Froling P4 Pellet 8-60, P4 Pellet 8, P4 Pellet 15, P4 Pellet 20, P4 Pellet 25 Assembly Instructions Manual

...
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen
Tel. +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
Assembly instructions
P4 Pellet 8 - 60
Introduction
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 3 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
I
Dear installer,
The FRÖLING P4 Pellet is a state-of-the-art design that conforms to all currently applicable standards and testing guidelines.
Please read and follow the assembly instructions. They contain safety instructions as well as comprehensive information about transporting, setting up and assembling the boiler.
The constant further development of our products means that there may be minor differences from the pictures and content. If you discover any errors, please let us know.
Subject to technical change.
Delivery Certificate
Keeping a record of correct delivery and customer-specific data for the system allows us to respond quickly should problems arise.
We would therefore ask you to confirm that you have received the product in good condition.
Please send Fröling a copy of the shipping document, completely filled out and signed by the customer.
Guarantee Conditions
Our sale and delivery conditions generally apply. These conditions have been made available to customers, and customers have been made aware of them at the time of order completion.
You can also find the guarantee conditions in the enclosed guarantee certificate.
Address of manufacturer
FRÖLING Heizkessel- und Behälterbau GesmbH
Industriestraße 12 A-4710 Grieskirchen AUSTRIA
TEL 0043 (0)7248 606 0 FAX 0043 (0)7248 606 600 E-MAIL info@froeling.com INTERNET www.froeling.com
Contents
Page 4
M0930408_en I
C
1 General information 6
1.1 Notes on standards 6
1.2 Design Information 7
1.2.1 Approvals and reporting obligations ....................................................................7
1.2.2 Requirements for hot water supplies ................................................................... 7
1.2.3 Ventilation of boiler room ..................................................................................8
1.2.4 Installing the heating system / Standards ............................................................ 8
1.2.5 Combination with storage tank ........................................................................... 8
1.2.6 Chimney connection / chimney system ................................................................ 9
Draught limiter................................................................................................9
Boiler data for constructing the flue gas system:..................................................9
1.3 Installation Information 10
1.3.1 Hose lines ..................................................................................................... 10
Potential equalisation ..................................................................................... 11
2 Technology 12
2.1 Components and connections 12
2.2 Dimensions 13
2.3 Technical specifications 14
2.3.1 P4 Pellet 8/15/20/25....................................................................................... 14
2.3.2 P4 Pellet 32/38/48/60 ..................................................................................... 15
3 Assembly 16
3.1 Transport 16
3.1.1 Positioning..................................................................................................... 16
3.1.2 Temporary storage ......................................................................................... 16
3.2 Setting up in the boiler room 17
3.2.1 Remove boiler from pallet................................................................................ 17
3.2.2 Transporting in the boiler room ........................................................................ 17
3.2.3 Minimum distances in the boiler room................................................................ 18
3.3 Assembling the Pellet Boiler 19
3.3.1 Removing the suction cyclone .......................................................................... 19
3.3.2 Fitting the induced draught fan......................................................................... 19
3.4 Install delivery system 20
3.4.1 Universal suction system ................................................................................. 20
Variant 1 - Comfort pellet box ......................................................................... 21
Variant 2 - Eco pellet box................................................................................ 22
Installing the suction probes and lines .............................................................. 23
3.4.2 Suction screw system...................................................................................... 24
3.4.3 Bag silo system.............................................................................................. 27
3.4.4 Pellet storage area.......................................................................................... 29
Size of storage area....................................................................................... 29
Sloping floor ................................................................................................. 30
Impact cushion.............................................................................................. 30
3.5 Electrical Connection 31
3.5.1 Connecting the Comfort pellet box .................................................................... 32
Contents
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 5 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
C
4 Initial startup 33
4.1 Configuring the boiler 33
4.2 Setting “Max Level” sensor 33
5 Appendix 34
5.1 Delivery Certificate 34
5.2 Notes 35
General
Standards, Design, Assembly
Page 6
M0930408_en I
1
1 General information
CAUTION
Assembly and installation by untrained personnel.
Danger: Personal injury and damage to property.
The instructions and information provided in the instructions should be observed!
Only allow trained staff (heating installers or licensed electricians) to perform set-up and installation!
1.1 Notes on standards
The boiler must be installed and started up in compliance with local fire and building regulations and the following standards:
ÖNORM / DIN EN 303-5 Heating boilers for solid fuels, manually and automatically loaded combustion
systems, nominal heat output of up to 300 kW - Terminology, requirements, testing and marking
ÖNORM M 7510 Guidelines for checking central heating systems
ÖNORM / DIN EN 12828 Heating systems in buildings - design of hot water heating systems
ÖNORM B 8130 Safety devices, open water heating systems
ÖNORM B 8131 Closed water heating systems, safety requirements
DIN 4751 Parts 1-4 Heating system safety equipment
ÖNORM / DIN EN 13384-1 Chimneys serving one appliance
ÖNORM M 7515 /DIN 4705-1 Calculating chimney dimensions for combustion systems
TRVB H118 Technical directives for fire protection/prevention (Austria only)
ÖNORM H5170 Construction and fire protection requirements
VDI 2035 Prevention of damage caused by scaling in hot water and water heating
systems (Germany only)
ÖNORM H 5195-1 Protection against corrosion and scaling damage in hot water systems with
operating temperatures to 100°C (Austria only).
SWKI 97-1 Limescale and corrosion protection in heating systems (Switzerland only)
General
Standards, Design, Assembly
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 7 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
1
1.2 Design Information
It is forbidden to carry out modifications to the boiler or to change or deactivate safety equipment.
In addition to the operating instructions and the applicable regulations for the country in which the boiler will be operated for installation and operation of the boiler system, all fire, police, and electrical regulations must be observed.
1.2.1 Approvals and reporting obligations
NOTE
Each heating system must be officially approved.
When installing or modifying a heating system, you must inform the inspectors from the supervisory authority and get authorisation from the building authorities.
Austria: Report to the construction authorities of the community or
magistrate
Germany: Report new installations to an approved chimney sweeper /
the building authorities.
1.2.2 Requirements for hot water supplies
The requirements pertaining to the water used to fill the boiler are based on the following standards and guidelines:
Applicable standards and directives:
Austria: ÖNORM H 5195-1 Germany: VDI 2035 Switzerland: SWKI 97-1
There are no other special requirements for domestic hot water apart from this.
Note for filling with make-up water:
Bleed the filling hose before connecting to prevent air from getting into the system.
§
General
Standards, Design, Assembly
Page 8
M0930408_en I
1
1.2.3 Ventilation of boiler room
The openings for the supply air and the exhaust air should be arranged as nearly opposite each other as possible to achieve a good thermal draught effect.
The supply air must be drawn in directly from outside. The exhaust
air must be discharged directly outside.
Unless otherwise provided by the relevant building regulations for the room where the boiler is to be installed, the following standards apply:
Applicable standards:
- TRVB H 118
- ÖNORM H 5170
Rule of thumb: Provide a supply air cross-section of 2 cm
2
per kW of boiler rated output,
as per ÖNORM H 5170, but a total cross-section of at least 200 cm
2
1.2.4 Installing the heating system / Standards
The boiler has to be installed in a closed hydraulic system. The following standards govern the installation of heating systems:
Applicable standards:
ÖNORM / DIN EN 12828 Heating Systems in Buildings
The following prior standards still apply: Austria: - Closed systems as per ÖNORM B 8131
Germany: - Closed systems as per DIN 4751 Part 2
1.2.5 Combination with storage tank
NOTE
It is not generally necessary to use a storage tank for the system to run smoothly. However we recommend that you use it with a storage tank, as this allows you to achieve continuous reduction within the ideal performance range of the boiler.
Please contact your installer or a Fröling technician directly for the right measurements of the storage tank (as per ÖNORM M 7510 resp. Directive UZ37).
§
§
General
Standards, Design, Assembly
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 9 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
1
1.2.6 Chimney connection / chimney system
EN 303-5 specifies that the entire flue gas system must be designed to prevent, wherever possible, damage caused by seepage, insufficient feed pressure and condensation.
It should be noted here that flue gas temperatures of less than 160 K above room temperature can occur within the permitted operating range of the boiler.
The flue gas temperatures (when cleaned) and the additional flue gas values can be found in the technical specification sheets.
À See “Boiler data for constructing the flue gas system”
Establish the connection to the chimney via the shortest path, ascending as much under 30 – 45° as possible Insulate the connecting piece.
The entire flue gas system (chimney and connection) must be calculated as per ÖNORM / DIN EN 13384-1 or prior standards ÖNORM M 7515 / DIN 4705-1.
Local and other legal regulations also apply. The chimney must be approved by a smoke trap sweeper or chimney
sweeper.
As per TRVB H 118 (only in Austria) an explosion flap must be
installed in the flue pipe or in the chimney.
Draught limiter
We recommend that you install a draught limiter 1 Install the draught limiter directly under the mouth of the flue line,
as there is always low pressure here!
Boiler data for constructing the flue gas system:
P4 Pellet
Component MEH 8 15 20 25 32 38 48 60
Flue gas N
L
temperature
°C 140 150 150 150 160 160 160 170
Flue gas mass flow N
L
P
L
kg/h
25 11
36 15
52 20
65 25
78 32
92 41
140
60
155
70
Flue gas mass flow N
L
P
L
kg/s
0,007 0,003
0,010 0,004
0,014 0,006
0,018 0,007
0,022 0,009
0,025 0,011
0,039 0,017
0,043 0,019
Feed pressure N
L
required P
L
Pa
8 6
8 6
8 6
8 6
8 6
8 6
8 6
8 6
Feed pressure N
L
required P
L
mbar
0,08 0,06
0,08 0,06
0,08 0,06
0,08 0,06
0,08 0,06
0,08 0,06
0,08 0,06
0,08 0,06
Flue pipe diameter mm 130 130 130 130 150 150 150 150
NL = Nominal Load, PL = Partial Load
1
General
Standards, Design, Assembly
Page 10
M0930408_en I
1
1.3 Installation Information
Water lines should not be located in close proximity to the storage
area or the feeder units due to the dangers posed by condensation and bursting water pipes!
Check the delivered items for foreign objects in the individual
components.
In the pellet store room an impact cushion must be installed on the
opposite side to the filler pipes. This reduces wear on the pellets when they are blown in and stops the finish being worn off. Broken pieces of masonry or finish and other foreign bodies (small stones, pieces of wood, screws, etc.) can block the delivery system or the pellet feed into the boiler and cause the system to fail. In case of faults due to such foreign bodies, the guarantee is void.
In time pellets leave dust on the ground; this can impair the process
of moving them from the pellet storage area. For this reason you should check and clean if necessary before refilling.
1.3.1 Hose lines
For the hose lines used with the suction device, the universal suction system, and the silo delivery unit, observe the following:
Do not kink the hose lines! Minimum bending radius = 30cm. Lay the hose lines as straight as possible! If the lines are sagging, it
can lead to so-called “pockets.” Problem-free pellet feeding can not be guaranteed.
Lay the hose lines in short sections away from walking areas! Hose lines are not UV-proof!
Therefore: do not lay the hose lines outdoors!
Hose lines are suitable for temperatures up to 60°C!
Therefore: Hose lines must not come into contact with flue gas pipes or un-insulated heating pipes!
Hose lines must be earthed on both sides to ensure that no static
charge builds up as a result of transporting the pellets!
The suction line must be in a single section! The return-air line can be made up of several sections, but potential
equalisation must be established throughout the line!
General
Standards, Design, Assembly
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 11 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
1
Potential equalisation
When connecting the hose lines to the individual connection pipes, ensure there is potential equalization throughout the line!
U Expose approximately 3 cm of the earth conductor at the end of the
hose line
TIP: Slit the insulation open along the wire with a knife
U Bend the earth wire inwards in a loop
´ This prevents the earth wire from being damaged by the feed of
pellets.
U Fit a hose clip to the hose line U Attach the hose line to the connector
Ensure that contact is established between the earth conductor and
the connector!
U Tighten the hose clip
Technology
Components, Connections, and Dimensions
Page 12
M0930408_en I
2
2 Technology
2.1 Components and connections
P4 Pellet
Pos. Component Unit 8 / 15 20 / 25 32 / 38 48/60
A Boiler outfeed connection 1 6/4 6/4 6/4 B Boiler return feed connection 1 6/4 6/4 6/4 C Drain 1/2 1/2 1/2 1/2 D Air vent
Inch
1/2 1/2 1/2 1
E Pellet suction line F Return-air line
DA 60 DA 60 DA 60 DA 60
G Flue gas pipe connection
mm
130 130 150 150
1 Lambdatronic P 3200 control system 2 Switch box 3 Safety temperature limiter - STL 4 Induced draught fan
4
C A G
1
2
3 B D E F
Technology
Components, Connections, and Dimensions
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 13 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
2
2.2 Dimensions
P4 Pellet
Dimensions Component Unit 8 / 15 20 / 25 32 / 38 48 / 60
L Length, boiler 1) 740 740 820
L1 Total length inc. induced draught fan
mm
930 930 1110 900
B Width, boiler 600 770 860
B* Width, boiler, inc. support for
positioning unit
2)
700 870 960
1100
B1 Total width, inc. suction cyclone
mm
1185 1355 1445 1030
H Height, boiler
3)
1280 1280 1430 1275
H1 Total height, inc. suction cyclone 1660 1660 1900 1790 H2 Height, flue pipe connection 1350 1350 1530 1585 H3 Height, outfeed connection 460 460 460 1900 H4 Height, return connection 940 955 1085 1685 H5 Height, drainage connection 460 460 460 515 H6 Height, ventilation connection 1030 1030 1155 1240 H8 Height, induced draught fan
connection
1090 1090 1215 515
H15 Height, suction system connection
mm
1485 1485 1720 1310
Flue pipe diameter mm 130 130 150 1375
1) Corresponds to the minimum positioning length
2) Corresponds to the minimum positioning width after removing the stoker assembly, suction cyclone and positioning unit
3) Corresponds to the minimum positioning height after removing the stoker assembly, suction cyclone and positioning unit
Technology
Technical specifications
Page 14
M0930408_en I
2
2.3 Technical specifications
2.3.1 P4 Pellet 8/15/20/25
P4 Pellet
Component Unit 8 15 20 25
Rated heat output 10,5 14,9 20,0 25,0
Heating efficiency range
kW
3,1-10,5 3,1-14,9 6,0-20,0 7,5-25,0
Mains connection 230V / 50Hz fused 16A
Output W 96 123 110 110
Weight of boiler kg 350 350 430 430
Boiler capacity (water) L 70 70 80 80
Upstream resistance (ΔT=20°C) mbar 4,3 6,1 4,5 2,9
Minimum return feed temperature Not applicable because of internal return feed lift
Maximum boiler temperature setting 80 80 80 80
Minimum boiler temperature setting
°C
40 40 40 40
Permitted operating pressure bar 3 3 3 3
Boiler class 3 3 3 3
Permitted fuel Wood pellets Ø 6mm as per ÖNORM M 7135 / DIN
51731
Test report data
Testing institute TÜV-Austria1)
2) 3)
2) 4)
Test report no. 06-UWC
Wels-EX-
295/2
06-UWC
Wels-EX-
295/1
Test data at rated load
Carbon monoxide (CO) [mg/MJ] 24 39 35 30
Nitrogen oxide (NOx) [mg/MJ] 74 74 76 78
Organic hydrocarbons [mg/MJ] < 1,0 0,6 0,7 0,9
Dust [mg/MJ] 14 12 11 11
Kesselwirkungsgrad [%] 91,6 90,9 91,9 92,9
Prüfdaten bei Teillast
Carbon monoxide (CO) [mg/MJ] 77 77 72 66
Nitrogen oxide (NOx) [mg/MJ] 69 69 71 73
Organic hydrocarbons [mg/MJ] 1,4 1,4 1,3 1,1
Dust [mg/MJ] 11 11 11 10
Boiler efficiency rating [%] 92,0 92,0 93,3 94,5
1) TÜV Austria, Environment and Chemistry Division, Am Thalbach 15, A-4600 Thalheim/Wels
2) In accordance with ÖNORM / DIN EN 303-5, chapter 5.1.3 type test: for a boiler from a range with a consistent structure it is sufficient, if the ratio of rated heat output from the largest to the smallest boiler 2 : 1, to carry out the tests with the smallest and the largest boilers. The boiler manufacturer must ensure that all boilers, including those that have not been tested in a range, whose values have been determined depending on rated heat output by interpolation, fulfil the requirements of the norm.
3) Values of the type P4 Pellet 20 are interpolated between the test protocol 06-UWC/Wels-EX-295/1 and K44302/2.
5) Values of the type P4 Pellet 25 are interpolated between the test protocol 06-UWC/Wels-EX-295/1 and K44302/2.
Technology
Components, Connections, and Dimensions
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 15 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
2
2.3.2 P4 Pellet 32/38/48/60
P4 Pellet
Component Unit 32 38 48 60
Rated heat output 32,0 38,0 48,0 58,5
Heating efficiency range
kW
8,9-32,0 8,9-38,0 14,4-48 17,3-58,5
Mains connection 230V / 50Hz fused 16A
Output W 110 110 120 120
Weight of boiler kg 530 530 760 760
Boiler capacity (water) l 125 125 170 170
Upstream resistance (ΔT=20°C) mbar 1,5 2,1 3,6 5,3
Minimum return feed temperature Not applicable because of internal return feed lift
Maximum boiler temperature setting 80 80 80 80
Minimum boiler temperature setting
°C
40 40 40 40
Permitted operating pressure bar 3 3 3 3
Boiler class 3 3 3 3
Permitted fuel Wood pellets Ø 6mm as per ÖNORM M 7135 / DIN
51731
Test report data
Testing institute TÜV SÜD SZA1)
3) 4)
TÜV2)
Test report no. K44302/6 K44302/4 - 08-UWC/
Wels-EX-
337
Test data at rated load
Carbon monoxide (CO) [mg/MJ] 31 45 25 5
Nitrogen oxide (NOx) [mg/MJ] 79 77 77 77
Organic hydrocarbons [mg/MJ] 1,0 1,0 1,5 < 2
Dust [mg/MJ] 10 9 10 11
Boiler efficiency rating [%] 93,5 92,6 92,4 92,1
Prüfdaten bei Teillast
Carbon monoxide (CO) [mg/MJ] 61 61 36 10
Nitrogen oxide (NOx) [mg/MJ] 75 75 71 66
Organic hydrocarbons [mg/MJ] 1,0 1,0 1,5 < 2
Dust [mg/MJ] 10 10 10 10
Boiler efficiency rating [%] 95,7 95,7 94,0 92,3
1) TÜV Austria, Environment and Chemistry Division, Am Thalbach 15, A-4600 Thalheim/Wels
2) In accordance with ÖNORM / DIN EN 303-5, chapter 5.1.3 type test: for a boiler from a range with a consistent structure it is sufficient, if the ratio of rated heat output from the largest to the smallest boiler 2 : 1, to carry out the tests with the smallest and the largest boilers. The boiler manufacturer must ensure that all boilers, including those that have not been tested in a range, whose values have been determined depending on rated heat output by interpolation, fulfil the requirements of the norm.
3) Values of the type P4 Pellet 20 are interpolated between the test protocol 06-UWC/Wels-EX-295/1 and K44302/2.
5) Values of the type P4 Pellet 25 are interpolated between the test protocol 06-UWC/Wels-EX-295/1 and K44302/2.
Installation
Transport and Assembly
Page 16
M0930408_en I
3
3 Assembly
3.1 Transport
The boiler is delivered packed in cardboard and on a pallet.
Move the boiler without jarring or jolting Observe the transport information on the
packaging.
Consider centre of mass!
The boiler is marked with a sticker on the opposite of the side to lift
3.1.1 Positioning
U Position a fork-lift or similar lifting device at the pallet and position
the boiler
If it is not possible to position the boiler on the pallet:
U Remove cardboard packaging U Take the unit from the pallet, and if necessary also dismantle the
suction unit assembly
À See 3.2.1 Remove boiler from pallet
3.1.2 Temporary storage
If the system is to be installed at a later time:
U Store the boiler, insulation and control unit in a safe, dust-free, and
dry location Moisture and frost reduce the effectiveness of insulation and can
destroy electronic components.
Installation
Transport and Assembly
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 17 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
3
3.2 Setting up in the boiler room
3.2.1 Remove boiler from pallet
At the front of the boiler:
U Open insulation door U Pull out floor insulation U Remove protective transport materials on the left and right in the
recess
TIP: For transport in the boiler room remove the insulating door.
U Pull out the lock bolt of the door hinge (1) and remove it from the
guide
U Remove the insulating door
At the back of the boiler:
U Remove protective transport materials on the left and right in the
recess
3.2.2 Transporting in the boiler room
U Position a fork-lift or similar lifting device at the base frame of the
boiler and transport it to the designated position
If no lifting device of this type is available:
U After removing the suction unit thread a carrying belt through the
lateral openings (1) of the base frame and lift the boiler
U Position transport rollers or similar with appropriate load-bearing
capacity under the base frame and move to the designated position
U Set up boiler at intended location
Observe the minimum distances in the boiler room.
1
1
Installation
Transport and Assembly
Page 18
M0930408_en I
3
3.2.3 Minimum distances in the boiler room
P4 Pellet
Dimensions Component Unit 8/15 20/25 32/38 48/60
A Minimum distance
between suction cyclone and wall
300 300 300 300
B Maintenance
range for ID fan
300 300 300 300
C Space for
insulated door
550 720 830 490
D Minimum distance
from side of boiler to wall
mm
200 200 200 200
Installation
Assembling the Pellet Boiler
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 19 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
3
3.3 Assembling the Pellet Boiler
3.3.1 Removing the suction cyclone
U Remove sound insulation cover U Open the clamps on the suction unit container and lift the cover
´ The induced draught unit set is in the suction unit container
3.3.2 Fitting the induced draught fan
U Remove pre-installed cover plate U Unscrew pre-installed nuts and
spacer washers
U Attach and fix the ID fan as
illustrated
The straight edge must be up.
U Join both cables of the ID fan with the pre-installed cables U Push the cable behind the cladding and put back the cover plate.
Installation
Install delivery system
Page 20
M0930408_en I
3
3.4 Install delivery system
3.4.1 Universal suction system
A 25 m Suction hose G Manual re-arranging unit (Variant 2) B Hose clamps 50-65 mm H 2 Blind plates (Variant 2) C 2 Fire protection choke collar
(only in Austria)
I 6 Star-shaped handle (Variant 2)
D Komfort pellet box (Variant 1) J Cover plate for wall E Support for fire protection choke collar (Variant 1) K Suction probe F Installation module for wall
280
250
50
Before installation:
U Prepare hole in wall for pellet box (width: 28cm,
height: 25cm) Maintain a distance of at least 5 cm from the
finished floor.
F
G
I
A
C
A
B
E
D
J
B
A
B
K
Variant 2 - Eco pellet box
Variant 1 - Komfort pellet box
G
H
280
Dimensions in mm
50
250
Installation
Install delivery system
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 21 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
3
Variant 1 - Comfort pellet box
U Position Comfort pellet box (D) at hole in the
wall
For maintenance purposes, the distance to the
wall on the board side of the pellet box should be at least 10 cm.
U Fix Pellet box to the wall with 4 frame screws
M8x50 and 10 mm dowels
U Pack the space in the hole in the wall with a non-
flammable material The partition must be insulated to conform
with ÖNORM B 3836 or DIN 4102-11!
U Put the cover plate for the wall (J) onto the pipe
of the pellet box
U Secure the cover plate to the wall using four
M8x50 frame screws and 10 mm dowels
U Mount the bracket (E) for fire protection choke
collars on the pellet box Fire protection choke collars only in Austria.
D
J
E
10 cm
Installation
Install delivery system
Page 22
M0930408_en I
3
Variant 2 - Eco pellet box
U Place the wall installation module (F) by the hole
in the wall
U Secure the insertion module to the wall using
four M8x50 frame screws and 10 mm dowels
U Pack the space in the hole in the wall with a non-
flammable material The partition must be insulated to conform
with ÖNORM B 3836 or DIN 4102-11!
U Place the wall cover plate (J) on the installation
module pipes
U Secure the cover plate to the wall using four
M8x50 frame screws and 10 mm dowels
U Fit 2 cover plates (H) to the installation module
using two star-shaped screws (I)
U Fit change unit (G) with 2 star-shaped screws
The position of the change unit is not
specified!
F
J
G
I
H
Installation
Install delivery system
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 23 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
3
Installing the suction probes and lines
U Position the suction probes (K) at equal distances
in the pellet supply bin
U Secure the suction probes to the bottom using
frame screws
U Fix hose lines (A)to the suction probe using hose
clips (B)
U Lay the hose lines to the pellet box and secure
them using hose clips
WARNING! Read the label on the suction
probe or pellet box about the suction line and return-air line! Ensure correct connection!
WARNING! When connecting the hose lines,
beware of potential equalisation!
À Page 11, Potential equalisation
U Thread the fire protection choke collar (C) on to
the hose line (A)
Fire protection choke collars only in Austria.
U Attach the hose lines to the pellet box pipes
using hose clips (B)
U Lay the hose lines to the boiler, through
identified openings at the back plate and install with hose clamps to the identified connections
WARNING! Read the label on the suction
probe or pellet box about the suction line and return-air line! Ensure correct connection!
Suction line: hose line to left connection (1)
on the back of the boiler
Return-air line: hose line to right connection
(2) on the back of the boiler
WARNING! When connecting the hose lines,
beware of potential equalisation!
À Page 11, Potential equalisation
1
2
K
B
A
A
B
B
C
A
B
C
A
Installation
Install delivery system
Page 24
M0930408_en I
3
3.4.2 Suction screw system
A Flange bearing H Gearbox flange B Ejector flange I Drive flange seal C Trough mount with rubber pad J Geared motor D Bearing flange K 2 Cover plates for wall penetration E Open trough L Main worm F Suction intake with integrated support M Shaft end for main worm G Proximity switch N Worm extension (if needed)
Before installation:
U Prepare hole in wall for suction intake (width:
40cm, height: 22cm) Ensure that the channel in the hole in the wall
is positioned off centre.
A
B
C
D
E
F
M
L
K
H
I
J
N
G
Installation
Install delivery system
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 25 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
3
U Thread the main screw (H1) into the hole
The keyway must point towards the boiler!
U Thread the closed trough (J) on to the main
worm on the storage area side The rectangular flange points away from
the storage area!
U Thread the open trough (I) on to the main
worm
U Screw them together using four M10x30
hexagon bolts and nuts
Depending on the length of the delivery unit, a screw extension may be necessary:
U Place the screw extension (N) on the main
screw (L) and secure it using clamping pins
The screw blade must always be rising.
If no additional screw is used:
U Put the main screw's shaft end (M) on the
main screw's shaft (L) and secure it using clamping pins
U Secure the gearing flange (I) and the gearing
flange seal (H) to the suction piece using four M10 x 40 mm bolts and nuts
- 17 mm socket spanner
U Lubricate the screw's shaft end U Fit the drive motor (J)
Take care when inserting the keyway into
the shaft's groove!
U Attach the geared motor on the gearing flange
(l) using four M8 x 16 mm hexagonal screws and spacer washers - 13 mm hexagonal nut
U Fit the proximity switch (G) to the inspection
cover of the suction intake The proximity switch should project
approx. 1cm into the suction intake!
Adjusting the sensitivity during the initial
start-up
À Page 33, 4.2 Setting “Max Level” sensor
H1
I
J
G
N
M
H
I
J
G
G
L
L
Installation
Install delivery system
Page 26
M0930408_en I
3
U Secure the bearing flange (D) and the trough
mount (C) to the trough using four M10 x 40 mm bolts and nuts
U - 17 mm hexagonal nut U Place the flange bearing unit (A) and the ejecting
flange (B) on the shaft and secure them to the bearing flange using two M14 x 35 mm hexagonal screws and spacer washers
U - 21 mm socket spanner
Do not lubricate! The flange bearing is
permanently lubricated and is maintenance free!
U Arrange the trough parallel to the storage area
wall
U Secure the trough mount and suction piece to the
floor using two 10 mm dowels and 8 x 70 mm frame screws
U Pack the space in the hole in the wall with a non-
flammable material The partition must be insulated to conform
with ÖNORM B 3836 or DIN 4102-11!
U Secure the wall penetration cover plates (K) to
the store room external wall using three
U 10 mm dowels and 8 x 50 mm frame screws U Finally, the sloping floor is installed
The plates of the sloping floor must not be
placed on the trough!
À Page 30, Sloping floor
U Lay both hose lines in the boiler room to the
suction intake
On the left and right of the suction intake:
U Secure the suction hose (B) to the suction
connecting piece using a hose clamp (D) No side specified for connecting the suction or
return-air line!
U Put the supplied fire protection choke collar (1)
on the hose and secure it to the suction piece using two self-tapping screws
Fire protection choke collars only in Austria.
D
C
B
A
K
B
1
D
Installation
Install delivery system
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 27 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
3
U Lay the hose lines to the boiler, through
identified openings at the back plate and install with hose clamps to the identified connections
Suction line: hose line to left connection (1)
on the back of the boiler
Return-air line: hose line to right connection
(2) on the back of the boiler
WARNING! When connecting the hose lines,
beware of potential equalisation!
À Page 11, Potential equalisation
3.4.3 Bag silo system
U Fit frame with sack silo
À See assembly instructions “Pellet
sack silo Type I - V”
Observe the height of the boiler room
during planning.
Type I, II Type III - V
H Bag silo frame height [cm] 185 190 H1 Height including filler coupling [cm] 205 210 H2 Required minimum room height1) [cm]
Ideal store room height 2) [cm]
215 230
220 230
1) Minimum room height for connection to filler pipe in installation room.
2) When full, the bag silo has a heap shape. Optimum height is for use of the whole capacity.
1
2
Installation
Install delivery system
Page 28
M0930408_en I
3
U Mount bag silo as it is described in the delivered
assembly instructions
U Thread flange ring (1) onto bag silo U Fit bag silo and flange ring onto the bolts on the
suction probe and screw it together.
U Thread one fire protection choke collar each (B)
on to the suction and return-air lines Fire protection choke collars only in
Austria.
U Run hose lines through the openings in the wall
into the pellet store
U Secure the hose lines to the silo suction probe
using hose clamps (D)
Read the label on the silo suction probe! Suction line: hose line to the cover of the
suction cyclone
Return-air line: hose line to the suction motor
U Lay the hose lines to the boiler, through
identified openings at the back plate and install with hose clamps to the identified connections
WARNING! Observe the label for the suction
line and the return-air line on the silo suction probe and boiler. Ensure correct connection!
Suction line: hose line to left connection (1)
on the back of the boiler
Return-air line: hose line to right connection
(2) on the back of the boiler
WARNING! When connecting the hose lines,
beware of potential equalisation!
À Page 11, Potential equalisation
B
D
1 2
1
Installation
Install delivery system
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 29 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
3
3.4.4 Pellet storage area
For the universal suction system, the pellet store must be built with an inclined floor!
The following picture shows the most important components:
A 2 Filler pipes B Earth wire C Planking on the storage area door
D Sloping floor
E Impact cushion F Under-floor structure for sloping floor
Size of storage area
The storage area should be able to hold approximately 1.5 times the annual requirement. The exact amount of required space depends on the system's heating load.
Rule of thumb formula: 1m³ store / kW heating burden
A
B C D
E
F
Installation
Install delivery system
Page 30
M0930408_en I
3
Sloping floor
Fig.1: Store for a delivery unit with a suction probe Fig.2: Store for a delivery unit with a screw
The under-floor structure should be dimensioned so that the sloping floor is not deformed when subjected to static load. You should ensure that the pellets can slide down smoothly. This means the sloped floor should be at an angle of at least 45° and have a smooth surface (we recommend laminate).
When planning the under-floor structure, note:
1 m³ of pellets weighs approximately 650 kg. Ideally the suction probes should already be fitted before the sloped
floor is constructed.
A distance of 20 cm should be maintained between the cross-pieces
and the suction probe should be centrally positioned. (see Fig. 1)
The weight of the pellets must not be borne by the trough!
(see Fig. 2)
Impact cushion
The impact cushion is made of rubber and should be positioned opposite the filler pipes at least 20 cm from the wall. It prevents pellets from striking the wall and knocking off pieces of the finish when filling.
Pieces of the finish, screws, and other foreign objects can clog the
suction probe!
WARNING! Damage caused by foreign objects is not covered by the
guarantee!
NOTE
In time pellets leave dust on the ground; this can impair the process of moving them from the storage area.
Check the storage area before re-filling and clean if necessary Regular complete emptying and cleaning of the storage area ensures
consistent readiness for operation!
Installation
Connect pellet boiler
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 31 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
3
3.5 Electrical Connection
RISK
Working on electrical components.
Danger: Serious injuries from electric shocks.
U Work on electrical components should only be carried out by authorised
technicians
Flexible sheath conductors should be used for the wiring which
should be measured in compliance with the applicable regional standards and guidelines
The supply line (mains connection) must be fitted with a max. 16 A
fuse by the customer.
U Remove the insulating cover
U 2 Unscrew the self-tapping
screws behind the control
U Open the insulating door and
remove the centrally positioned fixing screw from below.
U Remove the front insulation
cover
U Wire the connections according
to the schematic diagram:
À For circuit diagram see operating
instructions “Lambdatronic P 3200”
Installation
Connect pellet boiler
Page 32
M0930408_en I
3
3.5.1 Connecting the Comfort pellet box
The connection of the Comfort pellet box to the pellet module board is established using a flexible cable (5x0.75mm², e.g. YMM as per ÖVE­K41-5 or H05VV-F as per DIN VDE 0281-5). This is a 24V control line.
The previous figure shows the plugged-in 5-pin connecting plug of the Comfort pellet box and the accompanying connection layout of the Lambdatronic P3200 control system.
To check the plug arrangement:
U Detach the protective plate (1)
from the board
U Carry out a check using the board
description
The servomotors (2) of the pellet
box must be switched to the “R” position!
The servomotors are ready to plug in and are connected to the board. All necessary plug clips are included with the pellet box in delivery
1
2
Core module of the Lambdatronic P3200
Primary ai
r
Secondary ai
r
Initial startup
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 33 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
4
4 Initial startup
4.1 Configuring the boiler
The boiler must be configured to the heating system on initial start-up.
NOTE
Optimum efficiency and consequently efficient operation with low
emissions can only be guaranteed if the system is adjusted by qualified technicians and the specified factory settings are observed.
Take the following precautions:
U It is recommended that the system is put into operation by the Fröling
customer service or an authorised installer.
Before you start heating with the boiler for the first time:
U Adjust the control to the system type
The keypad layout and necessary control steps for modifying the parameters can be found in the accompanying operating instructions for the “Lambdatronic P 3200”.
4.2 Setting “Max Level” sensor
In delivery configuration, the factory settings of the sensor are secured with a seal. Changes to the settings should only be carried out by qualified technicians.
The monitoring LED (1) should only light up when identifying
materials!
U If the monitoring LED stays on permanently, the sensitivity is set too
high!
´ Reduce the sensitivity by turning the adjusting screw (2) to the
left
U If the monitoring LED does not react when pellets are being fed in,
the sensitivity is set too low!
´ Increase the sensitivity of the adjusting screw by turning to the
right
1
2
Appendix
Delivery Certificate
Page 34
M0930408_en I
5
5 Appendix
5.1 Delivery Certificate
Customer no.:
Customer address: Installer:
Telephone number:
U
P4 Pellet 8 U P4 Pellet 32
U
P4 Pellet 15 U P4 Pellet 38
U
P4 Pellet 20 U P4 Pellet 48
P4 Pellet:
U
P4 Pellet 25 U P4 Pellet 60
Serial number
U
Bag silo system
U
Universal suction system Uno pellet box
U
Universal suction system Eco pellet box
U
Universal suction system Comfort pellet box
U
Underground feeder tank system
Delivery system:
U
U System operation discussed U
System maintenance discussed
U Operating principle and self-checking of
safety devices discussed.
U
All technical documentation handed over (documentation, certificate of conformity, ...)
U Test heating performed U
Commissioning report given to customer
U Rating plate attached U
Telephone number for manufacturer’s service department indicated
U No defects found U
Notice: All national and regional regulations relating to initial testing and subsequent testing of the system
must be observed. Please be advised that, in Austria, commercial systems with a rated heat output 50 kW must be regularly tested at yearly intervals in accordance with the Heating Plant Regulations (FeuerungsanlagenVO).
Date Customer Installer
Finally, we ask that you have the customer sign a copy of this confirmation and send it to FRÖLING Ges.m.b.H. . Fax: +43 (0)7248 606 600
Appendix
Notes
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 35 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930408_en
5
5.2 Notes
Loading...