INSTALLATION AND SERVICE MUST BE PERFORMED BY
A QUALIFIED INSTALLER.
IMPORTANT: SAVE FOR LOCAL ELECTRICAL INSPECTOR'S USE.
READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE.
40 1/8" Min.
101.9 cm Min.
_l with handle
"1='(70.5:m)
27 3A"
(45.7 cm Min.) (33 cm Min.)
13" Min.
Grounded 24" Min.
Wall Outlet (61 cm Min.)
Do not pinch the power supply cord between the range
and the wall.
Do not seal the range to the side cabinets.
I-_q6, '
47 ¼" Max.
(120 cm)
43 3A"
(111.1 cm)
with larger\ J
door open "_ _JJ/
feet extended
(91.4 cm)
**NOTE: 24" (61 cm) minimum clearance between the
cooktop and the bottom of the cabinet when the bottom
of wood or metal cabinet isprotected by not lessthan
1/4" (0.64 cm) flame retardant millboard covered with not
less than No. 28 MSG sheet metal, 0.015" (0.4 mm)
stainless steel, 0.024" (0.6 mm) aluminum, or 0.020" (0.5
mm) copper.
30" (76.2 cm) minimum clearance when the cabinet is
unprotected.
36"(91.4cm) 40 %" (101.9cm) 251/2"(64.8cm) 433/4"(111.1cm) 40 _/4"(102.2cm) 36"(91.4cm)standard
353/8"(90crn)rnin.
P/N318200870 (0201) Rev.E
Important Notes to the Installer
1. Read all instructions contained in these installation
instructionsbefore installing range.
2. Remove all packing material from the oven
compartments before connecting the electrical supply to
the range.
3. Observe all governing codes and ordinances.
4. Be sure to leave these instructions with the consumer.
Before installing the range in an area covered
with linoleum or any other synthetic floor
covering, make sure the floor covering can
withstand heat at least 90°F/32°C above room
temperature without shrinking, warping or
discoloring. Do not install the range over carpeting
unless you place an insulating pad or sheet of 1/4" (6.4
mm) thick plywood between the range and carpeting.
Important Note to the Consumer
Keep these instructions with your owner's guide for future
reference.
IMPORTANT SAFETY
INSTRUCTIONS
• Be sure your range is installed and grounded
properly by a qualified installer or service
technician.
• This range must be electrically grounded in
accordance with local codes or, in their absence,
with the National Electrical Code ANSI/NFPA No.
70--latest edition.
• The installation of appliances designed for
manufactured (mobile) home installation must conform
with Manufactured Home Construction and Safety
Standard, title 24CFR, part 3280 [Formerly the Federal
Standard for Mobile Home Construction and Safety,
title 24, Hun (part 280)] or when such standard is not
applicable, the Standard for Manufactured Home
Installation 1982 (Manufactured Home Sites,
Communities and Setups), ANSI Z225.1/NFPA 501A-
latest edition, or with local codes.
• Make sure the wall coverings around the range
can withstand the heat generated by the range.
_Never leave children alone or
unattended in the area where an appliance is in use.
As children grow, teach them the proper, safe use of all
appliances. Never leave the oven door open when the
range is unattended.
_Stepping, leaning or sitting on the
door(s) or drawer of this range can result in serious
injuries and can also cause damage to the range.
• Do not store items of interest to children in the
cabinets above the range. Children could be
seriously burned climbing on the range to reach items.
• To eliminate the need to reach over the surface
units, cabinet storage space above the units
should be avoided.
• Do not use the oven as a storage space. This
creates a potentially hazardous situation.
• Never use your range for warming or heating the
room. Prolonged use of the range without adequate
ventilation can be dangerous.
• Do not store or use gasoline or other flammable
vapors and liquids near this or any other
appliance. Explosions or fires could result.
• Reset all controls to the "off" position after using
a programmable timing operation.
• Save 4 shipping bolts from range packaging to
use as leveling legs for range.
@
• ALL RANGES
CAN TIR
• INJURYTO
PERSONS
COULD
RESULT.
• INSTALLANTI-
TIPDEVICE
PACKEDWITH
RANGE.
I _'!'VAV!-'_l|_II_[€ITO REDUCE
THE RISK OF TIPPINGOF
THE RANGE, THE RANGE
MUST BESECUREDBY
PROPERLYINSTALLEDANTI-
TIPBRACKET(S)PROVIDED
WITH THE RANGE. TO
CHECK IFTHE BRACKET(S)
ISINSTALLEDPROPERLY,
REMOVETHE LOWER
PANELOR STORAGE
DRAWERAND VERIFYTHAT
THE ANTI-TIP BRACKET(S)
ISENGAGED.
Two anti-tip brackets MUST be removed from
lower back of range and MUST be installed. For
detailed instructions, see page 8.
FOR MODELS WITH SELF-CLEAN FEATURE:
• Remove broiler pan, food and other utensils
before self-cleaning the oven. Wipe up excess
spillage. Follow the precleaning instructions in the
Owner's Guide.
2
Power Supply Cord Kit
The user is responsible for connecting the power supply
cord to the connection block located behind the back
panel access cover.
This appliance may be connected by means of
permanent "hard wiring" (flexible armored or
nonmetallic shielded copper cable), or by means of a
power supply cord kit. Onlya power supply cord kit
rated at 125/250 volts minimum, 40 amperes and
marked for use with ranges shall be used. Cord must
have 3 conductors (see Figures 1 and 5).
Mobile homes, new installations, recreational vehicles,
or areas where local codes do not permit grounding
through neutral, a 4 conductor power supply cord kit
rated at 125/250 volts minimum, 40 amperes and
marked for use with ranges should be used (see Figures
2 and 6).
Terminals on ends of wires must either be closed loop or
open-end spade lugs with upturned ends. Cord must
have strain relief clamp.
cover and the neutral conductor by a white cover. Cord
should be Type SRD or SRDT with a U.L.-listed strain
relief and be at least 4 feet long.
The minimum conductor sizes for the copper 4-wire
power cord are:
40 ampere circuit
2 No. 8 conductors
1 No. 10 white neutral
1 No. 8 green ground
[i i]
I
4-Wire Wall
Receptacle (14-50R)
Risk of fire or electrical shock may be
incurred if an incorrect size range cord kit is used,
the Installation Instructions are not followed, or
the strain relief bracket is discarded.
i
3-Wire Wall
3-Wire Power
Supply Cord Kit
Figure 1
If Connecting to a 4-Wire System
This range is manufactured with the ground connected to
the cabinet. The ground must be revised so the green
ground wire of the 4-wire power supply cord is
connected to the cabinet. See "Four Conductor Wire
Connection to Range" on page 4.
When a 4-wire receptacle of NEMA Type 14-50R is used
(see Figure 1), a matching U.L.-listed, 4-wire, 250 volt,
40 ampere range power supply cord (pigtail) must be
used. This cord contains 4 copper conductors with ring
terminals at the appliance end, terminating in a NEMA
Type 14-50P plug on the supply end. The fourth (ground)
conductor must be identified by a green or green/yellow
Receptacle
Figure 2
Electrical Connection to the Range
This appliance is manufactured with the neutral terminal
connected to the frame.
.
Three Conductor Wire Connection to Range
(The 3-conductor cord or cable must be replaced
with a 4-conductor cord or cable where grounding
through the neutral conductor is prohibited in mew
installations, mobile homes, recreational vehicles or
in other areas where local codes do not permit
neutral grounding.)
If local codes permit connection of the frame
grounding conductor to the neutral wire of the
copper power supply cord (see Figure 4).
A. Remove the 3 screws at the lower end of the
rear wire cover, then raise the lower end of the
rear wire cover (access cover) upward to expose
range terminal connection block (see Figure 3).
3
TO GAIN ACCESS TO LOWER TERMINAL BLOCK
BEND LOWER BACK COVER PLATE ALONG ROW
OF HOLES SHOWN HERE.
Figure 3
B. Remove the 3 loose nuts (after you removed the
rubber band) on the terminal block using 3/8"
nut driver or socket.
C. Connect the neutral of the copper power supply
cord to the center silver-colored terminal of the
terminal block, and connect the other wires to
the outer terminals. Math wires and terminals by
color (red wires connected to the right terminal,
black wires connected to the left terminal).
D. Lower the terminal cover and replace the 3
screws.
,
Four Conductor Wire Connection to Range
(mobile homes)
A. Remove the 3 screws at the lower end of the
rear wire cover, then raise the lower end of the
rear wire cover (access cover) upward to expose
range terminal connection block.
B. Remove the ground strap from the terminal
block and from the appliance frame. Retain the
ground screw.
C. Connect the ground wire (green) of the copper
power supply cord to the frame of the appliance
with the ground screw, using the hole in the
frame where the ground strap was removed (see
Figure 5).
D. Connect the neutral (white) wire of the copper
power supply cord to the center silver-colored
terminal of the terminal block, and connect the
other wires to the outer terminals.
E. Lower the terminal cover and replace the 3
screws.
Silver Colored Terminal
SilverColored Terminal
A CONSUMER
SUPPLIED STRAIN-RELIEF
MUST BE INSTALLED
AT THIS LOCATION
TO FUSED DISCONNECT BOX OR
APPROVED WIRING DEVICE FOR
3-WIRE COPPER POWER SUPPLY CORD (40 AMPERES)
Grounding
Figure 4
Do not loosen nuts, wich secure the
factory-installed range wiring to terminal block while
connecting range. Electrical failure or loss of electrical
connection may occur.
A CONSUMER
SUPPLIED STRAIN-RELIEF
MUST BE INSTALLED
AT THIS LOCATION
TO FUSED DISCONNECT BOX OR
APPROVED WIRING DEVICE FOR
4-WIRE COPPER POWER SUPPLY CORD (40 AMPERES)
NOTE: BE SURE TO REMOVE THE SUPPLIED GROUNDING STRAP
Ground
Figure 5
Electrical Connection to the Residence
Electrical System
The appliance may be connected directly to the fused
disconnect or circuit breaker box through flexible,
armored or nonmetallic sheathed copper cable (with
grounding wire). Locate the junction box to allow 2 to 3
feet of slack in the line so that the range can be moved
if servicing is ever necessary. Do not cut the conduit.
A U.L.-listed conduit connector must be provided at
each end of the power supply cable (at the appliance
and at the junction box). Wire sizes (copper wire only)
and connections must conform with the rating of the
appliance.
4
Electrical Shock Hazard
• Electrical ground is required on this appliance.
• Do not connect to the electrical supply until
appliance is permanently grounded.
• Disconnect power to the junction box before
making the electrical connection.
• This appliance must be connected to a
grounded, metallic, permanent wiring system,
or a grounding connector should be connected
to the grounding terminal or wire lead on the
appliance.
Failure to do any of the above could result in a
fire, personal injury or electrical shock.
Grounding Instructions
For appliances connected to a junction box, use U.L-
listed conduit connectors. Complete electrical connection
according to local codes and ordinances.
.
Where local codes permit connecting the
cabinet-grounding conductor to the neutral
(white) junction box wire (see Figure 6)
(The 3-conductor cord or cable must be replaced
with a 4-conductor cord or cable where grounding
through the neutral conductor is prohibited in mew
installations, mobile homes, recreational vehicles or
in other areas where local codes do not permit
neutral grounding.)
A. Disconnect the power supply.
B. Connect together the 3 wires: green (bare) and
white appliance cable wires and the neutral
(white) wire in the junction box.
C. Connect the 2 black wires together, then the
two red wires together.
Cable from
PowerSupply
Ground
(White Wire)
.
Where local codes DO NOT permit, or if
connecting to a 4-wire electrical system, DO
NOT connect the cabinet-grounding conductor
to the neutral (white) junction box wire (see
Figure 7)
A Disconnect the power supply.
B. Separate the bare copper and white appliance
cable wires.
C. Connect the white appliance cable wire to the
neutral (white) wire in the junction box.
D. Connect the 2 black wires together, then the
two red wires together.
E. Connect the bare copper grounding wire to the
grounding wire in the junction box.
Junction Cable from
Bare --_
Wire
Wire
Power Supply
Wire
Conduit
Cable from Connector
Range (or CSA listed)
Figure 7 - 4-WIRE ELECTRICAL SYSTEM
.
Locate junction box as shown in Figure 8.
If a service cord is used, the wall receptacle should
be located in accordance with the dimensions
below.
Center
Range
Line of
_Junction
Bareor
GreenWire
Cablefrom Connector
Range (or CSAlisted)
Figure 6 - GROUNDED NEUTRAL
Conduit
Box
5
7, Max:
(17,8 CmMax:) I
Center
Locate Electrical Hook-up Range
Inside Shaded Area
Line of
Figure 8