“ software together with the “Fronius Datalogger.“ This allows a defective solar module to be detected quickly.
module field.
EN-US
Functional Principle
Other System Requirements
- Each set of 5 incoming solar module strings is grouped into one measuring channel.
- 5 measuring channels record the total current of the respective con­nected solar module strings over the entire charging day.
- In the evening, the Fronius String Control 250/25 calculates an ave­rage value for all measuring channels.
- The Fronius String Control 250/25 compares the current of each measuring channel with the average value of all measuring channels.
- If the Fronius String Control 250/25 detects that one of the measuring channels deviates too much from the average, a status message is sent to the Fronius Datalogger.
- The permitted deviation from the average is freely definable.
- Fronius Datalogger
- PC with Fronius Solar.access software installed
3
Page 14
Intended Use
The device is intended solely for use as a collector and measuring device for the solar module DC strings. The device may be operated only with the following inverters:
- Fronius CL 33.3 DELTA / 44.4 DELTA / 55.5 DELTA
- Fronius CL 36.0 WYE 277 / 48.0 WYE 277 / 60.0 WYE 277
Any other purpose does not constitute intended use. The manufacturer shall not be liable for any damage resulting from such improper use.
Intended use also includes following all information from the operating instructions.
Components Supplied
FCC Compli­ance
Standards and Regulations
- 1 Fronius String Control 250/25
- 1 silicone tube
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Your Fronius String Control 250/25 complies with the requirements for the following standards "Inverters, converters and controllers for use in inde­pendent power systems":
- UL1741-2005
- ANSI / IEEE C62.41
- C22.2 No. 107.1-01 (Sep. 2001)
Product lis­tings and compliance
Abbreviations and Descripti­ons Used
The respective conformity declarations can be found in the appendix to these operating instructions.
DC cable ‘OUT’ DC output cable from Fronius String Control 250/25
to inverter. The polarity of the DC cable ‘OUT’ depends on how the solar module strings are connected to the Fronius String Control 250/25.
DC cable ‘IN’ Solar module strings from the solar modules to the
Fronius String Control 250/25. Each solar module string has one DC+ cable and one DC- cable.
4
Page 15
WARNING! Operating the device incorrectly can cause serious injury and damage. The following documentation should be read and understood in its entirety before the described func­tions are carried out:
- These operating instructions
- All system component operating instructions including safety instructions
Product Description
Safety
EN-US
Fronius String Control 250/25
- Housing
(1)
(2)
(3)
Item Description
(1) Cover screws (4 x)
(2) Cover
(3) Membrane
(4) Lower mounting clip
(6) (5)
(4)
(5) Housing ground (inside the housing)
(6) Upper mounting clip
Sides for possible cable input openings
5
Page 16
Fronius String Control 250/25
- Connection
Area
(1)
(15)
(14)
(2)
(3)
(4)
(5)
(6)
(7)
(13)
(12)
(11)
(10)
(8)
(9)
Item Description
(1) Address switches
(2) Measuring channel 5
(3) Measuring channel 4
(4) Measuring channel 3
(5) 25 Terminals with fuse holders for DC cable ‘IN’
cable cross section AWG 14 - AWG 8
(6) Measuring channel 2
(7) Measuring channel 1
(8) Connection 2 x M12 for DC cables ‘OUT’
(9) Connection 2 x M12 for DC cables ‘OUT’
(10) Connection 2 x M12 for grounding
(11) 2 x 8 Pressure type terminals for data communication cable
cable cross section max. AWG 14
(12) 25 Terminals for DC cable ‘IN’
cable cross section AWG 14 - AWG 8
(13) 13 Grounding terminals (e.g. for grounding of max. 25 solar
module frames) cable cross section max. AWG 6
6
Page 17
Fronius String Control 250/25
- Connection
Area
(continued)
Item Description
(14) 2 RJ 45 connections for data communication cable
(15) Connection for external 12 V DC power supply
EN-US
7
Page 18
Fronius String Control 250/25 Installation
CAUTION! Danger of injury by falling objects.
When working on elevated workplaces make sure that no objects like housing cover, tools or other components of the system can fall down. If necessary, install a wire mesh, a safe­ty net or suitable protection devices.
Wall anchors and Screws
Recommen­ded Screws for Mounting
Installation Position
Selecting a Location
Depending on the surface, different wall anchors and screws may be required for installing the Fronius String Control 250/25. Therefore, these wall anchors and screws are not included with the Fronius String Control 250/25. The installer is responsible for selecting the proper wall anchors and screws.
In most cases, you should use 1/4 in. or 5/16 in. stainless steel or alumini­um screws capable of supporting 46.26 lbs.
The Fronius String Control 250/25 can be installed in any position from horizontal to vertical. However, the cable inputs and outputs should point downwards as much as possible.
When selecting the location, please observe the following criteria:
- Install on a solid and planar surface; the housing must not be distorted when screwing it down.
- The ambient temperature may not fall below -13 °F (-25 °C) nor exceed + 140 °F (+60 °C).
- NEMA 3R protection means that the Fronius String Control 250/25 is not susceptible to water spray from any direction. However, the ma­nufacturer recommends, if possible, that the String Control 250/25 not be exposed to direct moisture or to a direct water jet (e.g., from sprink­lers).
- Protect from direct sunlight and direct exposure to the elements.
- Install under the solar modules where possible.
Safety
8
Page 19
Drilling Pat­tern
(a)
(a)
(a) = 8.86 in (225 mm)
(b) = 28.86 in. (733 mm)
(c) = 29.4 in. (746 mm)
Attaching the Fronius String Control 250/25 to a Concrete or Brick Wall
(b)
(c)
(d) = 9.84 in. (250 mm)
EN-US
(d)
1
2
1
1
3
4
2
2
3
4
5
5
3
1
4 x
3
2
4
5
9
Page 20
Attaching the Fronius String Control 250/25 to a Wooden Wall
1
1
1
2
2
1
Attaching the Fronius String Control 250/25 to a Metal Carrier
3
2
1
1
4 x
2
3
4
10
Page 21
Knocking out Cable Input Openings and Moun­ting Conduits on the Fronius String Control 250/25
EN-US
General
Cable Input Areas
Required cable input openings have to be knocked out of the Fronius String Control 250/25 housing with a proper knock out tool. Take care that safety notes and rating plates located on the housing are not damaged when knocking out cable input openings.
Generally cables can be lead into the Fronius String Control 250/25 from below or sidwise. The following figure shows all possible cable input areas and the approp­riate measurements. On grey marked areas cable input openings can be knocked out on the Fronius String Control 250/25.
DC OUT
GROUNDING OUT
= Cable input areas
DC OUT
GROUNDING OUT
11
DC OUT
GROUNDING OUT
Page 22
Maximum Conduit Size
The Fronius String Control 250/25 is designed for a maximum conduit size of 4 in.
Recommenda­tion for Inser­ting Cables
Preparation
Fronius recommends inserting all cables from below into the Fronius String Control 250/25. The following working steps refer to inserting cables from below. Connec­ting sidewise inserted cables is similar and will not be described in these operating instructions.
1
4x
1
2
1
3
2
3
1
1
1
2
2
2
12
Page 23
Knocking out Cabel Input Openings on the Fonius String Control 250/25
CAUTION! Danger of short circuit by loose metal parts from
knockouts. Loose metal parts in the Fronius String Control 250/ 25 may cause short circuits when the Fronius String Control 250/25 is powered up. When removing knockouts, make sure that:
- no loose metal parts fall into the fronius string Control 250/ 25
- any metal pieces that do fall into the Fronius String Control 250/25 are removed immediately
3/4 in.
EN-US
Mounting Conduits on the Fronius String Control 250/25
DATCOM
Example of possible cable input openings
1. Knock out the required cable input openings using a proper knock out
1
DC INDC IN
3 in.
4 in.3 in.
DC OUT
tool
Consider safety notes of the knock out tool manufacturer
NOTE! Only use water tight conduit fittings and conduits for outdoor installations. Conduit fittings and conduits are not included with the Fronius String Control 250/25.
1
1. Mount conduits and conduit fittings according to the cable input ope­nings
13
Page 24
Connecting Solar Module Strings to the Fronius String Control 250/25
General Infor­mation About Solar Modules
Safety
In order to select suitable solar modules and get the most efficient use out of the inverter, please note the following points:
- The open circuit voltage of the solar modules increases at constant irradiance and when temperature decreases. The open circuit voltage should never rise above the admissible inverter voltage, assuming an irradiance of 1000 W/m² and a temperature of 14 °F (-10 °C). Whenever the open circuit voltage of the solar modules exceeds the admissible inverter voltage, the inverter may be damaged, and all warranty rights will become null and void.
- More exact data for sizing the solar array for the particular location can be obtained using calculation tools such as the Fronius Configura­tion Tool (available on http://www.fronius-usa.com).
- See NEC table 690.7 for the appropriate code-related voltage adjust­ment factor for crystalline silicon modules, or use the manufacturer’s specified voltage coefficient.
WARNING! An electrical shock can be fatal. Danger from DC voltage from solar modules.
- Make sure that the input and output sides in front of the device are not charged before connecting anything.
- Any and all connections should only be carried out by quali­fied electricians.
- Follow the safety rules in these operating instructions.
WARNING! An electric shock can be fatal. Inadequately sized electrical components can cause serious injuries to persons and damage to (or loss of) property.
- All electrical installations must be in accordance with the
National Electrical Code, ANSI/NFPA 70, and any other codes and regulations applicable to the installation site.
- For installations in Canada the installations must be done in
accordance with applicable Canadian standards.
- Use minimum AWG 12, min. 194 °F (90 °C), copper wire for
all grounding wires .
- For appropriate grounding see NEC table 250.122.
- Use minimum AWG 12 to maximum AWG 8, min. 194 °F
(90 °C), copper or aluminium wire for all DC wiring connec­tions to the Fronius String Control 250/25. Voltage drop and other considerations may dictate larger size wires be used.
- Use only solid or stranded wire. Do not use fine stranded
wire.
14
Page 25
Safety
(continued)
CAUTION! Danger of damaging the Fronius String Control 250/ 25 from improperly connected terminals. Improperly connected terminals can cause thermal damage to the Fronius String Control 250/25 and may cause a fire. When connecting all DC ‘IN’ and DC ‘OUT’ cables, make sure that all terminals are tightened securely using the proper torque.
EN-US
Necessary Inside Cable Length of the Fronius String Control 250/25
To ensure problem-free DC cable connections to the terminals, all DC cables inside the Fronius String Control 250/25 must have a certain mini­mum length. Depending on which side the DC cables are inserted from into the Fronius String Control 250/25, different minimum lengths of the DC cables are needed.
For the minimum inside cable length of the Fronius String Control 250/25:
- consider the guidelines in the following figure
- consider the mandatory forming of a min. 4 in. wire loop
25.16 in.
639 mm
7.83 in.
199 mm
3.98 in. 3.90 in.
101 mm
15
99 mm
20.08 in.
25.47 in.
647 mm
12.05 in.
306 mm
306 mm
Page 26
Notes for Connecting Solar Module Strings to the Fronius String Control 250/25
NOTE! Connecting the DC wiring with the
wrong polarity may cause damage to the Fronius String Control 250/25. Check both the polarity and the open circuit voltage.
The DC Voltage must not exceed 600 V, regard­less of temperature.
NOTE! When connecting fewer than 25 solar module strings, we recommend assigning an equal number of DC cables to the measuring channels as much as possible. For example: When connecting 15 solar module strings, connect 3 DC cables per measuring channel. If possible, leave individual terminals free between the DC cables.
NOTE! When connecting Aluminium cables:
- consider national and international rules for connecting Alumi­nium cables
- consider technical information of the cable manufacturer
Terminal Assi­gnment with Grounded Solar Modules
With grounded solar modules, the ungrounded poles of the solar module strings must be connected to the fused terminals (A).
Negative Grounding
Positive Grounding
DC- DC+
B (in) B‘ (out) A‘ (out) A (in)
DC+ DC-
B (in) B‘ (out) A‘ (out) A (in)
16
Page 27
Connecting Solar Module Strings to the Fronius String Control 250/25
CAUTION! Danger of damaging the Fronius String Control 250/
25 by overload. Connect a maximum of 20 A to any DC input terminal, maximum 50 A per measuring channel.
1 2
Tightening torque
1.48 ft lb.
10mm
*)
1
4
3
2
4
Tightening torque
0.39 in. 10 mm
1.48 ft lb.
5
1
2
3
*) Connect grounding cables (e.g. from solar module frame) if available.
The third grounding terminal from top can only be connected from the side near the housing.
3
EN-US
Tightening torque
1.48 ft lb.
2
NOTE!
Form a min. 4 in. wire loop using all wires.
3
0.39 in. 10 mm
4
1
17
Page 28
Connecting the Fronius String Control 250/25 to the Inverter
Safety
WARNING! An electrical shock can be fatal. Danger from DC
voltage from solar modules.
- Make sure that the input and output sides in front of the device are not charged before connecting anything.
- Any and all connections should only be carried out by quali­fied electricians.
- Follow the safety rules in these operating instructions.
WARNING! An electric shock can be fatal. Inadequately sized electrical components can cause serious injuries to persons and damage to (or loss of) property.
- All electrical installations must be in accordance with the National Electrical Code, ANSI/NFPA 70, and any other codes and regulations applicable to the installation site.
- For installations in Canada the installations must be done in accordance with applicable Canadian standards.
- Use minimum AWG 12, min. 194 °F (90 °C), copper wire for all grounding wires .
- For appropriate grounding see NEC table 250.122.
- Use maximum 250 MCM for cable input from below and 350 MCM for sidewise cable input, min. 194 °F (90 °C), copper wire for all DC wiring connections to the inverter. Voltage drop and other considerations may dictate larger size wires be used.
- Use only solid or stranded wire. Do not use fine stranded wire.
WARNING! An electric shock can be fatal. Normally grounded conductors may be ungrounded and energized when a ground fault is indicated. The ground fault has to be repaired before operation is resumed.
NOTE! Do not connect the ground to the negative DC line at any point! This is already done within the inverter. If negative DC lines are connected to the DC terminals or prior to this to the ground, this will circumvent the GFDI protection system, preventing your inverter from properly detecting a fault current. Additionally, tur­ning the DC disconnect to the off/open-circuit condition will not disconnect the array from ground, as it only disconnects the DC positive.
18
Page 29
Safety
(continued)
Consider the maximum inverter current, when sizing the DC cables ‘OUT’.
For the required cable cross section you can also use 2 cables. In this case the cable cross section of both cables should be approximately of the same size.
Cable Lugs for DC Cable ‘OUT’
CAUTION! Danger of damaging the Fronius String Control 250/
25 from improperly connected terminals. Improperly connected terminals can cause thermal damage to the Fronius String Control 250/25 and may cause a fire. When connecting all DC ‘IN’ and DC ‘OUT’ cables, make sure that all terminals are tightened securely using the proper torque.
For DC cables ‘OUT’ single hole and 2-hole cable lugs according the following specification can be used:
Dx
x
max
x
max
0.47 in. 1.14 in. 1.50 in.
max
(M12) (29 mm) (38.1 mm)
D
D
Cable lugs must comply with natio­nal regulations and guide lines.
h
EN-US
h
Preparation
D
1
2
1
DC cable ‘OUT’
4
3
2
1
2
2x
1
2
2x
19
Page 30
Connecting DC Cable ‘OUT’ to the Fronius String Control 250/25
1
3
2
1
2x
4
2
3
2
1
2x
4
Tightening torque 20.65 ft lb. Tightening torque 20.65 ft lb.
NOTE! Label the DC cables ‘OUT’ according to their designated polarity.
3
3
2
1
2x
5
Tightening torque 20.65 ft lb.
1
2
1
2
*
1 2
Connection of 1 or 2 cables per DC output
* Important! When connecting 2 cables with a 2-hole cable lug consi-
der, that both cable lugs may only be put together on their flat side.
1
2
NOTE!
Form a min. 4 in. wire loop using all wires.
20
Page 31
Connecting the Fronius String Control 250/25 to the Inverter
1. Connect the DC cable ‘OUT’ to the inverter as per the inverter opera-
1
ting instructions.
NOTE! Note the following points when connecting:
- String fuses must always be in the ungrounded conductor
- Connect the DC cable ‘OUT’ to the inverter with the correct polarity.
NOTE! Connecting the DC wiring with the wrong polarity may cause damage to the inverter. Check both the polarity and the open circuit voltage.
The DC Voltage must not exceed 600 V, regard­less of temperature.
EN-US
21
Page 32
Criteria for the Proper Selection of String Fuses
General The use of string fuses in the Fronius String Control 250/25 US also adds
fuse protection to the solar modules. A crucial factor for the fuse protection of solar modules is the maximum short circuit current ISC of the respective solar module.
Criteria for the Proper Selec­tion of String Fuses
Effects of Using Under­rated Fuses
The following criteria must be fulfilled for each solar module string when using fuse protection:
-IN > 1.8 x I
-IN < 2.4 x I
SC
SC
-VN max. input voltage of inverter being used:
FRONIUS CL....................................... 600 V DC
IN....... Nominal current rating of fuse
ISC..... short circuit current for standard test conditions (STC) according to
solar module data sheet
VN..... Nominal voltage rating of fuse
NOTE! The string fuse size must not be greater than the maxi­mum fuse current rating of the PV module as provided on the PV module manufacturers data sheet. If no maximum fuse size is indicated, please contact the PV module manufacturer.
If the fuses are underrated, the nominal current rating of the fuse can be lower than the short circuit current of the solar module. Negative effect: The fuse may open under high irradiance conditions.
Fuse Recom­mendations
NOTE Only select fuses whose nominal voltage is higher or
equal to the max. input voltage of the inverter being used.
You should only use the following fuses, which have been tested by Froni­us, to ensure problem-free fuse protection:
- Littelfuse KLKD fuses
Fronius shall not be liable for any damage or other incidents resulting from the use of other fuses. In addition, all warranty claims are forfeited.
22
Page 33
Application Example
Example: Maximum short circuit current (ISC) of the solar module = 5.75 A
According to the criteria for selecting the correct fuse, the fuse must have a nominal current greater than 1.8 times and less than 2.4 times the short circuit current:
- 5.75 A x 1.8 = 10.35 A
- 5.75 A x 2.4 = 13.8 A
The fuse that should be selected according to the „Fuses“ table: KLK D12 with 12.0 A nominal current and nominal voltage 600 V AC / DC.
EN-US
Fuses
Nominal Fuse current value
4.0 A KLK D 4
5.0 A KLK D 5
6.0 A KLK D 6
7.0 A KLK D 7
8.0 A KLK D 8
‘Fuses’ table: Excerpt of suitable fuses, e.g. Littelfuse fuses
Nominal Fuse current value
9.0 A KLK D 9
10.0 A KLK D 10
12.0 A KLK D 12
15.0 A KLK D 15
20.0 A KLK D 20
23
Page 34
Inserting String Fuses
Safety
Selecting String Fuses
WARNING! An electrical shock can be fatal. Danger from DC
voltage from solar modules.
- Make sure that the input and output sides in front of the device are not charged before connecting anything.
- Any and all connections should only be carried out by quali­fied electricians.
- Follow the safety rules in these operating instructions.
Only use fuses for solar modules that meet the proper requirements for string fuses from the solar module manufacturer or as per the „Criteria for the Proper Selection of String Fuses“ section:
- max. 20 A per fuse holder
- max. 25 solar module strings
- max. 50 A per measuring channel
- max. 250 A of total input current
- Fuse dimensions: Diameter 0.41 x 1.38 - 1.50 in. (10.3 x 35 - 38 mm)
Important
- Please follow solar module safety instructions
- Follow all solar module manufacturer requirements
Inserting String Fuses
NOTE Insert string fuses in the fuse holders corresponding to the
number of available solar modules.
1
1
2
2
3
24
Page 35
Connecting Data Communication Cables to the Fronius String Control 250/25
Connection Options
There are two options for connecting the Fronius String Control 250/25 to Solar Net:
- Via connection-ready data communication cables with RJ 45 plugs Recommended cable size: CAT 5
- Via unterminated multi-core data communication cables Max. cable cross section 2.5 mm²
(1) Terminals for unterminated
multi-core data communication cables
(2) RJ 45 connections
(2)
(1)
EN-US
Additional Insulation for Data Commu­nication Ca­bles
Important! A silicone tube is included with the Fronius String Control 250/
25 for additional data communication cable insulation. When laying the data communication cables on the inside of the Fronius String Control 250/25, the data communication cables must be fed through the silicone tube.
25
Page 36
Configuration example
Inverter with Fronius Com Card
Fronius String Control 250/25
IN
Fronius Datalogger Web
IN
OUT
IN 1 +12V
2 GND 3 Tx+ 4 Rx+ 5 Rx­6 Tx­7 GND 8 +12V
OUT 1 +12V
2 GND 3 Rx+ 4 Tx+ 5 Tx­6 Rx­7 GND 8 +12V
OUT
*)
Line/ISDN
OUTIN
*)
IN 1 +12V
2 GND 3 Tx+ 4 Rx+ 5 Rx­6 Tx­7 GND 8 +12V
OUT 1 +12V
2 GND 3 Rx+ 4 Tx+ 5 Tx­6 Rx­7 GND 8 +12V
IN 1 +12V
2 GND 3 Tx+ 4 Rx+ 5 Rx­6 Tx­7 GND 8 +12V
OUT 1 +12V
2 GND 3 Rx+ 4 Tx+ 5 Tx­6 Rx­7 GND 8 +12V
Safety
*) Termination plug
WARNING! An electrical shock can be fatal. Danger from DC voltage from solar modules.
- Make sure that the input and output sides in front of the device are not charged before connecting anything.
- Any and all connections should only be carried out by quali­fied electricians.
- Follow the safety rules in these operating instructions.
26
Page 37
Connecting RJ
1
2
2
OUT
IN
IN
OUT
3
45 Data Com­munication Cables to the Fronius String Control 250/25
1
*
*
2
EN-US
1
* Silicon tube
NOTE! Procedure when only 1 data communication cable is being connected to the Fronius String Control 250/25 (e.g., when the Fronius String Control 250/25 is the last component in a Solar Net):
- Insert the termination plug in the free RJ 45 connection. The termination plug is included with the Fronius Datalogger.
Connecting Unterminated
1
Strip approx. 2 - 3 in. (50 - 70 mm) of insulation from the end of the data communication cables
Multi-core Data Commu-
2
nication Ca­bles to the Fronius String Control 250/25
*
3
2
0.39 in.
2
10 mm
1
IN
OUT
1
2
3
1
3
**
*
* Silicon tube ** Fixing lug
Important! You must know the assignment of each individual wire when connecting the wires to the terminals.
Fix the data communicaton cables to the fixing lug using cable ties
27
Page 38
Connecting Unterminated Multi-core Data Commu­nication Ca­bles to the Fronius String Control 250/25
(continued)
NOTE! Procedure when only 1 unterminated multi-core data communication cable is being connected to the Fronius String Control 250/25 (e.g., when the Fronius String Control 250/25 is the last component in a Solar Net):
- If the data communication cable is connected to the „IN“ terminals, connect the termination plug to the „OUT“ RJ 45 connection.
- If the data communication cable is connected to the „OUT“ terminals, connect the termination plug to the „IN“ RJ 45 connection.
The termination plug is supplied with the Fronius Datalogger.
Terminal assignments
IN
OUT
+12 V GND TX­RX­RX+ TX+ GND +12 V
+12 V GND RX­TX­TX+ RX+ GND +12 V
28
Page 39
Connecting an External Power Supply
2
1
General The Fronius String Control 250/25 is supplied power through Solar Net.
The power supply from Solar Net, however, may not be sufficient when combined with additional DATCOM components or when data communi­cation cables exceed a length of 66 m. In this case, an external power supply is available. (Fronius part number 43,0001,1211)
For reasons of access, Fronius recommends that the external power supply be plugged into another DATCOM component rather than the Fronius String Control 250/25 whenever possible.
If there is no other easier connection option, the following describes the work steps involved in connecting the external power supply to the Froni­us String Control 250/25.
EN-US
Safety
Connecting an External Po­wer Supply
WARNING! An electrical shock can be fatal. Danger from DC
voltage from solar modules.
- Make sure that the input and output sides in front of the device are not charged before connecting anything.
- Any and all connections should only be carried out by quali­fied electricians.
- Follow the safety rules in these operating instructions.
1
Feed the power supply cable into the Fronius String Control 250/25 (e.g. together with data communication cables within the silicon tube)
*
* Silicon tube
29
Page 40
Setting the Address
Safety
General
WARNING! An electrical shock can be fatal. Danger from DC
voltage from solar modules.
- Make sure that the input and output sides in front of the
device are not charged before connecting anything.
- Any and all connections should only be carried out by quali-
fied electricians.
- Follow the safety rules in these operating instructions.
Solar Net allows up to 200 Fronius String Control 250/25’s to operate simultaneously. The individual Fronius String Controls are assigned addresses to distinguish them from one another. The address switch is used to set the address (0 to 199):
Setting the Address ­Examples
1XX
0XX
(1)
(2)
(3)
(1) Jumper for the hundreds’ place (2) Setting dial for the tens’ place (3) Setting dial for the ones’ place
Fronius String Control 250/25 No. 1
Fronius String Control 250/25 No. 37
Fronius String Control 250/25 No. 123
0XX
1XX
010
0XX
1XX
370
0XX
1XX
231
30
Page 41
Installing the Protection Against Contact and Closing the Fronius String Control 250/25
Safety
Installing Protection Against Con­tact
WARNING! An electrical shock can be fatal. Danger from DC
EN-US
voltage from solar modules.
- Make sure that the input and output sides in front of the
device are not charged before connecting anything.
- Any and all connections should only be carried out by quali-
fied electricians.
- Follow the safety rules in these operating instructions.
1
3
3
2
2
3
2
1
1
1
Closing the Fronius String Control 250/25
Tightening torque 1.11 ft lb.
1
4
1
2
4x
3
2
1
31
Page 42
Settings
General
Initial Steps - Install Fronius Solar.access software on a PC
Settings for the Fronius String Control 250/25 are made in the “Fronius Solar.access“ software.
- Administration / Create PV System
- PV Systems / [System Name] / Settings / String Control
(1)
(2)
Possible Set­tings for the Fronius String Control 250/25
(3)
(1) Select the number (address) of the Fronius String Control 250/25 to
be set (2) Strings per Measuring Channel (3) Limit Values:
- Max. Energy Deviation in %
- Threshold Value in Ah per String
32
Page 43
Strings per Measuring Channel
Max. Energy Deviation
Enter the number of solar module strings for each measuring channel. This results in automatic compensation of measuring channel deviations, which would only be required if there were a different number of strings per channel.
EN-US
The 5 measuring channels record the total current of the respective con­nected solar module strings over the entire charging day. In the evening, the Fronius String Control 250/25 averages all measuring channels and compares the current of each measuring channel with the average value of all channels. If the Fronius String Control 250/25 detects that one of the measuring channels deviates too much from the average, a status message is sent to the Fronius Datalogger.
The percentage deviation above which a measuring channel is conside­red faulty is defined in the “Max. Energy Deviation“ input field.
Standard value for max. energy deviation: 5 - 10 %
Threshold
If applicable, observe information from the solar module manufacturer.
The average electric charge (Ah) of all strings at which evaluation of “Max. Energy Deviation“ is to start. This prevents possible status mes­sages in bad weather.
33
Page 44
Display of Data and Status Messages
Data Display
Current data from the Fronius String Control 250/25 are displayed in: PV Systems / [System Name] / Real-time / String Control
Status Mes­sages
Status messages generated by the Fronius String Control 250/25 are sent to the datalogger. The datalogger processes this as it would a status message generated by the inverter. Status messages can be sent as an SMS, fax or e-mail. For further details please refer to the DATCOM opera­ting instructions.
The Fronius String Control 250/25 service codes are states 901 to 905. These service codes indicate an excessive deviation in measuring chan­nels 1 to 5.
We recommend that you activate the earnings comparison in the “Set­tings - General“ menu. This provides you with a list of service messages each time data are downloaded from the datalogger to the PC. This list provides a quick overview of all the messages from the inverter and the Fronius String Control 250/25.
34
Page 45
Replacing String Fuses
Safety
Preparation
WARNING! Operating the equipment incorrectly can cause
serious injury and damage. The following activities must only be carried out by trained and qualified personnel. Follow the safety rules in these operating instructions.
WARNING! An electrical shock can be fatal. Danger from DC voltage from solar modules.
- Make sure that the input and output sides in front of the device are not charged before conducting maintenance work.
- Never remove a fuse while it is under load.
1
Disconnect AC power at the inverter
2
Attach a clearly legible and easy-to-understand warning sign to prevent anyone from switching it back on or from reconnecting any open or interrupted connections
EN-US
Replacing String Fuses
3
Check to make sure that solar module strings are deenergized
Short circuit solar module strings
5
Remove the cover
Test the fuse holder at the terminals for continuity
6
NOTE! Only use fuses for solar modules that meet the proper requirements for string fuses. Fuse dimensions: Diameter 0.41 x 1.38 - 1.50 in. (10.3 x 35 - 38 mm)
35
Page 46
Replacing String Fuses
(continued)
1
1
2
2
1
3
3
Find out and correct the cause of the defective fuse
Reattach the coverFinally...
1
Remove the short circuit to the solar module strings
2
Reconnect solar module strings to the Fronius String Control 250/25
3
Reestablish the connection to the AC supply lines
36
Page 47
Technical Data
Input data
DC input voltage range 0 - 600 V
Max. input voltage 600 V (at 1000 W/m² / 14°F in open circuit operation)
Max. array short circuit current 12.5 A per string (1.25 * Imax)
Max. number of strings (with solar module fuse) 25
Admissible cable cross section min. AWG 12 - max. AWG 8 (for DC cable ‘IN’) Copper
solid and stranded conductors
Number of measuring channels 5
Max. current per measuring channel 50 A
Max. input current per fuse holder 20 A
Max. fuse size (10 x 38 class CC fuse) 20 A, 600 V
Number of grounding terminals 25
Admissible cable cross section min. AWG 12 - max. AWG 6 for grounding cables Copper
solid and stranded conductors
EN-US
Output data (to the inver­ter)
Max. continuous DC current 250 A
Admissible cable cross section for DC cables ‘OUT’
cable outlet from below 250 MCM cable outlet from side 350 MCM
Copper
solid and stranded conductors
Number of DC+ output terminals 1
Number of DC- output terminals 1
Number of grounding terminals 1
Connection possibilities per output pole or 2 x M12 (0.47 in.) grounding terminal
Max. number of cables per output pole or 2 grounding terminal
Cable lugs for output poles or single hole cable lug grounding terminal or 2-hole cable lug
37
Page 48
General Data
Protection type NEMA 3R
Protection class Type 1 (grounded)
Ambient conditions -13°F - +140°F
-25°C - +60°C
Dimensions w x h x d (without mounting clips) 27.56 x 19.53 x 5.00 in.
700 x 496 x 127 mm
Dimensions w x h x d (with mounting clips) 30.63 x 19.53 x 5.00 in.
778 x 496 x 127 mm
Weight 26.46 lbs.
12 kg
Relative humidity 0 - 95 %
(non condensing)
Housing material Aluminium
Power supply via Solar Net
optional UL listed Class 2 (12V DC)
communication protocol SolarNet, RS 485
Connectors for data communication 2 x RJ 45
or 2 x 8 pressure type terminals
38
Page 49
EN-US
39
Page 50
40
Page 51
Page 52
Fronius Worldwide - www.fronius.com/addresses
Fronius International GmbH
4600 Wels, Froniusplatz 1, Austria E-Mail: pv@fronius.com http://www.fronius.com
Under http://www.fronius.com/addresses you will find all addresses of our sales branches and partner firms!
Fronius USA LLC Solar Electronics Division
USAA
10421 Citation Drive, Suite 1100, Brighton, MI 48116 E-Mail: pv-us@fronius.com http://www.fronius-usa.com
ud_fr_se_so_00913 012011
Loading...