Froling P4 Pellet 80, P4 Pellet 100, P4 Pellet 105 Assembly Instructions Manual

Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen
Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
Assembly Instructions
P4 Pellet 8 - 105
English version of the assembly instructions for technicians. Read and follow the instructions and safety instructions! Subject to technical change.
Introduction
Page 2
M0930811 v
I
Dear customer,
The FROLING P4 Pellet is a state-of-the-art design that conforms to all currently applicable standards and testing guidelines.
Please read and follow the assembly instructions. They contain safety instructions and comprehensive information relating to transporting, setting up and assembling the boiler.
The constant further development of our products means that there may be minor differences from the pictures and content. If you discover any errors, please let us know.
Subject to technical change.
Delivery certificate
Keeping a record that the delivery was received correctly and collecting customer-specific data relating to the system allows us to respond quickly should problems arise.
We would therefore ask you to confirm that you have received the product in good condition.
Please send Froling a copy of the delivery certificate, filled in and signed by the customer.
Guarantee conditions
Our sale and delivery conditions generally apply. These conditions have been made available to customers, and customers have been made aware of them at the time of order completion.
You can also find the guarantee conditions on the enclosed guarantee certificate.
Address of manufacturer
FRÖLING Heizkessel- und Behälterbau GesmbH
Industriestraße 12 A-4710 Grieskirchen AUSTRIA
TEL +43 (0)7248 606 0 FAX +43 (0)7248 606 600 E-MAIL info@froeling.com WEBSITE www.froeling.com
Contents
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 3 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
C
1 General Information 5
1.1 Standards 5
1.2 Qualification of assembly staff 5
1.3 Protective equipment for assembly staff 6
1.4 Design information 6
1.4.1 Installation and approval of the heating system ....................................................6
1.4.2 Information on the installation room (boiler room) ................................................6
Boiler room characteristics ................................................................................6
Ventilation of the boiler room.............................................................................7
1.4.3 Heating water requirements ...............................................................................7
1.4.4 Combination with storage tank ...........................................................................7
1.4.5 Chimney connection/chimney system ..................................................................8
Draught limiter................................................................................................8
Boiler data relating to design of the flue gas system P4 Pellet 8/15/20/25/32/38 ......8
Boiler data relating to design of the flue gas system P4 Pellet 48/60/80/100/105......9
1.4.6 Room air-independent operation .........................................................................9
Minimum specification of connection lines.......................................................... 10
1.4.7 Notes on boiler ventilation ...............................................................................10
2 Technology 11
2.1 Components and Connections 11
2.2 Dimensions 12
2.2.1 Supply air connections for room air-independent operation ................................... 13
2.2.2 Flue gas pipe position...................................................................................... 13
2.3 Technical specifications 14
2.3.1 P4 Pellet 8/15/20/25....................................................................................... 14
2.3.2 P4 Pellet 32/38/48/60 ..................................................................................... 15
2.3.3 P4 Pellet 80/100/105 ......................................................................................16
2.3.4 Airborne sound level ....................................................................................... 17
3 Assembly 18
3.1 Transportation 18
3.1.1 Positioning..................................................................................................... 18
3.1.2 Temporary storage .........................................................................................18
3.2 Set-up in the boiler room 19
3.2.1 Removing the boiler from the pallet................................................................... 19
3.2.2 Moving the boiler in the boiler room .................................................................. 20
3.2.3 Minimum distances in the boiler room................................................................ 20
3.3 Dismantling for location where positioning is difficult 21
3.3.1 Dismantling the stoker assembly and insulation ..................................................21
3.3.2 Remove the door and ash drawer (P4 Pellet 8/15/20/25)...................................... 23
3.3.3 Dismantling the suction cyclone cover................................................................ 24
3.3.4 Dismantling the stoker unit .............................................................................. 25
3.3.5 Positioning dimensions after dismantling ............................................................ 28
3.3.6 Notes on reassembly....................................................................................... 29
Contents
Page 4
M0930811 v
C
3.4 Assembling the Pellet Boiler 30
3.4.1 Installing the induced draught fan..................................................................... 30
3.4.2 Fit the ash container and doors (P4 Pellet 32/38/48/60/80/100/105) ..................... 31
3.5 Installing the discharge system 32
3.5.1 General installation information ........................................................................ 32
3.5.2 Hose Lines..................................................................................................... 32
Potential Equalisation..................................................................................... 33
3.5.3 Universal suction system ................................................................................. 34
Variant 1 – Komfort pellet box......................................................................... 35
Variant 2 – Eco pellet box ............................................................................... 36
Installing the suction probes and lines .............................................................. 37
3.5.4 Suction screw system...................................................................................... 38
3.5.5 Bag silo discharge system................................................................................ 41
3.5.6 Pellet storage area.......................................................................................... 43
Size of store ................................................................................................. 43
Sloping floor ................................................................................................. 44
Impact cushion.............................................................................................. 44
3.6 Electrical Connection 45
3.6.1 Connecting the Komfort pellet box .................................................................... 46
4 Initial Start-up 47
4.1 Configuring the Boiler 47
4.2 Setting the “Max level and min level” sensor 47
General
Standards, personnel, design
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 5 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
1
1 General Information
1.1 Standards
The installation and commissioning of the boiler must be carried out in accordance with local fire and building regulations.
The following standards and regulations should be observed in any case:
ÖNORM/DIN EN 303-5 Boilers for solid fuels, manually and automatically fed combustion systems;
rated heat output up to 300 kW;
ÖNORM M 7510-1 Guidelines for checking heating systems
Part 1: General requirements and one-off inspection
ÖNORM M 7510-4 Guidelines for checking heating systems
Part 4: Simple check for heating plants for solid fuels
EN 12828 Heating systems in buildings - design of water-based heating systems
EN 13384-1 Chimneys serving one appliance
TRVB H 118 Technical directives for fire protection/prevention (Austria only)
ÖNORM H 5170 Construction and fire protection requirements
ÖNORM M 7135 Compressed untreated wood or bark – pellets and briquettes – Requirements
and test
DIN 51731 Testing solid fuels – compressed untreated wood – Requirements and testing
ÖNORM H 5195-1 Prevention of damage by corrosion and scale formation in closed warm-water-
heating systems at operating temperatures up to 100 °C (Austria only).
VDI 2035 Prevention of damage in water heating installations - Scale formation in
domestic hot water supply installations and water heating installations (Germany only)
SWKI 97-1 Lime scale and corrosion protection in heating systems (Switzerland only)
1.BImSchV First Ordinance on Implementation of the Federal Emissions Control Act
1.2 Qualification of assembly staff
CAUTION
Assembly and installation by untrained personnel:
Risk of injury and damage to equipment!
The instructions and information provided in the instructions should be observed!
Only allow trained staff to carry out assembly and installation!
Assembly, installation, initial startup and servicing must only be carried out by qualified people:
- Heating technicians / building technicians
- Electrical installation technicians
- Froling customer services The assembly staff must have read and understood the instructions in
the documentation.
General
Standards, personnel, design
Page 6
M0930811 v
1
1.3 Protective equipment for assembly staff
You must ensure that staff have the protective equipment specified by accident prevention regulations.
y During transportation, set-up and assembly of the boiler:
- Work clothing
- Safety shoes
- Protective gloves
1.4 Design information
It is forbidden to carry out modifications to the boiler or to change or deactivate safety equipment.
Always comply with all fire, building, and electrical regulations when installing or operating the boiler system, and follow the operating instructions and mandatory regulations that apply in the country in which the boiler is operated.
1.4.1 Installation and approval of the heating system
The boiler should be operated in a closed heating system. The following standards govern the installation:
Applicable standard:
ÖNORM / DIN EN 12828 Heating systems in buildings
Each heating system must be officially approved.
The appropriate supervisory authority (inspection agency) must always be informed when installing or modifying a heating system, and authorisation must be obtained from the building authorities:
- Austria: Report to the construction authorities of the community or magistrate
- Germany: Report new installations to an approved chimney sweeper / the building authorities.
1.4.2 Information on the installation room (boiler room)
Boiler room characteristics
There must not be a potentially explosive atmosphere in the boiler
room as the boiler is not suitable for use in potentially explosive environments.
The boiler room must be frost-free. The boiler does not provide any light, so the customer must provide
sufficient lighting in the boiler room in accordance with national workplace design regulations.
When using the boiler above 2000 metres above sea level you should
consult the manufacturer.
§
General
Standards, personnel, design
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 7 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
1
Ventilation of the boiler room
Ventilation air for the boiler room should be taken from and expelled directly outside, and the openings and air ducts should be designed to prevent weather conditions (foliage, snowdrifts, ...) from having any effect on the air flow.
Unless otherwise specified in the applicable building regulations for the boiler room, the following standards apply for the design and dimensions of the air ducts:
Applicable standards:
- TRVB H 118
- ÖNORM H 5170
- UNI 10683
1.4.3 Heating water requirements
There are no special requirements for the filling water of the heating system. The following standards and guidelines apply:
Applicable standards and guidelines:
Austria: ÖNORM H 5195-1 Germany: VDI 2035 Switzerland: SWKI 97-1 Italy: D.P.R. no. 412
Notice on filling with make-up water:
Always bleed the filling hose before connecting, in order to prevent air from entering the system.
1.4.4 Combination with storage tank
NOTICE
It is not generally necessary to use a storage tank for the system to run smoothly. However we recommend that you use it with a storage tank, as this allows you to achieve continuous reduction within the ideal performance range of the boiler.
For the correct dimensions of the storage tank and the line insulation (in accordance with ÖNORM M 7510 or guideline UZ37) please consult your installer or Froling.
§
§
General
Standards, personnel, design
Page 8
M0930811 v
1
1.4.5 Chimney connection/chimney system
EN 303-5 specifies that the entire flue gas system must be designed to prevent, wherever possible, damage caused by seepage, insufficient feed pressure and condensation. It should be noted here that flue gas temperatures of less than 160 K above room temperature can occur within the permitted operating range of the boiler.
The flue gas temperatures (for clean systems) and additional flue gas values can be found in the technical specification sheets.
À See “Boiler data relating to design of the flue gas system”
Connect to the chimney via the shortest path, preferably with a vertical gradient of less than 30–45°. Insulate the connecting piece. The entire flue gas system (chimney and connection) must be calculated as per ÖNORM/DIN EN 13384-1 or prior standards ÖNORM M 7515/DIN 4705-1.
Local regulations and other statutory regulations also apply. The chimney must be approved by a smoke trap sweeper or chimney
sweep!
As per TRVB H 118 (only in Austria) an explosion flap must be
installed in the flue pipe or in the chimney.
Draught limiter
Recommended: Installing a draught limiter 1 Install the draught limiter directly under the mouth of the flue line,
as the pressure is lower at this location.
Boiler data relating to design of the flue gas system P4 Pellet 8/15/20/25/32/38
P4 Pellet
Description Units 8 15 20 25 32 38
Flue gas temperature RL °C 140 150 150 150 160 160
Flue gas mass flow RL PL
kg/h
25 11
36 15
52 20
65 25
78 32
92 41
Flue gas mass flow RL PL
kg/s
0.007
0.003
0.010
0.004
0.014
0.006
0.018
0.007
0.022
0.009
0.025
0.011
Necessary RL Feed pressure PL
Pa
8 6
8 6
8 6
8 6
8 6
8 6
Necessary RL Feed pressure PL
mbar
0.08
0.06
0.08
0.06
0.08
0.06
0.08
0.06
0.08
0.06
0.08
0.06
Flue pipe diameter mm 130 130 130 130 150 150
RL = Rated Load, PL = Partial Load
1
General
Standards, personnel, design
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 9 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
1
Boiler data relating to design of the flue gas system P4 Pellet 48/60/80/100/105
P4 Pellet
Description Units 48 60 80 100 105
Flue gas temperature RL °C 160 170 160 170 170
Flue gas mass flow RL PL
kg/h
140
60
155
70
215
75
275
95
285 100
Flue gas mass flow RL PL
kg/s
0,039 0,017
0,043 0,019
0,060 0,021
0,0760,02
6
0,079 0,028
Necessary RL Feed pressure PL
Pa
8 6
8 6
8 6
8 6
8 6
Necessary RL Feed pressure PL
mbar
0,08 0,06
0,08 0,06
0,08 0,06
0.08
0.06
0,08 0,06
Flue pipe diameter mm 150 150 200 200 200
RL = Rated Load, PL = Partial Load
1.4.6 Room air-independent operation
The P4 Pellet boiler has a central air connection on the back of the boiler. If appropriate supply air and flue gas connections are installed, the boiler can be operated independently of room air as a type C
42
or
type C
82
in the sense of EN 15035.
Definition of type C
4
as per EN 15035:
Boiler that is connected via its combustion air supply and flue gas outlet, with a connecting piece that may be supplied, to a shared chimney with a shaft for combustion air supply and a shaft for flue gas outlet. The mouths of the air and flue gas chimney are either concentric or so close to each other that similar wind conditions apply.
Air is supplied by an air and flue gas system.
Definition of type C
8
as per EN 15035:
A boiler that is connected via its combustion air supply and flue gas outlet, with a connecting piece, to a wind protection device and a single or shared chimney.
Air supply via an air supply line that is independent from the
chimney system.
This design requires a wind protection device. If a protective grating
is fitted, you must ensure that the mesh size is sufficiently large to prevent a significant loss of pressure and/or seal from dirt.
The second index “2” (C
42
/ C82) indicates type C boilers with a blower
fan behind the combustion chamber or the heat exchanger.
General
Standards, personnel, design
Page 10
M0930811 v
1
When dimensioning pipe bends in the supply air line you should note that:
The ratio of the radius of curvature (r) to pipe diameter (d) should be greater than 1:
r:d 1
For example P4 Pellet 8/15:
- Diameter of supply air connection = 80 mm
- Minimum radius of pipe bends = 80 mm
Install the supply air line in as straight a line as possible and over the
shortest path. The number of pipe bends should be kept to a minimum (ideally a maximum of 4 bends).
Also: The resistance of the supply air line can be a maximum of 20 Pa.
You can find the necessary dimensions of the supply air connections in the boiler in the technical data sheets.
À See 2.2.1 Supply air connections for room air-independent operation
Minimum specification of connection lines
Connecting piece for the combustion air supply as per EN 1856-2:
EN 1856-2 - T080 - N2 - D
Connecting piece for the flue gas outlet as per EN 1856-2:
EN 1856-2 - T200 - P1 - W
TXXX ... Temperature class (specified in °C) N2 ... Pressure class with test pressure = 20 Pa P1 ... Pressure class with test pressure = 200 Pa D ... Condensation resistance not required (dry) W ... Condensation resistance required (damp)
1.4.7 Notes on boiler ventilation
The boiler system should be set up rising slightly towards the back left, so the ventilation connection is the highest point of the boiler.
Fitting a functioning, automatic ventilating valve ensures constant removal of air in the boiler.
This prevents malfunctions due to air in the boiler system.
Fit an automatic ventilating valve! Tip: Fit a vertical pipe before the automatic ventilating valve as a
calming section, to ensure it is positioned above the level of the boiler water.
A microbubble separator can also optionally be fitted in the lines to the boiler.
Technology
Components, connections, and dimensions
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 11 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
2
2 Technology
2.1 Components and Connections
Pos. Description Units 8 / 15 20 / 25 32 / 38 48/60 80/100/105
A Boiler flow connection 1 6/4 6/4 6/4 2 B Boiler return connection 1 6/4 6/4 6/4 2 C Drain 1/2 1/2 1/2 1/2 1
D Air vent
Inch
1/2 1/2 1/2 1 1
E Pellet suction line F Return-air line
DA 60 DA 60 DA 60 DA 60 DA 60
G Flue gas pipe connection
mm
130 130 150 150 200
1 Lambdatronic P 3200 control 2 Switch box 3 Induced draught fan 4 Safety temperature limiter - STL 5 Main switch 6 Service interface
3
C A G 1 2 4 B D E F 5 6
Technology
Components, connections, and dimensions
Page 12
M0930811 v
2
2.2 Dimensions
Dimension Description Units 8 / 15 20 / 25 32 / 38 48 / 60 80/100/105
L Length, boiler 740 740 L* Length, boiler 820 900 1000 L1 Total length inc. induced
draught fan
940 940
L1* Total length inc. induced
draught fan
mm
1020 1100 1070
B Width of boiler 600 770 860 1030 1235
B* Width, boiler, inc. support
for positioning unit
1)
705 875 965 1275 1480
W1 Total width, inc. suction
cyclone
mm
1185 1355 1445 1790 2085
H Height, boiler
2)
1280 1280 1430 1585 1710
H1 Total height, inc. suction
cyclone
1660 1660 1900 1900 1900
H2 Height, flue pipe connection 1350 1350 1530 1685 1785 H3 Height, flow connection 460 460 460 515 520 H4 Height, return connection 940 955 1085 1240 1360 H5 Height, drainage connection 460 460 460 515 520 H6 Height, ventilation
connection
1030 1030 1155 1310 1430
H8 Height, induced draught fan
connection
1090 1090 1215 1375 1495
H15 Height, suction system
connection
mm
1480 1480 1720 1720 1720
Flue pipe diameter mm 130 130 150 150 200
1) Corresponds to the minimum positioning width after removing the stoker assembly, suction cyclone and positioning unit.
2) Corresponds to the minimum positioning height after removing the stoker assembly, suction cyclone and positioning unit.
Technology
Technical specifications
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 13 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
2
2.2.1 Supply air connections for room air-independent operation
P4 Pellet 8 / 15
P4 Pellet 20 / 25 P4 Pellet 32 / 38
P4 Pellet 48 / 60
100 115 115 170
235
230
215
305
P4 Pellet 80 / 100
315
190
P4 Pellet
Description Units 8/15 20/25 32/38 48/60 80/100/105
Supply air connection pipe (external diameter) mm 80 100 125 160 200
2.2.2 Flue gas pipe position
P4 Pellet
Description Units 8/15 20/25 32/38 48/60 80/100/105
A – Lateral distance mm 420 585 650 815 1000
B – Depth distance mm 90 90 85 90 80
Technology
Technical specifications
Page 14
M0930811 v
2
2.3 Technical specifications
2.3.1 P4 Pellet 8/15/20/25
P4 Pellet
Description Units 8 15 20 25
Rated heat output 10,5 14,9 20,0 25,0
Heating efficiency range
kW
3.1-10.5 3.1-14.9 6.0-20.0 7.5-25.0
Mains connection 230V / 50Hz fused 16A
Output W 96 123 110 110
Boiler weight kg 350 350 430 430
Boiler capacity (water) L 70 70 80 80
Upstream resistance (ΔT=20°C) mbar 4.3 6.1 4.5 2.9
Min. boiler return temperature Not applicable due to internal return temperature control
Maximum boiler temperature setting 80 80 80 80
Minimum boiler temperature setting
°C
40 40 40 40
Permitted operating pressure bar 3 3 3 3
Boiler class 3 3 3 3
Permitted fuel Wood pellets Ø 6mm as per ÖNORM M 7135 / DIN 51731
Test report data
Testing institute TÜV Austria1)
2) 3)
2) 4)
Test report no. 06-UWC
Wels-EX-
295/2
06-UWC
Wels-EX-
295/1
Test data at rated load
Carbon monoxide (CO) [mg/MJ] 24 39 35 30
Nitrogen oxide (NOx) [mg/MJ] 74 74 76 78
Organic Hydrocarbons (OGC) [mg/MJ] < 1.0 0.6 0.7 0.9
Dust [mg/MJ] 14 12 11 11
Boiler efficiency rating [%] 91.6 90.9 91.9 92.9
Test data at partial load
Carbon monoxide (CO) [mg/MJ] 77 77 72 66
Nitrogen oxide (NOx) [mg/MJ] 69 69 71 73
Organic Hydrocarbons (OGC) [mg/MJ] 1.4 1.4 1.3 1.1
Dust [mg/MJ] 11 11 11 10
Boiler efficiency rating [%] 92.0 92.0 93.3 94.5
1) TÜV Austria, Environment and Chemistry Division, Am Thalbach 15, A-4600 Thalheim/Wels
2) In accordance with ÖNORM / DIN EN 303-5, chapter 5.1.3 type test: for a boiler from a range with a consistent structure it is sufficient, if the ratio of rated heat output from the largest to the smallest boiler 2 : 1, to carry out the tests with the smallest and the largest boilers. The boiler manufacturer must ensure that all boilers, including those that have not been tested in a range, whose values have been determined depending on rated heat output by interpolation, fulfil the requirements of the norm.
3) Values of the type P4 Pellet 20 are interpolated between the test protocol 06-UWC/Wels-EX-295/1 and K44302/2.
4) Values of the type P4 Pellet 25 are interpolated between the test protocol 06-UWC/Wels-EX-295/1 and K44302/2.
Technology
Technical specifications
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 15 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
2
2.3.2 P4 Pellet 32/38/48/60
P4 Pellet
Description Units 32 38 48 60
Rated heat output 32,0 38,0 48,0 58,5
Heating efficiency range
kW
8.9-32.0 8.9-38.0 14.4-48 17.3-58.5
Mains connection 230V / 50Hz fused 16A
Output W 110 110 120 120
Boiler weight kg 530 530 760 760
Boiler capacity (water) L 125 125 170 170
Upstream resistance (ΔT=20°C) mbar 1.5 2.1 3.6 5.3
Min. boiler return temperature Not applicable due to internal return temperature control
Maximum boiler temperature setting 80 80 80 80
Minimum boiler temperature setting
°C
40 40 40 40
Permitted operating pressure bar 3 3 3 3
Boiler class 3 3 3 3
Permitted fuel Wood pellets Ø 6mm as per ÖNORM M 7135 / DIN 51731
Test report data
Testing institute TÜV SÜD SZA1)
3) 4)
TÜV2)
Test report no. K44302/6 K44302/4 - 08-UWC/
Wels-EX-337
Test data at rated load
Carbon monoxide (CO) [mg/MJ] 31 45 25 5
Nitrogen oxide (NOx) [mg/MJ] 79 77 77 77
Organic Hydrocarbons (OGC) [mg/MJ] 1.0 1.0 1.5 < 2
Dust [mg/MJ] 10 9 10 11
Boiler efficiency rating [%] 93.5 92.6 92.4 92.1
Test data at partial load
Carbon monoxide (CO) [mg/MJ] 61 61 36 10
Nitrogen oxide (NOx) [mg/MJ] 75 75 71 66
Organic Hydrocarbons (OGC) [mg/MJ] 1.0 1.0 1.5 < 2
Dust [mg/MJ] 10 10 10 10
Boiler efficiency rating [%] 95.7 95.7 94.0 92.3
1) TÜV SÜD SZA Austria, Technische Prüf-GmbH, accredited initial and boiler inspection body in accordance with BGBl. no. 211/92 Arsenal, Object 207, A-1030 Wien
2) TÜV Austria, Environment and Chemistry Division, Am Thalbach 15, A-4600 Thalheim/Wels
3) In accordance with ÖNORM / DIN EN 303-5, chapter 5.1.3 type test: for a boiler from a range with a consistent structure it is sufficient, if the ratio of rated heat output from the largest to the smallest boiler 2 : 1, to carry out the tests with the smallest and the largest boilers. The boiler manufacturer must ensure that all boilers, including those that have not been tested in a range, whose values have been determined depending on rated heat output by interpolation, fulfil the requirements of the norm.
4) Values of the model, P4 Pellet 48, are interpolated between the test protocol K44302/4 and 08-UWC/Wels-EX-337.
Technology
Technical specifications
Page 16
M0930811 v
2
2.3.3 P4 Pellet 80/100/105
P4 Pellet
Description Units 80 100 105
Rated heat output 80,0 100,0 105,0
Heating efficiency range
kW
24,0-80,0 30-100,0 24,0-105,0
Mains connection 230V / 50Hz fused 16A
Output W 115 112 112
Boiler weight kg 1090 1100 1100
Boiler capacity (water) L 280 280 280
Upstream resistance (ΔT=20°C) mbar 4,3 4,3 4,3
Min. boiler return temperature Not applicable due to internal return temperature control
Maximum boiler temperature setting 80 80 80
Minimum boiler temperature setting
°C
40 40 40
Permitted operating pressure bar 3 3 3
Boiler class 3 3 3
Permitted fuel Wood pellets Ø 6mm as per ÖNORM M 7135 / DIN 51731
Test report data
Testing institute TÜV1)
Test report no. TÜV
2)3)
10-UW/Wels-
EX-242/1
Test data at rated load
Carbon monoxide (CO) [mg/MJ] 6 6 6
Nitrogen oxide (NOx) [mg/MJ] 80 83 83
Organic Hydrocarbons (OGC) [mg/MJ] <1,5 <1 <1
Dust [mg/MJ] 12 13 13
Boiler efficiency rating [%] 93,2 94,3 94,3
Test data at partial load
Carbon monoxide (CO) [mg/MJ] 29 29 29
Nitrogen oxide (NOx) [mg/MJ] 62 62 62
Organic Hydrocarbons (OGC) [mg/MJ] <1 <1 <1
Dust [mg/MJ] 10 10 10
Boiler efficiency rating [%] 93,7 93,7 93,7
1) TÜV Austria, Environment and Chemistry Division, Am Thalbach 15, A-4600 Thalheim/Wels
2) In accordance with ÖNORM / DIN EN 303-5, chapter 5.1.3 type test: for a boiler from a range with a consistent structure it is sufficient, if the ratio of rated heat output from the largest to the smallest boiler 2 : 1, to carry out the tests with the smallest and the largest boilers. The boiler manufacturer must ensure that all boilers, including those that have not been tested in a range, whose values have been determined depending on rated heat output by interpolation, fulfil the requirements of the norm.
3) Values of the model, P4 Pellet 80, are interpolated between the test protocol 08-UW/Wels-EX-337 and 10-UW/Wels-EX­242/1. Partial load data from test protocol 10-UW/Wels-EX242/1
Technology
Technical specifications
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 17 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
2
2.3.4 Airborne sound level
The sound level specified in the following table is based on sound measurements on a P4 Pellet 15. (measuring device: Omega HHSL 1)
The sound level of the individual units was plotted at a distance of 1 m from the sound source.
Ambient level for measurement: 32 dBA
Unit Measurement
Units in continuous operation:
Induced draught fan (activation: 50%) 41 dBA
Induced draught fan (activation: 65%) 44 dBA
Induced draught fan (activation: 90%) 50 dBA
Units in non-continuous operation:
Suction turbine 68 dBA
Grate motor 42 dBA
Stoker motor / Stoker screw 33 dBA
Ignition fan 53 dBA
WOS motor / WOS system 60 dBA
Burn back slide valve actuator (open) 34 dBA
Burn back slide valve actuator (close) 50 dBA
Please note that all the measurements were taken in-house and do not come from a certified test station. This data should therefore be viewed as individual measurements to be used as guidelines.
Please also note the sound levels required in the standards listed below, which must be fulfilled by planning and construction measures:
ÖNORM B 8115-2 Sound insulation and room acoustics in building
construction - Requirements for sound insulation
ÖNORM H 5190 Heating systems - Acoustic insulation
Installation
Transport and Setup
Page 18
M0930811 v
3
3 Assembly
3.1 Transportation
The boiler is delivered packed in cardboard and on a pallet.
Move without jarring or jolting Protect the packaging against damp Consult the delivery information on the
packaging.
Observe the centre of gravity of the pallet!
The boiler is marked opposite the lifting side with a sticker.
3.1.1 Positioning
U Position a lifting truck or similar lifting device at the pallet and
position the boiler
If it is not possible to position the boiler on the pallet:
U Remove the cardboard and remove the boiler from the pallet
À See 3.2.1 Removing the boiler from the pallet
If the boiler must be dismantled for positioning:
U Dismantle the components of the boiler until it can be brought into
position
À See 3.3 Dismantling for location where positioning is difficult
For positioning using a crane:
U Remove the insulating cover, the
WOS cover and the heat exchanger cover
The hoisting point for the crane eye
is below the cover.
3.1.2 Temporary storage
If the system is to be installed at a later date:
U Store the boiler, insulation and control unit in a safe, dust-free, and
dry location Moisture and frost reduce the effectiveness of insulation and can
destroy electronic components.
Do NOT use forklifts for this task!
Installation
Transport and Setup
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 19 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
3.2 Set-up in the boiler room
3.2.1 Removing the boiler from the pallet
U Remove packing bands with an appropriate tool U Pull off the cardboard from above
U Remove the transport covers (1) of the ash drawers (P4 Pellet 8-25)
or insulated door(s) and ash bucket (P4 Pellet 32-105) and cleaning devices (2)
U Remove the protective casing
On the front of the boiler, P4 Pellet 8/15/20/25:
U Open the insulating door U Remove securing devices used during transportation on the left and
right side of the base.
U Pull out the lock bolt of the door hinge (1) and remove it from the
guide
U Remove the insulated door and pull out the floor insulation
On the front of the boiler, P4 Pellet 32/38/48/60/80/100/105:
U Remove securing devices used during transportation on the left and
right side of the base.
U Remove 2 screws each on the left and right of the ash collecting
plate and remove the collecting plate
U Pull out the floor insulation behind
At the back of the boiler:
U Remove securing devices used during transportation on the left and
right side of the base.
1
1
2
Installation
Transport and Setup
Page 20
M0930811 v
3
3.2.2 Moving the boiler in the boiler room
U Position a lifting truck or similar lifting device with an appropriate
load-bearing capacity at the base frame of the boiler and move to the specified place
U Set up boiler at intended location
Put red boiler underlays under the frame. Observe the minimum distances in the boiler room.
3.2.3 Minimum distances in the boiler room
P4 Pellet
Description Units 8/15 20/25 32/38 48/60 80/100/105
A Minimum distance to suction
cyclone assembly
300 300 300 300 300
B Induced draught fan
maintenance area
300 300 300 300 300
Space for insulated door 550 720 830 490 590 C
Space requirement with plug-in insulated door
400 400 300 - -
D Minimum distance to side of
boiler
mm
200 200 200 200 200
Installation
Transport and Setup
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 21 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
3.3 Dismantling for location where positioning is difficult
If the boiler cannot be brought into position because the space is confined, it is possible to dismantle individual components.
The following steps show the maximum possible dismantling steps. You should only carry out the steps that are necessary for positioning.
3.3.1 Dismantling the stoker assembly and insulation
U Remove the locking screws on the sound insulation hood of the
stoker assembly and remove the sound insulation hood.
U Lift the front part of the stoker assembly upwards and remove.
U Lift the back part of the stoker assembly upwards and remove U Remove insulating cover
Installation
Transport and Setup
Page 22
M0930811 v
3
U Unscrew the screws under the insulated cover with the contact
washers at the flaps of the controller cover.
U Open insulated door (only for P4 Pellet 8/15/20/25)
U Unscrew the screw together with the contact washer on the bottom
side of the controller cover
U Remove the controller cover
Installation
Transport and Setup
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 23 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
3.3.2 Remove the door and ash drawer (P4 Pellet 8/15/20/25)
U Fold out the hinge pins at the top of the insulated door and pull down U Lift the insulated door from the lower hinge and remove
U Open both ash doors and remove the ash drawer together with
accessories
U You can optionally remove the upper cover of the settling chamber
and the inner cover
Installation
Transport and Setup
Page 24
M0930811 v
3
3.3.3 Dismantling the suction cyclone cover
U Remove the covering of the
middle cable duct
At the pellet module:
U Unplug the relevant plugs:
- “Suction unit M3”
- “Max level S1”
- “Gate valve M8”
U Separate the cable tie at the cable leadthrough U Unthread the cables that have been unplugged
Installation
Transport and Setup
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 25 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
U Wind up the unplugged cables at the units U Open the clamps and take off the cover
3.3.4 Dismantling the stoker unit
U Remove the covering of the cable duct
At the pellet module:
U Unplug the relevant plugs:
- “Grate drive M6”
- “Burn back flap M7”
- “Stoker motor M1”
- “Ignition E1”
U Unthread the cables of the unplugged units
Installation
Transport and Setup
Page 26
M0930811 v
3
U Loosen the locking screw on the ignition fan U Take out the ignition fan
U Remove the back and front locking split pin of the grate drive and
pull out the bolt CAUTION! Secure the grate motor so it cannot fall down when the
bolt is removed.
U Push the bushing back at the grate rod U Remove the grate motor
Installation
Transport and Setup
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 27 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
U Depending on the design, cut open the aluminium band from the
heat insulation mat below the stoker duct and remove
U Remove two screw connections on the right and left at the stoker
unit flange The screws can be removed completely as the stoker unit is hung
on the boiler on two hooks.
The following assembly step requires two people:
Weight of stoker unit P4 Pellet 8/15/20/25: approx. 32 kg
Weight of stoker unit P4 Pellet 32/38: approx. 36 kg Weight of stoker unit P4 Pellet 48/60: approx. 46 kg Weight of stoker unit P4 Pellet 80/100/105: approx. 68 kg
U Pull the stoker unit up slightly until the hooks come out of the stoker
flange
U Tip the unit back slightly and lift away
The P4 Pellet is fully dismantled and can now be brought into
position.
Installation
Transport and Setup
Page 28
M0930811 v
3
3.3.5 Positioning dimensions after dismantling
P4 Pellet
Dimension Description Units 8/15 20/25 32/38 48/60 80/100/105
L Length, boiler 740 740 740 8201) 9102)
B Width of boiler 705 875 965 1275 1480
H Height of boiler
mm
1280 1280 1430 1585 1710
1) If the control unit is dismantled, the dimension can be reduced to 780 mm (e.g. for bringing into position through doors with a clearance of 800 mm)
2) If the control unit is dismantled, the dimension can be reduced to 880 mm (e.g. for bringing into position through doors with a clearance of 900 mm)
Dismantling the control unit:
U Remove the lateral plexiglass covers and secure the nuts of the
screw connection so they cannot turn
U Remove the screws on the left and right on the underside U Remove the cable marked “Display” and pull up and out U Remove the control unit
Installation
Transport and Setup
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 29 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
3.3.6 Notes on reassembly
U After positioning the boiler, assemble in reverse order
It is particularly important to observe the following points during assembly:
U Depending on the design of the insulation, after fitting the stoker
unit and the insulating material it may be necessary to stick a new aluminium band on top of the aluminium band that was previously cut.
When fitting the grate motor, check that it is in the correct position on the back support:
- Top position = P4 Pellet 8/15/20/25
- Bottom position = P4 Pellet 32/38
- A position = P4 Pellet 48/60/80/100/105
Observe the installation position of the actuating sleeve between the grate motor and the slide rod
U Carefully screw in the locking screw finger-tight
You must not carry on tightening to the extent that the ignition
fan pipe is deformed
Fix the cable with the cable ties supplied. There must not be any loose cables in the area of the igniter. Only connect the power supply after completing assembly. The individual units should be checked by the qualified technician
and adjusted if necessary during initial start-up.
Installation
Assembling the Pellet Boiler
Page 30
M0930811 v
3
3.4 Assembling the Pellet Boiler
3.4.1 Installing the induced draught fan
U Remove the locking screws on the sound insulation hood of the
stoker assembly and remove the sound insulation hood.
U Open the clamps on the suction cyclone container and lift the cover
´ The induced draught set is in the suction cyclone container
U Remove the induced draught fan from the suction cyclone container
U Remove pre-installed cover plate U Unscrew pre-installed nuts and spacer washers U Attach and fix the ID fan as illustrated
The straight edge of the tube flange must be at the top.
U Join both cables of the ID fan with the pre-installed cables
Ensure that the locking device (1) clicks into place.
U Push the cable behind the cladding and put back the cover plate.
1
Installation
Assembling the Pellet Boiler
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 31 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
3.4.2 Fit the ash container and doors (P4 Pellet 32/38/48/60/80/100/105)
U Remove the insulating cover and unscrew the two top retaining
screws with the contact washers of the controller cover
Caution: Do not lose the contact washers!
U Unscrew the lower retaining screw with contact washer and remove
the controller cover
U Put the insulated door in the boiler base and secure at the top with
bolts
U Take the two cover caps for the ash containers from the ash
containers and position them in the open flaps
U Put in the ash containers and secure with the locking lever
Installation
Install discharge system
Page 32
M0930811 v
3
3.5 Installing the discharge system
3.5.1 General installation information
NOTICE
Water lines should not be located in close proximity to the pellet store and the feeder units
due to the dangers posed by condensation and bursting water pipes!
Check the delivered items for foreign objects in the individual components In the pellet store room an impact cushion must be installed on the opposite side to the filler
pipes. This reduces wear on the pellets when they are blown in and stops the finish being worn off. Broken pieces of masonry or finish and other foreign bodies (small stones, pieces of wood, screws, etc.) can block the discharge system or the pellet feed into the boiler and cause the system to fail. In case of faults due to such foreign bodies, the guarantee is void.
In time pellets leave dust on the ground; this can impair the process of moving them from
the pellet storage area. For this reason you should check and clean if necessary before refilling.
3.5.2 Hose Lines
For the hose lines used with the suction device, the universal suction system, and the bag silo discharge unit, observe the following:
Do not kink the hose lines! Minimum bending radius = 30cm Lay the hose lines as straight as possible! If the lines are sagging, it can lead to so-called
“pockets.” Problem-free pellet feeding can not be guaranteed.
Lay the hose lines in short segments away from walking areas! Hose lines are not UV-proof!
Therefore: do not lay the hose lines outdoors!
Hose lines are suitable for temperatures up to 60°C!
Therefore: Hose lines must not come into contact with flue gas pipes or uninsulated heating pipes!
Hose lines must be grounded on both ends, to ensure that no static charge builds up as a
result of transporting the pellets!
The suction line must be a single piece! The return-air line can be made up of several pieces, but potential equalization must be
established throughout the line!
Installation
Install discharge system
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 33 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
Potential Equalisation
When connecting the hose lines to the individual connection pipes, ensure there is potential equalization throughout the line!
U Expose approximately 3 cm of the grounding strap on the end of the
hose line
TIP: Slit the insulation open along the wire with a knife
U Bend the earth wire inwards in a loop
´ This prevents the earth wire from being damaged by the feed of
pellets.
U Install a hose clamp on the hose line U Put the hose line on the connection
Ensure that contact is established between the grounding strap and
the connection!
U Tighten the hose clamp
Installation
Install discharge system
Page 34
M0930811 v
3
3.5.3 Universal suction system
A 25 m Suction hose G Manual re-arranging unit (Variant 2)
B Hose clamps 50-65 mm H 2 x Blind plates (Variant 2)
C 2 x Fire protection choke collars
(only in Austria)
I 6 x Star-shaped screw knobs (Variant 2)
D Komfort pellet box (Variant 1) J Cover plate for wall
E Support for fire protection choke collar (Variant 1) K Suction probe
F Installation module for wall
280
250
50
Before installation:
U Prepare a wall penetration for the pellet box
(width: 28cm, height: 25cm) Maintain a distance of at least 5 cm from the
finished floor.
F
G
I
A
C
A
B
E
D
J
B
A
B
K
Variant 2 - Eco pellet box
Variant 1 - Komfort pellet box
G
H
280
Dimensions in mm
50
250
Installation
Install discharge system
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 35 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
Variant 1 – Komfort pellet box
U Position Komfort pellet box (D) at the wall
penetration
The distance from the wall on the board side
of the pellet box should be at least 10 cm for maintenance purposes.
U Fix Pellet box to the wall with 4 M8x50 frame
screws and 10 mm dowels
U Fill the space in the wall penetration with a non-
flammable material The partition must be insulated as per ÖNORM
B 3836 or DIN 4102-11!
U Put the cover plate for the wall (J) onto the pipes
of the pellet box
U Secure the cover plate to the wall using 4 M8x50
frame screws and 10 mm dowels
U Mount the bracket (E) for fire protection choke
collars on the pellet box Fire protection choke collars only in Austria.
D
J
E
10 cm
Installation
Install discharge system
Page 36
M0930811 v
3
Variant 2 – Eco pellet box
U Place the wall insertion module (F) at the wall
penetration
U Secure the insertion module to the wall using 4
M8x50 frame screws and 10 mm dowels
U Fill the space in the wall penetration with a non-
flammable material The partition should be insulated in
accordance with ÖNORM B 3836 or DIN 4102-11.
U Place the wall cover plate (J) on the insertion
module pipes
U Secure the cover plate to the wall using 4 M8x50
frame screws and 10 mm dowels
U Install 2 blind plates (H) on the insertion module
using 2 star-shaped screw knobs (I)
U Install interchange unit (G) using 2 star-shaped
screw knobs
No position is specified for the interchange
unit!
F
J
G
I
H
Installation
Install discharge system
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 37 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
Installing the suction probes and lines
U Position the suction probes (K) at equal distances
in the pellet supply bin
U Secure the suction probes to the bottom using
frame screws
U Fix hose lines (A) to the suction probe using hose
clips (B)
U Lay the hose lines to the pellet box and secure
them using hose clips
CAUTION! Read the label on the suction probe
or pellet box about the suction line and return-air line! Ensure correct connection!
CAUTION! When connecting the hose lines,
beware of potential equalisation!
À Page 33, Potential Equalisation À For information on store layout see 3.5.6
Pellet storage area
U Thread the fire protection choke collar (C) on to
the hose line (A)
Fire protection choke collars only in Austria.
U Attach the hose lines to the pellet box pipes
using hose clips (B)
U Lay the hose lines to the boiler, through
identified openings at the back plate and install with hose clamps to the identified connections
CAUTION! Read the label on the suction probe
or pellet box about the suction line and return-air line! Ensure correct connection!
Suction line: hose line to left connection (1)
on the back of the boiler
Return-air line: hose line to right connection
(2) on the back of the boiler
CAUTION! When connecting the hose lines,
beware of potential equalisation!
À Page 33, Potential Equalisation
1
2
K
B
A
A
B
B
C
A
B
C
A
Installation
Install discharge system
Page 38
M0930811 v
3
3.5.4 Suction screw system
A Flange bearing H Gearbox flange
B Ejector flange I Drive flange seal
C Trough mount with rubber pad J Geared motor
D Bearing flange K 2 x Cover plates for wall penetration
E Open trough L Main worm
F Suction intake with integrated support M Shaft end for main worm
G Proximity switch N Worm extension (if needed)
Before installation:
U Prepare wall penetration for suction piece
(width: 34cm, height: 20cm) Ensure that the channel in the wall
penetration is positioned off centre.
A
B
C
D
E
F
M
L
K
H
I
J
N
G
Installation
Install discharge system
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 39 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
U Thread the basic screw (H1) into the
penetration
The key-way must be toward the boiler!
U Thread the closed trough (J) onto the basic
screw on the store side The quadratic flange points out of the
store!
U Thread the open trough (I) onto the basic
screw
U Secure together using 4 M10x30 hexagonal
bolts and nuts
Depending on the length of the discharge unit, a screw extension may be necessary:
U Place the screw extension (N) on the basic
screw (L) and secure it using spring dowels
The screw blade must always be rising.
If no additional screw is used:
U Put the the end of the basic screw shaft (M)
on the basic screw shaft (L) and secure it using spring dowels
U Secure the gearing flange (I) and the gearing
flange seal (H) to the suction piece using 4 hexagonal M10 x 40 mm bolts and nuts
- 17 mm hexagonal nut
U Lubricate the screw stub shaft U Put on the geared motor (J)
Take care when inserting the key-way into
the groove of the shaft!
U Attach the geared motor on the gearing flange
(l) using 4 M8 x 16 mm hexagonal bolts with spacer washers
- Hexagonal nut dimension 13 mm
U Install the proximity switch (G) on the
inspection cover of the suction piece The proximity switch should project
approx. 1cm into the suction piece
Adjusting the sensitivity during the initial
start-up
À Page 47, 4.2 Setting the “Max level and
min level” sensor
H1
I
J
N
M
H
I
J
G
G
L
L
Installation
Install discharge system
Page 40
M0930811 v
3
U Secure the bearing flange (D) and the trough
mount (C) to the trough using 4 hexagonal M10 x 40 mm bolts and nuts
- Hexagonal nut SW 17 mm
U Place the flange bearing unit (A) and the ejecting
flange (B) on the shaft and secure them to the bearing flange using 2 M14 x 35 mm hexagonal bolts and spacer washers
- 21 mm socket spanner Do not lubricate! The flange bearing is
permanently lubricated and is maintenance free!
U Arrange the trough parallel to the store wall U Secure the trough mount and suction piece to the
floor using 2 10 mm dowels and 8 x 70 mm frame screws
U Fill the space in the wall penetration with a non-
flammable material The partition must be insulated as per ÖNORM
B 3836 or DIN 4102-11!
U Secure the wall penetration cover plates (K) to
the external store wall using 3 10 mm dowels and 8 x 50 mm frame screws
U Finally, the inclined bottom is installed
The plates of the inclined bottom must not be
placed on the trough!
À Page 44, Sloping floor
U Lay both hose lines in the boiler room to the
suction intake
On the left and right of the suction intake:
U Secure the suction hose (B) to the suction
connecting piece using a hose clamp (D) No connection side specified for suction or
return-air line!
U Put the supplied fire protection choke collar (1)
on the hose and secure it to the suction piece using 2 self-tapping screws
Fire protection choke collars only in Austria.
D
C
B
A
K
B
1
D
Installation
Install discharge system
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 41 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
U Lay the hose lines to the boiler, through
identified openings at the back plate and install with hose clamps to the identified connections
Suction line: hose line to left connection (1)
on the back of the boiler
Return-air line: hose line to right connection
(2) on the back of the boiler
CAUTION! When connecting the hose lines,
beware of potential equalisation!
À Page 33, Potential Equalisation
3.5.5 Bag silo discharge system
U Fit frame with bag silo
À See assembly instructions “Pellet bag silo Type I - V”
Observe the height of the boiler room during
planning.
Type I, II Type III - V
H Bag silo frame height [cm] 185 190
H1 Height including filler coupling [cm] 205 210
H2 Required minimum room height
1)
[cm]
Ideal store room height
2)
[cm]
215 230
220 230
1) Minimum room height for connection to filler pipe in installation room.
2) When full, the bag silo has a heap shape. Optimum height is for use of the whole capacity.
1
2
Installation
Install discharge system
Page 42
M0930811 v
3
U Fit the bag silo in accordance with the assembly
instructions supplied
U Put the flange ring (1) onto the bag silo U Put the bag silo and flange ring onto the probe at
the threaded bolts and screw them together
U Thread one fire protection choke collar each (B)
onto the suction and return-air lines
Fire protection choke collars only in Austria.
U Run hose lines through the openings in the wall
into the pellet store
U Secure the hose lines to the silo suction probe
using hose clamps (D)
Read the label on the silo suction probe! Suction line: The hose line to the cover of the
suction unit
Return-air line: The hose line to the suction
motor
U Lay the hose lines to the boiler, through
identified openings at the back plate and install with hose clamps to the identified connections
CAUTION! Observe the label for the suction
line and the return-air line on the silo suction probe and boiler. Ensure correct connection!
Suction line: hose line to left connection (1)
on the back of the boiler
Return-air line: hose line to right connection
(2) on the back of the boiler
CAUTION! When connecting the hose lines,
beware of potential equalisation!
À Page 33, Potential Equalisation
1
B
D
1
2
Installation
Install discharge system
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 43 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
3.5.6 Pellet storage area
For the universal suction system, the pellet store must be built with an inclined floor!
The following picture shows the most important components:
A 2 x Filler pipes
B Earth wire
C Planking on the store door
D Sloping floor
E Impact cushion
F Under-floor structure for sloping floor
Size of store
The storage area should be able to hold approximately 1.5 times the annual requirement. The exact amount of required space depends on the system’s heating load.
Rule of thumb formula: 1m³ store / kW heating burden
A
B C D
E
F
Installation
Install discharge system
Page 44
M0930811 v
3
Sloping floor
Fig.1: Store for a discharge unit with a suction probe Fig.2: Store for a discharge unit with a screw
The under-floor structure should be dimensioned so that the sloping floor is not deformed when subjected to static load. You should ensure that the pellets can slide down smoothly. This means the sloped floor should be at an angle of at least 45° and have a smooth surface (we recommend laminate).
When planning the under-floor structure, note:
1 m³ of pellets roughly corresponds to a weight of 650 kg! Ideally the suction probes should already be fitted before the sloped
floor is constructed.
A distance of 20 cm should be maintained between the cross-pieces
and the suction probe should be centrally positioned. (see Fig. 1)
The weight of the pellets must not be borne by the trough! (see Fig. 2)
Impact cushion
The baffle plate is made of rubber and is positioned opposite the filling nozzles at a distance of approximately 20 cm from the wall. It prevents pellets from striking the wall and knocking off pieces of the finish when filling.
Pieces of the finish, screws, and other foreign objects can clog the
suction probe!
CAUTION! Damage caused by foreign objects is not covered by the
guarantee!
NOTICE
In time pellets leave dust on the ground; this can impair the process of moving them from the storage area.
Check the storage area before re-filling and clean if necessary Regular complete emptying and cleaning of the storage area ensures
consistent readiness for operation!
Installation
Connecting the pellet boiler
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 45 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
3
3.6 Electrical Connection
DANGER
When working on electric components:
Risk of serious injuries from electric shocks
U Work on electrical components should only be carried out by authorised
technicians
Wiring should be installed using flexible sheathed cable and
dimensioned in compliance with the locally applicable standards and guidelines
The power supply line (mains connection) must be fitted with a C16
A fuse by the customer.
U Remove insulating cover U 2 pieces Unscrew the retaining screws with contact washers behind
the control unit
U Open the insulated door and remove the centrally positioned
retaining screw and contact from below
U Remove the front insulating cover and wire the connections in
accordance with the circuit diagram
À Schematic diagrams: See operating instructions “Lambdatronic P
3200”
CAUTION
When using energy-efficient pumps on the speed-regulated pump outputs:
Malfunctions of the boiler and the hydraulic system are possible!
Take the following precautions: You must not connect any EC motor pumps at the speed-
regulated pump outputs of the boards.
Observe the additional instructions and information on board outputs in the operation instructions of the boiler controller.
Installation
Connecting the pellet boiler
Page 46
M0930811 v
3
3.6.1 Connecting the Komfort pellet box
The connection of the Comfort pellet box to the pellet module board is established using a flexible cable (5x0.75mm², e.g. YMM as per ÖVE­K41-5 or H05VV-F as per DIN VDE 0281-5).
This is a 24V control line.
The previous figure shows the plugged-in 5-pin connecting plug of the Komfort pellet box and the accompanying connection layout of the Lambdatronic P3200 control system.
To check the plug arrangement:
U Detach the protective plate (1) from
the board
U Perform check using the board’s
labels
The actuators (2) of the pellet
box must be switched to the “R” position!
The actuators are ready to plug in and are connected to the board. All necessary plug clips are included with the pellet box in delivery
1
2
Commissioning
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 47 Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M0930811
4
4 Initial Start-up
4.1 Configuring the Boiler
The boiler must be adjusted to the requirements of the heating system during commissioning
NOTICE
Optimum performance and efficient operation with low emissions can
only be guaranteed if the system is set up by a qualified technician and the specified factory settings are observed.
Take the following precautions:
U We recommend that the system is commissioned by Froling customer
services or an authorised installer.
Before heating up the boiler for the first time:
U Set the controller to match your heating system.
The keypad layout and necessary control steps for modifying the parameters can be found in the accompanying operating instructions for the “Lambdatronic P 3200”.
4.2 Setting the “Max level and min level” sensor
In delivery configuration, the factory settings of the sensor are secured with a seal. Changes to the settings should only be carried out by qualified technicians.
Depending on the design, a min level sensor may also be installed.
The monitoring LED (1) should only illuminate when identifying
materials!
U If the monitoring LED stays on permanently, the sensitivity is set too
high!
´ Reduce the sensitivity by turning the adjusting screw (2) to the
left
U If the monitoring LED does not react when pellets are being fed in,
the sensitivity is set too low!
´ Increase the sensitivity of the adjusting screw by turning to the
right
1
2
Loading...