Fronius Conformity VDE-AR-N 4105 2018 NA protection Fronius Symo 3.0-3-M - 8.2-3-M (E.6, E.7) Certificate [EN]

Manufacturer / applicant:
Fronius International GmbH Günter Fronius Straße 1 4600 Wels Austria
Type of grid and plant protection:
Integrated NS protection
Assigned to generation unit type:
Symo 8.2-3-M, Symo 8.0-3-M, Symo 7.0-3-M, Symo 6.7-3-M, Symo 6.0-3-M, Symo 5.5-3-M, Symo 5.0-3-M, Symo 4.5-3-M, Symo 3.7-3-M, Symo 3.0-3-M
Firmware version:
beginning with V1.1.4.0
Connection rule:
VDE-AR-N 4105:2018-11 – Power generation systems connected to the low-voltage distribution network
Technical minimum requirements for the connection to and parallel operation with low-voltage distribution networks.
Applicable standards /
directives:
DIN VDE V 0124-100 (VDE V 0124-100):2020-06 – Grid integration of power generation systems – low voltage
Test requirements for power generation units to be connected and operated parallel with the low-voltage distribution networks
BV project number:
19TH0406-VDE-0124-100:2020_0
Certification program:
NSOP-0032-DEU-ZE-V01
Certificate number:
U21-0406
Date of issue:
2021-05-18
Certification body
Thomas Lammel
Annex to the Certificate for the NS-protection No. U21-0406
Page 2 of 2
E.7 Requirements for the test report for the NS protection
Extract from test report for NS protection Nr. 19TH0406-VDE-0124-100:2020_0 “Determination of electrical properties”
NS protection as integrated NS protection
Manufacturer / applicant:
Fronius International GmbH Günter Fronius Straße 1 4600 Wels Austria
Type of grid and plant protection:
Integrated NS protection
Assigned to generation unit type:
Symo 8.2-3-M, Symo 8.0-3-M, Symo 7.0-3-M, Symo 6.7-3-M, Symo 6.0-3-M, Symo 5.5-3-M, Symo 5.0-3-M, Symo 4.5-3-M, Symo 3.7-3-M, Symo 3.0-3-M
Firmware version:
Beginning with V1.1.4.0
Integrated interface switch:
Type of switching equipment 1: Relay Type of switching equipment 2: Relay
Measurement period:
2019-09-20 – 2020-02-13
Protection function
Setting value
Trip value
Disconnection time a
Voltage drop protection U <
184,0 V
183,0 V
3,013 s
Voltage drop protection U <<
103,5 V
103,8 V
0,317 s
Rise-in-voltage protection U>
253,0 V
--
427 sb
Rise-in-voltage protection U>>
287,5 V
287,8 V
0,114 s
Frequency decrease protection f<
47,50 Hz
47,51 Hz
0,122 s
Frequency increase protection f>
51,50 Hz
51,52 Hz
0,126 s
a
proper time of interface switch 10 ms
b
longest disconnection of the rise-in-voltage protection as a moving 10-minute-average, tested according clause 5.7.7 Protection
devices and protection settings of VDE 0124-100 The disconnect time (sum of trip time of grid and plant protection and delay time of interface switch) must not exceed 200 ms. A check of the overall functional chain "NS protection – interface switch" resulted in a successful disconnection. The above mentioned grid and plant protection with the assigned power generation units has met the requirements for islanding
detection with the help of the active method (resonant circuit test). The above mentioned NS protection meets the requirements for synchronization.