Fronius Fronius Smart Meter TS 5kA-3 Operating Instruction [EN]

Operating Instructions
Fronius Smart Meter TS 5kA-3
Operating Instructions
EN
42,0426,0348,EN 013-25052022
Contents
Safety rules 5
Explanation of safety notices 7 General 7 Environmental conditions 8 Qualified personnel 8 Copyright 8 Data protection 8
General information 9
Fronius Smart Meter TS 5kA-3 11
Device description 11 Information on the device 12 Intended use 12 Scope of supply 13 Positioning 13 Measuring accuracy 14
Installation 15
Checklist for installation 17 Installation 18 Protective circuit 18 Auxiliary power supply cabling 18 Cabling 19 Selection criteria for current transformer 21 Connecting the current transformers 22 Suitable voltage transformers 22 Connecting the data communication cable to the inverter 23 Terminating resistors - Explanation of symbols 23 Connecting the terminating resistor 24 Terminating resistors 24 Mounting the connection cover 26 Multi-meter system - Explanation of symbols 26 Modbus participants - Fronius SnapInverter 27 Multi-meter system - Fronius SnapINverter 27 Modbus participants - Fronius GEN24 28 Multi-meter system - Fronius GEN24 inverter 29 Menu - Measured variables 30 Configuration menu - structure and parameters 33 Setting the transformation ratio of the current and voltage transformers 34 Setting the address on the Fronius Smart Meter TS 35
EN
Start-up 37
General 39 Connecting to the Fronius Datamanager 39 Configuring the Fronius Smart Meter TS as the primary meter 39 Configuring the Fronius Smart Meter TS as a secondary meter 40
Fronius GEN24 inverter 41
General 41 Installation using the web browser 41 Configuring the Fronius Smart Meter TS as the primary meter 42 Configuring the Fronius Smart Meter TS as a secondary meter 42
Technical data 44
3
Fronius manufacturer's warranty 46
4
Safety rules
5
6
Safety rules
EN
Explanation of safety notices
DANGER!
Indicates immediate danger.
If not avoided, death or serious injury will result.
WARNING!
Indicates a potentially hazardous situation.
If not avoided, death or serious injury may result.
CAUTION!
Indicates a situation where damage or injury could occur.
If not avoided, minor injury and/or damage to property may result.
NOTE!
Indicates a risk of flawed results and possible damage to the equipment.
General The device has been manufactured in line with the state of the art and according
to recognized safety standards. If used incorrectly or misused, however, it can cause:
Injury or death to the operator or a third party
-
Damage to the device and other material assets belonging to the operating
-
company.
All personnel involved in commissioning, maintenance, and servicing of the device must:
Be suitably qualified
-
Have knowledge of and experience in dealing with electrical installations and
-
Have fully read and precisely followed these Operating Instructions
-
The Operating Instructions must always be at hand wherever the device is being used. In addition to the Operating Instructions, attention must also be paid to any generally applicable and local regulations regarding accident prevention and environmental protection.
All safety and danger notices on the device:
Must be kept in a legible state
-
Must not be damaged
-
Must not be removed
-
Must not be covered, pasted or painted over
-
The terminals can reach high temperatures.
Only operate the device when all protection devices are fully functional. If the protection devices are not fully functional, there is a danger of:
Injury or death to the operator or a third party
-
Damage to the device and other material assets belonging to the operating
-
company
7
Any safety devices that are not fully functional must be repaired by an author­ised specialist before the device is switched on.
Never bypass or disable protection devices.
For the location of the safety and danger notices on the device, refer to the sec­tion headed "General remarks" in the Operating Instructions for the device.
Any equipment malfunctions which might impair safety must be remedied before the device is turned on.
This is for your personal safety!
Environmental conditions
Qualified per­sonnel
Operation or storage of the device outside the stipulated area will be deemed as not in accordance with the intended purpose. The manufacturer accepts no liab­ility for any damage resulting from improper use.
The servicing information contained in these operating instructions is intended only for the use of qualified service engineers. An electric shock can be fatal. Do not carry out any actions other than those described in the documentation. This also applies to qualified personnel.
All cables and leads must be secured, undamaged, insulated and adequately di­mensioned. Loose connections, scorched, damaged or inadequately dimensioned cables and leads must be immediately repaired by authorised personnel.
Maintenance and repair work must only be carried out by an authorised special­ist.
It is impossible to guarantee that bought-in parts are designed and manufac­tured to meet the demands made on them, or that they satisfy safety require­ments. Use only original spare parts (also applies to standard parts).
Do not carry out any alterations, installations, or modifications to the device without first obtaining the manufacturer's permission.
Components that are not in perfect condition must be changed immediately.
Copyright Copyright of these operating instructions remains with the manufacturer.
The text and illustrations are all technically correct at the time of printing. We reserve the right to make changes. The contents of the operating instructions shall not provide the basis for any claims whatsoever on the part of the pur­chaser. If you have any suggestions for improvement, or can point out any mis­takes that you have found in the instructions, we will be most grateful for your comments.
Data protection The user is responsible for the safekeeping of any changes made to the factory
settings. The manufacturer accepts no liability for any deleted personal settings.
8
General information
9
10
Fronius Smart Meter TS 5kA-3
EN
Device descrip­tion
The Fronius Smart Meter TS is a bidirectional electricity meter which optimises self-consumption and records the household's load curve. In conjunction with the Fronius inverter, Fronius Datamanager and Fronius data interface, the Froni­us Smart Meter TS provides a clear overview of a user's own power consumption.
The meter measures the power flow to the loads or to the grid and forwards the information via the Modbus RTU/RS485 communication to the Fronius inverter and the Fronius Datamanager.
CAUTION!
Observe and follow safety instructions!
Failure to observe the safety instructions will result in damage to personnel and equipment.
Switch off the power supply before establishing a mains connection.
Observe the safety instructions.
11
Information on the device
Technical data, markings and safety symbols are located on the Fronius Smart Meter TS. These must NOT be removed or painted over. They warn against incor­rect operation which can lead to serious injury and damage.
Markings:
The devices comply with all the requisite and relevant standards and guidelines that form part of the relevant EU Directive, and are therefore permitted to display the CE mark.
Insulated (protection class II)
Regulatory Compliance Mark (RCM) Complies with all applicable regulatory requirements in Australia and New Zealand regarding safety and electromagnetic compatibility, as well as specific requirements for radio equipment.
To comply with European Directive 2012/19/EU on Waste Electrical and Electronic Equipment and its implementation as national law, electrical equipment that has reached the end of its life must be collected separ­ately and returned to an approved recycling facility. Any device that you no longer require must be returned to your distributor or disposed of at an approved collection and recycling facility in your area. Ignoring this European Directive may have potentially adverse effects on the environ­ment and your health!
RoHS (Restriction of Hazardous Substances) The limited use of certain hazardous substances in electrical and elec­tronic equipment has been complied with in accordance with EU Direct­ive 2011/65/EU.
Safety symbols:
Danger of serious injury and property damage due to incorrect opera­tion.
Dangerous electrical voltage.
Intended use The Fronius Smart Meter TS is a fixed piece of equipment for public grids of
TN/TT systems and records self-consumption and/or individual loads in the sys­tem. The Fronius Smart Meter TS is required for systems with a battery storage
12
system and/or a Fronius Ohmpilot installed for communication between the indi­vidual components. The installation is carried out on an indoor DIN rail with cor­responding back-up fuses, which are adapted to the cable cross-sections of the copper conductors and to the maximum current of the meter. The Fronius Smart Meter TS must only be operated in accordance with the specifications in the en­closed documentation and in accordance with local laws, regulations, provisions, standards and within the limits of technical possibilities. Any use of the product other than as described in the intended use shall be deemed to be not in accord­ance with the intended purpose. The available documentation forms part of the product and must be read, observed and kept in good condition. It must also be accessible at all times at the place of installation. The available documents do not replace regional, state, provincial or national laws, or regulations or stand­ards that apply to the installation, electrical safety and use of the product. Froni­us International GmbH assumes no responsibility for compliance with or non­compliance with these laws or regulations in connection with the installation of the product.
Interventions on the Fronius Smart Meter TS, e.g. modifications and alterations, are not permitted. Unauthorised interventions will void the warranty and war­ranty claims and, as a rule, void the user's authority to operate the equipment. The manufacturer shall not be liable for any damage resulting from such use.
Reasonably foreseeable misuse: The Fronius Smart Meter TS is not suitable for the supply of life-sustaining med­ical devices or for the billing of subtenants.
EN
Scope of supply
Positioning The Fronius Smart Meter TS can be installed in the following positions in the sys-
tem:
Positioning at the feed-in point:
(1) 2x seal wire (2) 2x connection cover (3) Fronius Smart Meter TS 5kA-3 (4) Quick Start guide
13
Positioning at consumption point:
For use as a secondary meter to measure individual loads and producers, see chapter Multi-meter system - Fronius SnapINverter on page 27.
Measuring ac­curacy
14
The Fronius Smart Meter TS has accuracy class 1 when measuring active energy (EN IEC 62053-21) in the voltage ranges 400 - 480 VLL or 230 -277 VLN. Within the voltage ranges 173 - 400 VLL or 100 - 230 VLN the accuracy class is 2 (active energy according to EN IEC 62053-21, reactive energy according to EN IEC 62053-23). For further details see Technical data on page 44.
Installation
15
16
Installation
EN
Checklist for in­stallation
For installation information, see the following chapters:
Switch off the power supply before establishing a mains connection.
1
Mount the Fronius Smart Meter TS (see Installation on page 18).
2
Connect automatic circuit breakers or automatic circuit breakers and discon-
3
nectors (see Protective circuit on page 18).
Connect the mains cable to the Fronius Smart Meter TS (see Cabling on
4
page 19).
Mount the current transformers on the conductors. Make sure that the cur-
5
rent transformers are pointing in the correct direction. An arrow either points to the load or the source (public grid) (see Connecting the current trans-
formers on page 22).
Connect the current transformer and Fronius Smart Meter TS (see Connect-
6
ing the current transformers on page 22).
Make sure that the current transformer phases match the mains voltage
7
phases (see Connecting the current transformers on page 22).
Note down the nominal current of the current transformer for each meter.
8
These values will be required during setup.
Connect the data communication connections of the Fronius Smart Meter
9
TS to the Fronius system monitoring (see Connecting the data communica-
tion cable to the inverter on page 23).
If necessary, set terminating resistors (see Connecting the terminating res-
10
istor on page 24).
Tug on each wire and plug to make sure that they are securely connected to
11
the terminal blocks.
Switch on the power supply to the Fronius Smart Meter TS.
12
Check the firmware version of the Fronius system monitoring. To ensure
13
compatibility between the inverter and the Fronius Smart Meter TS, the soft­ware must always be kept up to date. The update can be started via the in­verter web page or using Solar.web.
Set the transformation ratio of the current and voltage transformers (see
14
Setting the transformation ratio of the current and voltage transformers on
page 34).
If several Fronius Smart Meter TS are installed in the system, set the address
15
(see "Setting the address" under Setting the address on the Fronius Smart
Meter TS on page 35).
Configure and commission the meter (see Start-up on page 37).
16
17
Installation The Fronius Smart Meter TS can be
mounted on a 35 mm DIN rail. The housing comprises 3 modules accord­ing to DIN 43880.
Protective cir­cuit
Auxiliary power supply cabling
The Fronius Smart Meter TS is a hard-wired device and requires a disconnecting device (circuit breaker, switch or disconnector) and overcurrentprotection (auto­maticcircuit breaker).
The Fronius Smart Meter TS consumes 10 - 30 mA, the nominal capacity of the disconnecting devices and the overcurrentprotection is determined by the wire thickness, the mains voltage and the required breaking capacity.
Disconnecting devices must be mounted within sight and as close as possible
-
to the Fronius Smart Meter TS; they must also be easy to use. The disconnecting devices must satisfy the requirements of IEC 60947-1
-
and IEC 60947-3, as well as all national and local regulations for electrical systems. To monitor more than one mains voltage, use connectedautomatic circuit
-
breakers. The overcurrentprotection must protect the mains terminals with the desig-
-
nations L1, L2 and L3. In rare cases, the neutral conductor has an overcur­rentprotection, which must interrupt both neutral and non-earthed cables concurrently.
IMPORTANT!
An auxiliary power supply is required to operate the Fronius Smart Meter TS. The fuse (F) must comply with the national standards and guidelines as well as the dimensions of the conductors.
18
Cabling IMPORTANT!
Always switch off the power supply before connecting the mains voltage inputs to the Fronius Smart Meter TS.
Recommended thickness of stranded mains voltage cables for the terminals of the measuring input and measuring output:
Wire: 1 - 4 mm²
-
Recommended torque: max. 0.6 Nm
-
EN
The measuring inputs of the current transformers must be earthed on one side as shown in the circuit diagram.
Connect each voltage cable to the terminal strip as shown in the graphics below.
1 phase, 2 conductors (CT connection)
1 phase, 2 conductors (VT/CT connection)
19
2 phases, 3 conductors (CT connection)
2 phases, 3 conductors (VT/CT connection)
20
3 phases, 3 conductors (CT connection)
3 phases, 3 conductors (VT/CT connection)
3 phases, 4 conductors (Aron CT connection)
3 phases, 4 conductors (CT connection)
EN
Selection criter­ia for current transformer
3 phases, 4 conductors (VT/CT connection)
General
Do not use current transformers with a voltage output. Current transformers are directional. If they are mounted backwards or with swapped wires, the measured power will be negative.
Primary current
Maximum current per phase. A current converter with a primary current greater than the maximum expected current per phase should be selected. The closer the expected current is to this value, the more precise the measurement will be.
Secondary current
The current transformer must supply alternating current at a nominal current of 1 or 5 A. The nominal values for the current transformer are listed in the current transformer data sheet.
Power
The Fronius Smart Meter TS needs 0.5 VA to carry out its measurements. Losses also occur on the outgoing and return leads. The power of the current converter
21
must be greater than the sum total of the power of the Fronius Smart Meter TS and the leads. The higher the power, the better.
Line resistances at different cross-sections (copper wires)
Secondary cur-
rent
[A]
Cross-section
[mm²]
Line resistances at different lead lengths
(outgoing and return lead)
0.5 m 1.0 m 2.5 m 5 m 10 m
5 1.5 0.3 VA 0.6 VA 1.5 VA 2.9 VA 5.8 VA
5 2.5 0.2 VA 0.4VA0.9 VA 1.8 VA 3.6 VA
5 4 - - 0.6 VA 1.1 VA 2.2 VA
Example
The length of the outgoing and return lead (0.5 m each) between the Fronius Smart Meter TS and the current transformer is a total of 1 m and has a copper cable cross-section of 1.5 mm²; the line resistance is therefore 0.6 VA according to the table above. The self-consumption of the Fronius Smart Meter TS is 0.5 VA. Line resistance 0.6 VA + self-consumption 0.5 VA = 1.1 VA → A current transformer with a rating of 1.5 VA, 5 VA or higher is suitable here.
Accuracy class
Use Class 1 or better (Class 0.5 / 0.2, etc.). Class 1 is equivalent to a deviation of ± 1% of the secondary current at maximum power.
Mounting
Rigid or hinged "Rigid" is usually cheaper with better power and accuracy values. Hinged current transformers can be opened for attachment to the conductor. To prevent it being opened inadvertently, a plastic cable tie can be secured to the current trans­former. Hinged current transformers can be installed in a system without inter­rupting the voltage.
Connecting the current trans­formers
Suitable voltage transformers
Make sure that the current transformers match the voltage phases. Make
1
sure that current transformer L1 measures the current on the same phase that is monitored by voltage input L1. The same applies for phases L2 and L3.
Make sure that the current transformers are pointing in the correct direction.
2
Observe the data sheet for the current transformer.
Note down the nominal current of the current transformer for each meter.
3
These values will be required for setup.
Attach the current transformers to the conductor to be measured and con-
4
nect the cables of the current transformer to the Fronius Smart Meter TS.
IMPORTANT!
Always switch off the power supply before disconnecting live conductors.
The current transformers are connected to connections 4 and 5; 6 and 7; 8
5
and 9. If necessary, excessively long cables can be shortened accordingly. Observe the sequence in which the phases are connected. Accurate power measurement is only ensured if the mains voltage phases match the current phases.
Only voltage transformers with a voltage range from 220 to 480 V (phase ­phase) and from 100 to 277 V (phase - neutral conductor) may be used. The
22
voltage transformers must be connected to terminals 1, 2, 3 and N at the point of direct voltage measurement.
EN
Connecting the data communic­ation cable to the inverter
Connect the data communication connections of the Fronius Smart Meter TS to the Modbus interface of the Fronius inverter using a network cable (type CAT5 or higher).
Several Smart Meters can be installed in the system, see chapter Multi-meter
system - Fronius SnapINverter on page 27.
To avoid interference, the terminating resistor must be used (see chapter
Connecting the terminating resistor
on page 24).
Terminating res­istors - Explana­tion of symbols
IMPORTANT!
More information on successful commissioning.
Note the following information about connecting the data communication cable to the inverter.
Use network cables of type CAT5 or higher.
-
Use a mutual twisted cable pair for corresponding data lines (D+/D-, M1+/
-
M1-). If the data lines are close to the mains cabling, use wires or cables that are
-
designed for 300 to 600 V (never less than the operating voltage). Use double-insulated or sheathed data lines when they are close to bare con-
-
ductors. Use shielded twisted pair cables to avoid faults.
-
Two wires can be installed in each terminal; the wires are twisted first, inser-
-
ted into the terminal and tightened. Note: A loose wire can disable an entire area of the network. The data communication connections of the Fronius Smart Meter TS are
-
electrically isolated from hazardous voltages.
Inverter in the system
e. g. Fronius Symo
Meter - Fronius Smart Meter TS
Terminating resistor R 120 Ohm is set with a wire jumper between M- and T.
23
Modbus RTU slave
e. g. Fronius Ohmpilot, Fronius Solar Battery, etc.
Terminating resistor
R 120 Ohm
Connecting the terminating res­istor
Terminating res­istors
The terminating resistor is integrated in the Fronius Smart Meter TS and is manufactured with a bridge between the M and T connections (T = termina­tion).
Due to interference, it is recommended that terminating resistors are used as il­lustrated below to ensure proper functioning.
24
EN
* The terminating resistor is integrated in the Fronius Smart Meter TS and is manufactured with a bridge between the M and T connections (T = termination).
25
Mounting the connection cover
1
Insert the connection covers into the guides and press firmly.
IMPORTANT!
When fitting the connection covers, ensure that the cables are not kinked, pinched, crushed or otherwise dam­aged.
Multi-meter sys­tem - Explana­tion of symbols
Grid
supplies the loads in the system if insufficient power is being gen­erated by the PV modules or supplied by the battery.
Inverter in the system
e. g. Fronius Primo, Fronius Symo, etc.
Utility meter
Measures the measurement data relevant for billing amounts of energy (in particular kilowatt hours of energy sourced from the grid and energy fed into the grid). Based on the relevant billing data, the electricity retailer will invoice the energy sourced from the grid and the purchaser of the surplus energy will reimburse the energy fed into the grid.
Primary meter
Records the system's load curve and provides measurement data for energy profiling in Fronius Solar.web. The primary meter also controls the dynamic feed-in control.
26
Secondary meter
Records the load curve of individual loads (e.g. washing machine, lamps, TV, heat pump, etc.) in the consumption branch and provides measurement data for energy profiling in Fronius Sol­ar.web.
Producer meter
Records the load curve of individual producers (e.g. wind power plant) in the consumption branch and provides measurement data for energy profiling in Fronius Solar.web.
Modbus RTU slave
e. g. Fronius Ohmpilot, Fronius Solar Battery, etc.
Loads in the system
e. g. washing machine, lamps, TV, etc.
Additional loads in the system
e. g. heat pump
Additional producers in the system
e. g. wind power plant
Terminating resistor
R 120 Ohm
EN
Modbus parti­cipants - Fronius SnapInverter
A maximum of 4 Modbus participants can be connected to the Modbus terminal.
IMPORTANT!
Only one primary meter, one battery and one Ohmpilot can be connected per in­verter. Due to the high data transfer of the battery, the battery occupies 2 parti­cipants.
Example:
Input Battery
Modbus
Fronius
Ohmpilot
Quantity
Primary
meter
1 0
1 1
1 2
1 3
Quantity
Secondary
meter
Multi-meter sys­tem - Fronius SnapINverter
If several Fronius Smart Meter TS are installed, a separate address must be set for each (see Setting the address on the Fronius Smart Meter TS on page 35). The primary meter is always assigned address 1. All the other meters are numbered consecutively with the address range from 2 to 14. Different Fronius Smart Meter power categories can be used in combination.
IMPORTANT!
Max. Use 3 secondary meters in the system. To avoid interference, it is recom-
27
mended to install the terminating resistors according to chapter Connecting the
terminating resistor on page 24.
Location of the primary meter in the consumption branch. *Terminating resistor R 120 Ohm
Modbus parti­cipants - Fronius GEN24
Location of the primary meter at the feed-in point. *Terminating resistor R 120 Ohm
The following must be observed in a multi-meter system:
Only assign each Modbus address once.
-
Terminating resistors must be positioned individually for each channel.
-
The inputs M0 and M1 can be selected for this purpose. A maximum of 4 Modbus participants can be connected to the Modbus terminal on inputs M0 and M1.
IMPORTANT!
Only one primary meter, one battery and one Ohmpilot can be connected per in­verter. Due to the high data transfer of the battery, the battery occupies 2 parti­cipants.
28
Example 1:
Input Battery
Modbus 0 (M0)
Modbus 1 (M1)
Example 2:
Input Battery
Fronius
Ohmpilot
Fronius
Ohmpilot
Quantity
Primary
meter
0 4
0 2
0 1
1 3
Quantity
Primary
meter
Quantity
Secondary
meter
Quantity
Secondary
meter
EN
Multi-meter sys­tem - Fronius GEN24 inverter
1 3
Modbus 0 (M0)
0 4
0 2
Modbus 1 (M1)
If several Fronius Smart Meter TS are installed, a separate address must be set for each (see Setting the address on the Fronius Smart Meter TS on page 35). The primary meter is always assigned address 1. All the other meters are numbered consecutively with the address range from 2 to 14. Different Fronius Smart Meter power categories can be used in combination.
IMPORTANT!
Max. Use 7 secondary meters in the system. To avoid interference, it is recom­mended to install the terminating resistors according to chapter Connecting the
terminating resistor on page 24.
0 1
29
Location of the primary meter in the consumption branch. *Terminating resistor R 120 Ohm
Location of the primary meter at the feed-in point. *Terminating resistor R 120 Ohm
The following must be observed in a multi-meter system:
Connect the primary meter and the battery to different channels (recom-
-
mended). The remaining Modbus participants must be distributed equally.
-
Only assign each Modbus address once.
-
Terminating resistors must be positioned individually for each channel.
-
Menu - Measured variables
30
Image ScreenDescription
00
Total active energy drawn*
1. Total efficiency
2.
Image ScreenDescription
01
02
03
04
Total active energy supplied**
1. Total efficiency
2.
Total active energy drawn*
1. Average conductor voltage in the system
2.
Total active energy drawn*
1. Average phase voltage in the system
2.
Total active energy drawn*
1. Power factor (L = inductive, C = capacit-
2. ive)
EN
05
06
07
08
Total active energy drawn*
1. Frequency
2.
Total active energy drawn*
1. Total reactive power
2.
Total reactive energy supplied**
1. Total reactive power
2.
Total active energy drawn**
1. Total apparent power
2.
31
Image ScreenDescription
09
10
11
12
Total active energy drawn*
1. Average demanded power (P = demand),
2. calculated for the set interval. The value remains unchanged for the entire inter­val. It is "0" in the first interval after the start. Maximum demanded power (dMd = Peak
3. demand) that has been reached since the last reset.
Not used
-
Not used
-
Active energy drawn*
1.
13
14
15
Apparent power
1.
Reactive energy drawn
1.
Power factor (L = inductive, C = capacit-
1. ive)
32
Image ScreenDescription
16
18
19
20
Phase voltage
1.
Operating hours counter
1. Neutral current
2.
Current
1.
Effective power
1.
EN
Configuration menu - structure and parameters
* Displayed when easy connection mode is activated (measurement = A).
This value indicates the total energy without considering the direction.
** Factory setting - displayed when drawn and delivered energy are meas-
ured separately (measurement = b).
Screen Code Description Values
PASS*** P1 Enter the current password 2633*
nPASS P2 Password change ** Four digits (0000-9999)
SYStEM P3 Type of system 3Pn*: three-phase system,
4-core 3P: three-phase system, 3­core 2P: two-phase system, 3­core
Ct rAtIo P4 Current transformer ratio from 1* to 1000
Ut rAtIo P5 Voltage transformer ratio from 1* to 1000
MEASurE P6 Measurement mode ** A: easy connection, meas-
ures all energy without tak­ing the direction into ac­count. B*: measures imported and exported energy separately.
33
Screen Code Description Values
InStALL P7 Connection check On: activated
Off*: deactivated
P int P8 Average power calculation
interval (minutes)
MOdE P9 Display mode ** Full*: full display
tArIFF P10 Tariff management ** On: activated
HoME P11 Screen showing measured
variables displayed at star­tup and after 120 seconds of inactivity **
Ad­drESS***
bAUd P15 Baud rate (kBit/s) ** 9.6* / 19.2 / 38.4 / 57.6 /
PArITY P16 Parity ** Even/No*
STOP bit P16-2Only if parity = No. Stop bit.**1* / 2
rESET P17 Activation of the reset func-
P14 Modbus address 1* - 247
tion for energy tariffs, max­imum requested power and part values of active and re­active energy (the latter are only transmitted via the serial interface) **
1* - 30
Easy: reduced display. The values that are not dis­played are still transmitted via the serial interface.
Off*: deactivated
For full display (Mode = Full): 0* - 19
115.2
No*: reset function deactiv­ated. Yes: reset function activ­ated.
Setting the transformation ratio of the cur­rent and voltage transformers
End P18 Returns to the measured
variables start screen
* Factory settings ** The settings can be protected by changing the default password (pass-
word cannot be reset).
*** Settings that need to be configured.
Only the transformation ratio of the current and voltage transformers must be set. All other parameters are preset at the factory.
Symbol Name Event Function
Up
Down
Enter
1 x
1 x
2 seconds
Scroll one screen forward, increase the value by 1
Scroll one screen back, decrease the value by 1
Call up settings, confirm value
None
34
Press and hold "Enter" for 2
1
seconds.
Use "Up" or "Down" to access the
2
P1 screen.
Set password "2633" with "Up" and
3
"Down" and confirm each individual value with "Enter".
Note down the password.
4
IMPORTANT!
The password cannot be reset.
Use "Up" or "Down" to access the
1
P4 screen.
Press and hold "Enter" for 2
2
seconds.
Set the transformation ratio with
3
"Up" and "Down" and confirm each individual value with "Enter".
Press "Up" to access screen P18
4
and press and hold "Enter" for 2 seconds to exit the settings.
EN
Setting the ad­dress on the Fronius Smart Meter TS
Ratio of current transformers1) (0001 - 10002)). Ratio of voltage transformers
1)
Important! Changing the transformation ratios will reset the counters in the
1), 3)
(001.0 - 10002)).
Fronius Smart Meter TS to 0.
2)
Transformation ratio in the current transformer x Transformation ratio of the
voltage transformers = max. 1000
3)
Changeover only when using voltage transformers (direct voltage measurement
VT = 1)
Symbol Name Event Function
Up
1 x
Scroll one screen forward, increase the value by 1
Down
1 x
Scroll one screen back, decrease the value by 1
Enter
2 seconds
Call up settings, confirm value
35
Press and hold "Enter" for 2
1
seconds.
Use "Up" or "Down" to access the
2
P1 screen.
Set password "2633" with "Up" and
3
"Down" and confirm each individual value with "Enter".
Use "Up" or "Down" to access the
1
P14 screen.
Press and hold "Enter" for 2
2
seconds.
Set the address with "Up" and
3
"Down" and confirm each individual value with "Enter".
Press "Up" to access screen P18
4
and press and hold "Enter" for 2 seconds to exit the settings.
36
Start-up
37
38
Fronius SnapINverter
General IMPORTANT! Settings under the "Meter" menu item are only to be made by
trained and qualified personnel!
The service password must be entered in order to access the "Meter" menu item.
Three-phase or single-phase Fronius Smart Meter TS can be used. In both cases, the selection is made under the "Fronius Smart Meter" item. The Fronius Datamanager automatically identifies the meter type.
A primary meter and several secondary meters can be selected. The primary meter needs to be configured first before a secondary meter can be selected.
EN
Connecting to the Fronius Datamanager
Configuring the Fronius Smart Meter TS as the primary meter
Access point:
Select the "Setup" menu on the inverter display and enable the "Wi-Fi Access
1
Point".
Establish the connection to the inverter in the network settings (the inverter
2
is displayed with the name "Fronius_240.XXXXXX").
Password: Enter 12345678 and confirm.
3
In the browser address bar, enter and confirm the IP address http://
4
192.168.250.181 and confirm.
The Fronius Datamanager start page is displayed.
LAN:
Connect the Fronius Datamanager and computer to a LAN cable.
1
Place the Fronius Datamanager IP switch in the 'A' position.
2
In the browser address bar, enter and confirm the IP address http://
3
169.254.0.180 and confirm.
Go to the Fronius Datamanager website.
1
Open the web browser.
-
In the address bar of the browser, enter the IP address (IP address for
-
WLAN: 192.168.250.181, IP address for LAN: 169.254.0.180) or the host and domain name of the Fronius Datamanager and confirm. The Fronius Datamanager website will be displayed.
-
Click the "Settings" button.
2
Log in to the login area with the "service" user and the service password.
3
Call up the "Meter" menu area.
4
Select the primary meter from the drop-down list.
5
Click the "Settings" button.
6
In the pop-up window, set the position of the meter (feed-in point or con-
7
sumption point). For more information on the position of the Fronius Smart Meter TS, see Positioning on page 13.
Click the "Ok" button when the OK status is displayed. If the Timeout status
8
is displayed, try again.
39
9
Click the button to save the settings.
The Fronius Smart Meter TS is configured as a primary meter.
The "Current general view" menu area displays the power of the PV modules, self-consumption, the energy fed into the grid and the battery charge (if avail­able).
Configuring the Fronius Smart Meter TS as a secondary meter
Go to the Fronius Datamanager website.
1
Open the web browser.
-
In the address bar of the browser, enter the IP address (IP address for
-
WLAN: 192.168.250.181, IP address for LAN: 169.254.0.180) or the host and domain name of the Fronius Datamanager and confirm. The Fronius Datamanager website will be displayed.
-
Click the "Settings" button.
2
Log in to the login area with the "service" user and the service password.
3
Call up the "Meter" menu area.
4
Select the secondary meter from the drop-down list.
5
Click the "Add" button.
6
Enter the name of the secondary meter in the "Name" input field.
7
Enter the previously assigned address in the “Modbus address” input field.
8
Add meter description.
9
10
Click the button to save the settings.
The Fronius Smart Meter TS is configured as a secondary meter.
40
Fronius GEN24 inverter
General IMPORTANT! Settings under the "Device configuration" menu item are only to be
made by trained and qualified personnel!
The service password must be entered in order to access the "Device configura­tion" menu item.
Three-phase or single-phase Fronius Smart Meter TS can be used. In both cases, the selection is made under the "Components" menu area. The meter type is de­termined automatically.
A primary meter and several secondary meters can be selected. The primary meter needs to be configured first before a secondary meter can be selected.
EN
Installation us­ing the web browser
WLAN:
1
Open the access point by touching the sensor once → Communication LED: flashes blue.
Establish the connection to the inverter in the network settings (the inverter
2
is displayed with the name "FRONIUS_PILOT" and the serial number of the device).
Password: enter 12345678 and confirm.
3
IMPORTANT!
To enter the password on a Windows 10 operating system, the link "Connect using a security key instead" must first be activated to establish a connection with the password: 12345678.
In the browser address bar, enter and confirm the IP address
4
192.168.250.181. The installation wizard is opened.
Follow the installation wizard in the individual sections and complete the in-
5
stallation.
Add system components in Solar.web and start up the PV system.
6
The network wizard and the product setup can be carried out independently of each other. A network connection is required for the Solar.web installation wiz­ard.
Ethernet:
41
Establish a connection to the inverter (LAN1) with a network cable (CAT5
1
STP or higher).
2
Open the access point by touching the sensor once → Communication LED: flashes blue.
In the browser address bar, enter and confirm IP address 169.254.0.180. The
3
installation wizard is opened.
Follow the installation wizard in the individual sections and complete the in-
4
stallation.
Add system components in Solar.web and start up the PV system.
5
The network wizard and the product setup can be carried out independently of each other. A network connection is required for the Solar.web installation wiz­ard.
Configuring the Fronius Smart Meter TS as the primary meter
Configuring the Fronius Smart Meter TS as a secondary meter
Access the inverter website.
1
Open the web browser.
-
In the address bar of the browser, enter the IP address (IP address for
-
WLAN: 192.168.250.181, IP address for LAN: 169.254.0.180) or the host and domain name of the inverter and confirm. The inverter website is displayed.
-
Click the "Device configuration" button.
2
Log in to the login area with the "Technician" user and the technician pass-
3
word.
Access the "Components“ menu area.
4
Click the "Add component" button.
5
In the "Position" drop-down list, set the position of the meter (feed-in point
6
or consumption point). For more information on the position of the Fronius Smart Meter TS, see Positioning on page 13.
Click the "Add" button.
7
Click the "Save" button to save the settings.
8
The Fronius Smart Meter TS is configured as a primary meter.
Access the inverter website.
1
Open the web browser.
-
In the address bar of the browser, enter the IP address (IP address for
-
WLAN: 192.168.250.181, IP address for LAN: 169.254.0.180) or the host and domain name of the inverter and confirm. The inverter website is displayed.
-
Click the "Device configuration" button.
2
Log in to the login area with the "Technician" user and the technician pass-
3
word.
Access the "Components“ menu area.
4
Click the "Add component" button.
5
In the "Position" drop-down list, select the meter type (producer/load meter).
6
Enter the previously assigned address in the “Modbus address” input field.
7
Enter the name of the meter in the "Name" input field.
8
In the "Category" drop-down list, select the category (producer or load).
9
Click the "Add" button.
10
Click the "Save" button to save the settings.
11
42
The Fronius Smart Meter TS is configured as a secondary meter.
EN
43
Technical data
Technical data Modbus transmission speed: 9600 baud
Parity bit:none
Software version:
Fronius Datamanager 2.0 (from version 3.16.1 onwards)
-
Fronius Symo Hybrid (from version 1.16.1 onwards)
-
Measuring input
Nominal voltage (3-phase) Operating range (class 1) Operating range (class 2)
Nominal voltage (1-phase) Operating range (class 1) Operating range (class 2)
Voltage transformer ratio (kVT) 1 - 1000
Self-consumption - voltage path (max. voltage)
Nominal frequency Tolerance
Nominal current, l
Maximum current, I
Starting current 10 mA
Current transformer ratio (kCT) 1 - 1000
Short-time overload (EN IEC 62053-21, EN IEC 62053-23)
b
max
400 - 480 V 320 - 552 V 173 - 400 VLL ± (2 % RDG/accuracy)
230 - 277 V 184 - 318.55 V 100 - 230 VLN ± (1 % RDG/accuracy)
e. g. VT 20000/400V kVT = 50 for direct connection: kVT = 1
10 VA
50 - 60 Hz 45 - 65 Hz
1 A + 5 A
6 A
e. g. TC 800/5A kCT = 160 for direct connection: kCT = 1
5 l
/ 0.5 s
max
44
Self-consumption - current path (max. current)
Maximum value kVT x kCT 1000 (CT/5A)
Current distortion factor in acc. with EN IEC 62053-21
Power factor Operating range (EN IEC 62053-21, EN IEC 62053-23)
Energy
Max. display As per table
Resolution As per table
LED indicator 1 pulse / 0.1 Wh
Active energy accuracy (EN IEC 62053-21)
0.3 W per phase
active cosφ 0.5 ind - 0.8 cap, reactive sinφ 0.5 ind - 0.5 cap
Class 1 Class 2: 100 - 230 VLN (173 - 400 VLL)
Energy
Reactive energy accuracy (EN IEC 62053-23)
Response time after switch-on (EN IEC 62053-21, EN IEC 62053-23)
kCT x kVT Maximum display Resolution
1 - 9.9 9 9 9 9 9 9 . 9 9 kWh / kvarh 10 Wh / varh
10 - 99.9 9 9 9 9 9 9 9 . 9 kWh / kvarh 100 Wh /
100 - 999.9 9 9 9 9 9 9 9 9 kWh / kvarh 1 kWh / varh
≥ 1000 9 9 9 9 9 9 . 9 9 MWh / kvarh 10 kWh /
Average power
Measured variable Effective power
Calculation Average value over set period of time
Integration time 5 / 8 / 10 / 15 / 20 / 30 / 60 minutes
Output
Class 2
< 5 s
varh
varh
EN
RS485 communication
Electrically isolated from input and auxiliary voltage
Standard RS485 - 3 conductors
Transmission Serial, asynchronous
Protocol Modbus RTU
Addresses 1 - 255
Number of bits 8
Stop bit 1
Parity bit None - even - odd
Baud rate 9600, 19200, 38400 bit/s
Response time ≤ 200 ms
Insulation (EN IEC 62052-11, EN IEC 62053-21)
Installation category III
Pollution degree 2
Insulation voltage 4 kV RMS
Impulse withstand voltage Test circuit
4 kV 1.2/60 µs Voltage input, current input, pulse output, communication
Test voltage Test circuit
Test voltage Test circuit
2.75 kV RMS. 50 Hz/1 min Voltage input, current input, pulse output, communication
4 kV RMS. 50 Hz/1 min All circuits and earth
45
Electromagnetic compatibility
Test in acc. with EN IEC 62052-11
Operating conditions
Reference temperature 25 °C (± 5 °C)
Operating range -25 to +65 °C
Temperature limit for storage and transport
Max. power loss (for thermal dimen­sioning of the switch cabinet)
Housing
Housing 3 modules according to DIN 43880
Sealable housing/terminal cover
Connection Screw connection
Mounting Can be snapped onto 35 mm DIN rail
Housing material Noryl, self-extinguishing
Degree of protection (EN 60529) IP54 housing, IP20 connections
Weight 240 grams
Terminals
Measuring input
Wire min. 1 mm² / max. 4 mm²
Recommended torque max. 0.6 Nm
-30 to +80 °C
≤ 2.8 W
Fronius manu­facturer's war­ranty
Data output and auxiliary power supply
Wire min 0.05 mm² / max. 2.5 mm²
Recommended torque max. 0.4 Nm
Detailed, country-specific warranty terms are available on the internet: www.fronius.com/solar/warranty
To obtain the full warranty period for your newly installed Fronius inverter or storage system, please register at: www.solarweb.com.
46
EN
47
-
-
Loading...