Fronius Fronius Galvo Installation (Online) Installation Instruction [EN]

Installation Instructions
Fronius Galvo - Installation
Installation Instructions
EN
42,0426,0171,EN 021-16052022
Contents
Installation location and position 5
Attaching the Mounting Bracket 11
Safety 11 Selecting wall plugs and screws 11 Recommended screws 11 Opening the inverter 11 Do not warp or deform the mounting bracket 12 Fitting the mounting bracket to a wall 13 Attaching the mounting bracket 13 Mounting the inverter on a mast 14 Fitting the mounting bracket to metal supports 14
Connecting the inverter to the public grid (AC side) 15
Safety 15 Monitoring the grid 15 AC terminals 16 Type of AC cable 16 Preparing the aluminium cables for connection 16 Requirements for the neutral conductor 17 Connecting the inverter to the public grid (AC) 17 Routing the AC cables 17 Maximum fuse rating on alternating current side 18
Connecting solar module strings to the inverter 20
Safety 20 General information about solar modules 22 DC terminals 22 Connecting aluminium cables 23 Solar module strings - checking the polarity and voltage 23 Notes regarding dummy devices 23 Inverter DC connection 24 Cable routing in the DC area 25
Grounding the solar modules in the inverter 26
General 26 Solar module ground on the negative pole via a fuse 27 Configuring the inverter for grounded solar modules 27
Data communication 28
Australian Conduits 31
Tightly sealing the conduits 31 Seal conduits 31
Attaching the inverter to the mounting bracket 32
Attaching the inverter to the mounting bracket 32
Starting for the first time 34
Starting the inverter for the first time 34
Notes regarding software updates 36
Notes regarding software updates 36
USB Stick as a Data Logger and for Updating Inverter Software 37
USB flash drive as a datalogger 37 Data on the USB flash drive 37 Data volume and storage capacity 38 Buffer memory 39 Suitable USB flash drives 39 USB stick for updating the inverter software 40 Removing the USB flash drive 40
EN
3
Notes regarding maintenance 41
Serial Number Sticker for Customer Use 42
4
Installation location and position
EN
Explanation of safety notices
DANGER!
Indicates immediate danger.
If not avoided, death or serious injury will result.
WARNING!
Indicates a potentially hazardous situation.
If not avoided, death or serious injury may result.
CAUTION!
Indicates a situation where damage or injury could occur.
If not avoided, minor injury and/or damage to property may result.
NOTE!
Indicates a risk of flawed results and possible damage to the equipment.
Safety
WARNING!
Danger due to incorrect operation and incorrectly performed work.
This can result in serious injury and damage to property.
Only qualified personnel are authorised to commission your inverter and only
within the scope of the respective technical regulations. Read the Installation and Operating Instructions before installing and com-
missioning the equipment.
WARNING!
Danger due to work that has been carried out incorrectly.
This may result in serious injury and damage to property.
Surge protective devices must only ever be installed and connected by a
qualified electrical installation engineer! Follow the safety rules.
Ensure that both the AC side and the DC side of the inverter are de-ener-
gised before carrying out any installation and connection work.
5
Fire prevention
CAUTION!
Danger due to poor or unprofessional installation.
This may result in damage to inverters and other live photovoltaic system com­ponents. Poor or unprofessional installation can cause overheating of cables and terminal connections and result in arcs. These can cause heat damage, which in turn may lead to fires.
Observe the following when connecting AC and DC cables:
Tighten all terminals to the torque specified in the operating instructions
Tighten all grounding terminals (PE / GND), including free ones, to the torque
specified in the operating instructions Do not overload cables
Check cables for damage and verify that they are laid correctly
Take note of the safety instructions, Operating Instructions and any local
connection regulations
Using fastening screws, always screw the inverter firmly to the mounting
bracket to the torque specified in the Operating Instructions. Ensure that the fastening screws are tight before starting the inverter!
Proper use/ intended pur­pose
Note! Fronius will not accept any costs associated with production downtimes,
installer costs, etc., that may arise as the result of a detected arc and its con­sequences. Fronius accepts no liability for fires that can occur despite the pres­ence of the integrated arc detection/extinguishing system (e.g. fires caused by a parallel arc).
Note! After an arc has been detected, the entire photovoltaic system must be checked for possible damage before resetting the inverter.
Observe the manufacturer's connection, installation and operating instructions at all times. To reduce the hazard potential to a minimum, perform all installation and connection work carefully according to the instructions and regulations. Refer to the device Installation Instructions for the tightening torques to be used at the relevant terminal connections.
The inverter is intended exclusively to convert direct current from solar modules into alternating current and to feed this into the public grid. Utilisation not in accordance with the intended purpose comprises:
Any use above and beyond this purpose
-
Making any modifications to the inverter that have not been expressly ap-
-
proved by Fronius the installation of components that are not distributed or expressly ap-
-
proved by Fronius.
Fronius shall not be liable for any damage resulting from such action. No warranty claims will be entertained.
Proper use also includes:
Carefully reading and obeying all the instructions and all the safety and
-
danger notices in the Operating Instructions and Installation Instructions Performing all stipulated maintenance work
-
Installation as specified in the Installation Instructions
-
6
When designing the photovoltaic system, ensure that all components are oper-
NH
3
ated within their permitted operating ranges at all times.
Observe all the measures recommended by the solar module manufacturer to ensure that the solar module retains its properties in the long term.
Obey the regulations of the power supply company regarding connection meth­ods and energy fed into the grid.
EN
Explanation of symbols and choice of loca­tion
The inverter is suitable for indoor installation.
The inverter is suitable for outdoor installation.
Because of its IP 65 protection class, the inverter is resistant to water jets from any direction and can also be used in damp en­vironments.
In order to minimise the heating up of the inverter, do not ex­pose it to direct insolation. Install the inverter in a protected location, e.g. in the vicinity of the solar modules or beneath the eaves.
Can be used at altitudes of up to 2000 m
IMPORTANT! The inverter must not be installed or used at alti­tudes above 2000 m.
Do not install the inverter in:
Areas where ammonia, corrosive vapours, acids or salts are
-
present (e.g. fertiliser stores, ventilation openings from cattle sheds, chemical plants, tanneries, etc.)
7
Do not install the inverter in:
All inverters are designed to be dust-tight. However, in areas
Do not install the inverter in:
During certain operating phases the inverter may produce a slight noise. For this reason it should not be installed close to living areas.
Places where there is an increased risk of damage from farm
-
animals (horses, cattle, sheep, pigs, etc.) Stables or adjoining areas
-
Storage areas for hay, straw, chaff, animal feed, fertilisers,
-
etc.
with a heavy build-up of dust, the thermal efficiency may still be impaired by dust forming on the cooling surfaces. Regular clean­ing is necessary in such situations. We therefore recommend not installing the inverter in areas and environments with high dust accumulation.
Greenhouses
-
Storage or processing areas for fruit, vegetables or viticul-
-
ture products Areas used in the preparation of grain, green fodder or an-
-
imal feeds
Installation posi­tion
The inverter is suitable for vertical installation on a vertical wall or column.
The inverter is suitable for a horizontal installation position.
The inverter is suitable for installation on a sloping surface.
8
Do not install the inverter on a sloping surface with its connection sockets at the top.
Do not install the inverter at an angle on a vertical wall or column.
Do not install the inverter horizontally on a vertical wall or pillar.
Do not install the inverter on a vertical wall or pillar with its con­nection sockets facing upwards.
EN
General com­ments regarding choice of loca­tion
Do not install the inverter overhanging with the connection sock­ets at the top.
Do not install the inverter overhanging with the connection sock­ets at the bottom.
Do not install the inverter on the ceiling.
Please note the following criteria when choosing a location for the inverter:
Only install on a solid, non-flammable surface
9
Max. ambient temperatures:
-25 °C / +50 °C
Relative humidity: 0-100%
The airflow within the invert­er is from the left to the top (cold air taken in from the left, hot air dissipated out of the top). The exhaust air can reach a temperature of 70 °C.
The environmental conditions of the inverter must be maintained at the install­ation location.
If the inverter is to be installed on the outer wall of a cattle shed, maintain a minimum all-round clearance of 2 m between the inverter and all ventilation and other openings in the building. The installation location must not be exposed to ammonia, corrosive vapours, salts or acids.
10
Attaching the Mounting Bracket
EN
Safety
WARNING!
Danger due to residual voltage in capacitors.
This may result in an electric shock.
Wait for the capacitors to discharge. The discharge time is five minutes.
CAUTION!
Danger due to dirt or water on the terminals and contacts of the inverter's con­nection area.
This may result in damage to the inverter.
When drilling, ensure that terminals and contacts in the connection area do
not become dirty or wet. The mounting bracket without a power stage set does not conform to the
protection class of the inverter as a whole, and therefore must not be in­stalled without a power stage set. The mounting bracket should be protected from dirt and moisture during in-
stallation.
Note! Degree of protection IP 65 is only applicable if
the inverter is placed in the mounting bracket and permanently attached us-
-
ing screws the cover for the data communication area is permanently attached to the
-
inverter with screws.
Selecting wall plugs and screws
Recommended screws
Opening the in­verter
Degree of protection IP 20 applies to the mounting bracket with no inverter and the venting duct.
Important! Different fixings may be required to fit the mounting bracket depend­ing on the type of underlying surface. Fixings are therefore not included in the scope of supply of the inverter. The installer is responsible for selecting the right type of fixing.
To install the inverter, the manufacturer recommends the use of steel or alumini­um screws with a diameter of 6 - 8 mm.
WARNING!
Danger from inadequate ground conductor connection.
This can result in serious injury and damage to property.
The housing screws provide a suitable ground conductor connection for
grounding the housing and must NOT be replaced by any other screws that do not provide a reliable ground conductor connection.
11
1 2
3 4
Do not warp or deform the mounting brack­et
Note! When fitting the mounting bracket to the wall, ensure that the mounting
bracket does not become warped or deformed.
12
Fitting the mounting brack­et to a wall
1 2
Tip: Install the inverter so that its display is at eye level
3
EN
Note! When mounting the mounting
bracket on the wall, ensure that the mounting bracket does not become warped or deformed.
Attaching the mounting brack­et
1 2
13
3
Mounting the in­verter on a mast
Fitting the mounting brack­et to metal sup­ports
When mounting the inverter on a mast or a vertical carrier, Fronius recom­mends the use of a standard mast fix­ing kit.
This kit enables the inverter to be mounted on round or rectangular masts with various cross-sections.
Example of a mast fixing kit
The mounting bracket must be affixed at a minimum of four points.
1
14