Frigidaire GLGQ2152EE0, LEQ2152EE0 Installation Guide

Pre-lnstallation Requirements................................................... 2
Installation
instructions
Instrucciones
Before beginning installation, carefully read these instructions. This will simpfify the installation and ensure the dryer is installed correctly and safely. Leave these instructions near the Dryer after installation for future reference.
NOTE: The electrical service to the Dryer must conform with local codes and ordinances and the latest edition of the National Electrical Code, ANSI/
NFPA70. NOTE: The gas service to the Dryer must conform with local codes and ordinances and the latest edition of the National Fuel Gas Code ANSI
Z223.1. NOTE: The Dryer is designed under ANSI Z 21.5.1 or ANSI/UL 2158 - CAN/CSA C22.2 No. 112 (latest editions) for HOME USE only. This Dryer is not
recommended for commercial applications such as restaurants or beauty salons, etc.
Antes de comenzar la instalacion, lea cuidadosamente estas instrucciones. Esto simplificar_ la insta/adon y asegurar_ que la secadora se insta/e correctamente y de manera segura. Despu_s de completar la insta/acibn, coloque estas instrucciones cerca de la secadora para referencia futura.
NOTA: La alimentaci6n electrica para la secadora debera cumplir con los c0digos y reglamentos locales y con la 01tima edici0n del Codigo Electrico
Nacional, ANSI/NFPA 70. NOTA: La alimentacion de gas para la secadora debera cumplir con los codigos y reglamentos locales y con la ultima edicion del Codigo Nacional para
Gases Combustibles, ANSI Z223.1. NOTA: La secadora esta clasificada para USO DOMEST/CO solamente, de acuerdo con la norma ANSI Z21.5.1 o ANSI/UL 2158 - CAN/C SAC 22.2
No. 112 (las Oltimas ediciones). Esta secadora no se recomienda para uso commercial tal como en restaurantes, salones de belleza, etc.
For your safety the information in this manual must
be followed to minimize the risk of fire or explosion or to prevent property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquid in
the vicinity of this or any ott]er appliance.
- WHAT TO DO/F YOU SMELL GAS
Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Clear the room, building or area of all occupants. Immediately call your gas supplier from a neighbor's pt]one. Follow the gas supplier's instructions. If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer,
service agency or the gas supplier.
ElectricalRequirements.............................................................. 2
ExhaustSystemRequirements ............................................... 2-3
Gas Supply Requirements .............................................. 3
Location of Your Dryer .............................................. 3
Rough-In Dimensions ............................................... 4
Mobile Home Installation ......................................... 5
Unpacking ............................................................ 5
ReversingDoor Swing............................................................ 5-6
ElectricalInstallation .................................................................. 7
Grounding Requirements ......................................................... 7
Electrical Connections--?-wire .................................. 7
Electrical Connections--4-wire .................................. 8
Gas Connection ....................................................... 8
General Installation .................................................. 8
Replacement Parts ................................................... 8
Requerimientos de instalacion preliminares ................. 9
Requerimientos electricos.......................................................... 9
Requerimientos del sistema de escape .................... 9-10
Desembalaje............................................................................. 1?
Puertareversible.................................................................. 13-14
Conexiones electricas - trifilares ........................................ 15
Conexiones el_ctricas - tetrafilares ............................. 16
Conexi6n del gas............................................................. 16
Para su seguridad, siga las instrucciones contenidas en
este manual a fin de reducir a un minimo los riesgos de incendio o explosion o para evitar dat_os materiales, lesiones personales o la muerte.
No almacene ni utilice gasolina u otros vapores y Iiquidos inflamables en la proximidad de este o de cualquier otto artefacto electrico.
QUE DEBE HACER S! PERCIBE OLOR A GAS
No trate de encender ning0n artefacto electrico. No toque ningun interruptor electrico; no use ningun tel(_fono en su
edificio. Haga salir a todos los ocupantes de la habitaciOn, del edificio y del lugar.
Llame a su proveedor de gas desde el telefono de un vecino. Siga las instrucciones del proveedor de gas.
Si no Iogra comunicarse con su proveedor de gas, Ilame al departamento de bomberos.
La instalacion y el servicio de mantenimiento debe de realizarlos un instalador calificado, la agencia de servicios o el proveedor de gas.
P/N 134763200 (0605)
PRE-INSTALLATIONREQUIREMENTS
Tools and Materials Required for installation:
1. Phillips head screwdriver.
2. Channel-lock adjustable pliers.
3. Carpenter's level.
4. Flat or straight blade screwdriver.
5. Duct tape.
6. Rigid or flexible metal 4 inch (10.2 cm) duct.
7. Vent hood.
8. Pipe thread sealer (Gas).
9. Plastic knife.
ELECTRICALREQUIREMENTS
I ELECTRIC Dryer ]
CIRCUIT- Individual 30 amp. branch circuit fused with 30 amp. time delay
fuses or circuit breakers.
Use separately fused circuits for washers and dryers, and DO NOT operate a washer and a dryer on the same circuit.
POWER SUPPLY - 3 wh-e or 4-wire, 240 volt, single phase, 60 Hz, Alternating Current.
POWER SUPPLY CORD KiT - The dryer MUST employ a 3-conductor power supply cord NEMA 10-30 type SRDTrated at 240 volt AC minimum, 30 amp.,
with 3 open end spade lug connectors with upturned ends or closed loop
connectors and marked for use with clothes dryers. WARNING - Risk of Shock. Appliance grounded to neutral conductor
through a link. Grounding through the neutral link is prohibited for (1) New
branch circuit installations (2) mobile homes; (3) recreational vetqides; and (4) areas where local codes do not permit grounding through the neutral,
(1) disconnect the link from the neutral, (2) use grounding terminal or lead
to ground appliance in accordance with local codes and (3) connect neutral terminal or lead to branch ch-cuit neutral in usual manner (if ttqe appliance
is to be connected by means of a cord kit, use 4-conductor cord for this purpose). USE COPPER CONDUCTOR ONLY. The dryer MUSTemploy a 4- conductor power supply cord NEMA 14-30 type SRDT or ST (as required) rated at 240 volt AC minimum, 30 amp., with 4 open end spade lug connectors
with upturned ends or closed loop connectors and marked for use with
clothes dryers. See ELECTRICAL CONNECTIONS FOR A 4-WIRE SYSTEM. (Canada - 4-wire power supply cord is installed on dryer.)
OUTLET RECEPTACLE - NEMA 10-30R receptacle to be located so the power supply cord is accessible wtqen the dryer is in ttqe installed position.
(Canada - NEMA 14-30R receptacle.)
li
NEMA 10-30R NEMA 14-30R
GAS Dryer
CIRCUIT - Individual 15 amp. branch circuit fused with a 15 amp.
maximum time delay fuse or circuit breaker.
POWER SUPPLY - 3 wire, 120 volt single phase, 60 Hz, Alternating Current.
POWER SUPPLY CORD - The dryer is equipped with a 120 volt 3-wire power cord.
NOTE: Do not under any _ _1_1_
circumstances remove
grounding prong from plug.
G PRONG
EXHAUST SYSTEM REQUIREMENTS
Use only 4 inch (10.2 cm) diameter (minimum) rigid or flexible metal duct and approved vent hood which has a swing-out damper(s) that open
when the dryer is in operation. When the dryer stops, the dampers
automatically close to prevent drafts and the entrance of insects and rodents. To avoid restricting the outlet, maintain a minimum of 12 inches (30.5 cm) clearance between the vent hood and the ground or any other
obstruction.
and safe operation of your dryer. Failure to foflow these instructions can create excessive drying times and fire hazards.
Excessive lint carl build up inside exhaust system and create a fire hazard and restrict air flow. Restricted air flow will increase dryer times. If your present system is made up of plastic duct or metal foil duct, replace it
with a rigid or flexible metal duct. Ensure the present duct is free of
any lint prior to installing dryer duct.
_f_- Risk of Fire - A clothes dryer produces combustible lint. If
the dryer is not exhausted outdoors some fine lint will be expelled into the
laundry area. An accumulation of lint in any area of the home can create a health and fire hazard. The dryer must be connected to an exhaust outdoors. Regularly inspect the outdoor exhaust opening and remove any accumulation of lint around the outdoor exhaust opening and in the surrounding area.
clothing, draperies/curtains, paper) to come in contact with exhaust
system. The dryer MUST NOT be exhausted into a chimney, a wall, a
ceiling, or any concealed space of a building which can accumulate lint, resulting in a fire hazard.
elbows allowed in the "MAXIMUM LENGTH" charts can cause an accumulation of lint in the exhaust system. Phgging the system could
create a fire hazard, as well as increase drying times.
nor use any screws or rivets to assemble the exhaust system. Lint can become caught in the screen, on the screws or rivets, clogging the duct work and creating a fire hazard as well as increasing drying times. Use an approved vent hood to terminate the duct outdoors, and seal all
joints with duct tape. All male duct pipe fittings MUST be installed
downstream with the flow of air. _Explosion hazard. Do not install the dryer where
gasofine or other flammables are kept or stored. If the dryer is
instalbd in a garage, it must be a minimum of 18 inches (45.7 cm) above
the floor. Failure to do so can result in death, explosion, fire or burns.
Number
of
90°
Turns
The following are spedfic requirements for proper
Do not use plastic flexible duct to exhaust the dryer.
Do not allow combustible materials (for example:
Exceeding the length of duct pipe or number of
Do not screen the exhaust ends of the vent system,
MAXIMUM LENGTH
of 4" (10.2 cm) Dia. Rigid Metal Duct
VENT HOOD TYPE
(Preferred)
Louvered
-4
0 1 2 3
4
Number
of
90°
Turns
(10.2 cm)
60 ft. 52 ft.
44 ft.
32 ft. 28 ft.
of 4" (10.2 cm) Dia. Flexible Metal Duct
(18.28 m) (15.84 m) (13.41 m)
(9.75 m) (8.53 m)
MAXIMUM LENGTH
VENT HOOD TYPE
(Preferred)
Louvered
(6.35 cm)
48 ft.(14.63 m) 40 ft.(12.19 m) 32 ft. (9.75 m) 24 ft. (7.31 m)
16 ft. (4.87 m)
0 1 2 3
(10.2 cm)
30 ft. (9.14 m) 22 ft. (6.71 m) 14 ft. (4.27 m)
NOTRECOMMENDED
(6.35cm)
18 ft. (5.49 m) 14ft. (4.27 m) loft. (3.05 m)
2 Printed in U.S.A.
The dryer MUST be isolated from the gas supply piping system during
any pressure testing of the gas supply piping system at test pressures equal to or less than
1/2 psig (3.45 kPa).
INSTALL MALE FITTINGS IN CORRECT DIRECTION
In installations where the exhaust system is not described in the charts, the
following method must be used to determine if the exhaust system is acceptable:
1. Connect an inclined or digital manometer between the dryer and the point the exhaust connects to the dryer.
2. Set the dryer timer and temperature to air fluff (cool down) and start the dryer.
3. Read the measurement on the manometer.
4. The system back pressure MUST NOT be higher than
0.75 inches of water column. If the system back pressure is lessthan 0.75 inches of water column, the
system is acceptable. If the manometer reading is higher than 0.75 inches of water column, the system is
too restrictive and the installation is unacceptable.
Although vertical orientation of the exhaust system is acceptable, certain extenuating circumstances could affect the perfor- mance of the dryer: , Only the rigid metal duct work should be used.
Venting vertical through a roof may expose the exhaust system to down drafts causing an increase in vent
restriction. Running the exhaust system through an uninsulated
area may cause condensation and faster accumulation of lint.
, Compression or crimping of the exhaust system will
cause an increase in vent restriction.
The exhaust system should be inspected and cleaned a minimum of every 18 months with normal usage. The more the dryer is used, the more often you should check the exhaust system and vent hood for proper operation.
EXHAUST DIRECTION
All dryers shipped from the factory are set up for rear exhausting. However, on electric dryers, exhausting can be to the right or left side of the cabinet or the bottom of the dryer. On gas dryers, exhausting can be to the right side of the cabinet or the bottom of the dryer. Directional exhausting can be accomplished by installing Exhaust Kit, P/N 131456800, available through your parts distributor. Follow the instructions supplied
with the kit.
LOCATION OF YOUR DRYER
DO NOT INSTALL YOUR DRYER:
1. In an area exposed to dripping water or outside weather conditions.
2. In an area where it will come in contact with curtains, drapes, or anything that will obstruct the flow of combustion and ventilation air.
3. On carpet. Floor MUST be solid with a maximum slope of 1 inch (2.54
cm).
INSTALLATION IN RECESS OR CLOSET
1. A dryer installed in a bedroom, bathroom, recess or closet, MUST be exhausted outdoors.
2. No other fuel burning appliance shall be installed in the same closet as the Gas dryer.
3. Your dryer needs the space around it for proper ventilation.
DO NOT install your dryer in a closet with a solid door.
4. A minimum of 120 square inches (774.2 square cm) of opening, equally divided at the top and bottom of the door, is required. Air openings
are required to be unobstructed when a door is installed. A Iouvered door with equivalent air openings for the full length of the door is
acceptable.
MINIMUM INSTALLATION CLEARANCES - Inches (cm) SIDES REAR TOP FRONT
Alcove 0 (0 cm) 0 (0 cm) Closet 0 (0 cm) 0 (0 cm) 1(2.54 cm) Closet door ventilation required: 2 Iouvered openings each 60 square inches (387 square centimeters) -- 3 inches (7.6 cm) from bottom and top
of door.
This dryer MUST be exhausted outdoors.
5. The following illustrations show minimum clearance dimensions for proper operation in a recess or closet installation.
ii u
--_ii_--O" (0 cm) 1" (2. 54 cm) _i'- 0" (0 cm)
EXHAUST DUCT LOCATING DIMENSIONS
I S SAME AS OTHER SIDE
GAS SUPPLY REQUIREMENTS
_Replace copper connecting pipe that is not plastic-
coated. Stainless steel or plastic-coated brass MUST be used.
1. Installation MUST conform with local codes, or it] the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (latest
edition).
2. The gas supply line should be of 1/2 inch (1.27 cm) pipe.
3. If codes allow, flexible metal tubing may be used to connect your dryer to the gas supply line. The tubing MUST be constructed of stainless steel or plastic-coated brass.
4. The gas supply line MUST have an individual shutoff valve.
5. A 1/8 inch (0.32 cm) N.RT. plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of the gas supply connection to the dryer.
6. The dryer MUST be disconnected from the gas supply piping system during any pressure testing of the gas supply piping system at test pressures in excess of 1/2 psig (3.45 kPa).
o,,
CLOSET DOOR
48.5" To clear open door
(123.19cm)
Dryer lnsta#ation Dimensions
Free=Standing & Under Counter
Electrical supply
on rear of unit
/
l
o o _,,_,_
i
....... J
l
__!: "__
27.0"
(68. 58cm)
I
,'T.,
To rear & base exhaus
36"
(91.44cm)
(34.29cm)
(72.39cm)
28.5"
27.25 to front of cabinet (69.22cm)
27.75 to clear knobs (70.49cm)
28.5 to clear door handle (72.39cm)
Gas supply pipe on rear of unit
\
(5.72cm)
5.0" (12.7cm)
Center line height
, right, left
vent
4.375" To side exhausts (11.12cm)
5.875" To base exhaust (14.93cm)
2.25"
I--
Stacked Dryer insta#ation Dimensions
(68. 58cm)
i
27.0" -_
28.25" to front of cabinet(71.76cm)
28.75" to clear knobs (73.03cm)
29.5" to clear door handle 49" to clear open door (124.46cm)
T
72.00"
(11.12cm) (182.88cm)
4.375" Side
exhausts
Gas supply pipe on rear of unit
41.00"
(104.14cm)
Center line
height for rear,
right, left vents
o oL_
w o
I 2.375"
(6.03cm)
38.25"
(97.16cm)
4
MOBILE HOME INSTALLATION
UNPACKING
1. Dryer MUST be exhausted outside (outdoors, not beneath the mobile home) using metal ducting that will not support combustion. Metal ducting must be 4 inches (10.16 cm) in diameter with no obstructions. Rigid metal duct is preferred.
2. If dryer is exhausted through the floor and area beneath the mobile home is enclosed, the exhaust system MUST
terminate outside the enclosure with the termination securely fastened to the mobile home structure.
3. When installing a gas dryer into a mobile home, a provision must be made for outside make up air. This provision isto be not lessthan twice the area of the dryer exhaust outlet.
4. This dryer MUST be fastened to the floor. Mobile Home Installation Kit No. 346764 is available from your dealer.
5. Refer to pages 2 and 3 for other important venting requirements.
6. Installation MUST conform to current Manufactured Home Construction & Safety Standard (which is a Federal Regulation
Title 24 CFR-Part 32-80) or when such standard is not
applicable, with American National Standard for Mobile Homes.
The dryer is designed under ANSI Z 21.5.1 or
ANSI/UL2158 - CAN/CSA C22.2 (latest editions) for HOME USE only.
1. Using the four shipping carton corner posts (two on each side), carefully lay the dryer on its left side and remove the foam shipping base.
To prevent damage, do not use the control panel
as a means to pick up or move the dryer.
2. Return the dryer to an upright position.
FOAM SHIPPING
_P_C KING
REVERSING DOOR SWING
Correct
DON'T
O
Your dryer is designed so the door swing may be reversed at any time without additional parts. Conversion is accomplished by transferring hinges to the opposite side of the cabinet.
"Solid door "Reversal Instructions:
1. Open the dryer door. Remove the four hinge hole plugs from the left side of the door opening. Place nearby for future
installation. NOTE: You may need a plastic knife to help pull out the plugs. Be careful not to scratch the paint.
2. Remove the four screws that secure the door hinges to the dryer front panel (see below). NOTE: Remove one screw from each of the two hinges first. Hold the door firmly before removing the last two screws.
3. Rotate the door 180° and reinstall the door hinges to the dryer front panel with the four screws.
4. Install the four hinge hole plugs in the open screw holes on the right side of the door opening.
Incorrect
©
REMOVE 4 SCREWS
(ONE FROM EACH
HINGE FIRST)
Loading...
+ 11 hidden pages