Selecting a Location – General Information for Fronius Primo 3.8–8.2 ................................................9
Selecting a Location – General Information for Fronius Primo 10.0–15.0 ............................................10
Installation information ...............................................................................................................................11
Auswahl von Dübel und Schrauben......................................................................................................11
Attaching the Wall Bracket....................................................................................................................11
Installing the Inverter on a Mast............................................................................................................12
Notes on the Knockouts.............................................................................................................................13
General .................................................................................................................................................13
Knock or drill out knockouts ..................................................................................................................13
Serial Number Sticker for Customer Use...................................................................................................33
Serial Number Sticker for Customer Use..............................................................................................33
EN-US
3
4
Symbol Explanations
EN-US
Explanation of
Safety Instructions
Explanation of
Symbols – Selecting a Location
DANGER! Indicates an immediate danger. Death or serious injury may result if
appropriate precautions are not taken.
WARNING! Indicates a possibly dangerous situation. Death or serious injury may
result if appropriate precautions are not taken.
CAUTION! Indicates a situation where damage or injury could occur. Minor injury
or damage to property may result if appropriate precautions are not taken.
NOTE! Indicates the possibility of flawed results and damage to the equipment.
IMPORTANT! Indicates tips for correct operation and other particularly useful information.
It does not indicate a potentially damaging or dangerous situation.
If you see any of the symbols depicted in the "Safety Rules," special care is required.
The inverter is suitable for indoor installation.
The inverter is suitable for outdoor installation.
Because of its NEMA4X protection class, the inverter is not susceptible
to hose water on any side and can also be operated in moist environments.
In order to keep inverter heating as low as possible, the inverter should
not be exposed to direct sunlight. Ideally, the inverter should be installed
in a protected location, e.g., near the solar modules or under an overhanging roof.
Fronius Primo 3.8–8.2
5
max.
13123 ft.
4000 m
> 13123 ft.
> 4000 m
max.
11811 ft.
3600 m
> 11811 ft.
> 3600 m
Altitude above sea level: up to 13,123 ft (4000 m)
IMPORTANT! The inverter must not be installed or operated above an
altitude of 13,123 ft. (4000 m).
Fronius Primo 10.0–15.0
Altitude above sea level: up to 11,811 ft (3600 m)
IMPORTANT! The inverter must not be installed or operated above an
altitude of 11,811 ft. (3600 m).
NH
3
Do not install the inverter:
-where it may be exposed to ammonia, corrosive gases, acids or
salts
(e.g., fertilizer storage areas, vent openings for livestock stables,
chemical plants, tanneries).
During certain operation phases the inverter may produce a slight noise.
For this reason it should not be installed in an occupied living area.
Do not install the inverter in:
-areas where there is an increased risk of accidents, e.g., from farm
animals (horses, cattle, sheep, pigs, etc.)
-stables or adjoining areas
-storage areas for hay, straw, chaff, animal feed, fertilizers, etc.
The inverter is designed to be dustproof in principle. However, in areas
of high dust accumulation, the cooling surfaces can become dusty, which
can impair the thermal performance. In this case, the dust must be removed regularly. We therefore recommend that installation is not carried
out in areas and environments with high dust accumulation.
Do not install the inverter in:
-greenhouses
-storage or processing areas for fruit, vegetables, or viniculture products
-areas used in the preparation of grain, green fodder, or animal
feeds.
6
Symbol Explanations – Installation Position
EN-US
The inverter is suitable for vertical installation on a vertical wall or pillar.
The inverter is suitable for horizontal installation.
The inverter is suitable for installation on an inclined surface.
Do not install the inverter on an inclined surface with the connection
sockets facing upwards.
Do not install the inverter in a sloping position on a vertical wall or pillar.
Do not install the inverter in a horizontal position on a vertical wall or pillar.
Do not install the inverter on a vertical wall or pillar with the connection
sockets facing upwards.
Do not install the inverter so that it is overhanging with the connection
sockets facing upwards.
7
Do not install the inverter so that it is overhanging with the connection
sockets facing downwards.
Do not install the inverter on the ceiling.
8
Choosing the Location
Intended UseThe inverter is designed exclusively to be connected and used with nongrounded solar
modules. The solar modules cannot be grounded at either the positive or negative pole.
The solar inverter is designed exclusively to convert direct current from solar modules into
alternating current and feed this power into the public grid.
The following are deemed not to be in conformity with its intended purpose:
-utilization for any other purpose, or in any other manner
-alterations to the inverter that are not expressly recommended by Fronius
-installation of components that are not expressly recommended or sold by Fronius.
The manufacturer is not responsible for any damage resulting from improper use.
All warranty claims are considered void in such cases.
Proper use also means
-carefully reading and obeying all the instructions and safety and danger notices in the
operating instructions
-carrying out all the specified inspection and servicing work
-installation as per operating instructions.
When configuring the photovoltaic system, make sure that all photovoltaic system components are operating completely within their permitted operating range.
EN-US
Selecting a Location – General Information for
Fronius Primo
3.8–8.2
All measures recommended by the solar module manufacturer for maintaining solar module properties must be followed.
Utility company regulations regarding grid power feed must be followed.
Please note the following criteria when choosing a location for the inverter:
Only install on a solid surface
6 in.
150 mm
Max. ambient temperatures:
-40°F to +131°F
(-40°C to +55°C)
Relative humidity:
0–100%
The air flow direction within the
inverter is from left and right to
8 in.
200 mm
-40 °F - +131 °F
-40 °C - +55 °C
0 - 100 %
4 in.
100 mm
top (cold air intake on the left and
right, hot air outflow at the top).
The waste air can reach a temperature of 70°C.
When installing the inverter in a switch cabinet or similar closed environment, it is necessary to make sure that the hot air that develops will be dissipated by forced-air ventilation.
If you wish to install the inverter on the outer walls of a cattle shed, it is important to maintain a minimum clearance of 6 ft. 7 in. (2 m) between all sides of the inverter and air vents
and other openings.
The place of installation should not be exposed to ammonia, corrosive gases, salts, or acids.
9
Selecting a Location – General Information for
Fronius Primo
10.0–15.0
Please note the following criteria when choosing a location for the inverter:
Only install on a solid surface
8 in.
200 mm
Max. ambient temperatures:
-40°F to +140°F
(-40°C to +60°C)
Relative humidity:
0–100%
The air flow direction within the
inverter is from right to top (cold
air intake on the right, hot air out-
4 in.
100 mm
4 in.
100 mm
flow at the top).
-40 °F - +140 °F
-40 °C - +60 °C
0 - 100 %
When installing the inverter in a switch cabinet or similar closed environment, it is necessary to make sure that the hot air that develops will be dissipated by forced-air ventilation.
If you wish to install the inverter on the outer walls of a cattle shed, it is important to maintain a minimum clearance of 6 ft. 7 in. (2 m) between all sides of the inverter and air vents
and other openings.
The place of installation should not be exposed to ammonia, corrosive gases, salts, or acids.
10
Installation information
EN-US
Auswahl von Dübel und Schrauben
Screw Recommendation
Attaching the
Wall Bracket
IMPORTANT! Je nach Untergrund ist unterschiedliches Befestigungsmaterial für die Mon-
tage der Montagehalterung erforderlich. Das Befestigungsmaterial ist daher nicht im
Lieferumfang des Wechselrichters enthalten. Der Monteur ist für die richtige Auswahl des
Befestigungsmaterials selbst verantwortlich.
To install the inverter, the manufacturer recommends using steel or aluminum screws with
a diameter of 0.2–0.3 in. (6–8 mm).
NOTE! When attaching the wall bracket to the wall or a pillar, make sure that the
wall bracket is not warped or deformed.
11
Installing the Inverter on a Mast
?
Example of a mast mounting kit
Fronius Primo 208-240
Installation Help
For installation of the inverter on a mast or
beam, Fronius recommends using the "Pole clamp" (order no. SZ 2584.000) mast
mounting kit from Rittal GmbH.
The kit can be used to mount the inverter on
round or rectangular masts with the following diameters: from 40 to 190 mm
(round)
from 50 to 150 mm (rectangular)
12
Notes on the Knockouts
GeneralThe wall bracket contains several knockouts of different sizes. When knocked out, the
openings are used for the inputs of various wires.
1/2 in.for data communication cable (DATCOM)
for Fronius Primo 3.8-8.2:
3/4 in.for AC and DC cables
for Fronius 10.0-15.0:
3/4 in. 1 1/4 in.
*A grounding electrode terminal may be required depending on local regula-
IMPORTANT! The knockouts on the rear of the wall bracket are made of metal.
for AC and DC cables
tions.
The cable for the ground electrode terminal can be fed through the designated opening on the underside of the wall bracket.
EN-US
Knock or drill out
knockouts
CAUTION! Danger of short circuit from loose metal parts from knockouts. Loose
metal parts in the inverter may cause short circuits when the inverter is powered
up. When removing knockouts, make sure that
-no loose metal parts fall into the connection area of the inverter,
-any metal pieces that do fall into the connection area are removed immediately.
IMPORTANT! The side knockouts and the knockouts on the underside of the wall bracket
may be knocked out using a hammer or screwdriver, or drilled out using a step drill.
The knockouts at the back may only be drilled out using a step drill.
Use suitable eye protection when knocking/drilling out the knockouts.
Only knock out knockouts using a hammer or screwdriver from the inside outwards.
Only use suitable step drills to drill out the knockouts.
Do not use spiral drills for drilling out!
Only drill out knockouts using a step drill from the outside inwards.
When drilling out using a step drill, ensure that the DC disconnector
and the AC/DC connection block are not damaged.
13
*
When drilling out the knockouts at the back, place the wall bracket on
an even surface with the back upwards so that shavings and pieces
of metal can fall out of the wall bracket.
Attach appropriate conduits to all knocked/drilled out knockouts.
In the event of installation outside, only use watertight conduits and
conduit fittings.
Conduits and conduit fittings are not included with the inverter.
14
Suitable Grids
Suitable GridsInverters can be operated on the following grids:
-208 V Delta - Corner Grounded, without neutral conductor
-208 V Delta: 120 V WYE, with neutral conductor
-220 V Delta - Corner Grounded, without neutral conductor
-220 V Delta: 127 V WYE, with neutral conductor
-240 V Delta - Corner Grounded, without neutral conductor
-240 V: 120 V WYE, with neutral conductor
-240 V: 120 V split phase, with neutral conductor
-50 Hz (220 V Delta - Corner Grounded, 50 Hz, without neutral conductor)
-50 HN (220 V Delta: 127 V WYE, 50 Hz, with neutral conductor)
EN-US
15
Notes on connection area
Permitted cablesCables with the following design can be connected to the AC and DC terminals of the in-
verter:
Cu / Al Cu
Fronius Primo 3.8–8.2Fronius Primo 10.0–15.0
Cable cross-sections:Cable cross-sections:
Cu: min. AWG 14 – max. AWG 6
Al: AWG 6
-Copper or aluminum: round, solid
-Copper: round, stranded, up to conductor class 4
Cu : min. AWG 14 - max. AWG 2
Al : AWG 6
DC =
Cu: min. AWG 14 - max. AWG 6
Al : AWG 6
Cu / Al: min. AWG 4 - max. AWG 2 (with
optional input combiner)
AC ~
Cu: min. AWG 10 - max. AWG 2;
AWG 6 - AWG 2 (for solid / stranded / fine
stranded cables)
The terminals are designed for connecting single-wire, round aluminum cables. The following points must be taken into account when connecting aluminum cables due to the nonconducting oxide layer of aluminum:
-reduced rated currents for aluminum cables
-the connection requirements listed below.
NOTE! Take into account local specifications when configuring cable cross sections.
Connection Requirements:
Carefully clean off the oxide layer of the stripped end of the cable, e.g., using a knife.
1
IMPORTANT! Do not use brushes, files, or sandpaper; aluminum particles may get stuck
and can transfer to other cables.
16
After removing the oxide layer of the cable end, rub in a neutral grease, e.g., acid-free
2
and alkali-free Vaseline.
Then immediately connect it to the terminal.
3
Repeat the steps above whenever the cable is disconnected and then reconnected.
EN-US
17
Notes on grid connection
Monitoring the
Grid
AC Connection
IMPORTANT! The resistance in the leads to the AC-side connection terminals must be as
low as possible for optimal functioning of grid monitoring.
NOTE! Fronius Primo 3.8–8.2 only:
To ensure a proper ground connection, all 3 grounding terminals GND must be
tightened with the specified torque during installation.
NOTE! Loop the AC cables when connecting them to the AC terminals:
Fronius Primo 3.8–8.2: min. 4 in. (102 mm)
Fronius Primo 10.0–15.0: in accordance with NEC
IMPORTANT! The ground conductor GND of the AC cable must be laid so that it is disconnected last.
Measure the ground conductor GND longer, for example, and loop.
If AC cables are laid over the shaft of the
DC main switch or across the DC main
switch connection block, the cables may be
damaged when the inverter is pivoted or the
inverter may not be able to be pivoted.
IMPORTANT! Do not lay AC cables over
the shaft of the DC main switch or across
the DC main switch connection block!
Example: Fronius Primo 3.8–8.2
Example: AC cables (Fronius Primo 3.8–8.2)
If excessively long AC or DC cables are laid
in loops in the connection area, fix the cables to the designated eyelets at the top and
bottom of the connection block using cable
ties.
18
Maximum AC
fuse protection
AC ~
24
max. 63 A
AC ~
24
EN-US
max. 100 A
31
Fronius 3.8–8.2
31
Fronius 10.0–15.0
InverterPhasesMax. outputMax. fuse protec-
tion
Fronius Primo 3.8-1 208-240 1 / 23800 W63 A
Fronius Primo 5.0-1 208-240 1 / 25000 W63 A
Fronius Primo 6.0-1 208-240 1 / 26000 W63 A
Fronius Primo 7.6-1 208-240 1 / 27600 W63 A
Fronius Primo 8.2-1 208-240 1 / 28200 W63 A
Fronius Primo 10.0-1 208-240 1 / 210,000 W100 A
Fronius Primo 11.4-1 208-240 1 / 211,400 W100 A
Fronius Primo 12.5-1 208-240 1 / 212,500 W100 A
Fronius Primo 15.0-1 208-240 1 / 215,000 W100 A
IΔN ≥ 100 mA
Additional external AC and/or DC
disconnect
NOTE! A residual current circuit breaker for the AC connecting cable may be re-
quired depending on local regulations, the power supply company as well as other conditions. A type A residual current circuit breaker with a trip current of at least
100 mA is generally sufficient in this case. Nevertheless, false alarms can be triggered for the type A residual current circuit breaker in individual cases and depending on local conditions.
For this reason, Fronius recommends that you use a residual current circuit
breaker suitable for a frequency converter.
Depending on the installation, an additional external AC and/or DC disconnect may be required if the inverter is installed in a location not easily accessible to utility or fire personnel.
Contact your local authorities for additional information.
19
Notes on DC Connection
General Information about Solar
Modules
Inverter DC Connection
In order to select suitable solar modules and get the most efficient use out of the inverter,
please note the following points:
-The open circuit voltage of the solar modules increases as the temperature decreases
(assuming constant irradiance).
-Note the temperature coefficients in the solar module data sheet.
-More exact data for sizing the solar modules can be obtained using calculation tools
such as the Fronius Configuration Tool (available at http://www.solarweb.com).
-See NEC table 690.7 for the appropriate code-related voltage adjustment factor for
crystalline silicon modules, or use the manufacturer’s specified voltage coefficient.
NOTE! Before connecting solar modules, make sure that the voltage specified by
the manufacturer corresponds to the actual measured voltage.
Note the safety instructions and specifications of the solar module manufacturer
regarding solar module grounding.
The inverter is designed exclusively to be
connected and used with nongrounded solar modules.
The solar modules cannot be grounded at
either the positive or negative pole.
Multi MPP Tracker Inverter – Fronius Primo 3.0–
8.2
IMPORTANT! Check the polarity and voltage of the solar module strings.
If DC cables are laid over the shaft of the
DC main switch, or across the DC main
switch connection block, they could be damaged when the inverter swivels in, or the
inverter could be prevented from swiveling
in.
IMPORTANT! Do not lay the DC cable over
the DC main switch or across the DC main
switch connection block.
Multi MPP Tracker inverters have 2 independent DC inputs (MPP Tracker). These inputs
can be connected to a number of different modules.
Each MPP Tracker has 2 DC+ terminals. There are a total of 4 DC- terminals.
20
Connecting 2–4 strings in Multi MPP Tracker mode:
PV 1
PV 2
Connect the strings separately to the two
MPP Tracker inputs (DC+1/DC+2). The
DC- terminals can be used as desired, since they are connected internally.
Set MPP TRACKER 2 to "ON" when starting for the first time (also possible in the ba-
DC+2
DC-2
DC-1
DC+1
Connecting two solar module fields to a Multi MPP
Tracker inverter
max. 18 A
per MPPT
DC+1 DC+2
12
12
DC-
12
34
sic menu subsequently).
Single MPP Tracker mode on a Multi MPP Tracker inverter:
PV 1
PV 2
max. 36 A to
a single
DC terminal
DC+1
DC+2
1
1
22
DC-
1234
If the strings are connected with a string
collection box and only one collective line is
used for connection to the inverter, connection DC+1 (pin 2) and DC+2 (pin 1) must be
bridged.
The cable cross-section of the DC connecting line and bridging wire must be the same. Bridging the DC- terminal is not
necessary because it is bridged internally.
DC-1
DC+1
*
Set MPP TRACKER 2 to "OFF" when starting for the first time (also possible in the ba-
*
D1
D1
=
sic menu subsequently).
If the Multi MPP Tracker inverter is opera-
Connecting multiple combined solar module fields to a
line on a Multi MPP Tracker inverter
ted in Single MPP Tracker mode, the currents of the connected DC lines are
distributed evenly across both inputs.
EN-US
Single MPP Tracker mode with just one string on a Multi MPP Tracker inverter:
21
WHEN ONLY ONE STRING IS USED
DC
+1
DC
+2
DC
-1
DC
-2
PV 1
DC-1
DC+1
max. 36 A to
a single
DC terminal
DC+1
DC+2
1
1
22
DC-
1234
*
*
D1
Connecting just one string to a Multi MPP Tracker inverter
D1
=
If only one string is used for connection to
the inverter, connection DC+1 (pin 2) and
DC+2 (pin 1) must be bridged.
The cable cross-section of the DC connecting line and bridging wire must be the same. Bridging the DC terminal is not
necessary because it is bridged internally.
Set MPP TRACKER 2 to "OFF" when starting for the first time (also possible in the basic menu subsequently).
If the Multi MPP Tracker inverter is operated in Single MPP Tracker mode, the currents of the connected DC lines are
distributed evenly across both inputs.
Multi MPP Tracker Inverter – Fronius Primo 10.0–
15.0
Multi MPP Tracker inverters have 2 independent DC inputs (MPP Tracker). These inputs
can be connected to a number of different modules.
MPP Tracker 1 has 4 DC+ terminals.
MPP Tracker 2 has 2 DC+ terminals.
There are a total of 6 DC- terminals.
Connecting 2-6 strings in Multi MPP Tracker mode:
Connect the strings separately to the two
PV 1PV 1
PV 2
MPP Tracker inputs (DC+1/DC+2). The
DC- terminals can be used as desired, since they are connected internally.
Set MPP TRACKER 2 to "ON" when starting for the first time (also possible in the basic menu subsequently).
MPP1: each Terminal
I
1
max
DC
2
= 15 A
+1
DC
+2
4
312
DC
-1
DC
123412
-2
DC-1
DC+1
DC-2
DC+2
22
Connecting two solar module fields to a Multi MPP
Tracker inverter
Notes on Laying Data Communication Cables
EN-US
Laying Data Communication Cables
IMPORTANT! The inverter must not be operated with one option card and 2 knocked-out
option card slots.
In this case Fronius provides an appropriate dummy cover as an accessory:
42,0405,2020 ... for Fronius Primo 3.8–8.2
42,0405,2094 ... for Fronius Primo 10.0–15.0
IMPORTANT! If data communication cables are wired into the inverter, observe the following points:
-Provide separate conduits for data communication cables
-Lay data communication cables in the supplied protective hose
-Knock out the appropriate opening
-Cleanly deburr the knocked-out opening
-Fronius Primo 3.9–8.2 only:
Insert the supplied cable gland into the opening (if both openings are knocked out, an
additional cable gland 42,0405,2019 is required)
-Clip the inverter onto the wall bracket
-Guide the data communication cables through the cable glands from behind
-When pivoting the inverter, ensure that the cables are not trapped, kinked, or damaged in any other way. Do not loop the data communication cables.
-Lay the data communication cables in the data communication area of the inverter and
connect to the Solar Net "IN" and "OUT" connections.
Plug the termination plugs into the remaining Solar Net connections.
23
Notes on Clipping the Inverter into the Wall Bracket
Clipping the Inverter onto the
Wall Bracket
The side areas of the housing cover are designed to function as carrying grips and/or
handles.
ON
NOTE! The inverter is fitted with a
OFF
Lock
lock for safety reasons, which allows the inverter to be pivoted in
the wall bracket only when the DC
main switch is off.
-Only clip on and pivot the inverter in the wall bracket
when the DC main switch is
22.1 lbf.in / 2.5 Nm
off.
-Do not use excessive force to
clip on the inverter and pivot
it.
The fixing screws in the data communication area of the inverter are used to fix the inverter
to the wall bracket. Fixing screws must be properly tightened to ensure correct contact between the inverter and the wall bracket.
CAUTION! Danger of damaging the inverter due to improperly tightened fixing
screws.
Improperly tightened fixing screws may cause arcs to occur when the inverter is
operated, which may lead to fire. Always tighten the fixing screws with the specified torque.
24
Notes on Anti-theft device
Anti-Theft DeviceFronius Primo 3.8–8.2 only
An optional anti-theft device is included in the scope of delivery.
If required, the anti-theft device is installed before the inverter is screwed to the wall bracket.
To ensure that the fixing screws cannot fall out in the inverter's data communications area,
these are fitted with a screw release.
To remove the fixing screw from the inverter
-Push the fixing screw upwards from the other side e.g. using needle-nose pliers
-Undo the fixing screw
Mounting the Anti-Theft Device
IMPORTANT! Please refer to the instructions for attaching the inverter to the wall bracket.
Swing the inverter out
1
Push the fixing screw upwards from
2
the other side e.g. using needle-nose
pliers
Undo the fixing screw
3
EN-US
2
TX25
2
TX25
1
2
Insert the fixing screw into the anti-theft
4
device
Insert the anti-theft device plus fixing
5
screw into the inverter
Swing the inverter in
6
Tighten both fixing screws to the speci-
7
3
1
22.1 lbf.in
2.5 Nm
fied torque
25
1
2
2
max 0.28 in. (7 mm)
Fit the padlock to the anti-theft device
8
26
Notes on Software Updates
EN-US
Notes on Software Updates
Insert the USB stick in the inverter data
1
communication area
Access the Setup menu
2
+
1
2
2
USB
3
4
4
5
Select the "USB" menu item
3
Select "Update Software"
4
Install the update
5
27
USB Stick as a Data Logger and for Updating Inverter Software
USB stick as a
data logger
Data on the USB
stick
A USB stick connected to the USB A socket can act as a data logger for an inverter.
Logging data saved to the USB stick can at any time
-be imported into the Fronius Solar.access software via the included FLD file,
-be viewed directly in third-party applications (e.g., Microsoft® Excel) via the included
CSV file.
Older Excel versions (up to Excel 2007) have a row limit of 65536.
If the USB stick is used as a datalogger, three files are automatically created:
-FRONIUS.sys system file:
This file saves information from the inverter that is irrelevant to the customer. The file
must not be deleted individually. Only delete all files together (sys, fld, csv).
-DALO.fld log file:
Log file for reading out data in Fronius Solar.access.
You can find additional information on the Fronius Solar.access Software in the "DATCOM Detail" operating instructions at http://www.fronius.com
-DATA.csv log file:
A log file for reading out data in a spreadsheet program (e.g., Microsoft® Excel)
(1)USB root directory
USB_Drive(1)
GALVO / SYMO / PRIMO / ECO
(2)
01 (3)
FRONIUS.sys
DALO.fld
DATA.csv
02
FRONIUS.sys
DALO.fld
DATA.csv
Data structure on the USB stick
Structure of the CSV file:
(1)(2)(3)(4)(5)(6)(7)
(2)Fronius inverter (Fronius Galvo,
Fronius Symo, Fronius Primo, or
Fronius Eco)
(3)Inverter number – can be set in the
setup menu under DATCOM
If multiple inverters exist with the same inverter number, the three files are saved in
the same folder. A number is appended to
the file name (e.g., DALO_02.fld)
28
(8)(9)
(1)ID
(2)Inverter no.
(3)Inverter type (DATCOM code)
(4)Logging interval in seconds
(5)Energy in watt-seconds with reference to the logging interval
(6)Inductive reactive power
(7)Capacitive reactive power
(8)Averages over the logging interval (AC voltage, AC current, DC voltage, DC cur-
rent)
(9)Additional information
EN-US
Data Quantity and
Memory Capacity
One USB stick with a memory capacity of 1 GB, for example, can record logging data at a
logging interval of 5 minutes for approx. 7 years.
CSV file
CSV files can store only 65535 rows (data records) (up to Microsoft® Excel version 2007,
afterwards there is no limit).
At a logging interval of 5 minutes, the 65535 rows are written within approx. 7 months (CSV
data size of approx. 8 MB).
To avoid a loss of data, the CSV file should be backed up to a PC within these 7 months
and deleted from the USB stick. If the logging interval is set longer, this time frame is extended accordingly.
FLD file
The FLD file should not be larger than 16 MB. At a logging interval of 5 minutes, this corresponds to a storage duration of approx. 6 years.
If the file exceeds this 16 MB limit, it should be backed up to a PC, and all data should be
deleted from the USB stick.
After you have backed up the data and removed it from the USB stick, the stick should be
immediately reinserted so that it can record logging data; no further steps are required.
NOTE! A full USB stick can lead to the loss of data or the overwriting of data.
When inserting the USB stick, make sure that it has a sufficient memory capacity.
Buffer MemoryIf the USB stick is removed (e.g. to back up data), the logging data are written to a buffer
memory in the inverter.
As soon as the USB stick is reinserted, the data are automatically transferred from the buffer memory to the USB stick.
The buffer memory can store a maximum of 6 logging points. Data are logged only during
inverter operation (power greater than 0 W). The logging interval is fixed at 30 minutes.
This leads to a timeframe of 3 hours for recording data to the buffer memory.
When the buffer memory is full, the oldest data in the buffer memory are written over with
the new data.
29
IMPORTANT! The buffer memory requires a constant power supply.
If there is an AC power outage during operation, all data in the buffer memory are lost. The
automatic night switch-off must be deactivated so that the data are not lost at night (set
"Night Mode" to ON – see chapter "Setting and Displaying Menu Items," section "Displaying and Setting Parameters in the 'DATCOM' Menu Item").
On the Fronius Eco, the buffer memory also functions with just a DC supply.
Suitable USB
Sticks
Due to the number of USB sticks on the market, we cannot guarantee that every USB stick
will be recognized by the inverter.
Fronius recommends using only certified, industrial USB sticks (look for the USB-IF logo).
The inverter supports USB sticks using the following file systems:
-FAT12
-FAT16
-FAT32
Fronius recommends that the USB stick only be used for recording logging data or for updating the inverter software. USB sticks should not contain any other data.
USB symbol on the inverter display, e.g., in the "NOW" display mode:
When the inverter recognizes a USB stick,
the USB symbol will appear at the top right
of the display.
When inserting the USB stick, make sure
that the USB symbol is displayed (it may
also be flashing).
USB Stick for Updating Inverter
Software
NOW
AC Output Power
NOTE! Please be aware that in outdoor applications the USB stick may only function in a limited temperature range. Make sure, for example, that the USB stick
will also function at low temperatures for outdoor applications.
The USB stick can be used to help end customers update inverter software via the USB
menu item in the SETUP menu item: the update file is first saved on the USB stick and then
transferred to the inverter. The update file must be saved in the USB stick root directory.
30
Removing the
USB Stick
Safety information for removing a USB stick
X
Do not disconnect
USB-Stick
while LED is flashing!
EN-US
IMPORTANT! To prevent a loss of data,
the connected USB stick should only be
removed under the following conditions:
-via the SETUP and "Safely remove
USB / hardware" menu items
-when the "Data Transfer" LED is no
longer flashing or illuminated.
31
Notes on Maintenance
Maintenance
Maintenance and repair work must only be carried out by authorised personnel.
CleaningThe inverter and the display can be cleaned with a damp cloth if necessary.
Do not use any cleaning agents, abrasive cleaners, or solvents to clean the inverter.
NOTE! For horizontal installation positions and when installing outside:
check once per year that all screws are secured tightly.
32
Serial Number Sticker for Customer Use
EN-US
Serial Number
Sticker for Customer Use
?
Serial No. on rating plate
Fronius Inverter
Installation
+
The inverter's serial number can be found
on the rating plate on the bottom of the inverter.
The installation position may make it difficult to access or read the serial number,
e.g. if the inverter has been installed in a
dark or shaded area.
Two serial number stickers are enclosed
with the installation instructions for the in-
*
verter:
*57 x 20 mm
**67 x 20 mm
DRM‘s for
Australia
4/8
3/7
I8
I9
1/5
2/6
I6
I7
I4
I5 IO3
RG/0
CL/0
IO212V+12V+IO0
IO1 GND GND D-
D+
**
The customer can attach these stickers
themselves in a clearly visible place, e.g. on
the front of the inverter or on the operating
instructions.
Application example
Application example:
Serial number stickers on the operating in-
I9
I5 IO3
IO1GND GND D-
4/8I72/6
CL/0
RG/0
3/7
1/5
DRM‘s for
I8
***
2
Australia
IO2 12V+12V+IO0
I6
I4
only Australia
D+
1
I9
4/8I72/6
3/7
1/5
DRM‘s for
I8
I6
Australia
I5 IO3
IO1GND GND D-
CL/0
RG/0
IO2 12V+12V+IO0
D+
I4
structions or on the front of the inverter.
Australia only:
Affix DRM Australia sticker in Datamanager
area.
Fronius Inverter
Operating
Instructions
* Serial Number Sticker for Customer Use, 57 x 20 mm
** DRMs for Australia for Customer Use, 67 x 20 mm
33
34
EN-US
35
Fronius Worldwide - www.fronius.com/addresses
Fronius International GmbH
4600 Wels, Froniusplatz 1, Austria
E-Mail: pv-sales@fronius.com
http://www.fronius.com
Under http://www.fronius.com/addresses you will find all addresses of our sales branches and partner firms!
Fronius USA LLC Solar Electronics Division
6797 Fronius Drive, Portage, IN 46368
E-Mail: pv-us@fronius.com
http://www.fronius-usa.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.