600 V/500 V - 460 V, 575 V - 440 V
auto-transformer
Operating instructions
EN
Autotransformer
42,0426,0084,EN 012-25082020
Contents
Safety rules5
Explanation of safety notices5
General5
Proper use5
Environmental conditions6
Obligations of the operator6
Obligations of personnel6
Mains connection6
Protecting yourself and others7
Noise emission values7
Danger from toxic gases and vapours8
Danger from flying sparks8
Risks from mains current and welding current9
Meandering welding currents10
EMC Device Classifications10
EMC measures10
EMF measures11
Specific hazards11
Danger from shielding gas cylinders12
Safety measures at the installation location and during transport12
Safety measures in normal operation13
Commissioning, maintenance and repair14
Safety inspection14
Disposal14
Safety symbols14
Data protection15
Copyright15
General16
Machine concept16
Possible voltage ranges16
Application areas16
Scope of supply16
Warning notices affixed to the device16
Mains connection17
Control elements and connections18
Safety18
Control elements and connections18
Before commissioning19
Safety19
Setup regulations19
Intended purpose19
Fitting the mains cable to the auto-transformer21
Safety21
Specified mains cable for the auto-transformer21
Preparing the mains cable for connection to the auto-transformer21
Connecting the mains cable to the auto-transformer22
Running functionality checks23
Setting the auto-transformer to 500 V mains voltage25
Safety25
General25
Setting the auto-transformer to 500 V mains voltage25
Adapting the rating plate26
Running functionality checks27
Fitting the auto-transformer28
Safety28
General28
Mounting the auto-transformer and the system components28
Putting the auto-transformer into service31
Safety31
Putting the auto-transformer into service31
EN
3
Care, maintenance and disposal32
Safety32
At every start-up32
Every 6 months32
Disposal33
Troubleshooting34
Safety34
Troubleshooting34
Technical data37
Safety37
600 V/500 V - 460 V, 575 - 440 V auto-transformer37
4
Safety rules
EN
Explanation of
safety notices
DANGER!
Indicates immediate danger.
If not avoided, death or serious injury will result.
▶
WARNING!
Indicates a potentially hazardous situation.
If not avoided, death or serious injury may result.
▶
CAUTION!
Indicates a situation where damage or injury could occur.
If not avoided, minor injury and/or damage to property may result.
▶
NOTE!
Indicates a risk of flawed results and possible damage to the equipment.
GeneralThe device is manufactured using state-of-the-art technology and according to recog-
nised safety standards. If used incorrectly or misused, however, it can cause:
-injury or death to the operator or a third party,
-damage to the device and other material assets belonging to the operating company,
-inefficient operation of the device.
All persons involved in commissioning, operating, maintaining and servicing the device
must:
-be suitably qualified,
-have sufficient knowledge of welding and
-read and follow these operating instructions carefully.
The operating instructions must always be at hand wherever the device is being used. In
addition to the operating instructions, attention must also be paid to any generally applicable and local regulations regarding accident prevention and environmental protection.
All safety and danger notices on the device
-must be in a legible state,
-must not be damaged,
-must not be removed,
-must not be covered, pasted or painted over.
For the location of the safety and danger notices on the device, refer to the section
headed "General" in the operating instructions for the device.
Before switching on the device, rectify any faults that could compromise safety.
This is for your personal safety!
Proper useThe device is to be used exclusively for its intended purpose.
5
The device is intended solely for the welding processes specified on the rating plate.
Any use above and beyond this purpose is deemed improper. The manufacturer shall not
be held liable for any damage arising from such usage.
Proper use includes:
-carefully reading and following all the instructions given in the operating instructions
-studying and obeying all safety and danger notices carefully
-performing all stipulated inspection and maintenance work.
Never use the device for the following purposes:
-Thawing out pipes
-Charging batteries
-Starting engines
The device is designed for use in industry and the workshop. The manufacturer accepts
no responsibility for any damage caused through use in a domestic setting.
The manufacturer likewise accepts no liability for inadequate or incorrect results.
Environmental
conditions
Obligations of the
operator
Operation or storage of the device outside the stipulated area will be deemed as not in
accordance with the intended purpose. The manufacturer shall not be held liable for any
damage arising from such usage.
Ambient temperature range:
-during operation: -10 °C to + 40 °C (14 °F to 104 °F)
-during transport and storage: -20 °C to +55 °C (-4 °F to 131 °F)
Relative humidity:
-up to 50% at 40 °C (104 °F)
-up to 90% at 20 °C (68 °F)
The surrounding air must be free from dust, acids, corrosive gases or substances, etc.
Can be used at altitudes of up to 2000 m (6561 ft. 8.16 in.)
The operator must only allow persons to work with the device who:
-are familiar with the fundamental instructions regarding safety at work and accident
prevention and have been instructed in how to use the device
-have read and understood these operating instructions, especially the section
"safety rules", and have confirmed as much with their signatures
-are trained to produce the required results.
Checks must be carried out at regular intervals to ensure that operators are working in a
safety-conscious manner.
Obligations of
personnel
Mains connectionDevices with a higher rating may affect the energy quality of the mains due to their cur-
6
Before using the device, all persons instructed to do so undertake:
-to observe the basic instructions regarding safety at work and accident prevention
-to read these operating instructions, especially the "Safety rules" section and sign to
confirm that they have understood them and will follow them.
Before leaving the workplace, ensure that people or property cannot come to any harm
in your absence.
rent consumption.
This may affect a number device types in terms of:
-Connection restrictions
-
Criteria with regard to the maximum permissible mains impedance
-
Criteria with regard to the minimum short-circuit power requirement
*)
at the interface with the public grid
*)
*)
see "Technical data"
In this case, the plant operator or the person using the device should check whether the
device may be connected, where appropriate by discussing the matter with the power
supply company.
IMPORTANT! Ensure that the mains connection is earthed properly
EN
Protecting yourself and others
Anyone working with the device exposes themselves to numerous risks, e.g.
-flying sparks and hot pieces of metal
-Arc radiation, which can damage eyes and skin
-Hazardous electromagnetic fields, which can endanger the lives of those using cardiac pacemakers
-Risk of electrocution from mains current and welding current
-Greater noise pollution
-Harmful welding fumes and gases
Suitable protective clothing must be worn when working with the device. The protective
clothing must have the following properties:
-Flame-resistant
-Insulating and dry
-Covers the whole body, is undamaged and in good condition
-Safety helmet
-Trousers with no turn-ups
Protective clothing refers to a variety of different items. Operators should:
-Protect eyes and face from UV rays, heat and sparks using a protective visor and
regulation filter
-Wear regulation protective goggles with side protection behind the protective visor
-Wear stout footwear that provides insulation even in wet conditions
-Protect the hands with suitable gloves (electrically insulated and providing protection
against heat)
-Wear ear protection to reduce the harmful effects of noise and to prevent injury
Noise emission
values
Keep all persons, especially children, out of the working area while any devices are in
operation or welding is in progress. If, however, there are people in the vicinity:
-Make them aware of all the dangers (risk of dazzling by the arc, injury from flying
sparks, harmful welding fumes, noise, possible risks from mains current and welding
current, etc.)
The device generates a maximum sound power level of <80 dB(A) (ref. 1pW) when idling
and in the cooling phase following operation at the maximum permissible operating point
under maximum rated load conditions according to EN 60974-1.
It is not possible to provide a workplace-related emission value during welding (or cutting) as this is influenced by both the process and the environment. All manner of different welding parameters come into play, including the welding process (MIG/MAG, TIG
welding), the type of power selected (DC or AC), the power range, the type of weld
metal, the resonance characteristics of the workpiece, the workplace environment, etc.
7
Danger from
toxic gases and
vapours
The fumes produced during welding contain harmful gases and vapours.
Welding fumes contain substances that cause cancer, as stated in Monograph 118 of the
International Agency for Research on Cancer.
Use at-source extraction and a room extraction system.
If necessary, use a welding torch with an integrated extraction device.
Keep your face away from welding fumes and gases.
Fumes and hazardous gases
-must not be breathed in
-must be extracted from the working area using appropriate methods.
Ensure an adequate supply of fresh air. Ensure that there is a ventilation rate of at least
20 m³ per hour at all times.
Otherwise, a welding helmet with an air supply must be worn.
If there is any doubt about whether the extraction capacity is sufficient, the measured
toxic emission values should be compared with the permissible limit values.
The following components are responsible, amongst other things, for the degree of toxicity of welding fumes:
-Metals used for the workpiece
-Electrodes
-Coatings
-Cleaners, degreasers, etc.
-Welding process used
Danger from flying sparks
The relevant material safety data sheets and manufacturer's specifications for the listed
components should therefore be studied carefully.
Recommendations for trade fair scenarios, risk management measures and for identifying working conditions can be found on the European Welding Association website under
Health & Safety (https://european-welding.org).
Flammable vapours (e.g. solvent fumes) should be kept away from the arc's radiation
area.
Close the shielding gas cylinder valve or main gas supply if no welding is taking place.
Flying sparks may cause fires or explosions.
Never weld close to flammable materials.
Flammable materials must be at least 11 metres (36 ft. 1.07 in.) away from the arc, or
alternatively covered with an approved cover.
A suitable, tested fire extinguisher must be available and ready for use.
Sparks and pieces of hot metal may also get into adjacent areas through small gaps or
openings. Take appropriate precautions to prevent any danger of injury or fire.
Welding must not be performed in areas that are subject to fire or explosion or near
sealed tanks, vessels or pipes unless these have been prepared in accordance with the
relevant national and international standards.
Do not carry out welding on containers that are being or have been used to store gases,
propellants, mineral oils or similar products. Residues pose an explosive hazard.
8
Risks from mains
current and welding current
An electric shock is potentially life threatening and can be fatal.
Do not touch live parts either inside or outside the device.
During MIG/MAG welding and TIG welding, the welding wire, the wirespool, the feed
rollers and all pieces of metal that are in contact with the welding wire are live.
Always set the wirefeeder up on a sufficiently insulated surface or use a suitable, insulated wirefeeder holder.
Make sure that you and others are protected with an adequately insulated, dry base or
cover for the earth or ground potential. This base or cover must extend over the entire
area between the body and the earth or ground potential.
All cables and leads must be secured, undamaged, insulated and adequately dimensioned. Replace loose connections and scorched, damaged, or inadequately dimensioned cables and leads immediately.
Use the handle to ensure the power connections are tight before every use.
In the case of power cables with a bayonet connector, rotate the power cable around the
longitudinal axis by at least 180° and pretension.
Do not wrap cables or leads around the body or parts of the body.
The electrode (rod electrode, tungsten electrode, welding wire, etc.) must
-never be immersed in liquid for cooling
-Never touch the electrode when the power source is switched on.
EN
Double the open circuit voltage of a power source can occur between the welding electrodes of two power sources. Touching the potentials of both electrodes at the same time
may be fatal under certain circumstances.
Arrange for the mains cable to be checked regularly by a qualified electrician to ensure
the ground conductor is functioning properly.
Protection class I devices require a mains supply with ground conductor and a connector
system with ground conductor contact for proper operation.
Operation of the device on a mains supply without ground conductor and on a socket
without ground conductor contact is only permitted if all national regulations for protective
separation are observed.
Otherwise, this is considered gross negligence. The manufacturer shall not be held liable
for any damage arising from such usage.
If necessary, provide adequate earthing for the workpiece.
Switch off unused devices.
Wear a safety harness if working at height.
Before working on the device, switch it off and pull out the mains plug.
Attach a clearly legible and easy-to-understand warning sign to the device to prevent
anyone from plugging the mains plug back in and switching it on again.
After opening the device:
-Discharge all live components
-Ensure that all components in the device are de-energised.
If work on live parts is required, appoint a second person to switch off the main switch at
the right moment.
9
Meandering welding currents
If the following instructions are ignored, meandering welding currents can develop with
the following consequences:
-Fire hazard
-Overheating of parts connected to the workpiece
-Irreparable damage to ground conductors
-Damage to device and other electrical equipment
Ensure that the workpiece is held securely by the workpiece clamp.
Attach the workpiece clamp as close as possible to the area that is to be welded.
Position the device with sufficient insulation against electrically conductive environments,
e.g. Insulation against conductive floor or insulation to conductive racks.
If distribution boards, twin-head mounts, etc., are being used, note the following: The
electrode of the welding torch / electrode holder that is not used is also live. Make sure
that the welding torch / electrode holder that is not used is kept sufficiently insulated.
In the case of automated MIG/MAG applications, ensure that only an insulated wire electrode is routed from the welding wire drum, large wirefeeder spool or wirespool to the
wirefeeder.
EMC Device Classifications
EMC measuresIn certain cases, even though a device complies with the standard limit values for emis-
Devices in emission class A:
-Are only designed for use in industrial settings
-Can cause line-bound and radiated interference in other areas
Devices in emission class B:
-Satisfy the emissions criteria for residential and industrial areas. This is also true for
residential areas in which the energy is supplied from the public low-voltage mains.
EMC device classification as per the rating plate or technical data.
sions, it may affect the application area for which it was designed (e.g. when there is
sensitive equipment at the same location, or if the site where the device is installed is
close to either radio or television receivers).
If this is the case, then the operator is obliged to take appropriate action to rectify the
situation.
Check and evaluate the immunity to interference of nearby devices according to national
and international regulations. Examples of equipment that may be susceptible to interference from the device include:
-Safety devices
-Power, signal and data transfer lines
-IT and telecommunications devices
-Measuring and calibrating devices
10
Supporting measures for avoidance of EMC problems:
tional measures are necessary (e.g. use a suitable line filter).
2.Welding power leads
-must be kept as short as possible
-must run close together (to avoid EMF problems)
-must be kept well apart from other leads
3.Equipotential bonding
4.Earthing of the workpiece
-If necessary, establish an earth connection using suitable capacitors.
5.Shielding, if necessary
-Shield off other nearby devices
-Shield off entire welding installation
EMF measuresElectromagnetic fields may pose as yet unknown risks to health:
-effects on the health of others in the vicinity, e.g. wearers of pacemakers and hearing aids
-wearers of pacemakers must seek advice from their doctor before approaching the
device or any welding that is in progress
-for safety reasons, keep distances between the welding cables and the welder's
head/torso as large as possible
-do not carry welding cables and hosepacks over the shoulders or wind them around
any part of the body
Specific hazardsKeep hands, hair, clothing and tools away from moving parts. For example:
-Fans
-Cogs
-Rollers
-Shafts
-Wirespools and welding wires
EN
Do not reach into the rotating cogs of the wire drive or into rotating drive components.
Covers and side panels may only be opened/removed while maintenance or repair work
is being carried out.
During operation
-Ensure that all covers are closed and all side panels are fitted properly.
-Keep all covers and side panels closed.
The welding wire emerging from the welding torch poses a high risk of injury (piercing of
the hand, injuries to the face and eyes, etc.).
Therefore always keep the welding torch away from the body (devices with wire-feed
unit) and wear suitable protective goggles.
Never touch the workpiece during or after welding - risk of burns.
Slag can jump off cooling workpieces. The specified protective equipment must therefore
also be worn when reworking workpieces, and steps must be taken to ensure that other
people are also adequately protected.
Welding torches and other parts with a high operating temperature must be allowed to
cool down before handling.
Special provisions apply in areas at risk of fire or explosion - observe relevant
national and international regulations.
Power sources for work in areas with increased electric risk (e.g. near boilers) must carry
the "Safety" sign. However, the power source must not be located in such areas.
Risk of scalding from escaping coolant. Switch off cooling unit before disconnecting
coolant flow or return lines.
Observe the information on the coolant safety data sheet when handling coolant. The
coolant safety data sheet may be obtained from your service centre or downloaded from
the manufacturer's website.
Use only suitable load-carrying equipment supplied by the manufacturer when transporting devices by crane.
11
-Hook chains and/or ropes onto all suspension points provided on the load-carrying
equipment.
-Chains and ropes must be at the smallest angle possible to the vertical.
-Remove gas cylinder and wire-feed unit (MIG/MAG and TIG devices).
If the wire-feed unit is attached to a crane holder during welding, always use a suitable,
insulated wirefeeder hoisting attachment (MIG/MAG and TIG devices).
If the device has a carrying strap or handle, this is intended solely for carrying by hand.
The carrying strap is not to be used if transporting with a crane, counterbalanced lift truck
or other mechanical hoist.
All lifting accessories (straps, handles, chains, etc.) used in connection with the device or
its components must be tested regularly (e.g. for mechanical damage, corrosion or
changes caused by other environmental factors).
The testing interval and scope of testing must comply with applicable national standards
and directives as a minimum.
Odourless and colourless shielding gas may escape unnoticed if an adapter is used for
the shielding gas connection. Prior to assembly, seal the device-side thread of the
adapter for the shielding gas connection using suitable Teflon tape.
Danger from
shielding gas cylinders
Shielding gas cylinders contain gas under pressure and can explode if damaged. As the
shielding gas cylinders are part of the welding equipment, they must be handled with the
greatest of care.
Protect shielding gas cylinders containing compressed gas from excessive heat, mechanical impact, slag, naked flames, sparks and arcs.
Mount the shielding gas cylinders vertically and secure according to instructions to prevent them falling over.
Keep the shielding gas cylinders well away from any welding or other electrical circuits.
Never hang a welding torch on a shielding gas cylinder.
Never touch a shielding gas cylinder with an electrode.
Risk of explosion - never attempt to weld a pressurised shielding gas cylinder.
Only use shielding gas cylinders suitable for the application in hand, along with the correct and appropriate accessories (regulator, hoses and fittings). Only use shielding gas
cylinders and accessories that are in good condition.
Turn your face to one side when opening the valve of a shielding gas cylinder.
Close the shielding gas cylinder valve if no welding is taking place.
If the shielding gas cylinder is not connected, leave the valve cap in place on the cylinder.
Safety measures
at the installation
location and during transport
12
The manufacturer's instructions must be observed as well as applicable national and
international regulations for shielding gas cylinders and accessories.
A device toppling over could easily kill someone. Place the device on a solid, level surface such that it remains stable
-The maximum permissible tilt angle is 10°.
Special regulations apply in rooms at risk of fire or explosion
-Observe relevant national and international regulations.
Use internal directives and checks to ensure that the workplace environment is always
clean and clearly laid out.
Only set up and operate the device in accordance with the degree of protection shown
on the rating plate.
When setting up the device, ensure there is an all-round clearance of 0.5 m (1 ft. 7.69
in.) to ensure that cooling air can flow in and out freely.
When transporting the device, observe the relevant national and local guidelines and
accident prevention regulations. This applies especially to guidelines regarding the risks
arising during transport.
Do not lift or transport operational devices. Switch off devices before transport or lifting.
Before transporting the device, allow coolant to drain completely and detach the following components:
-Wirefeeder
-Wirespool
-Shielding gas cylinder
After transporting the device, the device must be visually inspected for damage before
commissioning. Any damage must be repaired by trained service technicians before
commissioning the device.
EN
Safety measures
in normal operation
Only operate the device when all safety devices are fully functional. If the safety devices
are not fully functional, there is a risk of
-injury or death to the operator or a third party
-damage to the device and other material assets belonging to the operator
-inefficient operation of the device
Any safety devices that are not functioning properly must be repaired before switching on
the device.
Never bypass or disable safety devices.
Before switching on the device, ensure that no one is likely to be endangered.
Check the device at least once a week for obvious damage and proper functioning of
safety devices.
Always fasten the shielding gas cylinder securely and remove it beforehand if the device
is to be transported by crane.
Only the manufacturer's original coolant is suitable for use with our devices due to its
properties (electrical conductibility, anti-freeze agent, material compatibility, flammability,
etc.).
Only use suitable original coolant from the manufacturer.
Do not mix the manufacturer's original coolant with other coolants.
Only connect the manufacturer's system components to the cooling circuit.
The manufacturer accepts no liability for damage resulting from use of other system
components or a different coolant. In addition, all warranty claims will be forfeited.
Cooling Liquid FCL 10/20 does not ignite. The ethanol-based coolant can ignite under
certain conditions. Transport the coolant only in its original, sealed containers and keep
well away from any sources of ignition.
Used coolant must be disposed of properly in accordance with the relevant national and
international regulations. The coolant safety data sheet may be obtained from your service centre or downloaded from the manufacturer's website.
13
Check the coolant level before starting to weld, while the system is still cool.
Commissioning,
maintenance and
repair
Safety inspectionThe manufacturer recommends that a safety inspection of the device is performed at
It is impossible to guarantee that bought-in parts are designed and manufactured to meet
the demands made of them, or that they satisfy safety requirements.
-Use only original spare and wearing parts (also applies to standard parts).
-Do not carry out any modifications, alterations, etc. to the device without the manufacturer's consent.
-Components that are not in perfect condition must be replaced immediately.
-When ordering, please give the exact designation and part number as shown in the
spare parts list, as well as the serial number of your device.
The housing screws provide the ground conductor connection for earthing the housing
parts.
Only use original housing screws in the correct number and tightened to the specified
torque.
least once every 12 months.
The manufacturer recommends that the power source be calibrated during the same 12month period.
A safety inspection should be carried out by a qualified electrician
-after any changes are made
-after any additional parts are installed, or after any conversions
-after repair, care and maintenance has been carried out
-at least every twelve months.
For safety inspections, follow the appropriate national and international standards and
directives.
Further details on safety inspection and calibration can be obtained from your service
centre. They will provide you on request with any documents you may require.
DisposalDo not dispose of this device with normal domestic waste! To comply with the European
Directive on Waste Electrical and Electronic Equipment and its implementation as
national law, electrical equipment that has reached the end of its life must be collected
separately and returned to an approved recycling facility. Any device that you no longer
require must either be returned to your dealer or given to one of the approved collection
and recycling facilities in your area. Ignoring this European Directive may have potentially adverse affects on the environment and your health!
Safety symbolsDevices with the CE mark satisfy the essential requirements of the low-voltage and elec-
tromagnetic compatibility directives (e.g. relevant product standards of the EN 60 974
series).
Fronius International GmbH hereby declares that the device is compliant with Directive
2014/53/EU. The full text on the EU Declaration of Conformity can be found at the following address: http://www.fronius.com
14
Devices marked with the CSA test mark satisfy the requirements of the relevant standards for Canada and the USA.
Data protectionThe user is responsible for the safekeeping of any changes made to the factory settings.
The manufacturer accepts no liability for any deleted personal settings.
CopyrightCopyright of these operating instructions remains with the manufacturer.
The text and illustrations are all technically correct at the time of printing. We reserve the
right to make changes. The contents of the operating instructions shall not provide the
basis for any claims whatsoever on the part of the purchaser. If you have any suggestions for improvement, or can point out any mistakes that you have found in the instructions, we will be most grateful for your comments.
EN
15
General
(1)
(2)
(3)
(5)
(4)
Machine conceptThe auto-transformer allows the
TransSteel 3500/5000 MIG/MAG power
source to be used with mains voltages of
600 V, 575 V and 500 V. The mains
voltage is transformed to 460 V or 440 V.
The auto-transformer has its own main
switch, which can be used to centrally
switch all the components of the welding
system on or off.
A cylinder holder extension is delivered
with the auto-transformer to enable the
auto-transformer to be mounted on the
PickUp 5000 trolley together with a cooling
unit and a power source.
Possible voltage
ranges
Application areasThe auto-transformer can be used for all products in the TransSteel 3500/5000 series.
Scope of supply
The auto-transformer transforms voltages as follows:
-600 V/500 V - 460 V
-575 V - 440 V
The auto-transformer is prepared for 600 V and 575 V mains voltage at the factory. To
use the auto-transformer at a mains voltage of 500 V, set it to 500 V mains voltage (see
the "Setting the auto-transformer to 500 V mains voltage" section).
(1)Auto-transformer with 1.5 m con-
nection cable for the power source
(2)Four 5 x 16 mm screws for screw-
ing to the trolley
(3)Four 5 x 25 mm screws for screw-
ing to the power source or cooling
unit
(4)Eight M 5 x 12 screws for the cylin-
der holder extension
(5)Cylinder holder extension
(6)Operating instructions (not shown)
Warning notices
affixed to the
device
16
The auto-transformer has safety symbols on the rating plate. The safety symbols must
NOT be removed or painted over. The symbols warn against operating the equipment
incorrectly, as this may result in serious injury and damage.
Do not dispose of used units with domestic waste.
Dispose of them according to safety rules.
Do not use the functions until you have fully read
all the operating instructions.
IP 23
S
1
21 kVA
35 A
3 x 500V36 A
24.7 A
35 A
600/575V31 A21.5 A
PRIM
U
1
I
1maxI1eff
100%
24 A
40%
38 A
X (40°C)
I
2
U
2
3 x 460 / 440 V
SEC
IEC 60974-1
A-4600 Wels
www.fronius.com
Type:
Ser.No.:
Art.No.:
2047XXXX
4,001,706
Autotrafo 3x600/500V-460V
Mains connectionThe devices are designed for the mains voltage specified on the rating plate. If your ver-
sion of the appliance does not come with mains cables and plugs ready-fitted, these
must be fitted in accordance with national regulations and standards. For details of fuse
protection of the mains lead, please see the technical data.
EN
CAUTION!
An inadequately dimensioned electrical installation can cause serious damage.
The mains lead and its fuse must be dimensioned to suit the local power supply. The
▶
technical data shown on the rating plate applies.
17
Control elements and connections
(1)
(3)(2)
Safety
Control elements
and connections
WARNING!
Operating the equipment incorrectly can cause serious injury and damage.
Do not use the functions described until you have thoroughly read and understood the
following documents:
these operating instructions
▶
all the operating instructions for the system components, especially the safety rules
▶
Front view
No.
Function
(1)Mains switch
for switching the auto-transformer and all the welding system components on and
off
(2)Strain relief device for the mains cable
(3)Power source connection cable
for supplying the power source with transformed voltage
Rear view
18
Before commissioning
EN
Safety
Setup regulations
WARNING!
Work that is carried out incorrectly can cause serious injury or damage.
The activities described below must only be carried out by trained and qualified personnel. Do not carry out the activities described below until you have fully read and understood the following documents:
these operating instructions
▶
all the operating instructions for the system components, especially the safety rules
▶
WARNING!
If one of these machines topples over or falls it could cause serious or even fatal
injury.
Place device on a solid, level surface in such a way that it remains stable.
The device is tested to IP 23 in conjunction with a power source or a cooling unit, meaning:
-Protection against penetration by solid foreign bodies with diameters > 12 mm (0.49
in.)
-Protection against direct sprays of water up to 60° from the vertical
NOTE!
If the auto-transformer is used without a device (power source and cooling unit)
fixed onto it, the protection class of the auto-transformer is reduced to IP 20.
Cooling air
The system must be set up in such a way that the cooling air can flow unimpeded
through the slots in the side panels.
Dust
Make sure that metallic dust cannot accumulate directly on the device (from grinding
work, for example).
Outdoor operation
The device can be set up and operated outdoors in accordance with IP23. Avoid direct
wetting (e.g. from rain).
Intended purposeThe device is intended solely for voltage transformation for the voltages specified on the
rating plate.
The device is intended solely for use in conjunction with a Fronius power source.
Any use above and beyond this purpose is deemed improper. The manufacturer is not
liable for any damage, unexpected or incorrect results arising out of such misuse.
19
Utilisation in accordance with the "intended purpose" also comprises
-carefully reading and obeying all operating instructions and safety and danger
notices
-carrying out all the specified inspection and servicing work
The device is designed for use in industry and the workshop. The manufacturer accepts
no responsibility for any damage caused through use in a domestic setting.
20
Fitting the mains cable to the auto-transformer
EN
Safety
WARNING!
Work that is carried out incorrectly can cause serious injury or damage.
The activities described below must only be carried out by trained and qualified personnel. Do not carry out the activities described below until you have fully read and understood the following documents:
these operating instructions
▶
all the operating instructions for the system components, especially the safety rules
▶
WARNING!
An electric shock can be fatal.
Before starting work:
Turn the mains switch of the auto-transformer to the "O" position
▶
Unplug the auto-transformer from the mains
▶
Put up an easy-to-understand warning sign to stop anybody inadvertently switching
▶
it back on again
Using a suitable measuring instrument, check to make sure that electrically charged
▶
components (e.g. capacitors) have been discharged
WARNING!
Specified mains
cable for the
auto-transformer
An inadequate ground conductor connection can cause serious injury or damage.
The housing screws provide a suitable ground conductor connection for earthing the
housing and must NOT be replaced by any other screws that do not provide a reliable
ground conductor connection.
Specified EU mains cable:
Cable typeCross-section for 500VCross-section for 600
V / 575 V
H07RN-F4G44G45 m (199.6 in.)
Specified UL / CSA mains cable:
Cable typeCross-section for 500VCross-section for 600
V / 575 V
SOOWAWG 8AWG 105 m (199.6 in.)
Length
Length
Preparing the
mains cable for
connection to the
auto-transformer
CAUTION!
If wire end ferrules are not used, there is a risk of short circuits between the phase
conductors or between phase conductors and the PE conductor.
Fit wire-end ferrules to all phase conductors and the PE conductor of the stripped mains
cable.
21
1
2
110mm (4.33in.)
90mm (3.54in.)
10mm (.394in.)
10mm (.394in.)
1
6
3
4
5
1
2
110mm (4.33in.)
Connecting the
mains cable to
the auto-transformer
WARNING!
Work that is carried out incorrectly can cause serious injury and damage.
The following activities must only be carried out by trained and qualified personnel. Pay
particular attention to the "Safety rules" section.
1
2
22
1
2
3
3
2
1
EN
4
Running functionality checks
WARNING!
Work that is carried out incorrectly can cause serious injury and damage.
The following activities must only be carried out by trained and qualified personnel.
Observe the safety rules in the operating instructions for the power source and the autotransformer.
WARNING!
An electric shock can be fatal.
If the device needs to be switched on briefly for testing while the housing is open:
Do not touch any parts inside the housing
▶
Use only suitable measuring or test probes for measurements and tests inside the
▶
housing
Connect the power source connection cable to the power source as described in the
1
power source operating instructions
Remove the left side panel of the auto-transformer
2
Check that the phase conductor and PE conductor of the power source connection
3
cable and the auto-transformer mains cable are securely attached to the wiring terminal and are correctly connected
Check the insulation and PE conductor using a suitable device
4
23
Connect the auto-transformer to the mains
5
Using a suitable device, test the mains voltage at the INPUT 600V (575V) / 500V,
6
50/60HZ terminal screws; mains voltage = 600 V (575 V)
Turn the mains switch of the auto-transformer to the "I" position
7
Using a suitable device, test the output voltage at the OUTPUT 460V (440V),
8
50/60HZ terminal screws; output voltage = 460 V (440 V)
Turn the mains switch of the auto-transformer to the "O" position
9
Unplug the auto-transformer from the mains
10
Fit the left side panel of the auto-transformer
11
Check the insulation and PE conductor using a suitable device: place the test probe
12
of the testing device on any of the cover's fastening screws
24
Setting the auto-transformer to 500 V mains voltage
EN
Safety
WARNING!
Work that is carried out incorrectly can cause serious injury or damage.
The activities described below must only be carried out by trained and qualified personnel. Do not carry out the activities described below until you have fully read and understood the following documents:
these operating instructions
▶
all the operating instructions for the system components, especially the safety rules
▶
WARNING!
An electric shock can be fatal.
Before starting work:
Turn the mains switch of the auto-transformer to the "O" position
▶
Unplug the auto-transformer from the mains
▶
Put up an easy-to-understand warning sign to stop anybody inadvertently switching
▶
it back on again
Using a suitable measuring instrument, check to make sure that electrically charged
▶
components (e.g. capacitors) have been discharged
WARNING!
An inadequate ground conductor connection can cause serious injury or damage.
The housing screws provide a suitable ground conductor connection for earthing the
housing and must NOT be replaced by any other screws that do not provide a reliable
ground conductor connection.
GeneralThe auto-transformer is prepared for 600 V and 575 V mains voltage at the factory. To
use the auto-transformer at a mains voltage of 500 V, set it to 500 V mains voltage as
described below.
Setting the autotransformer to
500 V mains
voltage
Work that is carried out incorrectly can cause serious injury and damage.
The following activities must only be carried out by trained and qualified personnel. Pay
particular attention to the "Safety rules" section.
Phase conductors that are not fully reconnected or that are connected incorrectly
can cause serious damage.
Always reconnect all phase conductors.
WARNING!
CAUTION!
25
3
4
1
2
1
1
1
2
1
2
1
2
3
5
4
Adapting the rating plate
26
CAUTION!
Operating the auto-transformer at an incorrect mains voltage can cause serious
damage.
If the auto-transformer has been converted to a mains voltage of 500 V, cross out "600
V" in the space above the rating plate and enter "500 V" in the empty box beside it.
Indicate the conversion to 500 V mains voltage as shown
1
500V
EN
Running functionality checks
WARNING!
Work that is carried out incorrectly can cause serious injury and damage.
The following activities must only be carried out by trained and qualified personnel.
Observe the safety rules in the operating instructions for the power source and the autotransformer.
WARNING!
An electric shock can be fatal.
If the device needs to be switched on briefly for testing while the housing is open:
Do not touch any parts inside the housing
▶
Use only suitable measuring or test probes for measurements and tests inside the
▶
housing
Connect the power source connection cable to the power source as described in the
1
power source operating instructions
Remove the left side panel of the auto-transformer
2
Check that the phase conductor and PE conductor of the power source connection
3
cable and the auto-transformer mains cable are securely attached to the wiring terminal and are correctly connected
Check the insulation and PE conductor using a suitable device
4
Connect the auto-transformer to the mains
5
Using a suitable device, test the mains voltage at the INPUT 600V (575V) / 500V,
6
50/60HZ terminal screws; mains voltage = 500 V
Turn the mains switch of the auto-transformer to the "I" position
7
Using a suitable device, test the output voltage at the OUTPUT 460V (440V),
8
50/60HZ terminal screws; output voltage = 460 V
Turn the mains switch of the auto-transformer to the "O" position
9
Unplug the auto-transformer from the mains
10
Fit the left side panel of the auto-transformer
11
Check the insulation and PE conductor using a suitable device: place the test probe
12
of the testing device on any of the cover's fastening screws
27
Fitting the auto-transformer
2
1
3
Safety
WARNING!
Work that is carried out incorrectly can cause serious injury or damage.
The activities described below must only be carried out by trained and qualified personnel. Do not carry out the activities described below until you have fully read and understood the following documents:
these operating instructions
▶
all the operating instructions for the system components, especially the safety rules
▶
WARNING!
An electric shock can be fatal.
Before starting work:
Turn the mains switch of the auto-transformer to the "O" position
▶
Unplug the auto-transformer from the mains
▶
Put up an easy-to-understand warning sign to stop anybody inadvertently switching
▶
it back on again
Using a suitable measuring instrument, check to make sure that electrically charged
▶
components (e.g. capacitors) have discharged
WARNING!
Beware of the danger of the trolley tipping over.
Always place the heavy auto-transformer at the bottom. As the centre of gravity is now
lower, there is less chance of the trolley tipping over.
GeneralIf the auto-transformer is only mounted on the PickUp 5000 trolley with a power source,
the supplied cylinder holder extension does not have to be fitted.
Mounting the
auto-transformer
and the system
components
1
28
2
3
1
2
3
4
1
2
3
2
1
EN
3
4
29
4
2
3
1
5
1
6
30
Putting the auto-transformer into service
EN
Safety
Putting the autotransformer into
service
WARNING!
Work that is carried out incorrectly can cause serious injury or damage.
The activities described below must only be carried out by trained and qualified personnel. Do not carry out the activities described below until you have fully read and understood the following documents:
these operating instructions
▶
all the operating instructions for the system components, especially the safety rules
▶
Turn the power source mains switch to the "O" position
1
Turn the mains switch of the auto-transformer to the "O" position
2
Connect the mains cable of the auto-transformer to the mains
3
Turn the mains switch of the auto-transformer to the "I" position
4
-The auto-transformer is ready for use
31
Care, maintenance and disposal
Safety
WARNING!
Work that is carried out incorrectly can cause serious injury or damage.
The activities described below must only be carried out by trained and qualified personnel. Do not carry out the activities described below until you have fully read and understood the following documents:
these operating instructions
▶
all the operating instructions for the system components, especially the safety rules
▶
WARNING!
An electric shock can be fatal.
Before starting work:
Turn the mains switch of the auto-transformer to the "O" position
▶
Unplug the mains cable of the auto-transformer from the mains
▶
Put up an easy-to-understand warning sign to stop anybody inadvertently switching
▶
it back on again
Using a suitable measuring instrument, check to make sure that electrically charged
▶
components (e.g. capacitors) have discharged
WARNING!
Inadequate PE conductor connections can cause serious injury and damage.
The housing screws provide a suitable PE conductor connection for earthing (grounding)
the housing and must NOT be replaced by any other screws which do not provide a reliable PE conductor connection.
At every start-up-Check the mains plug and mains cable for damage
-Check that there is a gap of 0.5 m (1 ft. 8 in.) all around the device to ensure that
cooling air can flow and escape unhindered
NOTE!
Air inlets and outlets must never be covered, not even partially.
Every 6 months-Dismantle device side panels and clean inside of device with dry reduced com-
pressed air
NOTE!
Risk of damage to electronic components.
Do not bring air nozzle too close to electronic components.
32
-If a lot of dust has accumulated, clean the cooling air ducts.
DisposalDispose of in accordance with the applicable national and local regulations.
EN
33
Troubleshooting
Safety
WARNING!
Work that is carried out incorrectly can cause serious injury or damage.
The activities described below must only be carried out by trained and qualified personnel. Do not carry out the activities described below until you have fully read and understood the following documents:
these operating instructions
▶
all the operating instructions for the system components, especially the safety rules
▶
WARNING!
An electric shock can be fatal.
Before starting work:
Turn the mains switch of the auto-transformer to the "O" position
▶
Unplug the mains cable of the auto-transformer from the mains
▶
Put up an easy-to-understand warning sign to stop anybody inadvertently switching
▶
it back on again
Using a suitable measuring instrument, check to make sure that electrically charged
▶
components (e.g. capacitors) have discharged
WARNING!
Troubleshooting
Inadequate PE conductor connections can cause serious injury and damage.
The housing screws provide a suitable PE conductor connection for earthing (grounding)
the housing and must NOT be replaced by any other screws which do not provide a reliable PE conductor connection.
Power source inoperative
Mains switch is ON, but indicators are not lit up
Cause:
Remedy:
Cause:
Remedy:
Cause:
Remedy:
Cause:
Remedy:
There is a break in the mains lead; the mains plug is not plugged in
Check mains lead, check mains voltage if necessary
Mains outlet socket or plug is faulty
Replace faulty components
The mains switch of the auto-transformer is faulty
Contact After-Sales Service (Replace the mains switch of the auto-transformer)
Replace mains cable/contact After-Sales Service (replace wiring terminal)
Auto-transformer connected asymmetrically
Connect auto-transformer symmetrically
Wiring terminal - break/contact fault
Contact After-Sales Service (fix/replace the wiring terminal)
36
Technical data
EN
Safety
600 V/500 V - 460
V, 575 - 440 V
auto-transformer
NOTE!
Incorrectly rated mains plugs, mains leads or fuses can result in serious damage.
If the power source is designed for a special voltage, the technical data on the rating
plate apply. Rate the mains plug, mains lead and their fuse protection accordingly.
Mains voltage 1 (U1)3 x 600 V / 575 V
Mains voltage 2 (U1)3 x 500 V
Mains voltage tolerance+/- 10 %
Mains frequency50 / 60 Hz
Output voltage 1 (U2)3 x 460 V / 440 V
Mains fuse protection (slow-blow)35 A slow-blow
Maximum apparent power (S1)30 kVA
Effective apparent power (S1)21 kVA
Cos phi0.9
Maximum primary current (I
mains voltage 1 (600 V)
mains voltage 1 (575 V)
mains voltage 2 (500 V)
1max
)
30 A
31 A
36 A
Effective primary current (I
mains voltage 1 (600 V)
mains voltage 1 (575 V)
mains voltage 2 (500 V)
Secondary current (I2) for
10 min / 40 °C
10 min / 40 °C
Protection
Protection class in conjunction with power
source or cooling unit
Type of coolingConvection cooling
Insulation classH
Marks of conformityCE
Dimensions l x w x h658 x 301 x 248 mm
Weight52.5 kg
40 % d.c.
100 % d.c.
1eff
)
20.6 A
21.5 A
24.7 A
38 A
24 A
IP 20
IP 23
25.91 x 11.85 x 9.76 in.
115.74 lb.
37
38
EN
39
FRONIUS INTERNATIONAL GMBH
Froniusstraße 1
A-4643 Pettenbach
AUSTRIA
contact@fronius.com
www.fronius.com