Manufacturer / applicant:
Fronius International GmbH
Günter Fronius Straße 1
4600 Wels
Austria
Type of power generation unit:
Photovoltaic (PV) inverter
Active power (nominal power at
reference conditions) [kW]:
VDE-AR-N 4105:2018-11 – Power generation systems connected to the low-voltage
distribution network
Technical minimum requirements for the connection to and parallel operation with lowvoltage distribution networks.
Applicable standards /
directives:
DIN VDE V 0124-100 (VDE V 0124-100):2020-06 – Grid integration of power
generation systems – low voltage
Test requirements for power generation units to be connected and operated parallel with
the low-voltage distribution networks
The above mentioned generation units have been tested and certified according to the test guideline VDE 0124-100. The
electrical properties required in the connection rule are satisfied.
• Verification of permissible system perturbations
• Verification of the symmetry characteristics of three-phase inverter modules
• Verification of the characteristics of the power generation unit on the network
• Verification of P
AV,E
surveillance
• Verification of dynamic network support
• Verification of the possibility to take part in the generation management / network security management
The certificate contains the following information:
• Technical specifications of the power generation units, the deployed auxiliary equipment and the software version used.
• Summarized information about the characteristics of the power generation unit (mode of operation)
15TH0304-VDE-0124-100:2020_0
Certification body
Thomas Lammel
Certification body Bureau Veritas Consumer Products Services Germany GmbH accredited according to DIN EN ISO/IEC 17065
A partial representation of the certificate requires the written permission of Bureau Veritas Consumer Products Services Germany GmbH

Annex to the Unit Certificate No. U21-0399
E.5 Requirements for the test report for power generation units
Extract from the test report for unit certification Nr. 15TH0304-VDE-0124-100:2020_0
„Determination of electrical properties“
Description of the power generation unit
Manufacturer / applicant:
Fronius International GmbH
Günter Fronius Straße 1
4600 Wels
Austria
Type of power generation unit:
Photovoltaic (PV) inverter
Rated current (AC) Ir [A]:
Initial short-current AC current [A]:
Description of the structure of the power generation unit:
The power generation unit is equipped with a PV and line-side EMC filter. The power generation unit has no galvanic isolation
between DC input and AC output. Output switch-off is performed with single-fault tolerance thanks to the inverter bridge and two
series-connected relays. This enables a safe disconnection of the power generation unit from the network in case of error.
Active power
(results at nominal grid voltage)
S
Emax
[kVA] at cos φ = 1
P
Emax
[kW] at cos φ
under-excite
= 0,9
S
Emax
[kVA] at cos φ
under-excite
= 0,9
P
Emax
[kW] at cos φ
over-excited
= 0,9
S
Emax
[kVA] at cos φ
over-excited
= 0,9
Note:
At cosφ = 1 the active power is equal to the rated apparent power.
For the implementation of a reactive power set point assignment, the active power is reduced if necessary.

Annex to the Unit Certificate No. U21-0399
E.5 Requirements for the test report for power generation units
Extract from the test report for unit certification Nr. 15TH0304-VDE-0124-100:2020_0
„Determination of electrical properties“
Reactive power transfer function – standard cos φ (P)-characteristic curve
Active power P
Emax setpoint
[%]
According to VDE 0124-100, an accuracy of cos φ 0,01 is required for testing the Reactive power transfer function. The standard
cos φ-(P)-characteristic curve is respected. To provide the set point of the reactive power, active power will be reduced at 100 %
P / P
n.
*For the implementation of a reactive power set point assignment, the active power is reduced.
Switch-on without specification (to the primary energy source) ki
Switch-on at auxiliary conditions (of the primary energy source) ki
Switch-off at auxiliary conditions (of the primary energy source) ki
Worst value of all switching operations ki
Flicker for rated current >75A (at SCR = 20)
System flicker coefficient cψ:
The self-generation unit(s) are comply with DIN EN 61000-3-12 (VDE 0838-12).