PERFORMANCE DATA
NO LOAD & NO DOOR OPENINGS AT MID-POINT CONTROL SETTING
Type A With Run/Start Capacitor 65°F (18°C) Ambient 90°F (32°C) Ambient
Operating Time 25 to 35% 45 to 55%
Freezer Temperature 2° to 8°F (-17° to -13°C) 0° to 5°F (-18° to -15°C)
Refrigerator Temperature 35° to 40°F (2° to 4°C) 35° to 40°F (1° to 4°C)
Low Side Pressure (cut-in) 8 to 16 psig ( 55 to 110 kPa) 8 to 16 psig (55 to 110 kPa)
Low Side Pressure (cut-out) 1 to 4 psig (7 to 28 kPa) 1 to 4 psig (7 to 28 kPa)
High Side Pressure
(last 1/3 cycle)
Wattage (last 1/3 cycle) 88 to 115 88 to 115
Amps (running) 0.8 to 1.1 0.8 to 1.1
Base Voltage 115 vac (127 vac max) 115 vac (127 vac max)
Refrigerant Charge 4.25 oz. (121 g)
110 to 120 psig
(758 to 827 kPa)
150 to 175 psig
(1034 to 1207 kPa)
DEFROST SPECIFICATIONS
Defrost
Cabinet Size: 15’/16’/18’/20’
Safety Thermostat Heater
Cut-in Cut-out Watts Ohms Termina-
110°F
(43.3°C)
135°F
(57.2°C)
375 35
Thermistor
tion
47°F
(8.3°C)
CONDENSER FAN MOTOR
Watts RPM Amps
3.1 1100 CW Opposite Shaft 0.03 Running
EVAPORATOR FAN MOTOR
Watts RPM Amps
6.2 2600 CW 0.05 Running
ICE MAKER SPECIFICATIONS
Electrical 115 vac (127 vac max) 60 Hertz
Ice maker with
Thermostat
Heater Wattage 165 W
black housing
Ice maker with
white housing
Opens at 52°F (11°C) Closes at 12°F ( -11°C)
Opens at 48°F (8.9°C) Closes at 9°F ( -12.8°C)
ICE MAKER CONNECTOR PLUG CONNECTIONS
Wire Number Wire Color Connects to:
1 Green / Yellow Ground
2 Yellow Water Valve
3 Black Line
4 Light Blue Neutral
ICE MAKER INFORMATION
Test Cycling: Remove cover by
inserting screwdriver in notch at
bottom and prying cover from housing. Use screwdriver to rotate motor gear counterclockwise until holding switch circuit is completed. All components of ice maker should
function to complete the cycle.
Water Fill Volume: The water ll adjustment screw will change the ll time. One
full turn is equal to 20cc (.68 oz.). The correct ll is 102 to 130cc (3.4 to 4.3 oz.).
When a water valve is replaced, the ll volume must be checked.
SERVICE DATA SHEET
A01511103
STANDARD - AUTOMATIC DEFROST
TOP MOUNT FREEZER - R134a
IMPORTANT SAFETY NOTE
The information provided herein is designed to assist qualified repair personnel only.
Untrained persons should not attempt to make repairs due to the possibility of electrical
shock. Disconnect power cord before servicing this appliance.
IMPORTANT
If any green grounding wires are removed during servicing, they must be returned to their
original position and properly secured.
CAUTION
All electrical parts and wiring must be shielded from torch flame. DO NOT allow
torch to touch insulation; it will char at 200°F and flash ignite (burn) at 500°F.
Excessive heat will distort the plastic liner.
DOOR AJAR ALARM
Condition: Fresh Food Door is left open for more than 5 minutes and alarm sounds.
Duration: Alarm will sound for 2 minutes, then stop. If the “Door Ajar” condition remains,
the alarm will repeat every 30 minutes for two intervals.
Fresh Food Light: After 15 minutes of “Door Ajar” condition, the Fresh Food light will turn off.
Reset: Close the Fresh Food door or Press the Fresh Food Door switch.
MANUAL DEFROST
Unit will complete normal defrost cycle.
enter --> Press the FF door switch 5 times in 2 secs.; Alarm sounds 5 short beeps
to acknowledge MANUAL DEFROST.
exit --> Cycle power to the unit or enter and exit
SERVICE MODE. (See SERVICE MODE)
Defrost is terminated when defrost thermistor located on the evaporator coil reaches 47°F.
Safety Thermostat in the defrost circuit is a safety device only. It will interrupt power to the defrost
heater at 135° F.
IMPORTANT
PLEASE RETURN THIS SHEET TO ITS ORIGINAL LOCATION.
SERVICE MODE
SERVICE MODE will step through available tests to diagnose individual electrical circuits. Fresh
Food compartment light will be OFF while in SERVICE MODE.
enter/exit
initiate first/next test
1 Compressor Press the FF door switch twice to start the first test. In each test, the
2 Heater
3 FF Light
4 Evaporator Fan
Normal Cooling
Mode
Press Door Switch 3
Times and Hold 4th Press Until
Long Beep
Enters Service
Mode
Press Door Switch
2 Times
2 Beeps
Manual Defrost
Press Door Switch 5 Times to
Enter Manual Defrost. POR
or Enter Service Mode to Exit
Manual Defrost.
--> Press the door switch 3 times and hold the 4th press until 1 long
beep is heard. The door switch must be pressed 4 times in 2 seconds.
--> Press the door switch 2 times; 2 short beeps acknowledge selection.
component listed will be powered on. The component will stay powered
until the next test is activated, or until 5 minutes of inactivity expire. Listen
for operating sounds; feel for heat or air flow, as appropriate, to determine
the result of each test. Press the FF door switch twice again to advance
between tests. Two beeps will sound to confirm the next test has started.
Service Mode
Press Door Switch
2 Times
Test 1:
Compressor ON
Press Door Switch
2 Times
2 Beeps
Test 4: Evaporator
Fan ON
2 Beeps
To Exit Service Mode from
any Test Press Door Switch
3 Times and Hold 4th Press
Press Door Switch
2 Times
2 Beeps
Test 2: Power ON
to Defrost Heater
Test 3: Fresh
Food Light ON
Press Door Switch
2 Times
2 Beeps
P/N A01437001
IMPORTANT
START-UP NOTE: Upon 1st start-up or power cycle, the compressor will come
on after 12 seconds and run for 115 seconds. If the door switch is not cycled
during this time, the compressor will cut off after 115 seconds and not turn
back on for another 5 minutes. It may take up to 10 minutes for the compressor
to turn on and run in normal mode.
TEMPERATURE/RESISTANCE CHART
FOR FRESH FOOD THERMISTOR AND DEFROST THERMISTOR
°F kOHMS °F kOHMS °F kOHMS °F kOHMS
-10 83.88 11 47.25 32 27.20 53 16.87
-9 81.56 12 46.02 33 27.04 54 16.49
-8 79.32 13 44.84 34 26.38 55 16.13
-7 77.15 14 43.67 35 25.75 56 16.77
-6 75.04 15 42.55 36 25.13 57 15.41
-5 73.02 16 41.45 37 24.53 58 15.07
-4 71.02 17 40.39 38 23.95 59 14.74
-3 69.08 18 39.36 39 23.38 60 14.42
-2 67.16 19 38.36 40 22.83 61 14.10
-1 65.34 20 37.39 41 22.29 62 13.79
0 63.55 21 36.44 42 21.77 63 13.49
1 61.82 22 35.53 43 21.26 64 13.21
2 60.15 23 34.63 44 20.77 65 12.92
3 58.20 24 33.78 45 20.29 66 12.65
4 56.97 25 32.94 46 19.83 67 12.38
5 55.43 26 32.13 47 19.37 68 12.11
6 53.97 27 31.33 48 18.92 69 11.85
7 52.53 28 30.57 49 18.49 70 11.60
8 51.16 29 29.83 50 18.07 71 11.36
9 49.81 30 29.10 51 17.66 72 11.12
10 48.51 31 28.39 52 17.26 73 10.88
I
GROUND TO COMPRESSOR BASE
FZC
M
C
DH1
FF
THERMISTOR
DEFROST
THERMISTOR
EFC
FF1
ERF-1500
FRONT VIEW
CN1
CN5
DH2
CONTROL
BOX
SAFETY
BIMETAL
ERF1500
MC1
CC
CN2
BACK VIEW
CFC
CN4
CN3
WVC
MOLEX-43335-2002
TYCO-520935-4
CC
WVC
FF DOOR SWITCH
TEMPERATURE
CONTROL
DEFROST
THERMISTOR
FF
THERMISTOR
CONTROL BOX
CONTROL BOX
YELLOW/GREY
GREY
GREY
ORANGE
RED
GREY/WHITE
GREY/WHITE
PIN 7
PIN 4
GREY/WHITE
GREY/WHITE
FZC
RED
GREY/BLACK
MOLEX 19-09-2019 MOLEX 19-09-1019
DH1/DH2
TYCO-1-480703-0
GREY
IMC
RED RED
PIN 7
GREY/WHITE
PIN 4
FF1
YELLOW/GREY
GREY
ORANGE
GREY/WHITE
GREY/BLACK
ERF-1500
DC SIDE
12
11 CN2
8
10
RED
2
9
DOOR
CN2
1
GND
CTRL
CN2
DEFROST
CN2
SENSOR
LAMP
NEUTRAL
LINE
COMP
HEATER
AC SIDE
CN1 7
CN5
CN1 5
CN1 3
YELLOW/BLACK
YELLOW/BLACK
LT.BLUE
CONTROL BOX
FRESH FOOD
LIGHT
GROUND TO
CABINET
BLACK
LT. BLUE
GREEN/YELLOW
LIVE (NON RIBBED)
NEUTRAL (RIBBED)
GROUND
LT. BLUE
PIN 3
RED
PIN MXN
COMPRESSOR
CC
LT. BLUE
LT. BLUE
LT.BLUE
3
BLACK
1
BLACK
LT.BLUE
PIN 2
PIN 1
BLACK
LT.BLUE
BLACK
LT.BLUE
PIN 6
PIN 3
BLACK
LT.BLUE
SPLICE
GREEN/YELLOW
LT. BLUE
GREEN/YELLOW
PIN 2
RED
PIN 3
PIN 1
CONDENSER
FAN
CFC
RED
RED
PIN 6
RED
RED
YELLOW
YELLOW
PIN 1
PIN 4
MC1
PIN 6
RED
YELLOW
YELLOW
LT. BLUE
YELLOW
PIN 1
PIN 2
WVC
WATER
VALVE
(ICEMAKER)
DEFROST HEATER
BROWN
BROWN
PIN 3
BROWN
BROWN
LT.BLUE
BLACK
PIN 3
PIN 1
PIN 9
BROWN
BLACK
LT. BLUE
PIN 1
DH1
LT.BLUE
DEFROST BIMETAL
YELLOW
LT. BLUE
BLACK
GREEN/YELLOW
PIN 2
PIN 4
PIN 3
PIN 1
IMC
BLUE
PIN 1
DH2
ICE MAKER
INLINE CONNECTOR ABBREVIATION KEY
ABBREVIATION EXPLANATION
MC1
6 PIN CONNECTION LEFT OF COMPRESSOR
IN MACHINE COMPARTMENT
FF1
9 PIN CONNECTION IN CONTROL BOX
CC
2 PIN CONNECTION TO COMPRESSOR
CFC
3 PIN CONNECTION TO CONDENSER FAN
WVC
2 PIN CONNECTION TO ICE MAKER WATER
VALVE (GREEN)
IMC
ICE MAKER CONNECTION IN FREEZER
FZC
9 PIN CONNECTION IN FREEZER
EFC
EVAPORATOR FAN CONNECTION IN FREEZER
DH1
DEFROST HEATER CONNECTION IN FRZ LEFT
OF EVAP FAN
DH2
DEFROST HEATER CONNECTION IN FRZ RIGHT
OF EVAP FAN
TYCO 1-480705-0 TYCO 350715-1
TYCO 1-480700-0 TYCO 1-480701-0
MC1
CFC
JST-VLR-09 JST-VLP-09
TYCO-1-480701-0 TYCO-1-480700-0
FF1/FZC
EFC
CONTROL BOX
FAN
CN1 9
RED/WHITE
RED/WHITE
PIN 9
FF1
RED/WHITE
GROUND TO
CABINET IN
MACHINE
COMPARTMENT
RED/WHITE
GREEN/YELLOW
PIN 2
PIN 5
FZC
GREEN/YELLOW
RED/WHITE
GREEN/YELLOW
COIL COVER GROUND
LT. BLUE
PIN 1
RED/WHITE
GREEN/YELLOW
PIN 2
PIN 3
EVAPORATOR FAN
EFC
Wire Diagram A02646801