Water Supply Requirements ...........................................................................................................................................3
Exhaust System Requirements ...................................................................................................................................4
Gas Supply Requirements ............................................................................................................................................5
Mobile Home Installation............................................................................................................................................7
Before beginning installation, carefully read these instructions. This will simplify the installation and ensure the laundry center is
installed correctly and safely. Leave these instructions near the laundry center afterinstallation for future reference.
NOTE: The electrical service to the laundry center must conform with local codes and ordinances and the latest edition of the
National Electrical Code, ANSI/NFPA 70, or in Canada, the Canadian Electrical Code, CSA C22.1
NOTE: The gas service to the laundry center must conform with local codes and ordinances and the latest edition of the National
Fuel Gas Code ANSI Z223.1/NFPA 54, or in Canada, the Canadian Natural Gas and Propane Installation Code, CSA B149.1.
NOTE: The laundry center is designed under ANSI Z21.5.1 or ANSI/UL 2158- CAN/CSA C22.2 No. 112 (latest edition) for HOME
USE only. This laundry center is not recommended for commercial applications such as restaurants or beauty salons, etc.
Your safety and the safety of others is very important.
We have provided many important safety messages in the Use & Care Guide, Operating Instructions, Installation Instructions and
on your appliance. Always read and obey all safety messages.
This is the safety alert symbol. This symbol alerts you to hazards that can kill or hurt you or others. All safety messages will be preceded by the safety alert symbol and the word "DANGER" or "WARNING". These words mean:
You will be killed or seriously injured if you don't follow instructions.
DANGER
You can be killed or seriously injured if you don't follow instructions.
All safety messages will identify the hazard, tell you how to reduce the chance of injury, and tell you what can happen if the
instructions are not followed.
For your safety the information in this manual must be followed to minimize the risk of fire or explosion or to
prevent property damage, personal injury or loss of life.
- Do not store or use gasoline or other flammable vapors and liquid in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Clear the room, building or area of all occupants. Immediately call your gas supplier from a neighbor’s phone.
• Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be preformed by a qualified installer, service agency or the gas supplier.
2
PRE-INSTALLATION REQUIREMENTS
Tools and Materials Required for Installation:
1. Phillips head screwdriver.
2. Channel-Iock adjustable pliers.
3. Carpenter’s level.
4. Flat or straight blade screwdriver.
5. Duct tape.
6. Rigid or flexible metal 4 inch (10.16 cm) duct.
7. Vent hood.
8. Pipe thread sealer (Gas).
9. Ratchet with 3/8 inch (0.96 cm) socket.
ELECTRIC Laundry Center
Circuit- Individual 30 amp branch circuit fused with 30 amp
minimum time delay fuses or circuit breakers.
POWER SUPPLY - 3-wire or 4-wire , 240 volt, single phase, 60
Hz, Alternating Current.
POWER SUPPLY CORD KIT- The laundry center MUST employ
a 3-condutor power supply cord NEMA 10-30 type SRDT rated
at 240 volt AC minimum, 30 amp, with 3 open end spade lug
connectors with upturned ends or closed loop connector
4-condutor power supply cord NEMA 14-30 type SRDT or ST (as
required) rated at 240 volt AC minimum, 30 amp, with 4 open
end spade lug connectors with upturned ends or closed loop
connectors and marked for use with clothes dryers. If being
installed in a new branch circuit installation, manufactured
(mobile) home, recreational vehicle or area which prohibits
grounding through the neutral conductor, the laundry center
MUST employ a 4-condutor power supply cord NEMA 14- 30
type SRDT or ST (as required) rated at 240 volt AC minimum,
30 amp, with 4 open end spade lug connectors with upturned
ends or closed loop connectors and marked for use with clothes
dryers. See ELECTRICAL CONNECTIONS. (Canada - 4-wire
power supply cord is installed on laundry center).
OUTLET RECEPTACLE - NEMA 10-30R (3-wire) receptacle or
NEMA 14- 30R (4-wire) receptacle to be located so the power
supply cord is accessible when the laundry center is in an installed
position.
OR a
GAS Laundry Center
CIRCUIT - Individual 15 amp minimum branch circuit fused with
a time delay fuse or circuit breaker.
POWER SUPPLY -3 wire, 120 volt single phase, 60 Hz,
Alternating Current.
POWER SUPPLY CORD -The gas laundry center is equipped
with a 120 volt 3-wire power cord.
WATER SUPPLY REQUIREMENTS
Hot and cold water faucets MUST be installed within 42 inches
(106.68 cm) of your laundry center’s water inlet. The faucets
MUST be 3/4 inch (1.9 cm) garden hose type so inlet hoses can
be connected. Water pressure MUST be between 10 and 120
pounds per square inch (maximum unbalance pressure, hot vs.
cold, 10 psi). Your water department can advise you of your
water pressure.
NEMA 10-30R
Do not allow combustible materials (for
example: clothing, draperies/curtains, paper) to come in
contact with exhaust system. The dryer MUST NOT be
exhausted into a chimney, a wall, a ceiling, or any concealed
space of a building which can accumulate lint, resulting in a fire
hazard.
Exceeding the length of duct pipe or number
of elbows allowed in the "MAXIMUM LENGTH" charts can
cause an accumulation of lint in the exhaust system. Plugging
the system could create a fire hazard, as well as increase drying
times.
Do not screen the exhaust ends of the vent
system, nor use any screws, rivets or other fastening means
that extend into the duct and catch lint to assemble the
exhaust system. Lint can become caught in the screen, on the
screws or rivets, clogging the duct work and creating a fire hazard
as well as increasing drying times. Use an approved vent hood
to terminate the duct outdoors, and seal all joints with duct
tape. All male duct pipe fittings MUST be installed downstream
with the flow of air.
Explosion hazard. Do not install the dryer
where gasoline or other flammables are kept or stored. If
the dryer is installed in a garage, it must be a minimum of 18
inches (45.7 cm) above the floor. Failure to do so can result in
death, explosion, fire or burns. The exhaust system back pressure
MUST not exceed 0.6 inches (1.52 cm) of water column,
measured with an inclined manometer at the point the exhaust
connects to the dryer. The exhaust system should be inspected
and cleaned a minimum of every 18 months with normal
usage. The more the dryer is used, the more often you should
check the exhaust system and vent hood for proper operation.
The maximum length of the exhaust system depends upon the
type of duct used, number of elbows and type of exhaust hood.
The maximum length for both rigid and flexible duct is shown in
the chart below.
EXHAUST DUCT LENGTHS
EXHAUST HOOD TYPE
Number
of 90°
Turns
4”
(10.2 CM)
MAXIMUM LENGTH OF 4-INCH (10.2 CM)
DIAMETER RIGID METAL DUCT
0
1
2
3
MAXIMUM LENGTH OF 4-INCH (10.2 CM)
0
1
2
3
56 ft. (17.07 m)
46 ft. (14.02 m)
34 ft. (10.36 m)
32 ft. (9.75 m)
DIAMETER FLEXIBLE METAL DUCT
30 ft. (9.14 m)
22 ft. (6.7 m)
16 ft. (4.88 m)
10 ft. (3.05 m)
Louvered
42 ft. (12.8 m)
36 ft. (10.97 m)
28 ft. (8.53 m)
18 ft. (5.48 m)
22 ft. (6.7 m)
14 ft. (4.27 m)
10 ft. (3.05 m)
5 ft. (1.5 m)
2.5”
(6.35 CM)
4
The laundry center may be exhausted four (4) ways with rear
flush installation:
1. Straight back
2. Down (8 inch [20.32 cm] length of 4 inch [10.16 cm] rigid
duct and 1 elbow down)
3. Left (8 inch [20.32 cm] length of 4 inch [10.16 cm] rigid
duct, 1 elbow down and 1 elbow left)
4. Right (8 inch [20.32 cm] length of 4 inch [10.16 cm] rigid
duct, 1 elbow down and 1 elbow right)
To exhaust up, add an 11 inch (27.94 cm) length of standard 4
inch (10.16 cm) diameter duct and a 90° elbow. The unit will
be positioned about 4½ inches (11.43 cm) away from the wall
(flush to wall exhausting may be done by going below the dryer
then sideways).
An exhaust hood positioned
to line up with the dryer
exhaust can be installed
directly through the outside
wall. To exhaust to the side
or down, add an 8 inch
(20.32 cm) length of standard
4 inch (10.16 cm) diameter
duct and a 90° elbow.
GAS SUPPLY REQUIREMENTS
1.Installation MUST conform with local codes, or in the absence
of local codes, with the National Fuel Gas Code, ANSI Z223.1
(latest edition) or in Canada, the current AN/CGA B149.
2.The gas supply line should be of 1/2 inch (1.27 cm) pipe.
3.If codes allow, flexible metal tubing may be used to connect
your dryer to the gas supply line. The tubing MUST be
constructed of stainless steel or plastic-coated brass.
4.The gas supply line MUST have an individual shutoff valve.
5.A 1/8 inch (0.32 cm) N. P. T. plugged tapping, accessible for
test gage connection, MUST be installed immediately
upstream of the gas supply connection to the dryer.
6.The dryer and its individual shutoff valve MUST be
disconnected from the gas supply piping system during any
pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.45 kPa).
7.The dryer MUST be isolated from the gas supply piping system
by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pressures
equal to or less than 1/2 psig (3.45 kPa).
LOCATION OF YOUR LAUNDRY CENTER
DO NOT INSTALL YOUR LAUNDRY CENTER:
1.In an area exposed to dripping water or outside weather conditions.
2.In an area where it will come in contact with curtains or drapes.
3.On carpet. Floor MUST be solid with a maximum slope of 1 inch (2.54 cm).
INSTALLATION IN RECESS OR CLOSET
1.A laundry center installed in a bedroom, bathroom, recess or closet, MUST be exhausted outdoors.
2.No other fuel burning appliance shall be installed in the same closet as the Gas laundry center.
3.Your laundry center needs the spacearound it for proper ventilation.
DO NOT INSTALL YOUR LAUNDRY CENTER IN A CLOSET WITH A SOLID DOOR.
4.A minimum of 120 square inches (774.2 square cm) of opening, equally divided at the top and bottom of the door, is required.
Air openings are required to be unobstructed when a door is installed. A louvered door with equivalent air openings for the full
length of the door is acceptable.
5.The following illustrations show minimum clearance dimensions and air openings for proper operation in a recess or closet
installation.
60 SQ. IN.
(387.1 SQ. CM)
0 IN.
(0 C M)
0 IN.
(0 C M)
DRYER
1 IN.
(2.54 CM)
60 SQ. IN.
(387.1 SQ. CM)
0 IN.
(0 C M)
Closet Door
60 SQ. IN.
(387.1 SQ. CM)
WASHER
60 SQ. IN.
(387.1 SQ. CM)
5
2 ½ IN.
(6.35 CM)
1 7/8 IN.
(4.76 CM)
4 13/16 IN.
(12.22 CM)
11 7/16 IN.
(29.5 CM)
25 ¼ IN.
(64.13 CM)
47“
16 ¼ IN.
(41.27 CM)
ROUGH-IN DIMENSIONS
(78.26 CM)
30 13/16 IN.
36 1/16IN.
(91.60 CM)
43 IN.
PIPE (REAR)
GAS SUPPLY
5 ¼ IN.
(13.33 CM)
(109.22 CM)
41 ¼ IN
(104.77 CM)
29 7/16 IN
(74.77 CM)
9 3/8 IN.
(23.81 CM)
(REAR)
DRAIN OUTLET
VENT
12 ½ IN.
(31.7 5 CM)
ELECTRICAL
CONNECTION
75 ½ IN.
(191.77 CM)
54 5/16 IN.
(REAR)
WATER INLETS
43 IN.
(109.22 CM)
(137.95 CM)
3 ¾ IN.
(9.52 CM)
27 IN.
(68.58CM)
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.