SERVICE DATA TECH SHEET
Gas Free-Standing Ranges with Venturi Burner System
Before servicing, disconnect electrical supply
at circuit breaker, fuse or power cord.
This service data sheet is intended for use by
persons having electrical and mechanical training and a level of
knowledge of these subjects generally considered acceptable
in the appliance repair trade. The manufacturer cannot be
responsible, nor assume any liability, for injury or damage of
any kind arising from the use of this data sheet.
SAFE SERVICING PRACTICES
To avoid the possibility of personal injury and/or property damage, it is important
that safe servicing practices be observed. The following are examples, but without
limitation, of such practices.
1. Before servicing or moving an appliance remove power cord from electrical
outlet, trip circuit breaker to OFF, or remove fuse.
2. Never interfere with the proper installation of any safety device.
3. GROUNDING: The standard color coding for safety ground wires is GREEN
or GREEN WITH YELLOW STRIPES. Ground leads are not to be used as
current carrying conductors. It is extremely important that the service
technician reestablish all safety grounds prior to completion of
service. Failure to do so will create a potential safety hazard.
4. Prior to returning the product to service, ensure that:
• All electric connections are correct and secure.
• All electrical leads are properly dressed and secured away from sharp
edges, high-temperature components, and moving parts.
• All uninsulated electrical terminals, connectors, heaters, etc. are adequately
spaced away from all metal parts and panels.
• All safety grounds (both internal and external) are correctly and securely
reassembled.
Gas Regulator & Shut-off Valve Location
The gas regulator is located on the back of the appliance (See Fig.1).
The shut-off valve is located on the gas regulator as shown (Fig. 2).
After properly installing or if converting the appliance to L.P. Gas, be
sure to set the shut-off valve back to the “ON” position before operating.
Fig. 1
Fig. 2
IMPORTANT
DO NOT REMOVE THIS BAG
OR DESTROY THE CONTENTS
WIRING DIAGRAMS AND SERVICE INFORMATION ENCLOSED
REPLACE CONTENTS IN BAG
p/n 316904011 (0907)
Surface Burner Heads
Lighter
Ports
Flash Tube
Assemby
Charge Ports
Surface Burner System
Spark
Electrodes
Surface Gas Valves & Air Shutter
Air Shutter adjustment
Venturi
Air
Shutters
Fig. 4
Surface Burner Flame Adjustments
1. The air shutter adjustment for each of the 4 surface burners is located
at the open end of the venturi tube near the valve gas orifice (See Fig.
4). Should the air shutter need adjustment, rotate the air shutter to
allow more or less air into the burner tube. If the air is properly adjusted,
the flame will be steady, relatively quiet, and have approximately 1/2"
sharp blue cone (usually the center of air shutter's adjustment). If the
flame is yellow in color, increase air shutter opening size. If the flame
is a distinct blue but lifting away from the burner, reduce the air shutter
opening size.
2. Check gas pressure with all burners ON (See Check the Regulator
Inlet & Outlet).
Surface Burner Troubleshooting
Check the Regulator Inlet & Outlet -
Check gas pressure to manifold or surface burner. Ranges should be
checked under maximum flow (all burners turned ON and with changes
in flow). The outlet of ranges using Natural Gas should check 4” WCP;
ranges on LP gas 10” WCP. If gas pressure is incorrect check inlet supply
to gas regulator. Inlet pressure should be at least 1” WCP above outlet
pressure. If pressure at inlet of the gas regulator exceeds 8” WCP Natural
Gas or 11” WCP LP gas, the gas supplier should be contacted.
Surface Burners Slow to Ignite or Not Igniting -
1. Check for spark at the 2 surface spark electrodes. If the spark
electrodes are operating, go to step 2 below. If the spark electrodes
are not operating, go to step 5 below.
2. Check gas pressure with all surface burners turned ON (See
Check the Regulator Inlet & Outlet).
3. Clean surface burner head charge ports & lighter ports. The ports may
be cleaned using a strand of wire or some similar object. DO NOT
ENLARGE BURNER PORTS when cleaning (See Fig. 3).
4. Check alignment of burner flash tube assemblies (See Fig. 3).
5. Disconnect power & turn OFF power to the appliance. Remove the
panel at the top right rear of the range that covers the spark module.
6. Reconnect electrical power. Turn one of the surface burner valves to
“LITE” and check between “L” and “N” on the spark module for 120
VAC. If the meter reads 120 VAC, go to step 7. If the meter reads 0
VAC, check the wiring to and from the surface burner switches and the
surface burner switches. Note: It is unlikely that all 4 surface burner
switches will fail simultaneously since the surface burner switches are
wired in parallel.
7. Listen to the spark module. If a snapping sound is heard and the
surface electrodes are not arcing, the high voltage lead to surface
electrodes is open. If the snapping sound is not heard go to step 8.
Spark
Wire
leads to
Spark
Module
Gas
Valve
Orifice
Fig. 5
Caps
Surface
Gas
Burner
Valve
Surface
Burner &
Venturi
Spark
switches
Manifold
Valve
screw
8. Disconnect electrical power and remove the 2 wires from output
terminals 1 & 2. Using an Ohm Meter check the high voltage wiring
between the spark module and the burner electrodes for a short to the
chassis. If no shorted wiring is found replace the spark module.
Oven Burner Troubleshooting
The oven burner is ignited by an electronic glowbar ignition system. The
ignition circuit consists of the oven thermostat, the oven igniter and the
oven safety valve. These 3 components are wired in series. The most
important points to know about the oven ignition system are:
1. The oven igniter resistance decrease as the igniter surface temperature
increases.
2. The gas safety valve operates by current not voltage.
From a cold start, the oven igniter needs 30-60 seconds with voltage
applied, to reduce its electrical resistance enough to provide a minimum
of 2.9 amps of current flow in the series circuit. This is the required current
flow needed for the gas safety valve to open to supply gas to the oven
burner. NOTE: The oven igniter needs 2.9 amps or greater to the open
gas safety valve.
The oven igniter should provide a steady current flow of between 3.2 to 3.6
amps in the circuit. At that point the oven igniter temperature is between
1800° to 2500°F. The oven igniter will remain energized at all times during
burner operation. If the oven igniter glows red but does not draw at least
2.9 amps, the fault is usually with the oven igniter, not the oven safety
valve. If the oven igniter does not glow check the thermostat and circuit
wiring for an open circuit. NOTE: Be sure that the oven shut-off valve lever
located on the gas regulator is set to ON position (See Fig. 1).
Oven Burner Will Not Cycle Off -
1. Disconnect electrical power from appliance. If the oven burner does
not cycle OFF, the gas safety valve is defective. If the oven burner
cycles OFF go to step 2.
2. Check polarity to the appliance. If polarity is incorrect, check range
wiring for a short to chassis. If polarity is correct go to step 3.
3. Allow oven to heat to 300°F, disconnect power and lift the cooktop to
obtain access to the oven thermostat. Set the oven thermostat to
200°F and remove wires from the oven thermostat.
4. Check across the thermostat terminals with an Ohm Meter. If the
meter reads continuity, the oven thermostat is defective.
Oven Burner System
Spark
Spark
Module
Module
Wiring
Gas Safety
Valve
Gas Valve
Cover
Increase gas volume
for Natural Gas
Fig. 7
Oven Burner Adjustments
1. Check orifice hood
adjustment on the oven
safety valve to be sure it is
adjusted for the type of gas
supplied to the range
(Natural or LP - See Fig. 7).
2. Check the oven safety valve
orifice hood for straight
injection of gas into the oven
burner. If the orifice hood is
tipped, the oven burner will
not draw in air properly.
3. Check air shutter
adjustments on oven burner
(See Fig. 8).
4. Check gas pressure (as
described earlier).
Air
Shutter
Orifice
Hood
Air
Shutter
Lock
Screw
Oven Igniter
Oven
Burner
Fig. 6
SpudPin
Decrease gas
volume
for LP Gas
Air
Shutter
Fig. 8
Flame
Spreader
Burner
Support
Oven
Burner
Tube
Orifice
Hood
Oven Calibration -
1. Place the probe for the oven tester in the center of the oven.
2. Turn thermostat to 350°F and allow it to cycle 3 times. Record the
temperatures at the highest and lowest point of the third cycle and
determine the average.
3. If the average temperature does not fall within 330° to 390°F,
replace the oven thermostat.
Natural Gas BTU Ratings
This appliance is factory preset for use with Natural Gas with a 9,000
BTU rating for each surface burner and 18,000 BTU rating for the oven
burner. NOTE: For operation at elevations above 2000 ft., appliance
rating shall be reduced at the rate of 4 percent for each 1000 ft. above
sea level.