Frigidaire FRS09PYW1, FRS09PYC1, FRS12PYW1, FRS12PYC1, FRS184YW2 Installation Manual

...
Page 1
Model(indoor/outdoor):
FRS09PYW1/FRS09PYC1 FRS12PYW1/FRS12PYC1 FRS184YW2/FRS184YC2 FRS18PYW2/FRS18PYC2 FRS224YW2/FRS224YC2 FRS22PYW2/FRS22PYC2
ac.eriadigirf.www moc.eriadigirf.www
All about the
Installation
of your
7651-249-668-1adanaC7651-249-668-1ASU
Page 2
Safety precautions
04
Safety precautions
DANGER! Avoid Serious Injury
This appliance must be installed by a qualified licensed HVAC technician in accordance with all applicable codes. All electrical connections should be performed by a licensed electrician.
or Death
1. Do not attempt to install the split air conditioner by yourself.
2. This air conditioner contains no
user-serviceable parts. Always call
an authorized Electrolux servicer for repairs.
3. When moving the air conditioner,
always call an authorized Electrolux
servicer for disconnection and re-installation.
4. Do not insert or place fingers or objects into the air discharge area in the front of the indoor unit.
5. Do not insert or place fingers or objects into the air discharge area in the outdoor unit.
6. Do not start or stop the air conditioner by unplugging the power cord or turning off the power at the electrical box.
7. Do not cut or damage the power cord.
8. If the power cord is damaged it should only be replaced by an authorized Electrolux servicer.
9. In the event of a malfunction (sparks, burning smell, etc.) immediately stop
the operation, disconnect the power
cord, and call an authorized Electrolux servicer.
10.Do not operate the air conditioners with wet hands
11.Do not pull on the power cord.
12.Do not drink any water that is drained from the air conditioners.
1. Provide occasional ventilation during use. Do not direct airflow at fireplaces or other heat related sources as this could cause flare ups or make units run excessively.
2. Do not climb on or place objects on the outdoor unit.
3. Do not hang objects off the indoor
unit.
4. Do not place containers containing water on the indoor and/or outdoor
units.
5. Turn off the air conditioner at the power source when it will not be
used for an extended period of time.
6. Periodically check the condition of the outdoor unit’s installation base for any damage.
7. Do not apply heavy pressure to the radiator fins of the indoor and/or outdoor units.
8. Operate the indoor unit with air filters in place.
9. Do not block or cover the intake
grille, discharge area and outlet
ports.
10.Ensure that any electrical/electronic equipment is one yard away from the indoor unit and outdoor unit.
11.Do not use or store flammable
gases near the indoor and/or
outdoor units.
CAUTION! Avoid Injury or damage to the unit or other property
Page 3
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring of instructions may cause harm or damage. The seriousness is classified by the following indications.
1. Connect with the power properly. Otherwise, it may cause electric shock or fire due to excess heat generation.
shock.
sounds, smell, or smoke comes from it. It may cause fire and electric shock.
switching on or off the power. It may cause electric shock or fire due to heat generation.
damp environment. It may cause electric shock.
electric parts. It may cause failure of
05
Safety precautions
3. Disconnect the power if strange
machine, electric shock or fire.
2. Always ensure effective grounding. No grounding may cause electric
4. Do not operate or stop the unit by
5. Do not operate with wet hands or in
6. Do not allow water to run into
heating appliances. It may cause fire and electric shock.
unspecified power cord. It may cause electric shock or fire.
9.Do not damage or use an
8. Do not use the power cord close to
flammable gas or combustibles, such as gasoline, benzene, thinner, etc. It may cause an explosion or fire.
7. Do not use the power cord near
power cord and ensure that the
is danger of fire or electric shock.
cord will not be compressed. There
10.Do not place heavy object on the
Page 4
operation. It may cause electric
removed, do not touch the metal parts of the unit. It may cause an injury.
shock or injury.
and electric shock.
It may cause failure of appliance
11.Do not open the unit during
13.Do not disassemble or modify unit.
14.When the air filter is to be
switch off, and turn off the circuit breaker. Do not clean unit when power is on as it may cause fire, electric shock or injury.
to air flow.
not using the unit for a long time.
15.When the unit is to be cleaned,
16.Avoid direct exposure of occupants
17.Turn off the main power switch when
18.The air conditioner may be dusted with an oil free cloth, or washed with a cloth dampened in a solution of warm water and mild dishwashing detergent. Rinse thoroughly and wipe dry. Wring excess water from cloth before wiping around controls.
Clean filter once every two weeks.
inlets or inside of air-outlet. It may cause failure of appliance or accident.
concern of damage due to falling of unit.
due to prolonged exposure. If bracket damages, there will be
the outdoor unit will not damage
19.Ensure that the installation bracket of
20.Always insert the filters securely.
22.Do not place obstacles around air-
cause failure.
Operation without filters may
from air conditioner. It contains
12.Do not drink water drained
contaminants and could make
you sick.
dedicated power circuit. No installation may cause fire and electric shock.
21.Always install circuit breaker and a
Safety precautions
06
Page 5
Precautions for Installation
Installation at the following sites may cause problems. If you must inevitably install
2. Sites with a high concentration of salinity, such as coastal areas.
3. Sites with sulfuric gas, such as hot water springs.
4. Sites with high frequency equipment, such as wireless equipment, welding machines and medical installations.
5. Sites with flammable gases or volatile material.
6. Sites with special environmental conditions.
7. Laundry rooms.
Choosing the installation site
the unit at one of these sites, please consult your local distributor beforehand:
1. Sites with machine oil.
Choosing the installation site
06
07
1. Carefully read the installation manual before beginning.
2. Follow each step as shown.
3. Observe all local, state and national electric codes. This appliance must be
installed by a qualified licensed HVAC technician in accordance with all applicable codes. All electrical connections should be performed by a licensed electrician.
4. Pay attention to danger and safety notices
Installation Warnings
Page 6
Outdoor Unit
1. The outdoor unit must be installed at a convenient site that is not exposed to strong winds. The site should be dry and well ventilated.
2. The site must support the weight of the outdoor unit and allow for vertical installation.
3. There must not be the possibility of increased noise and vibration at the site.
4. The unit must be installed at a site where the noise produced by its operation and air discharge does not disturb the neighbors or animals.
5. The site cannot have any leakage of flammable gases.
space around the unit, as shown
access the installation site.
More
More
More
More
More
in the figure.
6. The site must provide enough
7. Children must not be able to
than 1'
than 1.65'
than 1'
than 1.65'
than 6.6'
Choosing the installation site
08
8. The site must allow for the easy removal of the connector pipe and drain hose.
9. The unit must be installed at a site protected from direct sunlight.
Indoor Unit
1. The unit must be installed at a site that does not obstruct the flow of air.
2. The site must support the weight of the indoor unit.
3. The site must be easily accessible for maintenance and replacement of the air filter.
4. The site must allow for the necessary space around the indoor
figure.
that the unit be installed at the
flammable gases.
More
More
More
unit, as shown in the sideward
meter) between the unit and radio
5. There should be at least 3 feet (1
7.
inside wall, always leaving a space of
6. It must be far from fire, smoke or
center.
or television devices. It is ideal
than 6"
than 6"
than 6"
06
We recommend the indoor unit to be
installed as high up as possible on the
at least 6" between the top of the
indoor unit and the ceiling.
Page 7
Page 8
Attention
1. This illustration is for explanation purposes only.
4
3
1
Indoor unit
Outdoor
unit
5
6
Air filter
More
A
B
C
2. Copper tubes must be insulated independently
More than 6.6'
More than 1'
More than 1.65'
than 1.65'
More than 6"
More than 6"
More than 6"
2
6
8
7
Parts list
10
Page 9
1.58''
7.91''
5.31''
1.58''
A
B
(A:33.31" B:10.83")
=18000 Btu's
(A:36.97" B:11.73")
Indoor unit outline
Installation plate
the ceiling
from the wall
from the wall
Refrigerant pipe
6" or more fr
om
6" or more
hole (right) Ø 2.56"
6" or more
3.39"
4.21"
12000 Btu's
<
Indoor unit installation
Installation plates and dimensions
3.39"
4.21"
Refrigerant pipe hole (right) Ø 2.56"
Refrigerant pipe hole (right) Ø 2.56"
from the wall
6" or more
Installation plate
the ceiling
6" or more fr
om
Refrigerant pipe hole (right) Ø 2.56"
Indoor unit outline
from the wall
6" or more
A
B
Indoor unit installation
11
Page 10
Indoor unit installation
Attention
Fixing the Installation Plate
Drilling the Hole
1. Install the installation plate
horizontally over the structural parts on the wall using the spaces indicated on the plate, as shown
2. In the case of tiled, concrete or
diameter holes. Place anchorage supports for the appropriate assembly screws.
3. Fix the installation plate to the
1. Determine the position of the
installation plate and drill the
downward.
2. Always use a pipe cover with an
Installation plate
Fit the Installation Plate and drill holes in the wall according to the wall structure and corresponding mounting points on the installation plate (Dimensions are in “mm” unless otherwise stated).
Wall
Indoor unit
Outdoor unit
in the figures above.
A type screws.wall with eight
hole for the pipes using the
pipe hole so that it is tilted slightly
opening when drilling.
similar walls, create 0.2"
0.2"-0.
28"
4. At all times securing to the wall
studs is recommended.
1.97''
1.97''
3.94'' 4.88''
=21500 Btu's
(A:39.69" B:12.40")
Refrigerant pipe hole (right) Ø 2.56"
from the wall
6" or more
Installation plate
the ceiling
6" or more fr
om
Refrigerant pipe hole (right) Ø 2.56"
Indoor unit outline
from the wall
6" or more
A
B
12
Page 11
Connective pipe and drainage installation
Drainage
1. Run the drain hose sloping downward. Do not install the drain
2. When connecting extension drain hose, insulate the connecting part of extension drain hose with a shield pipe, do not let the drain hose slack.
Connective pipe
1. For the left-hand and right-hand piping, remove the pipe cover from
2. For the rear-right-hand and rear-left­hand piping, install the piping as
connective pipe.
Indoor unit installation
1. Pass the piping through the hole in the wall.
2. Put the upper claw at the back of the indoor unit on the upper hook of the installation plate, move the indoor unit from side to side to see that it is securely hooked.
Upper hook
Lower hook
Fastening the Indoor Unit
Do not put the end of drain hose into water.
Do not block water flow by a rise.
Do not block water flow by a rise.
piping
Pipe cover (left)
Pipe holder
Pipe cover (right)
Right piping
Connective pipe
Indoor unit outline
Rear right
piping
Rear left
Left piping
hose as illustrated sideward.
the side panel.
The pipe cover
must be kept as it may
conditioner
to any other place.
be used
the air
shown in the sideward figure. Bend
the connective pipe to
be laid at
the wall.
Fix the end of the
when relocating
1
.69"
a height of 1.69" or less from
13
Page 12
Attention
Piping and wrapping
1. Bundle the tubing, connecting cable, and drain hose with tape
2. Because the condensed water from rear of the indoor unit is gathered in ponding box and is
anything else in the box.
1. Connect the indoor unit first, then the outdoor unit.
2. Do not allow the piping to let out from the back of the indoor unit.
3. Be careful not to let the drain hose slack.
5. Be sure that the drain hose is located at the lowest side of the bundle. Locating
6. Never intercross nor intertwist the power wire with any other wiring.
7. Run the drain hose sloped downward to drain out the condensed water
smoothly.
Cushioning material
3. Piping can easily be made by lifting the indoor unit with a cushioning material between the indoor unit and the wall. Get it out after finish piping.
4. Push the lower part of the indoor unit up on the wall, Then move the indoor unit from side to side, up and down to check if it is hooked securely.
Indoor unit installation
Indoor unit
Cable
Ponding box
Pipe room
Wrapping belt
Drain hose
Connective pipe
securely and evenly as shown in the sideward figure.
piped out of room, do not put
connection
at the upper side may cause drain pan to overflow inside the unit.
4. Both of the auxiliary piping should be heat insulation.
14
Page 13
1. Install the outdoor part of the unit on a rigid surface to avoid excess noise and vibration.
2. Direct the air vent toward an area without obstacles.
especially in areas where it is frequently windy.
4. If the installation site is exposed to heavy winds, such as in coastal areas, place the unit along the widest part of the wall or use protective plates.
Outdoor unit installation
Strong wind
Outdoor unit installation
3. Install the unit at the site where it is exposed
to as little wind as possible,
schrubs or bushes.
blocks radiating air, including
15
5. Be sure there is no obstacle which
Page 14
Settlement of outdoor unit Anchor the outdoor unit tightly and horizontally on a concrete or rigid
Air inlet
Air
inlet
Air outlet
$
%
mount with a bolt and nut 0.39" or
Aft) B( ft)
Outdoor unit dimension ft(WxHxD)
[[
[[




'
[[
1'
0.32" diameter (Purchased separately).
Chassis
Drain connection
Drainage Plug
Condensate drainage of outdoor unit (no for cooling only)
The condensate and defrosting water formd during heating in the outdoor unit can be properly discharged by drainage pipe .
Installation method:Insert the drain connection into one of the 25 holes of the chassis and then connect drainage pipe with drain nozzle. Insert drainage plugs into the other holes
(Only for 12000Btu's).
Chassis
Drain connection
12000 Btu's
<
%WXV
Ø
16
Outdoor unit installation
Page 15
Flaring work
Main cause for refrigerant leakage is due to defect in the flaring work.
Carry out correct flaring work using the following procedure:
1. Cut the pipes and the cable. A) Use the piping kit accessory or
pipes purchased locally.
B) Measure the distance between the
indoor and the outdoor unit.
C) Cut the pipes a little longer than the
measured distance.
D) Cut the cable 4.9ft longer than the
pipe length.
2. Burr removal A) Completely remove all burrs from
the cut cross section of pipe/tube.
tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
indoor and outdoor unit, then put them on pipe/tube having
possible to put them on after flaring work)
Refrigerant piping connection
Refrigerant piping connection
Pipe
Correct
Wrong
Oblique Roughness Burr
Pipe
Reamer
Point down
Flare nut
Cooper tube
Remove flare nuts attached to
B) Put the end of the copper
3. Put nut on.
completed burr removal.(It is not
loop for excess.
Note: Keep original bend so not kinking of the tube occurs.
Unit comes with 16.4' tubing bundle. It is not recommended to cut. If too long,
17
Page 16
4. Flaring work.
die in the dimension shown in the table below.
OUTER
Connection Adjustment
1. Align the pipes to be connected.
OUTER TIGHTENING
Caution: Excessive twisting may break the nut, depending on the installation conditions.
Refrigerant piping connection
Bar
pipe
Handle
Clamp handle
Yoke
Red arrow mark
Flare
nut
Pipings
Indoor unit tubing
Copper
A (inch)
Max.
Min.
DIAMETER (inch)
0.051
0.063
0.071
0.095
0.028
0.039
0.039
0.087
2. Screw the flare nut with your fingers, and then tighten it with a spanner and torque wrench, as shown in the following figure.
ADDITIONAL TIGHTENING
DIAMETER (inch)
Firmly hold copper pipe in a
1/4
3/8
1/2
5/8
1/4
3/8
1/2
5/8
TORQUETORQUE (lbf.in)
139 174
260 304
434 477
651 694
(lbf.in)
18
Page 17
Operating
Voltage
(Min/Max)
RLA LRA FLA HP
Output
Watts
Volts FLA HP
Output
Watts
9K 115-1-60ǂ103/127 16.03 26 0.17 0.04 30 115V-AC 0.38 0.03 20 22
12K 115-1-60
ǂ
103/127 17.53 26 0.17 0.04 30 115V-AC 0.38 0.03 20 23
18K 208/230-1-60ǂ187/253 11.54 41 0.62 0.08 60
208/230V-AC
208/230V-AC
0.25 0.03 20 16
21.5K 208/230-1-60
ǂ
187/253
11.71 41 0.9 0.12 90 0.45 0.05 35 16
Electrical Data Table
Capacity
(BTU)
System Voltage
Volts-Ph.-
Freq
naFroodnInaFroodtuOrosserpmoC
MIN. Circuit
Ampacity
(MCA)
35
40
25
25
Max. Fuse/Circuit
Breaker
Amps(MOCP)
Connecting (Power and Control Cable)
The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of four
wires and provides the power for the indoor unit as well as the communication signal and ground between the outdoor and indoor unit.
Two wires are high voltage AC power, one is low voltage DC signal and one is a ground wire.
Consult local building codes, NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements.
Power voltage should meet the requirements in the following table.
3. Over current protection and circuit disconnect should meet the requirements in the following table and the applicable local and national electrical codes.
Page 18
1. The inside and outside connecting cable can be connected without removing the front grille.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed flexible cord, type
cord.
3. Lift the indoor unit panel up, remove the electrical box cover by loosening the screw.
4. Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoors respectively.
5. Wrap those cables not connected with terminals with insulation tapes, so that they will not touch any electrical components. Secure the cable onto the control board with the cord clamp.
Connect the cable to the indoor unit
Electrical work
cover
Electrical box
designation 16AWG or heavier
Code wire
1.57"
0.39"
20
Terminal block of indoor unit
N(1) 2 3
To Outdoor Unit
Cable
Page 19
1.
Page 20
1. Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.
liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3. Specification of power source.
4. Confirm that electrical capacity is sufficient.
5. See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
6. Confirm that the cable thickness is as specified in the power source specification.
7. Always install an earth leakage circuit breaker in a wet or moist area.
switch, which will damage the contact point, fuse breaking, disturbance of
9. The means for disconnection from a power supply shall be incorporated
in each active (phase) conductors.
Caution
After the confirmation of the above conditions, prepare the wiring as follows:
Air purging
below:
1. Pressure in the system rises.
2. Operating current rises.
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
5. Water may lead to corrosion of parts in the refrigeration system.
between the indoor and outdoor unit
moisture from the system.
Electrical work and air purging
2. The screws which fasten the wiring in the casing of electrical fittings are
8. The following would be caused by voltage drop: vibration of a magnetic
the normal function of the overload protector.
Air and moisture in the refrigeration system have undesirable effects as indicated
Therefore, the indoor unit and tubing
in the fixed wiring and have an air gap contact separation of at least
1/8 inch
must apply leakage test and be evacuated to remove any noncondensables and
3. Cooling or heating(only for
models with heating function) efficiency drops.
22
Page 21
Air purging with vacuum pump
1. Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
2. When relocating the unit to another place, perform evacuation using vacuum pump.
3. Pipe length and refrigerant amount:
the stopper. Do not try to open it further.
Air purging
Half union
Refrigerant
A
C
D
B
Packed valve
Gas
Indoor unitOutdoor unit
1. Operation of opening packed valve: Open the valve stem until it hits against
2. Operation of closing packed valve: Securely tighten the valve stem with a special tool. Then securely tighten the valve stem cap with a spanner or the like. Refer to
23
Flare nut
Stopper
Cap
Valve stem
Charge port
Valve body
Caution in handling the packed valve integrated in the outlets of outdoor unit.
for valve stem cap tightening torque tightening torque table in page 17
high side outlet. The low side outlet is shown in the sketch map below.
Note: There is a charging port integrated in the low side outlet, but not in the
Air
purging
Additional amount of
refrigerant to be charged
Connective pipe length
Use vacuum pump.
Use vacuum pump.
25'~98.4 '
Less than 25'
(=18000Btu's)
Use vacuum pump.25'~65.6
( 12000Btu's)
<
'
(=21500Btu's)
R410a: 0.32ozs/ft (Pipe length-25')
R410a: 0.22ozs/ft (Pipe length-25')
R410a: 0.32ozs/ft (Pipe length-25')
Page 22
Air purging
24
Vacuum pump
Charge hose
Manifold valve
-76cm/Hg
Charge hose
Handle Lo
Handle Hi
Outdoor unit
Indoor unit
When using the vacuum pump
For method of using a manifold valve, refer to its operation manual.
manifold valve.
evacuate. After starting evacuation, slightly loose the flare nut of the Lo valve on the gas pipe side and check if the air is entering (Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus), then tighten the flare nut. The procedure verifies if there are blocks inside the tubes.
valve B about 45 counterclockwise for 6~7
out, then tighten the flare nut again. Make sure the pressure
display in the pressure indicator is a little higher than the atmosphere pressure. This procedure verifies if the refrigerant goes through the tubes correctly.
o
manifold valve to the vacuum pump.
seconds after the gas comes
5. Make evacuation for 15 minutes or more and check that the compound meter indicates
-7.6 x 10 MicronsHg (-1x10 Pa).
5
1. Completely tighten the flare nuts at
connection point A, B, C and D. Connect valve core removal tool to the charging port, then connect vacuum hose to valve core tool. Open the schrader valve. Note: The schrader valve is inside the charging port.
2. Connect the other charge hose of
3. Fully open the handle Lo of the
4. Operate the vacuum pump to
packed valve.
9. Securely tighten the cap of the
stems B and A.
8. Fully open the packed valve
fully close the handle Lo of the manifold valve and stop the operation of the vacuum pump.
After the evacuation is completed,
6. Turn the stem of the packed
7. Close the schrader valve, then remove the valve core tool.
Replace the charging port cap.
Page 23
Electrical safety
Perform the electric safety check after completing installation:
Gas leak check
Soap water method
Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles come out, the pipes have
Leak detector
Use the leak detector to check for leakage.
Caution
A: Lo packed valve, B: Hi packed valve C and D are ends of indoor unit connection.
Outdoor unit check point
Cover
indoor unit check point
1. Insulated resistance: The insulated resistance must be more than 2M .
2. Grounding work: After finishing grounding work, measure the grounding resistance by visual detection and grounding resistance tester. Make sure the grounding resistance is less than 4 .
3. Electrical leakage check (performing during test running): During test operation after finishing installation, the serviceman can use the electric probe and multimeter to perform the electrical leakage check. Turn off the unit immediately if electrical leakage happens. Check and find out the solution ways till the unit operates properly.
Electrical safety and gas leak check
leakage point.
25
Page 24
Test running
Perform test operation after completing gas leak check at the flare nut connections and electrical safety check.
1. Connect the power, press the ON/OFF button on the remote controller to turn the unit on.
cannot be controlled by the remote controller to run in cooling mode, manual operation can be taken. Manual operation is used only when the remote controller is disable or maintenance necessary.
Test running
Manual control button
Auto/OFF
o
F), the unit 3. When the ambient temperature is too low(lower than 63
function), AUTO and FAN to check if all the functions work well.
2. Use the MODE button to select COOL, HEAT(Only for models with heating
26
Page 25
1. Contact a specialist to install the device.
2. Guarantee that the unit is appropriately fastened and complies with all of the aforementioned safety norms.
3. Before operating the air conditioner, ensure that the air filter is installed correctly.
4. If the unit has been out of use for a long period of time, it is recommended that the air filter be cleaned before use. During continuous use, clean the air filter every two weeks.
5. This air conditioner was designed for use under the following conditions:
If air conditioner is used outside of the above conditions, certain safety protection features may come into operation and cause the unit to function abnormally.
Optimum performance will be achieved within these operating temperature.
Preparing the device for operation
Preparing the device for operation
Cool
MODE
Indoor Indoor Outdoor Indoor Outdoor
Attention
Dehumidifier
Temperature Temperature Temperature
Heat
*
*
excess of this figure, the surface of the air conditioner may attract condensation.
Room relative humidity should be less than 80%. If the air conditioner operates in
Please set the horizontal louver to its maximum angle (vertically to the floor), and set HIGH fan mode.
61°F~86°F 41°F~115°F 61°F~86°F 61°F~86°F 41°F~115°F5°F~75°F
only for models with heating function
27
Outdoor
Loading...