Checklist for installation 8 Installation 8 Protective circuit 8 Cabling 9 Connecting the data communication cable to the inverter 9 Terminating resistors - Explanation of symbols 11 Terminating resistors 11 Multi-meter system - Explanation of symbols 12 Modbus participants - Fronius SnapINverter 13 Multi-meter system - Fronius SnapINverter 14 Modbus participants - Fronius GEN24 15 Multi-meter system - Fronius GEN24 inverter 16 Menu structure 17 Setting the address of the Fronius Smart Meter 17 Reading the Fronius Smart Meter operating parameters 18
EN
Start-up 21
Fronius SnapINverter 23
Fronius GEN24 inverter 25
Technical data 28
3
Safety rules
Explanation of safety notices
DANGER!
Indicates immediate danger.
If not avoided, death or serious injury will result.
WARNING!
Indicates a potentially hazardous situation.
If not avoided, death or serious injury may result.
CAUTION!
Indicates a situation where damage or injury could occur.
If not avoided, minor injury and/or damage to property may result.
NOTE!
Indicates a risk of flawed results and possible damage to the equipment.
General The device has been manufactured in line with the state of the art and according
to recognized safety standards. If used incorrectly or misused, however, it can cause:
Injury or death to the operator or a third party
-
Damage to the device and other material assets belonging to the operating
-
company.
All personnel involved in commissioning, maintenance, and servicing of the device must:
Be suitably qualified
-
Have knowledge of and experience in dealing with electrical installations and
-
Have fully read and precisely followed these Operating Instructions
-
The Operating Instructions must always be at hand wherever the device is being used. In addition to the Operating Instructions, attention must also be paid to any generally applicable and local regulations regarding accident prevention and environmental protection.
All safety and danger notices on the device:
Must be kept in a legible state
-
Must not be damaged
-
Must not be removed
-
Must not be covered, pasted or painted over
-
The terminals can reach high temperatures.
Only operate the device when all protection devices are fully functional. If the protection devices are not fully functional, there is a danger of:
Injury or death to the operator or a third party
-
Damage to the device and other material assets belonging to the operating
-
company
4
Any safety devices that are not fully functional must be repaired by an author­ised specialist before the device is switched on.
Never bypass or disable protection devices.
For the location of the safety and danger notices on the device, refer to the sec­tion headed "General remarks" in the Operating Instructions for the device.
Any equipment malfunctions which might impair safety must be remedied before the device is turned on.
This is for your personal safety!
EN
Environmental conditions
Qualified per­sonnel
Operation or storage of the device outside the stipulated area will be deemed as not in accordance with the intended purpose. The manufacturer accepts no liab­ility for any damage resulting from improper use.
The servicing information contained in these operating instructions is intended only for the use of qualified service engineers. An electric shock can be fatal. Do not carry out any actions other than those described in the documentation. This also applies to qualified personnel.
All cables and leads must be secured, undamaged, insulated and adequately di­mensioned. Loose connections, scorched, damaged or inadequately dimensioned cables and leads must be immediately repaired by authorised personnel.
Maintenance and repair work must only be carried out by an authorised special­ist.
It is impossible to guarantee that bought-in parts are designed and manufac­tured to meet the demands made on them, or that they satisfy safety require­ments. Use only original spare parts (also applies to standard parts).
Do not carry out any alterations, installations, or modifications to the device without first obtaining the manufacturer's permission.
Components that are not in perfect condition must be changed immediately.
Copyright Copyright of these operating instructions remains with the manufacturer.
The text and illustrations are all technically correct at the time of printing. We reserve the right to make changes. The contents of the operating instructions shall not provide the basis for any claims whatsoever on the part of the pur­chaser. If you have any suggestions for improvement, or can point out any mis­takes that you have found in the instructions, we will be most grateful for your comments.
Data protection The user is responsible for the safekeeping of any changes made to the factory
settings. The manufacturer accepts no liability for any deleted personal settings.
5
General
Device descrip­tion
Symbols on the device
The Fronius Smart Meter is a bidirectional electricity meter which optimises self­consumption and records the household's load curve. In conjunction with the Fronius inverter, Fronius Datamanager and Fronius data interface, the Fronius Smart Meter provides a clear overview of a user's own power consumption.
The meter measures the power flow to the loads or to the grid and forwards the information via the Modbus RTU/RS485 communication to the Fronius inverter.
CAUTION!
Observe and follow safety instructions!
Failure to observe the safety instructions will result in damage to personnel and equipment.
Switch off the power supply before establishing a mains connection.
Observe the safety instructions.
Technical data, markings and safety symbols are located on the Fronius Smart Meter. These must not be removed nor painted over. The notices and symbols warn of incorrect operation that could result in serious injury and damage to property.
Symbols on the rating plate:
CE mark
The devices conform to all the requisite and relevant standards and guidelines that form part of the relevant EU directive, and are therefore permitted to display the CE mark.
Regulatory Compliance Mark (RCM)
Complies with all applicable regulatory requirements in Australia and New Zealand regarding safety and electromagnetic compatibility, as well as specific requirements for radio equipment.
WEEE mark
In accordance with European Directive 2012/19/EU on waste electrical and electronic equipment and its implementation in national law, used electrical devices must be collected separately and recycled in an envir­onmentally responsible manner. Ensure that you return your used device to your dealer or obtain information regarding a local, authorised collection and disposal system. Failure to comply with this EU Directive may result in a negative impact on the environment and your health!
Positioning The Fronius Smart Meter can be installed at two possible locations in the system:
at the feed-in point and at the consumption point.
6
Placement at the feed-in point
Fronius Smart Meter located at the feed-in point.
Placement at the consumption point
Fronius Smart Meter located at the consumption load.
EN
7
Installation
Checklist for in­stallation
For installation information, see the following chapters:
Switch off the power supply before establishing a mains connection.
1
Mount the Fronius Smart Meter (see Installation on page 8).
2
Connect automatic circuit breakers or automatic circuit breakers and discon-
3
nectors (see Protective circuit on page 8).
Connect the mains cable to the Fronius Smart Meter (see Cabling on page
4
9).
Connect the output terminals of the Fronius Smart Meter to the Fronius in-
5
verter (see Connecting the data communication cable to the inverter on page 9).
If necessary, set terminating resistors (see Terminating resistors on page
6
11).
Tug on each wire and plug to make sure that they are securely connected to
7
the terminal blocks.
Switch on the power supply to the Fronius Smart Meter.
8
Check the firmware version of the Fronius inverter. To ensure compatibility
9
between the inverter and the Fronius Smart Meter, the software must always be kept up to date. The update can be started via the inverter web page or using Solar.web.
If several Fronius Smart Meters are installed in the system, set the address
10
(see "Setting the address" under Setting the address of the Fronius Smart
Meter on page 17).
Configure and commission the meter (see Start-up on page 21).
11
Installation The Fronius Smart Meter can be mounted on a 35 mm DIN rail. The housing
comprises 4 DUs (division units, max. 72 mm).
Protective cir­cuit
The Fronius Smart Meter is a hard-wired device and requires a disconnecting device (circuit breaker, switch or disconnector) and overcurrent protection (auto­matic circuit breaker).
The Fronius Smart Meter consumes 10 - 30 mA. The nominal capacity of the dis­connecting devices and the overcurrent protection is determined by the wire thickness, the mains voltage and the required breaking capacity.
Disconnecting devices must be mounted within sight and as close as possible
-
to the Fronius Smart Meter; they must also be easy to use. The disconnecting devices must satisfy the requirements of IEC 60947-1
-
and IEC 60947-3, as well as all national and local regulations for electrical systems. Use overcurrent protection rated for max. 63 A.
-
To monitor more than one mains voltage, use connected automatic circuit
-
breakers. The overcurrent protection must protect the mains terminals marked L1, L2
-
and L3. In rare cases, the neutral conductor has an overcurrent protection which must simultaneously interrupt neutral and unearthed lines.
8
Cabling
WARNING!
Danger from mains voltage.
An electric shock can be fatal.
Switch off the power supply before connecting the mains voltage inputs to
the Fronius Smart Meter.
IMPORTANT!
Do not install more than one cable per screw terminal. If necessary, use terminal blocks. Rate fuse according to the cross-section of the line.
Current path connection cross-section:
Wire (rigid): min. 1 mm² / max. 16 mm²
-
Wire (flexible): min. 1 mm² / max. 10 mm²
-
Recommended torque: 1.2 Nm / max. 1.4 Nm
-
Data communication and neutral conductor connection cross-section:
Wire (rigid): min. 0.05 mm² / max. 4 mm²
-
Wire (flexible): min. 0.05 mm² / max. 2.5 mm²
-
Recommended torque: 0.5 Nm / max. 0.8 Nm
-
Connect each voltage cable to the terminal strip as shown in the graphic below.
EN
Connecting the data communic­ation cable to the inverter
Fronius SnapINverter:
Connect the data communication connections of the Fronius Smart Meter to the Fronius system monitoring in the inverter. Several Smart Meters can be installed in the system, see chapter Multi-meter system - Fronius SnapINverter on page
14.
9
Connect A to D+.
1
Connect B to D-.
2
ConnectC to -.
3
Fronius GEN24 inverter:
Connect the data communication connections of the Fronius Smart Meter to the Modbus interface of the Fronius GEN24 inverter. Several Smart Meters can be installed in the system, see chapter Multi-meter system - Fronius GEN24 invert-
er on page 16.
Connect A to M1+.
1
Connect B to M1-.
2
Connect C to GND.
3
10
IMPORTANT! More information on successful commissioning.
Note the following information about connecting the data communication cable to the inverter.
Use cables of type CAT5 or higher.
Use a mutual twisted cable pair for data lines that belong together (D+, D-
and M1+, M1-). If the output cables are close to the mains cabling, use wires or cables that
are designed for 300 V to 600 V (never less than the operating voltage). Use double-insulated or sheathed output cables when they are close to bare
conductors. Use shielded twisted pair cables to avoid faults.
The outputs of the Fronius Smart Meter are electrically isolated from haz-
ardous voltages.