Fronius Conformity EN 50438 incl. attachment Fronius Eco Certificate [EN]

Annex to Certificate
Registration No.: AK 60104859 0001
Seite / Page 1 of 15
Models of the same family:
FRONIUS ECO 25.0-3-S; FRONIUS ECO 27.0-3-S
FRONIUS International GmbH Guenter Fronius-Str.1 A-4600 Wels-Thalheim _ Austria
Name and address of test house
TÜV Rheinland Italia S.r.l. Via Mattei. 3 - 20010 Pogliano Milanese (MI) - Italy
Telephone number
Tel: +39.02.939 687
Facsimile number
Fax: +39.02.939 687 23
E-mail address
info@it.tuv.com
Date of test
See First Page
Name of test Engineer
Alessandro Luciani
Signature of test Engineer
See First Page
Test location (if different from above)
See above
E.1 General Details E.1.1 Micro-generator details
E.1.2 Test house details
E.1.3 Test details
Annex to Certificate
Registration No.: AK 60104859 0001
Seite / Page 2 of 15
Under frequency
Over frequency
Parameter
Frequency [Hz]
Time[s]
Frequency [Hz]
Time[s]
Protection
Limit
47.00
0.5
51.00
0.5
Trip Value
46.99
0.44
51.02
0.46
Supplementary information: none
E.2 Type testing of the interface protection E.2.1 General
If the interface protection is considered as a dedicated device external to the micro-generator, only the operate time of the interface protection can be evaluated. In this case, the opening time of the interface switch shall be taken into account when evaluating the compliance with this European Standard.
E.2.2 Over / Under frequency
Annex to Certificate
Registration No.: AK 60104859 0001
Seite / Page 3 of 15
Under Voltage
Over Voltage
Parameter
Voltage [V]
Time [s]
Voltage [V]
Time [s]
Protection
Limit
195.5
(230 V -15%)
0.2
264.5
(230 V +15%)
0.2
Trip Value
197
0.154
262.3
154
Supplementary information: none
Over Voltage
Remarks
Parameter
Voltage [V]
Time [s]
Protection
Limit
255.3
(230 V +11%)
60
--
Trip Value
255.3
50
--
Supplementary information: none
E.2.3 Over / Under voltage
Annex to Certificate
Registration No.: AK 60104859 0001
Seite / Page 4 of 15
No.
P
EUT
(% of EUT
rating)
Reactive
load
(% of QL in
6.1.d)
P
ac
(% of
nominal)
Q
ac
(% of
nominal)
Run on
time [ms]
PEUT
[kW]
Actual Qf
Vdc
Remarks
1
100
100 0 0
393
26.5
1
850
Test A at BL
2
66
66 0 0
354
17.3
1
710
Test B at BL
3
33
33 0 0
270
8.2 1 620
Test C at BL
4
100
100
-5
-5
285
26.5
1
850
Test A at IB
5
100
100
-5 0 161
26.5
1
850
Test A at IB
6
100
100
-5
+5
122
26.5
1
850
Test A at IB
7
100
100 0 -5
228
26.5
1
850
Test A at IB
8
100
100 0 +5
157
26.5
1
850
Test A at IB
9
100
100
+5
-5
116
26.5
1
850
Test A at IB
10
100
100
+5 0 142
26.5
1
850
Test A at IB
11
100
100
+5
+5
337
26.5
1
850
Test A at IB
12
66
66 0 -5
113
17.3
1
710
Test B at IB
13
66
66 0 -4
132
17.3
1
710
Test B at IB
14
66
66 0 -3
180
17.3
1
710
Test B at IB
15
66
66 0 -2
198
17.3
1
710
Test B at IB
16
66
66 0 -1
286
17.3
1
710
Test B at IB
17
66
66 0 1
225
17.3
1
710
Test B at IB
18
66
66 0 2
258
17.3
1
710
Test B at IB
19
66
66 0 3
257
17.3
1
710
Test B at IB
20
66
66 0 4
133
17.3
1
710
Test B at IB
21
66
66 0 5
177
17.3
1
710
Test B at IB
22
33
33 0 -5
199
8.2 1 620
Test C at IB
23
33
33 0 -4
262
8.2 1 620
Test C at IB
24
33
33 0 -3
242
8.2 1 620
Test C at IB
25
33
33 0 -2
260
8.2 1 620
Test C at IB
26
33
33 0 -1
253
8.2 1 620
Test C at IB
27
33
33 0 1
241
8.2 1 620
Test C at IB
28
33
33 0 2
231
8.2 1 620
Test C at IB
29
33
33 0 3
137
8.2 1 620
Test C at IB
30
33
33 0 4
256
8.2 1 620
Test C at IB
31
33
33 0 5
175
8.2 1 620
Test C at IB
1)
P
EUT
: EUT output power
2)
PAC: Real power flow at S1 as in Figure 1. Positive value means the power from EUT to utility. Nominal value is the 0% test condition value.
3)
QAC: Reactive power flow at S1 as in Figure 1. Positive value means the power from EUT to utility. Nominal value is the 0% test condition
value
4)
BL: Balance condition, IB: Imbalance condition *: Needs to be measured if any of the recorded run-on times at imbalanced condition are longer than the one recorded for the rated balance condition at test condition A ** “Run on time” must be < 2s The filled out switch-off time values the highest among the three phase
E.2.4 Loss of main (LoM)