Friedrich Metal Products RT2 Installation Manual

Installation Instructions
SINGLE STAGE HEAT/COOL THERMOSTAT
Please read these instructions completely before attempting installation.
WARNING
Before installing thermostat, turn off all power to unit. There may be more than one power disconnect. Electrical shock can cause per­sonal injury or death.
Improper wiring or installation may damage thermostat. Wiring must conform to local and national electrical codes.
0.8
Selects System Mode: OFF. HEAT, or COOL
4.55
Turns Continuous Fan On or OFF
Model RT2
Increase Temperature
Decrease Temperature
3.30
INSTALLATION CONSIDERATIONS
The thermostat is a wall mounted, low-voltage thermostat, which maintains room temperature by controlling the opera­tion of a heating and air conditioning system. Batteries are not required; temperature and mode settings are preserved with the power off.
I. THERMOSTAT LOCATION
Thermostat should be mounted:
- Approximately 5 ft. (1.5m) from fl oor.
- Close to or in a frequently used room, preferably on an inside partitioning wall.
- On a section of wall without pipes or duct work.
Thermostat should NOT be mounted:
- Close to a window, on an outside wall, or next to a door leading to the outside.
- Exposed to direct light and heat from a lamp, sun, fi replace, or other temperature-radiating object which may cause a false reading.
- Close to or in direct airfl ow from supply registers and return-air grilles.
- In areas with poor air circulation, (behind a door or in an alcove.)
II. INSTALL THERMOSTAT
1. Turn off all power to unit.
2. If an existing thermostat is being replaced: A. Remove existing thermostat from wall.
B. Disconnect wires from existing thermostat, one at
a time. Be careful not to allow wires to fall back into the wall.
C. As each wire is disconnected, record wire color and
terminal marking.
D. Discard or recycle old thermostat.
NOTE: Mercury is a hazardous waste and MUST be disposed of properly.
3. Separate the thermostat and back plate.
4. Route thermostat wires through hole in back plate. Level
back plate against wall (for aesthetic value only - thermo­stat need not be leveled for proper operation) and mark wall through 2 mounting holes.
5. Drill two 3/16-in. mounting holes in wall where marked.
2
(Note: Mounting holes on back plate are designed to fi t on a horizontal J-box).
1.587
2.375
2.625
3.275
6. Secure back plate to wall with 2 anchors and screws provid­ed making sure all wires extend through hole in back plate.
7. Connect wires to proper terminal of the connector block
8. Push any excess wire back into wall. Excess wire inside the thermostat plastic case can interfere with proper air fl ow across the temperature sensor. Seal hole in wall to prevent air leaks. Leaks can affect operation.
9. Install thermostat on back plate.
10. Turn on power to the unit.
o
P
On initial power up, the LCD readout will display
.
III CHECK THERMOSTAT OPERATION
1. Fan Operation
A. Press fan button, starting fan operation. Fan icon turns
on.
B. Press Fan button, stopping fan operation. Fan icon turns
off.
2. Heating Operation
A. Press and Release MODE button until HEAT is dis-
played.
B. Press up button until LCD readout reads 10 degrees
above room temperature. Heating system should begin to operate within 5 minutes.
3. Cooling Operation
A. Press and Release MODE button until COOL is dis-
played
B. Press down button until LCD readout reads 10 degrees
below room temperature. Cooling system should begin to operate within 5 minutes.
IV. THERMOSTAT OPERATION
1. TEMPER ATURE DISPLAY
The thermostat will display room temperature until the UP or DOWN button is pressed. The word SET appears when these buttons are pressed and the current set point is displayed. If no buttons are pressed for 5 seconds, the display will change back to show room temperature.
2. TIMEGUARD TIMER
A 5-minute timeguard is built into the thermostat immediately upon power up, and any time the compressor turns off. The compres­sor will not turn on until the timeguard has expired. Pressing UP and FAN buttons simultaneously will override the timeguard for 1 cycle.
WIRING DIAGRAMS
NOTE: All excess wire should be pushed back into the wall as far as possible. Excess wire inside the thermostat plastic case may interfere with the air fl ow across the temperature sensor.
SINGLE STAGE HEAT/COOL WIRING
Thermostat
HEAT
COOL
FAN
24 VAC HOT
4 VAC COMM
Revers ing Va lve
W
Y
G
R
C
B
Unit Terminal Strip
W
Y
G
R
C
Connection to “B”
B
terminal required on
Heat Pump models
3. CYCLE TIMER
In normal heating and cooling operation the thermostat will not allow more than 4 equipment cycles per hour (or 1 cycle every 15 minutes). Both the Y and W outputs have a 15-minute timer that starts counting down when the output is turned on, (e.g., if Y output is turned on for 9 minutes and then satisfi es, it cannot turn back on for another 6 minutes regardless of demand). However, pressing UP and FAN buttons simultaneously or changing the set point will override the timer for 1 cycle.
4. MINIMUM ON TIMER
Once the equipment has turned on, it will remain on for a minimum of 3 minutes regardless of demand. However, the equipment can turn off in less than 3 minutes if a change in set point, or a change in mode occurs.
5. ERROR MESSAGES
E4 will be displayed if the thermostat has an internal memory failure. If E4 appears, replace the thermostat.
- - (two dashes) will be displayed if the temperature cannot properly read the room temperature. If - - appears, replace the thermostat.
2
Loading...
+ 2 hidden pages