Fronius Agilo 75.0-3, Agilo 100.0-3 Operating Instructions Manual

Page 1
/ Perfect Charging / Perfect Welding / Solar Energy
42,0426,0163,EN 005-03122014
Fronius Agilo Outdoor
75.0-3 / 100.0-3
Operating Instructions
Grid-connected inverter
EN
Page 2
0
Page 3
1
EN
Dear reader,
Introduction Thank you for the trust you have placed in our company and congratulations on buying this
high-quality Fronius product. These instructions will help you familiarise yourself with the product. Reading the instructions carefully will enable you to learn about the many different features it has to offer. This will allow you to make full use of its advantages.
Please also note the safety rules to ensure greater safety when using the product. Careful handling of the product will repay you with years of safe and reliable operation. These are essential prerequisites for excellent results.
Page 4
2
Page 5
3
EN
Contents
Safety rules ................................................................................................................................................ 7
General information 11
Protection of people and equipment .......................................................................................................... 13
Safety.................................................................................................................................................... 13
Protection of people and equipment ..................................................................................................... 13
Galvanic (electrical) isolation ................................................................................................................ 13
Monitoring the grid ................................................................................................................................ 13
Warning notices on the device.............................................................................................................. 14
Proper use ................................................................................................................................................. 16
Proper use ............................................................................................................................................ 16
Application area ................................................................................................................................... 16
Regulations governing the photovoltaic system.................................................................................... 16
Functional principle .................................................................................................................................... 17
Functional principle ............................................................................................................................... 17
Cooling of the inverter through forced-air ventilation ............................................................................ 17
Power derating...................................................................................................................................... 17
Solar module grounding........................................................................................................................ 17
The inverter in a photovoltaic system ........................................................................................................ 18
General ................................................................................................................................................. 18
Tasks .................................................................................................................................................... 18
Converting DC to AC current ................................................................................................................ 18
Display function and data communication ............................................................................................ 18
System add-on...................................................................................................................................... 18
Description of the device............................................................................................................................ 19
Outside of inverter................................................................................................................................. 19
Inverter interior...................................................................................................................................... 20
Connection compartment...................................................................................................................... 21
Data communication area ..................................................................................................................... 22
Possible relay contact functions............................................................................................................ 24
Data communication and Solar Net ........................................................................................................... 26
Solar Net and data interface ................................................................................................................. 26
Overcurrent and undervoltage cut-out .................................................................................................. 26
Description of the 'Fronius Solar Net' LED............................................................................................ 26
Example ................................................................................................................................................ 27
Installation and commissioning 29
Choice of location ...................................................................................................................................... 31
General comments regarding choice of location...................................................................................31
Cabling into the inverter ........................................................................................................................ 31
Criteria influencing choice of location ................................................................................................... 31
Unsuitable locations.............................................................................................................................. 32
Transport.................................................................................................................................................... 33
Transport............................................................................................................................................... 33
Transporting by its lifting eyes using a crane........................................................................................ 33
Transporting by crane using pallet fork................................................................................................. 33
Transporting by forklift truck or lift truck ................................................................................................ 34
Positioning the inverter .............................................................................................................................. 35
Prerequisites ......................................................................................................................................... 35
Positioning the inverter ......................................................................................................................... 35
Notes regarding the air supply .............................................................................................................. 35
Connecting the inverter to the public grid (AC) .......................................................................................... 36
Monitoring the grid ................................................................................................................................ 36
Mains connections ................................................................................................................................ 36
Connecting aluminium cables ............................................................................................................... 36
Max. cross-section of AC cables........................................................................................................... 36
Safety.................................................................................................................................................... 37
Connecting the inverter to the public grid ............................................................................................. 37
Page 6
4
Connecting AC cables with a cable lug................................................................................................. 39
Maximum fuse rating on alternating current side .................................................................................. 40
Connecting an external AC supply for the inverter ...............................................................................40
Fitting and connecting optional overvoltage protection.............................................................................. 41
General ................................................................................................................................................. 41
Safety.................................................................................................................................................... 41
Fitting and connecting overvoltage protection on the DC side.............................................................. 41
Fitting and connecting overvoltage protection on the AC side.............................................................. 42
Fitting and connecting overvoltage protection for the AC- supply......................................................... 42
Connecting the DC cable to the inverter .................................................................................................... 44
General comments regarding solar modules ........................................................................................44
DC connections..................................................................................................................................... 44
Connecting aluminium cables ............................................................................................................... 44
Max. cross-section of DC cables .......................................................................................................... 44
Safety.................................................................................................................................................... 45
Connecting DC cables .......................................................................................................................... 45
Connecting DC cables with a cable lug ................................................................................................ 46
Fuse protection against polarity reversal of DC cables......................................................................... 46
Grounding the solar modules in the inverter .............................................................................................. 47
General ................................................................................................................................................. 47
Grounding the solar module to the negative pole via a fuse................................................................. 47
Safety.................................................................................................................................................... 48
Configuring the inverter for grounded solar modules............................................................................ 48
Grounding the solar module on the negative pole: inserting a fuse...................................................... 48
Closing the inverter .................................................................................................................................... 50
Closing the inverter ............................................................................................................................... 50
Using for the first time ................................................................................................................................ 52
Factory configuration ............................................................................................................................ 52
Using for the first time ........................................................................................................................... 52
Configuring the inverter for existing solar module grounding................................................................ 53
Operation 55
Controls and indicators .............................................................................................................................. 57
Controls and indicators ......................................................................................................................... 57
Display .................................................................................................................................................. 57
Symbols showing function key allocation.............................................................................................. 58
Monitoring and status LEDs.................................................................................................................. 59
Startup phase and feeding energy into the grid ......................................................................................... 60
Startup phase........................................................................................................................................ 60
Feeding energy into the grid ................................................................................................................. 60
Navigation at the menu level...................................................................................................................... 61
Activate display backlighting ................................................................................................................. 61
Automatic deactivation of display backlighting / change to display mode 'NOW' ................................. 61
Open menu level................................................................................................................................... 61
The display modes..................................................................................................................................... 62
The display modes................................................................................................................................ 62
Choosing a display mode...................................................................................................................... 62
Overview of display values ................................................................................................................... 62
Values in display mode 'NOW'................................................................................................................... 64
Choosing a display mode...................................................................................................................... 64
Values in display mode 'NOW'.............................................................................................................. 64
Values in display modes 'TODAY / YEAR / TOTAL' ..................................................................................66
Choose display mode 'TODAY / YEAR / TOTAL' ................................................................................. 66
Values in display modes 'TODAY / YEAR / TOTAL' ............................................................................. 66
The Setup menu ........................................................................................................................................ 69
Initial setting .......................................................................................................................................... 69
Accessing the setup menu.................................................................................................................... 69
Move up and down the menu items ...................................................................................................... 69
Menu items in the Set-up menu ................................................................................................................. 70
Standby................................................................................................................................................. 70
Contrast ................................................................................................................................................ 70
Backlighting........................................................................................................................................... 70
Language ............................................................................................................................................. 71
Page 7
5
EN
Currency .............................................................................................................................................. 71
CO2 factor............................................................................................................................................. 71
Yield ...................................................................................................................................................... 71
DATCOM .............................................................................................................................................. 72
Device Info ............................................................................................................................................ 72
Device Status........................................................................................................................................ 74
Time ..................................................................................................................................................... 74
Status LT............................................................................................................................................... 74
Grid Status ............................................................................................................................................ 74
Fan test ................................................................................................................................................. 74
Version.................................................................................................................................................. 74
Setting and displaying the menu items ...................................................................................................... 76
Setting the menu items, general ........................................................................................................... 76
Exiting a menu item .............................................................................................................................. 76
Practical examples for setting and displaying menu items ................................................................... 77
Setting the display backlighting............................................................................................................. 77
Setting the currency and feed-in tariff ................................................................................................... 77
Setting the time and date ...................................................................................................................... 79
Switching the key lock on and off............................................................................................................... 81
General ................................................................................................................................................. 81
Switching the key lock on and off.......................................................................................................... 81
Troubleshooting and maintenance 83
Status diagnostics and troubleshooting ..................................................................................................... 85
Displaying status codes ........................................................................................................................ 85
Total failure of the display ..................................................................................................................... 85
Class 1 status codes............................................................................................................................. 85
Class 3 status codes............................................................................................................................. 87
Class 4 status codes............................................................................................................................. 88
Class 5 status codes............................................................................................................................. 94
Class 7 status codes............................................................................................................................. 96
Class 10 - 12 status codes.................................................................................................................... 99
Customer service .................................................................................................................................. 99
Maintenance .............................................................................................................................................. 100
Safety.................................................................................................................................................... 100
Maintenance guidelines ........................................................................................................................ 100
Replacement of components ................................................................................................................ 100
Opening the inverter for maintenance work .......................................................................................... 100
Operation in environments subject to heavy accumulations of dust ..................................................... 101
Replacing fuses ......................................................................................................................................... 102
Safety.................................................................................................................................................... 102
Replacing the reverse polarity protection fuse...................................................................................... 102
Appendix 105
Technical data............................................................................................................................................ 107
Fronius Agilo Outdoor 75.0-3................................................................................................................ 107
Fronius Agilo Outdoor 100.0-3.............................................................................................................. 108
Explanation of footnotes ....................................................................................................................... 109
Applicable standards and guidelines ......................................................................................................... 110
CE mark ................................................................................................................................................ 110
Parallel operation of in-plant generation systems ................................................................................. 110
Power failure ......................................................................................................................................... 110
Warranty terms and conditions, and disposal ............................................................................................ 111
Fronius manufacturer's warranty .......................................................................................................... 111
Disposal ................................................................................................................................................ 111
Page 8
6
Page 9
7
EN
Safety rules
Explanation of safety symbols
If you see any of the symbols depicted in the "Safety rules" chapter, special care is re­quired.
General
DANGER! Indicates immediate and real danger. If it is not avoided, death or se-
rious injury will result.
WARNING! Indicates a potentially dangerous situation. Death or serious injury may result if appropriate precautions are not taken.
CAUTION! Indicates a situation where damage or injury could occur. If it is not avoided, minor injury and/or damage to property may result.
NOTE! Indicates a risk of flawed results and possible damage to the equipment.
IMPORTANT! Indicates tips for correct operation and other particularly useful information.
It does not indicate a potentially damaging or dangerous situation.
The device is manufactured using state-of-the-art technology and according to recognised safety standards. If used incorrectly or misused, however, it can cause
- injury or death to the operator or a third party,
- damage to the device and other material assets belonging to the operat­ing company,
- inefficient operation of the device.
All persons involved in commissioning, maintaining and servicing the device must
- be suitably qualified,
- have knowledge of and experience in dealing with electrical installations and
- read and follow these operating instructions carefully.
The operating instructions must always be at hand wherever the device is be­ing used. In addition to the operating instructions, attention must also be paid to any generally applicable and local regulations regarding accident preven­tion and environmental protection.
All safety and danger notices on the device
- must be kept in a legible state
- must not be damaged/marked
- must not be removed
- must not be covered, pasted or painted over.
For the location of the safety and danger notices on the device, refer to the section headed "General remarks" in the operating instructions for the device.
Before switching on the device, rectify any malfunctions that could compro­mise safety.
Your personal safety is at stake!
Page 10
8
Proper use
Environmental conditions
Qualified service engineers
Safety measures at the installation location
When installing devices with openings for cooling air, ensure that the cooling air can enter and exit unhindered through the air ducts. Only operate the charger in accordance with the degree of protection shown on the rating plate.
The device is to be used exclusively for its intended purpose.
Any use above and beyond this purpose is deemed improper. The manufac­turer shall not be liable for any damage resulting from such improper use.
Proper use also includes:
- carefully reading and obeying all the instructions and all the safety and danger notices in the operating instructions
- performing all stipulated inspection and servicing work
- installation as specified in the operating instructions
The following guidelines should also be applied where relevant:
- Regulations of the company providing the mains power supply
- Instructions from the PV module manufacturer
Operation or storage of the device outside the stipulated area will be deemed as "not in accordance with the intended purpose". The manufacturer shall not be held liable for any damage arising from such usage.
For exact information on permitted environmental conditions, please refer to the "Technical data" in the operating instructions.
The servicing information contained in these operating instructions is intended only for the use of qualified service engineers. An electric shock can be fatal. Do not perform any actions other than those described in the documentation. This applies even if you are qualified to do so.
All cables and leads must be secure, undamaged, insulated and adequately dimensioned. Loose connections, scorched, damaged or inadequately dimen­sioned cables and leads must be immediately repaired by authorised person­nel.
Maintenance and repair work must only be carried out by authorised person­nel.
It is impossible to guarantee that bought-in parts are designed and manufac­tured to meet the demands made of them, or that they satisfy safety require­ments. Use only original spare parts (also applies to standard parts).
Do not carry out any modifications, alterations, etc. to the device without the manufacturer's consent.
Components that are not in perfect condition must be changed immediately.
Page 11
9
EN
Noise emission values
EMC Device Clas­sifications
EMC measures
Mains connection
Electrical installa­tions
The inverter generates a maximum sound power level of < 80 dB(A) (ref. 1 pW) when operating under full load in accordance with IEC 62109-1:2010.
The device is cooled as quietly as possible with the aid of an electronic tem­perature control system, and depends on the amount of converted power, the ambient temperature, the level of soiling of the device, etc.
It is not possible to provide a workplace-related emission value for this device because the actual sound pressure level is heavily influenced by the installa­tion situation, the power quality, the surrounding walls and the properties of the room in general.
Devices in emission class A:
- Are only designed for use in industrial settings
- Can cause line-bound and radiated interference in other areas
Devices in emission class B:
- Satisfy the emissions criteria for residential and industrial areas. This is also true for residential areas in which the energy is sup­plied from the public low-voltage mains.
EMC device classification as per the rating plate or technical data.
In certain cases, even though a device complies with the standard limit values for emissions, it may affect the application area for which it was designed (e.g. when there is sensitive equipment at the same location, or if the site where the device is installed is close to either radio or television receivers). If this is the case, then the operator is obliged to take appropriate action to rectify the situ­ation.
High-performance devices (> 16 A) can affect the voltage quality on the mains network because they can feed powerful current into the main supply.
This may affect a number of types of device in terms of:
- connection restrictions
- criteria with regard to the maximum permissible mains impedance *)
- criteria with regard to the minimum short-circuit power requirement *)
*) at the interface with the public mains supply
see Technical Data
In this case, the plant operator or the person using the device should check whether or not the device is allowed to be connected, where appropriate through discussion with the power supply company.
Electrical installations must only be set up set up to the relevant national and local standards and regulations.
Page 12
10
Protective meas­ures against ESD
Safety measures in normal opera­tion
Safety symbol
Disposal
Data protection
Copyright
Danger of damage to electrical components from electrical discharge. Suitable measures should be taken to protect against ESD when replacing and install­ing components.
Only operate the device if all safety devices are fully functional. If the safety devices are not fully functional, there is a risk of
- injury or death to the operator or a third party,
- damage to the device and other material assets belonging to the operator,
- inefficient operation of the device.
Any safety devices that are not functioning properly must be repaired by a suit­ably qualified engineer before the device is switched on.
Never bypass or disable safety devices.
Devices with the CE mark satisfy the essential requirements of the low-voltage and electromagnetic compatibility directives. Further details can be found in the appendix or the section headed "Technical data" in your documentation.
To comply with the European Directive 2002/96/EC on Waste Electrical and Electronic Equipment and its implementation as national law, electrical equip­ment that has reached the end of its life must be collected separately and re­turned to an approved recycling facility. Any device that you no longer require must either be returned to your dealer or given to one of the approved collec­tion and recycling facilities in your area. Ignoring this European Directive may have potentially adverse affects on the environment and your health!
The user is responsible for the safekeeping of any changes made to the fac­tory settings. The manufacturer accepts no liability for any deleted personal settings.
Copyright of these operating instructions remains with the manufacturer.
The text and illustrations are all technically correct at the time of printing. We reserve the right to make changes. The contents of the operating instructions shall not provide the basis for any claims whatsoever on the part of the pur­chaser. If you have any suggestions for improvement, or can point out any mistakes that you have found in the instructions, we will be most grateful for your comments.
Page 13
General information
Page 14
Page 15
13
EN
Protection of people and equipment
Safety
Protection of peo­ple and equip­ment
The inverter is constructed and operated in the safest possible way, both in terms of instal­lation and operation.
The inverter fulfils the role of protecting people and equipment: a) through galvanic (electrical) isolation b) by monitoring the grid
Galvanic (electri­cal) isolation
The inverter has a 50/60 Hz three-phase transformer that provides electrical isolation be­tween the DC side and the grid, thus guaranteeing the highest possible levels of safety.
Monitoring the grid
In the event of abnormal grid conditions, the inverter shuts down immediately according to national standards and guidelines and stops feeding energy into the grid (e.g. in the event of grid disconnection, interrupts, etc.)
Grid monitoring is carried out by:
- monitoring the voltage
- monitoring the frequency
- using over/undervoltage relays (option, depends on country setup)
- monitoring the stand alone situation
WARNING! If the equipment is used or tasks are carried out incorrectly, serious injury or damage may result. Commissioning of the inverter may only be carried out by trained personnel in accordance with the technical regulations. It is essen­tial that you read the "Safety Regulations" chapter before commissioning the equipment or carrying out maintenance work.
Page 16
14
Warning notices on the device
There are warning notices and safety symbols on and in the inverter. These warning notic­es and safety symbols must not be removed or painted over. They warn against operating the device incorrectly, as this may result in serious injury and damage.
Safety symbols:
Text of the warning notices:
WARNING!
Risk of serious injury and damage due to incorrect operation
Do not use the functions described here until you have fully read and understood the following documents:
- these operating instructions
- all the operating instructions for the system components of the photovoltaic system, especially the safety rules
Dangerous electrical voltage
Discharging of the energy storage device is time-controlled
(10
(10
(10
(10
(10
Fronius Agilo 100.0-3
Page 17
15
EN
An electric shock can be fatal. Make sure that both the input side and output side of the device are de-energised before opening the device. Wait for the capacitors to discharge (10 minutes).
Page 18
16
Proper use
Proper use The solar inverter is intended exclusively to convert direct current from solar modules into
alternating current and to feed this into the public grid. Utilisation not in accordance with the intended purpose comprises:
- utilisation for any other purpose or in any other manner
- making any modifications to the inverter that have not been expressly approved by Fronius
- the installation of parts that are not distributed or expressly approved by Fronius.
Fronius shall not be liable for any damage resulting from such action. No warranty claims will be entertained.
Proper use also includes:
- complying with all the instructions in the operating instructions
- performing all stipulated inspection and maintenance work
Application area The inverter has been developed exclusively for use in grid-connected photovoltaic sys-
tems; generating energy independently of the public grid is not possible.
Regulations gov­erning the photo­voltaic system
The inverter is designed to be connected and used exclusively in conjunction with solar modules. Use of the inverter with other DC generators (e.g. wind generators) is not permitted
When designing the photovoltaic system, ensure that all its components are operated with­in their permitted operating ranges at all times.
Observe all the measures recommended by the solar module manufacturer to ensure the lasting maintenance of the properties of the solar module.
Page 19
17
EN
Functional principle
Functional princi­ple
The inverter operates fully automatically. The control module starts monitoring the grid volt­age and frequency as soon as the solar modules produce enough energy after sunrise. When insolation has reached a sufficient level, the solar inverter will start to feed energy into the grid.
The inverter works in a way that ensures the maximum power possible is obtained from the solar modules. This is known as "Maximum Power Point Tracking" (MPPT).
As soon after dusk as the power available to feed into the mains falls below a sufficient level, the inverter disconnects from the mains supply. It retains all its settings and stored data.
Cooling of the in­verter through forced-air ventila­tion
Cooling of the inverter is performed by a forced-air ventilation system via a temperature­controlled radial fan. Air is sucked in from the front and fed, via a sealed duct, through the electronics compartment, before passing directly over the inductors and dissipating up­wards. The sealed air duct prevents the electronics compartment from coming into contact with the ambient air. This approach largely prevents any contamination of the electronics com­partment. The speed of the fan and temperature of the intake air are monitored.
The variable-speed, ball-bearing mounted fans in the inverter permit the following:
- optimum cooling of the inverter
- a higher level of efficiency
- cooler parts, therefore a longer service life
- lowest-possible energy consumption and noise levels
Power derating To protect the inverter if adequate heat dissipation is not possible, even with the fans run-
ning at full speed (e.g. when installed in containers without proper heat dissipation meas­ures), the operation known as power derating takes place above an ambient temperature of approximately 45 °C.
Power derating briefly reduces the power of the inverter to prevent the temperature ex­ceeding its permitted limit. The inverter remains operational for as long as possible without stopping.
Solar module grounding
The inverter is designed for use with non-grounded solar modules and those grounded on the negative pole. Grounding of the solar module on the negative pole is carried out inside the inverter via a fuse holder equipped with a corresponding fuse as required.
Page 20
18
The inverter in a photovoltaic system
General The solar inverter acts as a highly sophisticated link between the solar modules and the
public grid.
Tasks The main tasks of the inverter are as follows:
- converting DC to AC current
- fully automatic operational management
- display function and data communication
Converting DC to AC current
The inverter converts the direct current created in the solar modules into alternating cur­rent. This alternating current is fed synchronously with the grid voltage into the in-house network or the public grid.
Display function and data commu­nication
The display on the inverter acts as the interface between the inverter and the user. The display design is oriented towards simple operation and to making the system data avail­able at all times.
The inverter has a range of basic functions for logging minimum and maximum values on a daily and total basis. The values are output on the display.
An extensive selection of data communication elements opens up numerous recording and visualisation options.
System add-on The inverter is able to accommodate a wide variety of system add-ons, such as:
- a datalogger, to enable a PC to record and manage data from a photovoltaic system
- various large-format displays
- interfaces to transfer system data in a freely accessible format
- devices to combine and monitor solar module strings
The inverter is not designed to be used with optional plug-in cards. System add-ons must be installed in a separate housing.
IMPORTANT! The inverter has been developed exclusively for use in grid-connected pho­tovoltaic systems; generating energy independently of the public grid is not possible.
Page 21
19
EN
Description of the device
Outside of invert­er
Item Description
(1) (2)
Mounting lug (front and rear)
(3) Front base-cover (opposite: rear base-cover)
Behind the front base-cover the forklift truck receptacle is located.
(4) DC main switch, lockable when switched off
IMPORTANT! The door cannot be opened when the DC main switch is switched on.
(5) Door
(6) Control elements (display, buttons, monitoring and status LEDs)
(7) Exhaust air hood
(8) (9)
Lifting eye for crane transport (front and rear, under the exhaust air hood)
(10) (11)
Lifting eye for crane transport (front and rear, under the exhaust air hood)
(12) Air inlet grille
(1) (2)
(3)
(4)
(5)
(6)
(7)
(15) (16)
(14)
(12)
(13)
(10) (11)(8) (9)
Page 22
20
Inverter interior
(13) Door handle (lockable)
(14) Right side panel (opposite: left side panel)
(15) (16)
Mounting lug (front and rear)
Item Description
Item Designation
(1) Fan
(behind the air inlet grille)
(2) Data communication area
(3) Fuse holder for operation with solar modules grounded to the negative pole:
DC- to PE
(4) 2-pin automatic circuit breaker
to protect the AC power supply
(5) 4-pin automatic circuit breaker
to protect the measuring lines on the grid side
(6) DC main switch
The DC main switch shaft is not fitted when the inverter is delivered.
(1)
(2)
(3)
(4)
(5) (6)
(7)
(8)
Page 23
21
EN
Connection com­partment
(7) Connection area
(8) Door catch
(not shown)
Item Description
(1) DC+ connections
(2) DC- connections
(3) Openings for attaching the strain-relief clamps* for the DC+ cable
(4) Openings for attaching the strain-relief clamps* for the DC- cable
(5) Cable input opening with sliding cover and seal
(6) Openings for attaching the strain-relief clamps* for the AC cable
(7) Grounding terminal for AC cable
(8) AC power supply
(9) Mains connections L1, L2, L3 and N
* The strain-relief clamps and other installation and connection accessories are
part of the scope of supply of the inverter.
(1)
(2)
(3)
(4)
(6)
(7)
(8)
(9)
(5)
Page 24
22
Data communica­tion area
Item Description
(1) (2)
for future use
(3) Solar Net IN connection socket
'Fronius Solar Net' input, for connecting to other DATCOM components (e.g. in­verter, sensor box, etc.)
(4) Solar Net OUT connection socket
'Fronius Solar Net' output, for connecting to other DATCOM components (e.g. in­verter, sensor box, etc.)
(5) VSR connection socket
for connecting an external measuring and monitoring relay
The contact must be potential-free. Contact rating 24 V / 10 mA
(1) (2) (3) (4) (5) (6) (7) (10)(8) (9)
Page 25
23
EN
(6) NO/alarm terminals
S3 - 2 EXT
for connecting an external NO contact, e.g. to isolate the device from the grid voltage using an AC contactor; connected using bracket when delivered.
3 - 4 IN1
for connecting and evaluating a floating alarm contact
5 -6 IN2
for connecting and evaluating a floating alarm contact
7 - 8 IN3
for connecting and evaluating a floating alarm contact
The contacts must be potential-free.
Contact rating 24 V / 10 mA Cable cross-section: 0.5 - 6 mm² Tightening torque of terminals: 0.8 - 1.6 Nm
(7) 'Solar Net' LED
shows the current status of the Fronius Solar Net
(8) Fuse F1 for switched-mode power supply, 4 A slow-blow
Item Description
| S3 EXT 2 | 3 IN1 4 | 5 IN2 6 | 7 IN3 8 |
Page 26
24
Possible relay contact functions
(9) Relay output terminals
NC1 NC for relay contact 1 SC1 Relay contact 1 NO1 NO for relay contact 1
NC2 NC for relay contact 2 SC2 Relay contact 2 NO2 NO for relay contact 2
Cable cross-section: 0.5 - 6 mm² Tightening torque of terminals: 0.8 - 1.6 Nm Max. continuous current: 16 A Switching load: 500 mW (10 V / 5 mA) Switching capacity: 16 A / 250 V (AC1) and 16 A / 30 V (DC1) The relay outputs are not protected.
Relay contacts can be assigned different functions in the Basic service menu. The access code 22742 must be entered to access the Basic service menu:
- Press the 'Menu' key
- Select 'Setup' mode
- Press the unassigned 'Esc' button five times
- Enter the access code 22742
- Select the 'Switch contact 1' or 'Switch contact 2' parameter
- Set the desired relay contact function
(10) F2 fuse, 4 A slow-blow
Item Description
| NC1 SC1 NO1 | NC2 SC2 NO2 |
Function Switch contact ac-
tivation criterion
1)
Switch contact de­activation criteri­on
2)
Description
Off - Permanently OFF Function switched
off
On Permanently ON - Test function for NO/
alarm contact
AC Open AC contactor is open AC contactor is
closed
No contactor error signal or AC grid
Page 27
25
EN
Fan On Cabinet fan in opera-
tion
Cabinet fan not working
External ventilation / air conditioning can be activated
> 40 °C max. internal tem-
perature >/= 40 °C
max. internal tem­perature </= 30 °C
> 50 °C max. internal tem-
perature >/= 50 °C
max. internal tem­perature </= 40 °C
Sig. Rel. NO/alarm contact
trips
Error confirmation at the touch of a button
Status indicator / re­lay contact switches
Running Inverter feeding en-
ergy into the grid
Inverter not feeding energy into the grid
Control of powered non-return valve
Warning Defined warning sta-
tus codes
Error confirmation at the touch of a button
NO/alarm contact activation, when cer­tain warning status codes occur at a specific frequency according to the 'Er­ror-Counter' Service menu
Error Defined error status
codes
Error confirmation at the touch of a button
NO/alarm contact activation, when cer­tain error status codes occur at a specific frequency according to the 'Er­ror-Counter' Service menu
1)
Activation = the NC for the relay contact opens, the NO closes
2)
Deactivation = the NC for the relay contact closes, the NO opens
Function Switch contact ac-
tivation criterion
1)
Switch contact de­activation criteri­on
2)
Description
Page 28
26
Data communication and Solar Net
Solar Net and data interface
Overcurrent and undervoltage cut­out
The data communications electronics have a cut-out function that interrupts the power sup­ply in the Fronius Solar Net:
- in response to overcurrent, e.g. in the event of a short circuit
- in response to undervoltage
The overcurrent and undervoltage cut-out does not depend on the current flow direction. If the Fronius Solar Net measures a current flow > 3 A or a voltage < 6.5 V, the power supply in the Fronius Solar Net is interrupted. The power supply is restored automatically.
Description of the 'Fronius Solar Net' LED
The 'Fronius Solar Net' LED is on:
the power supply for data communication within the Fronius Solar Net is OK
The 'Fronius Solar Net' LED is off:
data communication error in the Fronius Solar Net
- Overcurrent (current flow > 3 A, e.g. resulting from a short circuit in the Fronius Solar Net)
- Undervoltage (not a short circuit, voltage in Fronius Solar Net < 6.5 V, e.g. if there are too many DATCOM components on the Fronius Solar Net and not enough electrical power is available)
In this case, power for the DATCOM components must be supplied by connecting an external power unit to one of the DATCOM components.
To detect the presence of an undervoltage, check some of the other DATCOM com­ponents as required.
The 'Fronius Solar Net' LED flashes briefly every 5 seconds:
following a shutdown as the result of an overcurrent or undervoltage, the inverter attempts to restore the power supply to the Fronius Solar Net every 5 seconds while the fault per­sists.
Fronius Solar Net was developed to make system add-ons flexible and capable of being used in a wide variety of different applications. Fronius Solar Net is a data network that enables more than one inverter to be linked up using system add-ons.
It is a bus system. A single cable is all that is required for one or more inverters to com­municate with all the system add-ons.
Fronius Solar Net automatically recognises a wide variety of system add-ons.
In order to distinguish between several identical system add-ons, each one must be as­signed a unique number.
Similarly, every inverter on the Fronius Solar Net must be assigned a unique number. Refer to the section entitled 'The Setup-Menu‘ for instructions on how to assign a unique number.
More detailed information on the individual system add-ons can be found in the relevant operating instructions or on the internet at http://www.fronius.com.
More detailed information on cabling DATCOM components can be found at http://www.fronius.com - Solar Electronics / Info & Support / Document downloads / Op­erating instructions / System monitoring / Fronius DATCOM cabling guide.
Page 29
27
EN
Once the fault is rectified, power to the Fronius Solar Net will be restored within 5 seconds.
Example Recording and archiving of inverter data using Fronius Datalogger Web, data output on ex-
ternal display:
Captions: Fronius Solar Net data network with
- 1 Fronius Agilo Outdoor
- 1 Fronius IG Plus with a 'Fronius Com Card'
- 1 Fronius Datalogger Web with LAN interface for connecting to a PC/laptop
- 1 Fronius Public Display Box
- 1 external display
Communication between the individual components themselves is handled by Fronius So­lar Net.
12VDC Class 2
Input only max. 42V AC/6A US: Class 2 only
12VDC 1A Class 2 Output
= Endstecker
= Fronius Com Card
PC / Laptop
IN
OUT
RS232
LAN
IN
OUT
Fronius Agilo Outdoor
Fronius Datalogger Web
Fronius IG Plus
Display
Fronius Public Display Box
OUT
IN
Page 30
28
Page 31
Installation and commissioning
Page 32
Page 33
31
EN
Choice of location
General com­ments regarding choice of location
The inverter is primarily designed for installation outdoors. Provided there is sufficient ventilation, the inverter may also be used in an indoor environ­ment.
The following points must also be taken into account in the choice of location:
- the cabling into the inverter,
- the specified bending radii of the cables,
- adequate bearing capacity per m² of floor for weight of the inverter: Fronius Agilo Outdoor 100.0-3 ... 806 kg Fronius Agilo Outdoor 75.0-3 ... 732 kg
IMPORTANT! The adequate bearing capacity of the floor must be ensured before intro­ducing and setting up the inverter!
Cabling into the inverter
The AC cable, DC cable and the data communications cable, if required, can be fed into the inverter as follows:
a) from below (e.g. via a cable duct or a false floor, maximum cable cross-section = 240
mm²)
b) from the side through the base c) from the rear through the base
Feeding the cabling through the base is only possible for cables with a cross-section of max. 120 mm².
Feeding the cabling from the rear is only possible for cables with a cross-section of max. 95 mm².
IMPORTANT! If AC cables, DC cables and data communication cables are fed together into the inverter, ensure adequate insulation is provided between the AC/DC cables and the data communication cables.
Criteria influenc­ing choice of lo­cation
a) b) c) Plan view
Place on a solid, even. level and fire-resistant surface only.
Max. ambient temperatures: -25 °C; +50 °C
Page 34
32
Unsuitable loca­tions
Do not install the inverter:
- in areas in which a heavy build-up of dust containing conductive particles (e.g. iron chips) is likely
- where it can be exposed to ammonia, corrosive gasses, acids or salts (e.g., fertilizer­storage areas, vent openings of livestock stables, chemical plants, tanneries)
- in areas where there is an increased risk of damage from farm animals (horses, cattle, sheep, pigs, etc.)
Can be used at altitudes of up to 2000 m
Maintain the following lateral clearances between the inverter and a wall:
* Wall - left side of inverter:
min. 400 mm (to permit the door to be opened fully)
min. 50 mm (to open the door 90°)
** Wall - right side of inverter:
min. 200 mm (to permit the air inlet grille to be opened fully)
min. 80 mm (to open the air inlet grille 90°)
Two or more inverters can be placed side-by-side or back-to-back.
The airflow within the inverter is from the front to the top (cold air taken in at the front, hot air emitted out of the top).
Because of its degree of protection, the inverter is not susceptible to splash water from any direction.
Ideally, the inverter should be installed in a protected location, e.g., under a roof over­hang.
450 mm
400 mm*
0 mm
200 mm**
Page 35
33
EN
Transport
Transport The inverter weighs approx. 806 kg and can be transported as follows:
- by its lifting eyes, e.g. using a crane or other suitable lifting gear and tackle
- by its forklift truck receptacle, e.g. using a forklift truck, lift truck or crane in conjunction with pallet forks
Transporting by its lifting eyes us­ing a crane
Transporting by its lifting eyes using a crane is only possible, when the exhaust air hood is dismantled .
Transporting by crane using pallet fork
Remove the front and rear base covers from on the inverter before transporting it using a pallet fork, forklift truck or lift truck.
WARNING! Falling equipment can cause serious or even fatal injury. When transporting the inverter using a crane
- always use all four of the lifting eyes provided for this purpose,
- the length of the lifting tackle (chain, rope, strap, etc.) must be chosen so that the angle between the lifting tackle and the horizontal is at least 60°.
min. 60°
WARNING! Falling equipment can cause serious or even fatal injury. When transporting the inverter using a crane and pallet fork
- the pallet fork must have a headroom of at least 1950 mm
- always insert the pallet fork into the forklift truck receptacle
- always insert the pallet fork completely into the forklift truck receptacle
- secure the inverter to prevent it slipping off the pallet fork
Page 36
34
Remove the front base cover Remove the rear base cover
Transporting by forklift truck or lift truck
Remove the front base-cover and the rear base-cover from the inverter before transporting it using a pallet fork, forklift truck or lift truck.
Removing the front base-cover Removing the rear base-cover
1
2
4
3
5
1
2
5
3
4
WARNING! Equipment that falls or topples over can cause serious or even fatal injury.
- always insert the fork into the forklift truck receptacle
- always insert the fork completely into the forklift truck receptacle
- secure the inverter to prevent it slipping off the fork or falling over
- avoid sudden changes in direction, braking or acceleration
1
2
4
3
5
1
2
5
3
4
Page 37
35
EN
Positioning the inverter
Prerequisites
Before positioning the inverter, clarify how the cables are going to be fed in. If it is not going to be possible to feed any cables into the inverter once it has been posi­tioned, all the AC, DC and data communication cables must, before the inverter is put in place,
- be dimensioned accordingly,
- protrude at least 650 mm out of the floor.
Positioning the inverter
IMPORTANT! Ensure that any covers which were removed previously are refitted before
the inverter is moved to its final position (e.g. fit the rear base-cover before positioning the inverter up against a wall).
Fixing material for fixing the inverter on the ground is not included with the inverter. The installer is responsible for the proper selection of dowels, screws, etc..
Transport the inverter to its location
Fit any covers that will no longer be accessible once the inverter is in its final position
Move the inverter into its final position
Adjust the inverter horizontally using the leveling feet.
The leveling feet are located at the bottom of the inverter, for better accessibility op­tionally remove the left and right base-cover.
Depending on the accessibility fix the inverter with suitable dowels and screws ideally 4 x at the mounting lugs on the floor.
Notes regarding the air supply
If the inverter is positioned in a protected area, the air supply to the inverter must be at least 1200 m³/h (approx. 20 m³/min).
WARNING! Equipment that falls or topples over can cause serious or even fatal injury.
- Place the inverter on a solid, level surface in such a way that it remains sta­ble.
- Do not under any circumstances tip the inverter while it is being positioned.
CAUTION! Risk of cable damage as a result of shearing or bending. if any cables are protruding out of the floor, use a crane or forklift truck to lift the inverter over the cables and position the inverter in its desired location.
WARNING! Equipment that topples over can cause serious or even fatal injury.
- Place the inverter on a solid, level surface in such a way that it remains sta­ble.
- Fix the inverter at the mounting lugs firmly to the ground.
1
2
3
4
5
Page 38
36
Connecting the inverter to the public grid (AC)
Monitoring the grid
IMPORTANT! To provide the best possible grid monitoring, the resistance in the leads to
the mains connections should be as low as possible.
Mains connec­tions
Legend:
L1 Phase conductor L2 Phase conductor L3 Phase conductor N Neutral conductor PE Ground conductor / grounding
IMPORTANT! Only the following cables may be connected to V-type terminals:
- RE (round single-wire)
- RM (round multi-strand)
- SE (sector-shaped single-wire)
- SM (sector-shaped multi-strand)
- fine-core cables, in conjunction with ferrules only
Fine-core cables without ferrules may only be connected to the M10 threaded bolts of the mains connections using a suitable M10 cable lug; tightening torque = 18 Nm
Connecting alu­minium cables
Aluminium cables can be connected to the mains connections.
Max. cross-sec­tion of AC cables
The max. cable cross-section of AC cables when feeding them in from below is 240 mm².
L1
L3
L2
N
M10
PE
NOTE! Ensure that the grid neutral conductor is grounded.
NOTE! When connecting aluminium cables:
- observe national and international guidelines regarding the connection of al­uminium cables
- follow the instructions of the cable manufacturer
- check every year that the cables are securely attached in accordance with the specified torque.
Page 39
37
EN
Safety
Connecting the inverter to the public grid
IMPORTANT!
Minimum cable cross section for the ground conductor PE: 10 mm² für Copper wire 16 mm² für Aluminium wire
1
WARNING! An electric shock can be fatal. Danger due to grid voltage and DC voltage from solar modules that are exposed to light.
- Make sure that both the AC side and the DC side of the inverter are de-ener­gised before carrying out any connection work.
- Only an authorised electrical engineer is permitted to connect this equipment to the public grid.
CAUTION! Risk of damage to the inverter as the result of incorrectly tightened ca­ble connections. Incorrectly tightened cable connections can cause heat damage to the inverter that may result in a fire. When connecting AC and DC cables, en­sure that all the cables are tightened to the inverter terminals with the specified torque.
CAUTION! Risk of damage to the inverter due to the ingress of moisture.
- Never open the inverter during rain.
- Do not establish any connections or carry out any maintenance work during rain.
NOTE! Ensure that the phases are connected in the right order: L1, L2, L3, N and PE. After connecting the phases, check the rotary field of the grid using a rotary field measuring device. The inverter is designed for a clockwise rotary field.
1
AC
OFF
1
Page 40
38
2
- Feed the AC cable into the inverter, ob-
serving the bending radii specified by the cable manufacturer
- Strip sheath from AC cable
- Strip at least 20 mm of wire from phase
conductors L1 - L3, neutral conductor N and ground conductor PE
- Align phase conductors L1 - L3 and neutral conductor N with the grid connections according to the phase
- Push the AC terminal over the phase conductor, the neutral conductor and the ground conductor
3
- Push the AC terminal up and over the
grid connection and the bare end of the cable
- Tighten the AC terminal: 5 mm Allen key
Tightening torque = 12 Nm
- Place the insulation caps onto the grid connections
- Repeat the process for phase conduc­tors L2 and L3 and the neutral conduc­tor N
4
- Align the ground conductor PE with the
grounding terminal
- Push the PE terminal up and over the grounding terminal and the bare end of the cable
- Tighten the PE terminal: 5 mm Allen key
Tightening torque = 12 Nm
2
3
1
3
2
1
4x L1 L2 L3 N
3
4
Page 41
39
EN
5
- Place the AC cable in the clamp of the
strain-relief device
- Attach the clamps of the strain-relief device to the rail
- Secure the AC cable with the clamps of the strain-relief device
e.g.:
A cable routed at an angle from the
bottom right - attach the clamp for the strain-relief device to positions 3 and 4
B cable routed at an angle from the
bottom left - attach the clamp for the strain-relief device to positions 1 and 2
C vertical cable routing - attach the
clamp for the strain-relief device to positions 5 and 6
Connecting AC cables with a ca­ble lug
Alternatively, an AC cable with a cable lug can be connected to the M10 threaded bolts on the mains connections in order to connect the AC cables to the V-type terminals.
5
NOTE! Different openings are available on the rail for attaching the clamps of the strain-relief device, depending on the cable routing.
1
A
B
C
2
4
6
3
5
NOTE! Ensure that the phases are connected in the right order: L1, L2, L3, N and PE. After connecting the phases, check the rotary field of the grid using a rotary field measuring device. The inverter is designed for a clockwise rotary field.
Page 42
40
4x
L1 L2 L3 N
+
PE
Maximum fuse rating on alternat­ing current side
Connecting an external AC sup­ply for the invert­er
Procedure for connecting an external AC supply for the inverter (e.g. to provide an external supply to controllers or fans):
1 2
* If present, connect ground conductor to grounding terminal 9
3
5
6
9
2
4
1
7
8
18 Nm
M10
M10
Inverter Phases Nominal output Fuse protection
Fronius Agilo 75.0-3 3 100 kVA 3 x 200 A
Fronius Agilo 100.0-3 3 100 kVA 3 x 200 A
1
3
5
7
2
4
6
8
1
LN
3
1
6
5
2
4
*
2
Page 43
41
EN
Fitting and connecting optional overvoltage protec­tion
General Standard type II overvoltage protection can be fitted in the inverter as an option:
- for the DC side,
- for the AC side,
- for the external AC supply of the inverter.
DIN rails and passage openings to the AC and DC terminals for the cables are provided in the inverter for fitting overvoltage protection. The existing remote contacts on the overvoltage protection can be connected to the NO/ alarm contact terminals in the data communication area. In the event of a fault, the incom­ing signals can then be evaluated and shown on the display.
Overvoltage protection is not included in the scope of supply of the inverter. The engineer is responsible for the correct selection of the relevant overvoltage protection so as to com­ply with national and international regulations.
Safety
Fitting and con­necting overvolt­age protection on the DC side
IMPORTANT!
- Provide a separate grounding terminal for each overvoltage protection device
- Make sure that the cables have adequate insulation resistance.
Fit overvoltage protection to the DIN rail on the DC side according to the manufactur­er's instructions
Fit a grounding terminal to the DIN rail on the DC side
Remove the 2 blank screw joints on the DC side
Insert 2 M20 screw joints from the inverter's accessories kit into the openings and se­cure them with the hexagonal nuts of the blank screw joint
Prepare the cable:
- Strip the cable on the overvoltage protection side
- Fit the M10 cable lug on the DC connection side
Max. cable cross-section must comply with the instructions of the overvoltage protection manufacturer.
Open the M20 screw joints
Feed the cable through
Connect the cable to the overvoltage protection device according to the manufactur­er's instructions
WARNING! Work that is carried out incorrectly can cause serious injury and dam­age. Overvoltage protection must only ever be installed and connected by a qual­ified electrical installation engineer! Follow the safety rules! Make sure that both the AC side and the DC side of the inverter are de-energised before carrying out any installation or connection work.
NOTE! Installing a Type I overvoltage protection device in the inverter is prohib­ited.
1
2
3
4
5
6
7
8
Page 44
42
Use the M10 hexagonal nut and the washer to connect the cable with the correct po­larity at the central M10 threaded bolt of the relevant DC connection
Close the M20 screw joints
Connect the overvoltage protection to the grounding terminal
If available, connect the remote contacts of the overvoltage protection device with two cables to the NO/alarm contact terminals in the data communication area
Fitting and con­necting overvolt­age protection on the AC side
IMPORTANT!
- Provide a separate grounding terminal for each overvoltage protection device
- Make sure that the cables have adequate insulation resistance.
Fit overvoltage protection to the DIN rail on the AC side according to the manufactur­er's instructions
Fit a grounding terminal to the DIN rail on the AC side
Remove 3-4 blank screw joints on the AC side, depending on the overvoltage protec­tion
Insert 3-4 M20 screw joints from the inverter's accessories kit into the openings and secure them with the hexagonal nuts of the blank screw joint
Prepare the cable:
- Strip the cable on the overvoltage protection side
- Fit the M10 cable lug on the AC connection side
Max. cable cross-section must comply with the instructions of the overvoltage protection manufacturer.
Open the M20 screw joints
Feed the cable through
Connect the cable to the overvoltage protection device according to the manufactur­er's instructions
Connect the cable to the upper part of the relevant AC connection in the correct phase sequence Tightening torque = 18 Nm
Close the M20 screw joints
Connect the overvoltage protection to the grounding terminal
If available, connect the remote contacts of the overvoltage protection device with two cables to the NO/alarm contact terminals in the data communication area
Fitting and con­necting overvolt­age protection for the AC- supply
IMPORTANT!
- Provide a separate grounding terminal for each overvoltage protection device
- Make sure that the cables have adequate insulation resistance.
Fit overvoltage protection to the DIN rail on the AC side according to the manufactur­er's instructions
Fit a grounding terminal to the DIN rail
Strip the cable on both sides
Max. cable cross-section must comply with the instructions of the overvoltage protec­tion manufacturer.
Connect cables L1 and N on the overvoltage protection device according to the man­ufacturer's instructions
9
10
11
12
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
Page 45
43
EN
Run the cable to the 2-pin automatic circuit breaker to safeguard the AC power supply
Connect cables L1 and N on the automatic circuit breaker in the correct phase se­quence
Connect the overvoltage protection to the grounding terminal
If available, connect the remote contacts of the overvoltage protection device with two cables to the NO/alarm contact terminals in the data communication area
Bind the cable with cable ties if necessary
5
6
7
8
9
Page 46
44
Connecting the DC cable to the inverter
General com­ments regarding solar modules
To enable suitable solar modules to be chosen and to use the inverter as efficiently as pos­sible, it is important to bear the following points in mind:
- If insolation is constant and the temperature is falling, the open circuit voltage of the solar modules will increase. The open circuit voltage must not exceed 950 V. If the open circuit voltage exceeds 950 V, the inverter will be destroyed and no war­ranty claims will be entertained.
- More exact values for dimensioning the solar modules can be provided by suitable cal­culation programs, like the Fronius Solar.configurator (which can be downloaded from www.fronius.com).
DC connections
IMPORTANT! Only the following cables may be connected to V-type terminals:
- RE (round single-wire)
- RM (round multi-strand)
- SE (sector-shaped single-wire)
- SM (sector-shaped multi-strand)
- fine-core cables, in conjunction with ferrules only
Fine-core cables without ferrules may only be connected to the M10 threaded bolts of the DC connections using a suitable M10 cable lug; tightening torque = 30 Nm
Connecting alu­minium cables
Aluminium cables can also be connected to the DC connections.
Max. cross-sec­tion of DC cables
The DC connections on the inverter are designed for cables with a cross-section of max. 240 mm². With this maximum cross-section, 2 cables can be connected to each pole.
NOTE! Before connecting the solar modules, check:
- that the voltage specified by the manufacturer corresponds to the actual measured voltage.
- whether the solar modules need to be grounded.
DC+ DC-
30 mm
M10 M10 M10 M10
+
NOTE! When connecting aluminium cables:
- observe national and international guidelines regarding the connection of al­uminium cables
- follow the instructions of the cable manufacturer
- Once a year, make sure that the cables are securely connected according to the specified torque.
Page 47
45
EN
Safety
Connecting DC cables
Remove contact protectors
Feed the DC cable into the inverter, observing the bending radii specified by the cable manufacturer
Strip at least 25 mm of insulation from the DC cable
Align the DC cable with the DC connections
3
- Push the DC terminal over the
DC cable
- Push the DC terminal up and over the DC connection and the bare end of the cable
- Tighten the DC terminal: 6 mm Allen key
Tightening torque = 25 Nm
- Repeat this process for every DC cable
4
- Place the DC cable in the clamp of the
strain-relief device
- Attach the clamp of the strain-relief de­vice to the rail
- Secure the DC cable with the clamp of the strain-relief device
- Repeat this process for every DC cable
Fit the contact protectors
WARNING! An electric shock can be fatal. Danger due to grid voltage and DC voltage from solar modules that are exposed to light.
- Make sure that both the AC side and the DC side of the inverter are de-ener­gised before carrying out any connection work.
- Only an authorised electrical engineer is permitted to connect this equipment to the public grid.
CAUTION! Risk of damage to the inverter as the result of incorrectly tightened terminals. Incorrectly tightened terminals can cause heat damage to the inverter that may result in a fire. When connecting AC and DC cables, ensure that all the terminals are tightened to the specified torque.
1
2
3
4
1
1
DC+ DC-
3
2
4
5
6
NOTE! Different openings are available on the rail for attaching the clamps of the strain-relief device, depending on the cable routing.
7
Page 48
46
e.g.:
A cable routed at an angle from the
bottom right - attach the clamp for the strain-relief device to positions 1 and 2
B cable routed at an angle from the
bottom left - attach the clamp for the strain-relief device to positions 3 and 4
C vertical cable routing - attach the
clamp for the strain-relief device to positions 5 and 6
Connecting DC cables with a ca­ble lug
Alternatively, a DC cable with a cable lug can be connected to the M10 threaded bolts on the DC connections in order to connect the DC cables to the V-type terminals.
2x DC+
2x DC-
Fuse protection against polarity reversal of DC ca­bles
The inverter is fitted with a fuse to protect against any polarity reversal of the DC cables. The fuse will blow if the inverter is activated with the polarity of the DC cables reversed. Status code 307 "DC low" is shown on the display, even in the event of sufficient levels of insolation.
Should this occur, the reverse polarity protection fuse must be replaced as described under "Replacing fuses" in the "Troubleshooting and maintenance" section.
1
2
3
4
5
6
AB
C
NOTE! Ensure the polarity is correct when connecting the DC cables.
18 Nm
M10
3
1
5
2
4
Page 49
47
EN
Grounding the solar modules in the inverter
General Some manufacturers of solar modules stipulate that the module must be grounded.
Locking ring for solar module grounding on the negati­ve pole
Inside the inverter is a means for grounding solar modules to the negative pole via a fu­se.
Grounding the solar module to the negative pole via a fuse
Fronius recommends the following fuse when grounding the solar module to the negative pole: nominal current rating 3 A / 1000 V, fuse dimensions 10 x 38 mm
IMPORTANT! Fuses for grounding the solar module are not part of the scope of supply of the inverter. If the manufacturer of the solar module stipulates that grounding is required, an appropriate fuse must be ordered separately
Grounding the solar module to the nega­tive pole via a fuse
(1) Solar module (2) Inverter (3) Fuse
WARNING! An electric shock can be fatal. Danger of electric shock if the solar module is not grounded or is not grounded properly. To comply with IEC 62109-2, any grounding required by the manufacturer of the solar module within the inverter must only be carried out via the specified fuse.
DC+
DC-
N
PE
(1)
(2)
=~=
~
(3)
L1 L2
L3
Page 50
48
Safety
Configuring the inverter for grounded solar modules
The inverter's insulation monitoring must be deactivated when the solar modules are grounded. At the second level of the Setup menu, the inverter must be configured so that when the grounding fuse trips, an error message is displayed or the inverter is switched off (according to the country setup). Access code 22742 must be entered in order to access the 2nd level of the Setup menu.
Grounding the solar module on the negative pole: inserting a fuse
WARNING! An electric shock can be fatal. Danger due to DC voltage from solar
modules that are exposed to light. The inverter's insulation monitoring is deacti­vated when the solar modules are grounded.
- Ensure that grounded solar modules are designed so that they are isolated according to Protection Class II
- Place the relevant safety sticker in a clearly visible place on the photovoltaic system
- Configure the inverter so that a warning message is displayed if the fuse trips.
Warning sticker for solar module ground­ing
IMPORTANT! The warning sticker and the fuse for grounding the solar module are not part of the scope of supply of the inverter and must be ordered separately.
Warnung!
Ein elektrischer Schlag kann tödlich sein. Gefahr durch DC-Spannung von den Solarmodulen. Die Isolationsüberwachung des Wechsel­richters ist deaktiviert. Die Solarmodule sind geerdet. VorArbeiten an der Photovoltaik-Anlage AC- und DC-Seite spannungsfrei schalten.
Warnung!
Ein elektrischer Schlag kann tödlich sein. Gefahr durch DC-Spannung von den Solarmodulen. Die Isolationsüberwachung des Wechsel­richters ist deaktiviert. Die Solarmodule sind geerdet. VorArbeiten an der Photovoltaik-Anlage AC- und DC-Seite spannungsfrei schalten.
Warnung!
Ein elektrischer Schlag kann tödlich sein. Gefahr durch DC-Spannung von den Solarmodulen. Die Isolationsüberwachung des Wechselrichters ist deaktiviert. Die Solarmodule sind geerdet. VorArbeiten an der Photovoltaik-k­AnlageAC- und DC-Seite spannungs­frei schalten.
Warnung!
Ein elektrischer Schlag kann tödlich sein. Gefahr durch DC-Spannung von den Solarmodulen. Die Isolationsüberwachung des Wechselrichters ist deaktiviert. Die Solarmodule sind geerdet. VorArbeiten an der Photovoltaik-k­AnlageAC- und DC-Seite spannungs­frei schalten.
Warnung!
Ein elektrischer Schlag kann tödlich sein. Gefahr durch DC-Spannung von den Solarmodulen. Die Isolationsüberwachung des Wechselrichters ist deaktiviert. Die Solarmodule sind geerdet. VorArbeiten an der Photovoltaik-k­AnlageAC- und DC-Seite spannungs­frei schalten.
WARNING! An electric shock can be fatal. Danger due to DC voltage from solar modules that are exposed to light. The DC main switch is only to be used to de-energise the power stage set. Grounding of the solar module on the negative pole remains in effect, even when the DC main switch is switched off. Do not under any circumstances touch DC+ or DC-.
Page 51
49
EN
1 2
Inserting the fuse grounds the solar modules on the negative pole.
1
1
1
2
2
Page 52
50
Closing the inverter
Closing the in­verter
Check that all covers and contact protection devices are fitted; fit any covers and contact protection devices that are missing
3
Tightening torque = 3 Nm
1
WARNING! An inadequate ground conductor connection can cause serious inju­ry or damage. The screws on the air inlet grille and on the covers provide a suitable ground con­ductor connection for the housing; these screws must not under any circumstanc­es be replaced by other screws that do not provide a reliable ground conductor connection.
1
1
4
3
2
2
NOTE! To avoid damaging the DC main switch, only close the door of the inverter once the switch itself is switched to the "OFF" position.
1
3
Page 53
51
EN
2 3
Tightening torque = 3 Nm
1
3
2
4
5
4
3
2
4
5
1
5
Page 54
52
Using for the first time
Factory configu­ration
The inverter is preconfigured in the factory. The language and the time must be set when the inverter is used for the first time.
Refer to the section in this manual entitled 'The Setup Menu' for the individual configuration options.
Using for the first time
After connecting the DC cable to the inverter and the inverter to the grid (AC):
Insert covers and contact protection
Close and secure air inlet grilles
Close door
Turn the DC main switch to the - 1 - position
If the solar modules are producing enough voltage, the inverter will enter the startup phase. The inverter is about to start up automatically.
Once the inverter has completed its automatic startup, the operating state LED will show steady green.
Provided that energy continues to be fed into the grid, the operating state LED will remain steady green to confirm that the inverter is functioning correctly.
A window then appears for setting the language:
The time and the date must then be set:
Use the 'Up' and 'Down' keys to select the desired language
Press the 'Enter' key to set the lan­guage
The time is displayed (HH:MM:SS, 24-hour format), the hours field starts flashing.
Use the 'Up' and 'Down' keys to select a value for the hour
Press the 'Enter' key
The minutes field starts flashing.
Repeats steps 7 and 8 for the minutes and seconds until...
1
2
3
4
5
6
7
8
9
Page 55
53
EN
If setting of the language and the time are skipped by pressing the Back key and no set­tings are made during the setup, these two prompts appear again the next time the inverter is started.
Configuring the inverter for exist­ing solar module grounding
Confirm any status codes that are displayed by pressing 'Enter'
Press the 'Menu' key
Press the unassigned 'Menu / Esc' key 5 times
Enter the access code 22742
The inverter is now in the 'Basic Service Menu' and the first parameter 'DC operating mode' is displayed.
the set time starts flashing.
Press the 'Enter' key
The time is applied and the date now ap­pears (DD.MM.YYYY), the day field starts flashing.
Use the 'Up' and 'Down' keys to select a value for the day
Press the 'Enter' key
The month field starts flashing.
Repeat steps 11 and 12 for the month and the last 2 digits of the year until ...
the set date starts flashing.
Press the 'Enter' key
10
11
12
13
14
NOTE! If the solar module is already grounded on the negative pole, the appro­priate grounding method must be set in the 'Basic Service Menu' when the invert­er is switched on. The access code 22742 must be entered in order to access the 'Basic Service Menu'.
1
2
3
4
Page 56
54
Use the 'Up' and 'Down' keys to select the 'Grounding Mode' parameter
Press the 'Enter' key
'Grounding method' is displayed.
Press the 'Enter' key
The currently selected grounding method is displayed.
Off = un-grounded system (no solar mod­ule grounding) Factory setting
Use the 'up' or 'down' buttons to se­lect the 'Negative' grounding method
Negative = solar module grounded on the negative pole:
Press the 'Enter' key
The 'Negative' grounding method is ap­plied, 'Grounding method' and 'Grounding monitoring' are displayed.
To quit the 'Basic Service Menu', press the 'Esc' key twice
5
6
7
Grounding Mode
8
Grounding Mode
9
10
Page 57
Operation
Page 58
Page 59
57
EN
Controls and indicators
Controls and indi­cators
Display Power for the display comes from the mains voltage. The display is therefore available per-
manently.
Item Description
(1) Display
for displaying values, settings and menus
Monitoring and status LEDs
(2) General status LED (red)
lights when there is a status code on the display
(3) Startup LED (orange)
for displaying whether the inverter is in its startup phase or is on standby
(4) Operating state LED (green)
for displaying the operating state
Function keys - allocated different functions depending on the selection:
(5) 'Left/up' key
for navigating to the left and up
(6) 'Down/right' key
for navigating down and to the right
(7) 'Menu/Esc' key
for switching to the menu level for quitting the Setup menu
(8) 'Enter' key
for confirming a selection
(1)
(2)
(3)
(4)
(5) (6) (7) (8)
IMPORTANT! The display on the inverter is not a calibrated measuring device. A slight in­accuracy of a few percent from the energy meter used by the energy supply company is intrinsic to the system. A calibrated meter will be needed to calculate the bills for the energy supply company.
Page 60
58
Display areas in display mode
Display areas in setup mode
(*) Scroll bar (**) INV no. = Inverter DATCOM number,
Save symbol - appears briefly while the selected values are being saved
Symbols showing function key allo­cation
The following symbols are displayed to indicate the function key assignments:
Function key assignment
Display modes
Parameter explanation
Display of values and units as well as status codes
Function key assignment
Next menu items
Currently selected menu item
Preceding menu items
Display modes
Inverter no. | Storage sym. (**)
(*)
1
Navigate: left
Navigate: up
Increase value
Navigate: right
Navigate: down
Reduce value
Menu / Back
Enter
Page 61
59
EN
Monitoring and status LEDs
(1) General status LED (red)
(2) Startup LED (orange)
(3) Operating state LED (green)
A list of the relevant status codes, and causes and remedies can be found in the 'Status diagnosis and repair' section under 'Maintenance and service'.
(3)
(2)
(1)
LED Colour Activity Explanation
(1) red lights up General status: the relevant status code is
shown on the display
Interruption while feeding energy into the grid
While error handling (the inverter waits for an ac­knowledgement or for an error to be rectified)
(2) orange lights up The inverter will enter its automatic startup or
self-test phase as soon after sunrise as the solar modules are delivering sufficient power
The inverter has been switched to standby mode in the setup menu = grid power feed operation switched off manually
The inverter software is being updated
(3) green lights up The LED lights up after the automatic startup
phase of the inverter, provided energy is being fed into the grid. The photovoltaic system is working properly.
Page 62
60
Startup phase and feeding energy into the grid
Startup phase Once it has been switched on automatically, the inverter carries out the following tests and
checks:
a) Self-test of all important inverter components - the inverter runs through a virtual
checklist
b) Synchronisation with the grid
c) Startup test
Before the inverter starts feeding energy into the grid, the grid conditions according to national regulations are tested. Depending on the country-specific regulations, the startup test can last just a few sec­onds or take several minutes.
During the startup phase:
- the operating state LED shows orange,
- the string 'warte...' (wait...) and the currently tested component are displayed, e.g.:
Feeding energy into the grid
- Once the tests have been completed the inverter starts feeding energy into the grid
- The display shows the current energy level that is being fed into the grid, e.g.:
- The operating state LED shows green, the inverter is working.
Page 63
61
EN
Navigation at the menu level
Activate display backlighting
Press any key
The display backlighting is activated.
The option remains in the setup menu to set the display backlighting so that it is on all the time or off all the time.
Automatic deacti­vation of display backlighting / change to display mode 'NOW'
If no key is pressed for 2 minutes,
- the display backlighting switches off automatically and the inverter switches to display mode 'NOW' (assuming the display backlighting is set to automatic).
- The switchover to the 'NOW' display mode can happen from anywhere within the dis­play modes or the Setup menu, with the exception of the 'Standby' menu item.
- The amount of energy currently fed in is displayed.
Open menu level
1
Press the 'Menu' key
'Menu' will appear on the display
The inverter is now at the menu level.
From the menu level
- the required display mode can be se­lected
- the Setup menu can be accessed
1
Page 64
62
The display modes
The display modes
The following display modes are available on the inverter:
Choosing a dis­play mode
Overview of dis­play values
Display mode 'NOW' ...... Displays real-time values
Display mode 'TODAY' ...... Displays values for energy fed into the grid today
Display mode 'YEAR' ...... Displays values for energy fed into the grid during
the current calendar year
Display mode 'TOTAL' ...... Displays values for energy fed into the grid since
the inverter was originally commissioned.
Open menu level
Use the 'left' and 'right' keys to select the required display mode
Press the 'Enter' key
The first value of the selected display mode is displayed.
1
2
3
Display mode Unit Display value
'NOW' W Energy supplied
Day characteristic
V Three-phase AC grid voltage
A Three-phase AC output current
Hz AC grid frequency
V PV array voltage
A PV array current
°C Ambient temperature
rpm Fan speed
Page 65
63
EN
HH:MM
SS
Time
DD.MM
YY
Date
'TODAY' 'YEAR'
kWh / MWh Energy Supplied
Day characteristic ('TODAY')
'TOTAL' Currency Yield
g / kg CO2 saving
W Max. output power
V Max. three-phase AC grid voltage
V Max. PV array voltage
HH:MM Operating hours
Display mode Unit Display value
Page 66
64
Values in display mode 'NOW'
Choosing a dis­play mode
Values in display mode 'NOW'
First value in display mode 'NOW'
Choose display mode 'NOW'
The first value in display mode 'NOW' ap­pears
Scroll to the next display value using the 'Down' key
Scroll back up using the 'Up' key
1
2
AC Output Power
Power (in watts) currently being fed into the grid
Press the 'Enter' key to display the day character­istic.
Day characteristic
Displays a plot showing the power output during the day. The time axis is scaled automatically.
Press the 'Back' key to remove the display
AC Grid Voltage
Phase voltage (Volt)
Press the 'Enter' key to display the string voltage.
String Voltage
displays the string voltage of each phase.
Press the 'Back' key to remove the display
AC Output Current
Phase current currently being fed into grid (Ampere)
NOW
TODAY
Page 67
65
EN
AC Grid Frequency
(Hertz)
PV Array Voltage
Voltage currently present on the solar modules (Volt)
PV Array Current
Current that is being supplied at present by the so­lar modules (Ampere)
Ambient Temperature
Temperature of the air sucked in to cool the invert­er (°C)
Fan Speed
(rpm)
Time
If the time is changed on an inverter or a system add-on, it will also be changed in any other devic­es that are connected via Fronius Solar Net.
Date
If the date is changed on an inverter or a system add-on, it will also be changed in any other devic­es that are connected via Fronius Solar Net.
Page 68
66
Values in display modes 'TODAY / YEAR / TOTAL'
Choose display mode 'TODAY / YEAR / TOTAL'
Values in display modes 'TODAY / YEAR / TOTAL'
First value in display mode 'TODAY'
First value in display mode 'YEAR'
First value in display mode 'TOTAL'
Choose display mode 'TODAY' or display mode 'YEAR' or display mode 'TOTAL'
The first value in the selected display mode appears.
Scroll to the next display value using the 'Down' key
Scroll back up using the 'Up' key
1
2
Energy Supplied
Energy fed into the grid during the period in ques­tion (kWh / MWh)
Press the 'Enter' key to display the day character­istic (only in display mode 'TODAY')
Day characteristic
Displays a plot showing the power output during the day. The time axis is scaled automatically.
Press the 'Back' key to remove the display
There may be discrepancies with values displayed on other measuring instruments be­cause of differences in measuring methods. As far as adding up the energy fed in is con­cerned, the only binding display values are those produced by the calibrated measuring device provided by the electricity supply company.
NOW
TODAY
Page 69
67
EN
Yield
Amount of money earned during the period in question (currency can be selected in the Setup menu)
Like the energy supplied figure, the yield figure may also exhibit discrepancies with other measured values.
The 'Setup Menu' section explains how to select a currency and charge rate. The factory setting depends on the respective country setup.
CO2 Savings
Amount by which CO2 emissions were reduced during the period in question (g / kg)
The value for CO2 savings depends on the power station facilities and corresponds to the CO2 emissions that would be released when generating the same amount of energy. The factory setting is 0.59 kg / kWh (source: DGS – Deutsche Gesellschaft für Sonnene­nergie e.V. (German Society for Solar Energy)
Max. Output Power
Largest amount of power (W) fed into the gird dur­ing the period in question
Max. AC Grid Voltage
Highest AC grid voltage (V) measured during the period in question
Max. PV Array Voltage
Highest PV array voltage (V) measured during the period in question
Page 70
68
Operating Hours
Length of time the inverter has been working (HH:MM).
Although the inverter does not operate during the night, the data required for the Sensor Box option is logged and stored 24 hours a day.
IMPORTANT! A prerequisite for the correct display of day and year values is that the time is set correctly.
Page 71
69
EN
The Setup menu
Initial setting After completing comissioning the inverter is pre-configured depending on the country set-
up.
The SETUP menu item allows the initial settings of the inverter to be changed easily to bring it in line, as closely as possible, with the preferences and requirements of the user.
Accessing the setup menu
Move up and down the menu items
'SETUP' menu level selected
Switch to the menu level (press the 'Menu' key)
Select 'Setup' mode using the 'Left' or 'Right' keys
Press the 'Enter' key
'Standby' menu item
The first menu item in the Setup menu, 'Standby', is shown.
1
2
3
Example: 'Standby' menu item Example: 'Contrast' menu item
Accessing the setup menu
Use 'Up' and 'Down' keys to move between the available menu items
1
2
Page 72
70
Menu items in the Set-up menu
Standby Manual activation / deactivation of Standby mode
- No energy is fed into the grid.
- The Startup LED will show steady orange.
- In Standby mode, no other menu item at menu level can be accessed or adjusted.
- The automatic switchover into the 'NOW' display mode after 2 minutes of keyboard in­activity does not occur.
- Standby mode can only be terminated manually by pressing the 'Enter' key.
- Feeding energy into the grid can be resumed at any time (deactivate 'Standby').
Switching off Standby mode (manually switching off feeding energy into the grid):
Select the 'Standby' item
Press the 'Enter' key
'STANDBY' and 'ENTER' appear alternately on the display. Standby mode is now active. The Startup LED shows steady orange.
Resuming feeding energy into the grid:
'STANDBY' and 'ENTER' appear alternately on the display when in Standby mode.
Press the 'Enter' key to resume feeding energy into the grid
The 'Standby' menu item is displayed. At the same time, the inverter enters the startup phase. The operating state LED shows steady green when feeding energy into the grid has been resumed.
Contrast Adjusts contrast on the display.
Since the contrast is temperature-dependent, when the ambient conditions change it may be necessary to adjust the 'Contrast' menu item.
Backlighting Initial setting for display backlighting
1
2
1
Unit -
Setting range 0 - 10
Factory setting 5
Unit -
Setting range AUTO / ON / OFF
Factory setting AUTO
AUTO: Display backlighting is activated by pressing any key. If no key
is pressed for 2 minutes, the display backlighting will go off again.
Page 73
71
EN
Language Setting the display language
Currency Sets the currency and charge rate for the energy fed into the grid
CO2 factor Setting the CO2 reduction factor
Yield Setting
- of an OFFSET value for the total energy display
- of a measuring offset factor for the day, year and total energy display
Meter deviation
Input of a value for the fed-in energy that will be added to the energy currently fed in (e.g. carry-over value when replacing an inverter)
Meter unit of measurement
Input of a unit (k..., M...)
ON: The display backlighting remains permanently on when the in-
verter is switched on.
OFF: The display backlighting is permanently switched off.
IMPORTANT! The 'Backlight' menu item only relates to the backlighting of the display and the keys.
Unit -
Display area German, English, French, Dutch, Italian, Spanish, Czech, Slo-
vak
Factory setting (depends on country setup)
Unit -
Display area Currency/ feed-in tariff
Factory setting (depends on country setup)
Unit kg/kWh
Setting range 00.01 - 99.99
Factory setting 0.59 kg/kWh
Setting range Meter deviation / meter unit of measurement / meter calibration
Unit Wh
Setting range Five digits
Factory setting 0
Unit -
Page 74
72
Meter calibration
Input of a correction value to ensure that the value shown on the inverter display corre­sponds with the calibrated display on the electricity meter
DATCOM Checking data communications, entering the inverter number, protocol settings
Status
Indicates data communication is taking place via a Fronius Solar Net or that a data com­munications error has occurred
Inverter number
Sets the number (= address) of the inverter in a system with several solar inverters
Protocol type
Specifies the communications protocol to be used to transfer the data:
Device Info For displaying the settings that will be of relevance to an energy supply company. The val-
ues shown will depend on the country setup or the device-specific settings of the inverter.
Setting range k / M
Factory setting -
Unit %
Setting range -5.0 - +5.0
Factory setting 0
Setting range Status / inverter number / protocol type
Unit -
Setting range 00 - 99 (00 = 100th inverter)
Factory setting 01
IMPORTANT! If a number of inverters are linked together in a data communications sys­tem, assign a unique address to each one.
Unit -
Setting range Solar Net / Interface
Factory setting Solar Net
Display area General / MPP Tracker / Grid Monitoring / Voltage Limits / Fre-
quency Limits / P AC Reduction
General:
Setup Country setup
Version Version of country setup
Group Group for updating the inverter software
MPP Tracker:
Page 75
73
EN
DC Mode DC mode
FIX Voltage value in V for fixed voltage operation
User Voltage value in V for MPP User operation
Grid Monitoring:
GMTi Start-up time of inverter in s
GMTr Reconnection time in s following a grid fault
ULL Mean grid voltage over 10 minutes in V.
LL Trip Trip time for long-term voltage monitoring
Voltage Limits:
UIL max Upper inner grid voltage in V
UIL min Lower inner grid voltage in V
UOL max Upper outer grid voltage limit value in V
UOL min Lower outer grid voltage limit value in V
Frequency Limits:
FIL max Upper inner grid frequency in Hz
FIL min Lower inner grid frequency in Hz
FOL max Upper outer grid frequency limit value in Hz
FOL min Lower outer grid frequency limit value in Hz
LVFRT:
Status Status of the LVFRT function (Low Voltage Fault Ride Through,
according to BDEW TR3 5.7)
DB min Dead Band Value min.
Lower voltage limit as % for the reactive power feed
DB max Dead Band Value max.
Upper voltage limit as % for the reactive power feed
k-Fac Gradient showing how much reactive current is fed in as a func-
tion of voltage
P AC Reduction:
Max. P AC Manual power reduction
GPIS Softstart function
GFDPRv Grid frequency-dependent power reduction in %/Hz
GFDPRr Return to nominal output in %/s (following a grid frequency-in-
duced power reduction)
Page 76
74
Device Status For displaying the measured insulation resistance
Time Setting time and date
IMPORTANT! The correct time and date is a prerequisite for the correct display of day and
year values and the day characteristic.
Status LT The status display of the most recent inverter fault can be displayed.
IMPORTANT! Due to the low level of insolation early in the morning and in the evening,
the status codes 306 (Power low) and 307 (DC low) are displayed routinely at these times of day. These status messages do not indicate any kind of fault.
- Press the 'Enter' key to see the status of the power stage set and the most recent fault
- Use the 'Up' and 'Down' keys to scroll through the list
- Press the 'Back' key to close the status and fault list
Grid Status The five most recent grid faults can be displayed:
- Press the 'Enter' key to see the five most recent grid faults
- Use the 'Up' and 'Down' keys to scroll through the list
- Press the 'Back' key to close the grid fault display
Fan test To check that the fan is working correctly
The fan test is started by pressing the 'Enter' key. While the test is ongoing, its ' Progress' is shown on the display.
OK Fan test successful Fail Fan is defective; the associated status code is displayed in 'NOW' view mode.
Version Displays the version and serial numbers of the PC boards in the inverter (e.g. for service
purposes)
Display area Messwertanzeige
PV Iso. (Value in MOhm)
Unit HH:MM, DDMMYYYY
Setting range Time/date
Factory setting -
Unit -
Setting range Start (Progress)
Factory setting -
Page 77
75
EN
Unit -
Display area Display / Display Software / Interface / SmartMedia Card / Con-
trol / Control Software / Monitoring / Monitoring Software / Inter­face
Factory setting -
Page 78
76
Setting and displaying the menu items
Setting the menu items, general
Accessing the set-up menu
Use the 'Up' or 'Down' buttons to select the desired menu item
Press 'Enter'
Exiting a menu item
To exit a menu item, press the 'Back' key
The menu level appears:
The first digit of a value to be set flash­es:
The available settings are displayed:
Use the 'Up' or 'Down' buttons to se­lect a value for the first digit
Press 'Enter'
The second digit of the value flashes.
Repeat steps 4 and 5 until ...
the whole value to be set flashes.
Press 'Enter'
Repeat steps 4 - 6 as required for units or other values that are to be set until the appropriate unit or the value flashes.
Press the 'Enter' key to save and ap­ply the changes.
To discard the changes, press the 'Esc' key.
Use the 'Up' or 'Down' buttons to se­lect the desired setting
Press the 'Enter' key to save and ap­ply the setting.
To discard the setting, press the 'Esc' key.
The currently selected menu item is dis­played.
The currently selected menu item is dis­played.
1
2
3
4
5
6
7
8
9
4
5
1
Page 79
77
EN
If no key is pressed for 2 minutes,
- the inverter switches from wherever it is within the Setup menu back to the 'NOW' dis­play mode (exception: 'Standby' menu item),
- the display backlighting goes out,
- The amount of energy currently fed in is displayed.
Practical exam­ples for setting and displaying menu items
The setting and displaying of menu items is illustrated using the following examples:
- Setting the display backlighting
- Setting the currency and feed-in tariff
- Setting the time and date
Setting the dis­play backlighting
Setting the cur­rency and feed-in tariff
Select the 'Backlight' menu item
Press the 'Enter' key
The current setting for the display back­lighting is shown.
Use the 'Up' and 'Down' keys to select the desired setting for the display backlighting
Press the 'Enter' key to apply the set­ting
The settings for the display backlighting are applied. The 'Backlight' menu item is displayed.
1
2
3
4
Select the 'Currency' menu item
Press the 'Enter' key to apply the cur­rency
1
2
Page 80
78
The currently selected currency is dis­played, factory setting = 'EUR'; the first of the three characters starts flashing.
Use the 'Up' and 'Down' keys to select a value for the first character
Press the 'Enter' key
The second character starts flashing.
Repeat steps 3 and 4 for the second and third characters until...
the selected currency starts flashing.
Press the 'Enter' key
The currency is applied and the present feed-in tariff in currency/kWh displayed, factory setting = 0.43 EUR / kWh; the first digit starts flashing.
Use the 'Up' and 'Down' keys to select a value for the first digit (e.g. 0)
Press the 'Enter' key
The second digit starts flashing.
Repeat steps 7 and 8 for the second digit and for each of the three digits after the decimal point until ...
the selected feed-in tariff starts flashing.
Press the 'Enter' key
3
4
5
6
7
8
9
10
Page 81
79
EN
Setting the time and date
The feed-in tariff is applied and the 'Cur­rency' menu item is displayed.
Select the 'Time' menu item
Press the 'Enter' key
The time is displayed (HH:MM:SS, 24-hour format), the hours field starts flashing.
Use the 'Up' and 'Down' keys to select a value for the hour
Press the 'Enter' key
The minutes field starts flashing.
Repeat steps 3 and 4 for the minutes and seconds until...
the set time starts flashing.
Press the 'Enter' key
The time is applied and the date now ap­pears (DD.MM.YYYY), the day field starts flashing.
Use the 'Up' and 'Down' keys to select a value for the day
Press the 'Enter' key
DATCOM
YIELD
1
2
3
4
5
6
7
8
Page 82
80
The month field starts flashing.
Repeat steps 7 and 8 for the month and the last 2 digits of the year until ...
the set date starts flashing.
Press the 'Enter' key
The date is applied and the 'Time' menu item is displayed.
9
10
DATCOM
YIELD
Page 83
81
EN
Switching the key lock on and off
General The inverter has a key lock function.
When the key lock is active, the Setup menu is not accessible, i.e. the setup data cannot be changed accidentally (or maliciously). The code 12321 has to be entered in order to activate / deactivate the key lock.
Switching the key lock on and off
Press the 'Menu' key
'MENU' is displayed.
Press the unassigned 'Menu / Esc' key 5 times
'Access Code' is displayed in the 'CODE' menu; the first digit starts flashing.
Enter the code 12321: use the 'Up' and 'Down' keys to select a value for the first digit of the code.
Press the 'Enter' key
The second digit starts flashing.
Repeat steps 3 and 4 for the second, third, fourth and fifth digit of the ac­cess code until ...
the selected code starts flashing.
Press the 'Enter' key
'Key Lock' is displayed in the 'LOCK' menu.
Use the 'Up' and 'Down' keys to turn the key lock on or off:
ON = key lock is on (the Setup menu is not accessible)
OFF = key lock is off (the Setup menu is accessible)
Press the 'Enter' key
1
2
3
4
Acess Code
5
6
7
8
Page 84
82
Page 85
Troubleshooting and maintenance
Page 86
Page 87
85
EN
Status diagnostics and troubleshooting
Displaying status codes
The inverter performs a system self diagnosis that automatically detects many faults that may occur and shows them on the display. This means you are promptly made aware of malfunctions in the inverter and the photovoltaic system, or of any installation or operating faults.
If the system self diagnosis has detected a specific fault, the associated status code will be shown on the display.
Total failure of the display
If the display fails to come on some time after sunrise:
- Check the AC voltage ON the inverter connections: the AC voltage must be 230 V (+ 10 % / - 5 %)*.
* The mains voltage tolerance depends on the country setup
Class 1 status codes
Class 1 status codes generally only arise momentarily and are caused by the public grid.
The initial response of the inverter in this case is to disconnect itself from the grid. The grid is subsequently checked for the stipulated monitoring period. If no further problem has been detected by the end of this period, then the inverter will resume feeding energy into the grid.
Depending on the country setup, the SoftStart-function GPIS is activated: after cutting out due to an AC fault, the output power of the inverter is continuously in­creased by 10% every minute in line with the VDE-AR-N 4105 guideline.
IMPORTANT! Status codes may sometimes appear briefly as a result of the inverter's con­trol response. If the inverter then continues working with no sign of any problem, this means that there was no fault.
102
AC voltage too high
Behaviour Following careful testing and when the grid conditions are within
the permissible range again, the inverter will resume feeding energy into the grid.
Remedy Check grid connections
If this status code keeps recurring, contact your system engi­neer
103
AC voltage too low
Behaviour Following careful testing and when the grid conditions are within
the permissible range again, the inverter will resume feeding energy into the grid.
Remedy Check grid connections
If this status code keeps recurring, contact your system engi­neer
Page 88
86
105
AC frequency too high
Behaviour Following careful testing and when the grid conditions are within
the permissible range again, the inverter will resume feeding energy into the grid.
Remedy Check grid connections
If this status code keeps recurring, contact your system engi­neer
106
AC frequency too low
Behaviour Following careful testing and when the grid conditions are within
the permissible range again, the inverter will resume feeding energy into the grid.
Remedy Check grid connections
If this status code keeps recurring, contact your system engi­neer
107
No AC grid
Behaviour Following careful testing and when the grid conditions are within
the permissible range again, the inverter will resume feeding energy into the grid.
Remedy Check grid connections
If this status code keeps recurring, contact your system engi­neer
108
Stand alone operation detected
Behaviour Following careful testing and when the grid conditions are within
the permissible range again, the inverter will resume feeding energy into the grid.
Remedy If this status code keeps recurring, contact your system engi-
neer
Page 89
87
EN
Class 3 status codes
Class 3 includes status codes that may occur while feeding energy into the grid, but gen­erally do not cause the process to be interrupted for any length of time.
The inverter disconnects automatically from the grid, the grid is then monitored as specified and the inverter attempts to resume feeding energy into the grid.
301
Overcurrent (AC)
Behaviour Short-term interruption while feeding energy into the grid due to
overcurrent in the alternating current circuit The inverter resumes with its startup routine.
Remedy Fault is rectified automatically
If this status code keeps recurring, contact your system engi­neer
303
Power module overtemperature
Behaviour Short-term interruption while feeding energy into the grid due to
overtemperature The inverter resumes with its startup routine.
Remedy Purge cooling air openings and heat sink if necessary;
fault is rectified automatically If this status code keeps recurring, contact your system engi­neer
304
Internal temperature too high
Behaviour Short-term interruption while feeding energy into the grid due to
overtemperature The inverter resumes with its startup routine
Remedy Purge cooling air openings and heat sink if necessary;
fault is rectified automatically If this status code keeps recurring, contact your system engi­neer
305
If the grid relay is closed, no energy is transferred to the grid
Behaviour Permanent interruption while feeding energy into the grid
Remedy If this status code keeps recurring, contact your system engi-
neer
307 (DC low)
DC input voltage too low for feeding energy into the grid
Behaviour Short-term interruption while feeding energy into the grid
The inverter resumes with its startup routine.
Page 90
88
Class 4 status codes
Some of the class 4 status codes necessitate intervention by a Fronius-trained service en­gineer.
Remedy Fault is rectified automatically
If this status code keeps recurring, contact your system engi­neer
IMPORTANT! Due to the low level of insolation early in the morning and in the evening, the status code 307 (DC low) is routinely displayed at these times of day. This status code does not indicate any kind of fault.
309
DC input voltage too high
Behaviour Short-term interruption while feeding energy into the grid
The inverter resumes with its startup routine.
Remedy Fault is rectified automatically
If this status code keeps recurring, contact your system engi­neer
321
Overcurrent (AC)
Behaviour Short-term interruption while feeding energy into the grid due to
a grid fault or a power module fault The inverter resumes with its startup routine.
Remedy Fault is rectified automatically
If this status code keeps recurring, contact your system engi­neer
322
Overtemperature on the air intake sensor
Behaviour Permanent interruption while feeding energy into the grid
Remedy Reduce the ambient temperature and ensure that a suitable hot
air extractor is installed if necessary If this status code keeps recurring, contact your system engi­neer
401
No communication with power stage set possible
Behaviour The inverter will automatically attempt to connect again and, if
possible, will resume feeding energy into the grid
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
406
Power module temperature sensor defective
Behaviour The inverter is disconnected from the grid for safety reasons.
Page 91
89
EN
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
407
Internal temperature sensor defective
Behaviour The inverter is disconnected from the grid for safety reasons.
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
412
Fixed voltage mode has been selected instead of MPP voltage mode, and the fixing volt­age has been set at too low or too high a value.
Behaviour The fixed voltage is lower than the current MPP voltage.
Remedy Check module voltage and change the connection of the solar
modules if the input voltage is too high; If the status code appears all the time: notify a Fronius-trained service engineer
415
External Emergency Stop line is blocked
Behaviour The inverter is disconnected from the grid for safety reasons.
Remedy Fault is rectified automatically;
If this status code keeps recurring: notify a Fronius-trained ser­vice engineer
416
No communication possible between power stage set and control system
Behaviour The inverter is disconnected from the grid for safety reasons.
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
425
No communication possible with the power module
Behaviour The inverter is disconnected from the grid for safety reasons
and then attempts a restart.
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
426
Intermediate circuit charging takes too long
Behaviour Short-term interruption while feeding energy into the grid
The inverter resumes with its startup routine.
Remedy Fault is rectified automatically
If this status code keeps recurring, contact your system engi­neer
Page 92
90
427
Power stage set not ready for too long (timeout)
Behaviour Short-term interruption while feeding energy into the grid
The inverter resumes with its startup routine.
Remedy Fault is rectified automatically
If this status code keeps recurring, contact your system engi­neer
431
Bootloading process interrupted
Behaviour The inverter is in bootloading mode and is not feeding any en-
ergy into the grid
Remedy Repeat the update process
If the status code is displayed all the time: notify a Fronius­trained service engineer
436
Receiving incorrect fault information from the power stage set
Behaviour Short-term interruption while feeding energy into the grid
The inverter resumes with its startup routine.
Remedy Fault is rectified automatically
If this status code keeps recurring, contact your system engi­neer
437
General error handling started in the power stage set
Behaviour Short-term interruption while feeding energy into the grid
The inverter resumes with its startup routine.
Remedy Fault is rectified automatically
If this status code keeps recurring, contact your system engi­neer
438
Receiving incorrect fault information from the power stage set
Behaviour Short-term interruption while feeding energy into the grid
The inverter resumes with its startup routine.
Remedy Fault is rectified automatically
If this status code keeps recurring, contact your system engi­neer
445
- Compatibility error (e.g. due to replacement of a PC board)
- Invalid power stage set configuration
Behaviour The inverter is not feeding any energy into the grid.
Page 93
91
EN
Remedy Update the inverter firmware;
If the status code is displayed all the time: notify a Fronius­trained service engineer
457
Mains relay sticking
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
459
Error when recording the measurement signal for the insulation test
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
460
Reference voltage source for the digital signal processor (DSP) is working out of toler­ance
Behaviour The inverter is not feeding any energy into the grid.
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
461
Fault in the DSP data memory
Behaviour The inverter is not feeding any energy into the grid.
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
463
AC polarity reversed
Behaviour The inverter is not feeding any energy into the grid.
Remedy Update the inverter firmware
If the status code is displayed all the time: notify a Fronius­trained service engineer
472
Fuse for solar module grounding is faulty
Behaviour The inverter is not feeding any energy into the grid.
Remedy Replace fuse for solar module grounding - notify a Fronius-
trained service engineer; if this status code keeps recurring, contact your system engi­neer
475
Solar module grounding, insulation fault (connection between solar module and ground)
Behaviour The inverter is disconnected from the grid for safety reasons.
Page 94
92
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
486
- External NO contact is open
- Optional measuring and monitoring relay has tripped
Behaviour The inverter is not feeding any energy into the grid.
Remedy Close external NO contact;
check measuring and monitoring relay If this status code keeps recurring, contact your system engi­neer
487
Air inlet temperature sensor is faulty
Behaviour The inverter is not feeding any energy into the grid.
Remedy Replace air inlet temperature sensor - notify a Fronius-trained
service engineer
488
AC measurement device is faulty
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
490, 491
Internal communication error
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
492
DC main switch is switched off
Behaviour The inverter is not feeding any energy into the grid.
Remedy Switch on DC main switch
493
DC relay is faulty
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
494
Grounding fault on the control board
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
Page 95
93
EN
495
The 3 V supply voltage on the control board is faulty
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
496
The 5 V supply voltage on the control board is faulty
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
497
The 14 V or 22 V supply voltage for the PWM driver is faulty
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
498
The 24 V supply voltage for the power electronics is faulty
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
499
The 24 V supply voltage on the control board is faulty
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
Page 96
94
Class 5 status codes
Class 5 status codes do not generally interfere with feeding energy into the grid, but can cause restrictions. A status code is displayed until it is acknowledged by pressing a key (the inverter, however, continues to operate normally in the background).
502
Insulation error on the solar modules
Description Warning message is shown on the display
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
509
No energy fed into the grid in the past 24 hours
Description Warning message is shown on the display
Remedy Check that all the conditions for feeding energy into the grid
without any problems have been satisfied. If the status code is displayed all the time: notify a Fronius­trained service engineer
516
No communication possible with the storage unit
Description Storage unit warning message
Remedy If the status indicator appears all the time: notify a Fronius-
trained service engineer
517
Power derating caused by too high a temperature
Description Warning message when power derating occurs
Remedy If the status indicator appears all the time: notify a Fronius-
trained service engineer
518
Internal DSP malfunction
Description Warning message is shown on the display
Remedy If the status indicator appears all the time: notify a Fronius-
trained service engineer
535
Error during fan self-test
Description Warning message is shown on the display
Remedy If the status indicator appears all the time: notify a Fronius-
trained service engineer
536
Main fan error
Page 97
95
EN
Description Warning message is shown on the display
Remedy If the status indicator appears all the time: notify a Fronius-
trained service engineer
551
Fuse for solar module grounding is faulty
Description Warning message is shown on the display
Remedy Replace fuse for solar module grounding - notify a Fronius-
trained service engineer; if this status code keeps recurring, contact your system engineer
555
Circulating fan error
Description Warning message is shown on the display
Remedy If the status indicator appears all the time: notify a Fronius-
trained service engineer
558
Functional incompatibility (one or more PC boards in the inverter are not compatible with each other, e.g. after a PC board has been replaced)
Description Possible device errors or malfunctions on the inverter
Remedy Update the inverter firmware using the Fronius Solar.update
software; the latest inverter firmware is available from http://www.fronius.com. If the status indicator appears all the time: notify a Fronius­trained service engineer
560
Power derating caused by overfrequency
Description The status code is displayed from a grid frequency of 50.2 Hz
and above. The inverter reduces the power along a 40%/Hz slope. The in­verter switches off at a grid frequency of 51.5 Hz. The status indicator is displayed until the inverter returns to nor­mal operation.
Remedy From a frequency of 50.2 Hz and above, the inverter tries to re-
connect to the grid. The fault is rectified automatically as soon as the inverter re­turns to normal operation. If the status indicator appears all the time: notify a Fronius­trained service engineer
597
External overvoltage protection has tripped (connected to the "IN1" NO/alarm contact ter­minals)
Description Warning message is shown on the display
Page 98
96
Class 7 status codes
Class 7 status codes relate to the control system, the configuration and inverter data re­cording, and may directly or indirectly affect the process of feeding energy into the grid.
Remedy Replace overvoltage protection - notify a Fronius-trained ser-
vice engineer
598
External overvoltage protection has tripped (connected to the "IN2" NO/alarm contact ter­minals)
Description Warning message is shown on the display
Remedy Replace overvoltage protection - notify a Fronius-trained ser-
vice engineer
599
External overvoltage protection has tripped (connected to the "IN3" NO/alarm contact ter­minals)
Description Warning message is shown on the display
Remedy Replace overvoltage protection - notify a Fronius-trained ser-
vice engineer
701 - 716
Provides information about the internal processor program status
Description Is of no concern when the inverter is working properly and only
appears in the "Status PS" setup parameter. In the event of an actual error, this status code supports Fronius TechSupport during the error analysis.
721
EEPROM has been re-initialised
Description Warning message is shown on the display
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
722 - 730
Provides information about the internal processor program status
Description Is of no concern when the inverter is working properly and only
appears in the "Status PS" setup parameter. In the event of an actual error, this status code supports Fronius TechSupport during the error analysis.
751
Time lost
Description Warning message is shown on the display
Remedy Reset the time and date
If the status code is displayed all the time: notify a Fronius­trained service engineer
Page 99
97
EN
752
Real Time Clock module faulty
Description Warning message is shown on the display
Remedy Reset the time and date
If the status code is displayed all the time: notify a Fronius­trained service engineer
753
Time not set for a long period (> 1/2 year)
Description Warning message is shown on the display
Remedy Reset the time and date
If the status code is displayed all the time: notify a Fronius­trained service engineer
754, 755
Provides information about the internal processor program status
Description Is of no concern when the inverter is working properly and only
appears in the "Status PS" setup parameter. In the event of an actual error, this status code supports Fronius TechSupport during the error analysis.
757
Hardware error in the Real Time Clock module
Description Warning message is shown on the display; the inverter is not
feeding any energy into the grid
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
761 - 765
Provides information about the internal processor program status
Description Is of no concern when the inverter is working properly and only
appears in the "Status PS" setup parameter. In the event of an actual error, this status code supports Fronius TechSupport during the error analysis.
766
Emergency derating has been activated (max. 750 W)
Description Warning message is shown on the display
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
767
Provides information about the internal processor program status
Description Is of no concern when the inverter is working properly and only
appears in the "Status PS" setup parameter. In the event of an actual error, this status code supports Fronius TechSupport during the error analysis.
Page 100
98
768
Different power derating in the hardware modules
Description Warning message is shown on the display
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
772
Storage unit not available
Description Warning message is shown on the display
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
773
Software update group 0 (invalid country setup)
Description Warning message is shown on the display
Remedy If the status code is displayed all the time: notify a Fronius-
trained service engineer
775
PMC power stage set not available
Description Warning message is shown on the display
Remedy Press the 'Enter' key to acknowledge the error
If the status code is displayed all the time: notify a Fronius­trained service engineer
776
Invalid device-type
Description Warning message is shown on the display
Remedy Press the 'Enter' key to acknowledge the error
If the status code is displayed all the time: notify a Fronius­trained service engineer
781 - 794
Provides information about the internal processor program status
Description Is of no concern when the inverter is working properly and only
appears in the "Status PS" setup parameter. In the event of an actual error, this status code supports Fronius TechSupport during the error analysis.
799
No communication between the control board and the monitoring board
Behaviour The inverter is not feeding any energy into the grid.
Remedy notify a Fronius-trained service engineer
Loading...