Friedrich Metal Products M09YH Installation Manual

SPLIT TYPE ROOM AIR CONDITIONER
G
1
G
3
2
1
2
3
208/230V
208/230V
208/230V
L2
L1
LO
HI
INSTALLATION MANUAL
(P/N 9332279009-01) ENGLISH
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all danger, warning, and caution notices given in
this manual.
WARNING:
CAUTION:
Hazel alerting symbols
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury and the potential for product or property damage.
Electrical
Safety / alert
If Necessary, Get Help
These instructions are all you need for most installation sites and mainte­nance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause overheating at con-
nection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing...
...In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
...In a Room
Properly insulate any tubing run inside a room to prevent “sweating that can cause dripping and water damage to walls and floors.
...In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnor­mal vibration.
...In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
...In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Keep all tubing runs as short as possible.
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of the flare and
union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either nar­row or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is specified as either “small” or “large” rather than as liquid or gas.
When Servicing
Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring.
Keep your fingers and clothing away from any moving parts.
Clean up the site after you finish, remembering to check that no metal
scraps or bits of wiring have been left inside the unit being serviced.
After installation, explain correct operation to the customer, using the operating manual.
This air conditioner uses new refrigerant HFC (R410A).
5 cm or over
The basic installation work procedures are the same as conventional refrigerant (R22) models.
However, pay careful attention to the following points:
(1) Since the working pressure is 1.6 times higher than that of conventional refrigerant(R22) mod-
els, some of the piping and installation and service tools are special.(See the table below.) Especially, when replacing a conventional refrigerant(R22) model with a new refrigerant R410A
model, always replace the conventional piping and flare nuts with the R410A piping and flare nuts.
(2) Models that use refrigerant R410A have a different charging port thread diameter to prevent
erroneous charging with conventional refrigerant(R22) and for safety. Therefore, check beforehand.[The charging port thread diameter for R410A is 1/2 threads per inch.]
(3) Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant(R22) models. Also, when storing the piping ,securely seal the opening by pinching, taping, etc.
(4) When charging the refrigerant, take into account the slight change in the composition of the
gas and liquid phases, and always charge from the liquid phase side whose composition is stable.
Special tools for R410A
Tool name
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/10m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the ex­pansion value or capillary tube may become blocked with con­taminants. As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in Table1.Never use copper pipes thinner than 0.8mm even when it is available on the market.
(1) Do not use the existing (for R22) piping and flare nuts.
• If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury, etc.(Use the special R410A materials.)
(2) When installing and relocating the air conditioner, do not mix gases other than the specified refrigerant(R410A)
to enter the refrigerant cycle.
• If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value and cause breakage, injury, etc.
When installing pipes shorter than 10ft (3m), sound of the outdoor unit will be transferred to the indoor unit, which will cause large operating sound or some abnormal sound.
mixing of other refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals-0.1 to 5.3 MPa (-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.
To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.
Contents of change
Table 1 Thicknesses of Annealed Copper Pipes
WARNING
CAUTION
Nominal
diameter
1/4
3/8
Outer diameter
(mm)
6.35
9.52
Thickness (mm)
R410A
0.80
0.80
[ref.] R22
0.80
0.80
INDOOR UNIT
1.
CUTTING THE HOLE IN THE WALL FOR THE CONNECTING PIPING
(1) Cut a 2-9/16” (65 mm) diameter hole in the wall at the position shown
in (Fig. 1).
(2) When cutting the wall hole at the inside of the installation frame, cut
the hole within the range of the left and right center marks of the installation frame. When cutting the wall hole at the outside of the installation frame, cut the hole at least 3/8” (10 mm) lower.
(3) Cut the hole so that the outside end is lower (3/16” to 3/8” (5 to
10 mm)) than the inside end.
(4) Always align the center of the wall hole. If misaligned, water leakage
will occur.
(5) Cut the wall pipe to match the wall thickness, stick it into the wall
cap, fasten the cap with vinyl tape, and stick the pipe through the hole. (The connection pipe is supplied in the installation set.) (Fig. 5)
(6) For left piping and right piping, cut the hole a little lower so that
drain water will flow freely. (Fig. 1)
2. INSTALLING THE WALL HOOK BRACKET
(1) Install the wall hook bracket so that it is correctly positioned hori-
zontally and vertically. If the wall hook bracket is titled, water will drip to the floor.
(2) Install the wall hook bracket so that it is strong enough to with-
stand the weight of an adult.
Fasten the wall hook bracket to the wall with 6 or more screws
through the holes near the outer edge of the bracket.
Check that there is no rattle at the wall hook bracket.
Fig. 1
Center mark
at least 3/8” (10 mm) lower
Fasten with vinyl tape
(Wall pipe)
(Wall cap)
Wall hook bracket
Fig. 2
2-9/16” (65 mm) dia. hole 2-9/16” (65 mm) dia.
(Inside)
Wall
WARNING
If the wall pipe is not used, the cord interconnecting the indoor and outdoor units may touch metal and cause electric leakage.
Install the wall hook bracket horizontally and perpen­dicularly.
CAUTION
3. FORMING THE DRAIN HOSE AND PIPE
[Rear piping, Right piping, Bottom piping]
Install the indoor unit piping in the direction of the wall hole and
bind the drain hose and pipe together with vinyl tape. (Fig. 3)
Install the piping so that the drain hose is at the bottom.
Wrap the pipes of the indoor unit that are visible from the outside
with decorative tape.
[For Left rear piping, Left piping]
Interchange the drain cap and the drain hose.
CAUTION
(1) In order to align the drain hose and drain cap, be
sure to insert securely and vertically. Incline in­sertion will cause water leakage.
(2) When inserting, be sure not to attach any mate-
rial besides water. If any other material is attached, it will cause deterioration and water leakage.
(3) After removing drain hose, be sure not to forget
mounting drain cap.
(4) Be sure to fix the drain hose with tape to the bot-
tom of piping.
(5) Prevent drain water frozen under low tempera-
ture environment.
When installing indoor unit's drain hose outdoors, necessary measure for frost protection should be taken to prevent drain water frozen.
Under low temperature environment (when outdoor temperature under 32 °F), after cooling operation is executed, water in the drain hose could be frozen. Once drain water is frozen, the drain hose will be blocked and water leakage may be resulted for indoor unit.
Installation method of Drain cap
Use a hexagonal wrench (3/16” (4 mm)
at opposite side) to insert the drain cap, till the drain cap contacts the tip of drain cock.
Hexagonal wrench
No gap
Drain cock
Drain cap
Fig. 3
Right piping
Bind with vinyl tape
Bottom piping
Indoor unit drain hose
Pipe (top) Rear piping
Indoor unit drain hose (bottom)
Drain cap
Removal method of drain hose
Remove the screw at the left of drain hose and pull out drain hose.
Screw
Drain fixture (white)
Be sure to install around the drain hose connector.
As the screw is inside, be sure to use screwdriver treated with magnet.
Drain hose
Center mark
at least 3/8” (10 mm)
lower
hole
3/16’’ to 3/8’’ (5 to 10 mm) low
(Outside)
Tapping screw
For left outlet piping, cut off the piping outlet cutting groove with a hacksaw.
Remove the drain cap by pulling at the projection at the end of the cap with pliers, etc.
Installation method of drain hose
Vertically insert the drain hose toward the inside, so that the drain fixture (white) can accu­rately align with the screw hole around the drain cock. After inserting and before re­placing, please reinstall and fix the removed screws.
Screw hole
Drain cock
Drain fixture (white)
Drain hose
Screw
For left piping and left rear piping, align the marks on the wall
hook bracket and shape the connection pipe.
Bend the connection piping at a bend radius of 2 - 3/4’’(70 mm) or
more and install no more than 1- 3/8’’(35 mm) from the wall.
After passing the indoor piping and drain hose through the wall
hole, hang the indoor unit on the hooks at the top and bottom of the wall hook bracket.
[Installing the indoor unit]
Hang the indoor unit from the hooks at the top of the wall hook
bracket.
Insert the spacer, etc. between the indoor unit and the wall hook
bracket and separate the bottom of the indoor unit from the wall.
Indoor unit
(Spacer)
Wall hook bracket
CONNECTING THE PIPING
CONNECTION
(1) Install the outdoor unit wall cap (supplied with the optional installa-
tion set or procured at the site) to the wall pipe. (2) Connect the outdoor unit and indoor unit piping. (3) After matching the center of the flare surface and tightening the nut
hand tight, tighten the nut to the specified tightening torque with a
torque wrench. (Table 2)
FLARING
(1) Cut the connection pipe to the nec-
essary length with a pipe cutter. (2) Hold the pipe downward so that
cuttings will not enter the pipe and
remove the burrs. (3) Insert the flare nut onto the pipe
and flare the pipe with a flaring
tool.
Insert the flare nut (always use the flare nut attached to the indoor and outdoor units respectively) onto the pipe and perform the flare processing with a flare tool. Use the special R410A flare tool, or the conventional (for R22) flare tool. When using the conventional flare tool, always use an allowance adjustment gauge and secure the A dimension shown in table 3 .
BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
OK NO
Do not bend the pipes in an angle more than 90°. When pipes are repeatedly bent or stretched, the material will harden, making it difficult to bend or stretch them any more. Do not bend or stretch the pipes more than three times.
Extend the pipe by unwinding it.
Check if [L] is flared uniformly and is not cracked or scratched.
Die
A
Pipe
Fig. 4
Connection pipe (1/4” (6.35 mm) dia.)
Bend (R70) with a pipe bender
Indoor unit
After hooking the indoor unit to the top hook, hook the fittings of the indoor unit to the two bottom hooks while lowering the unit and pushing it against the wall.
Fig. 5
Table 2 Flare nut tightening torque
1/4” (6.35 mm) dia.
3/8” (9.52 mm) dia.
Table 3 Pipe outside diameter
Pipe outside
diameter
1/4” (6.35 mm) 3/8” (9.52 mm)
Tighten with two wrenches.
Torque wrench
Indoor unit pipe
Flare nut
R410A, clutch type
Wrench (fixed)
Flare nut
Connection pipe
Flare tool for
0 to 1/32 0 to 1/32
Align the marks.
Connection pipe (3/8” (9.52 mm) dia.)
Top hooks
Bottom hooks
To prevent gas leakage, coat the flare surface with refrigerator oil.
Tightening torque
11.57 to 13.20 ft (160 to 180 kgf
21.70 to 30.38 ft (300 to 420 kgf
A (in)
Conventional (R22) flare tool
Clutch type
1/32 to 2/32
1/32 to 2/32
Wall hook bracket
lbs
cm)
lbs
cm)
Wing nut type
2/32 to 3/32
2/32 to 3/32
CAUTION
(1) Fasten a flare nut with a torque wrench as instructed in this manual. If
fastened too tight, the flare nut may be broken after a long period of time and cause a leakage of refrigerant.
(2) During installation, make sure that the refrigerant pipe is attached firmly
before you run the compressor. Do not operate the compressor under the condition of refrigerant piping not attached properly with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
GENERAL
This INSTALLATION MANUAL briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1.
TYPE OF COPPER PIPE AND INSULATION MATERIAL
Copper tubing for connectin the outdoor unit to the indoor unit and insulation material is available for purchase locally. When you purchase them, please specify the following.
A.
Deoxidized annealed copper pipe for refrigerant piping as:
Table 4
Small pipe Large pipe
Outer diameter Thickness Outer diameter Thickness
1/4”(6.35 mm) 1/32”(0.8 mm) 3/8”(9.52 mm) 1/32”(0.8 mm)
Cut each pipe to the appropriate length +12” (30 cm) to16” (40 cm) to dampen vibration between units.
B. Foamed polyethylene insulation for copper pipes as
required to precise length of piping. Wall thickness of the insulation should not be less than 5/16” (8 mm).
C. Use insulated copper wire for field wiring.
CAUTION
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
2. ADDITIONAL MATERIALS REQUIRED FOR INSTALLATION
A. Refrigeration (armored) tape B. Insulated staples or clamps for connecting wire
(See your local electrical codes.) C. Putty D. Refrigeration lubricant E. Clamps or saddles to secure refrigerant piping
3. OPERATING RANGE
Table 5
Cooling/Dry Mode
Outdoor temperature
Indoor temperature
Indoor humidity
About 14 to 115 °F
About 64 to 90 °F
About 80% or less
ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 49 ft (15 m) is charged in the outdoor unit at the factory. When the piping is longer than 49 ft (15 m), additional charging is necessary. For the additional amount, see the table below.
Table 6
Pipe length
Additional
refrigerant
Between 49 ft (15 m) and 66 ft (20 m), when using a connection pipe other than that in the table, charge additional refrigerant with 0.2 oz/ ft (20g/1 m) as the criteria.
49 ft (15 m)
None
66 ft (20 m)
3.5 oz (100 g)
CAUTION
(1) When adding refrigerant, add the refrigerant from
the charging port at the completion of work.
(2) The maximum length of the piping is 66 ft (20 m).
If the units are further apart than this, correct operation can not be guaranteed.
Heating Mode
About 5 to 75 °F
86 °F or less
STANDARD ACCESSORIES
The following installation accessories are supplied. Use them as required.
Name and Shape
Wall hook bracket
Remote control unit
Battery (penlight)
Remote control unit holder
The following items are necessary to install this air conditioner. (The items are not included with the air conditioner and must be purchased separately.)
Q’ty
1
1
2
1
Name and Shape
Cloth tape
Tapping screw (big)
Tapping screw (small)
Drain pipe
Name
Connection pipe assembly
Connection cord (3-conductor)
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant
Qty
1
8
2
1
Q’ty
1
1
1
1
1
1
1 set
1
1 set
1
ELECTRICAL REQUIREMENT
Always make the air conditioner power supply a special branch cir­cuit and provide a special switch and receptacle. Do not extend the power cord. Always select the size that corresponds to the capacity of the breaker to the size of the power cord.
CAUTION
9000 BTU/h 12000 BTU/h
MINIMUM CIRCUIT AMPACITY 10 A 12 A
MAXIMUM OVERCURRENT PROTECTION (TIME DELAY FUSE OR HACR TYPE CIRCUIT BREAKER)
15 A 15 A
SELECTING THE MOUNTING POSITION
Decide the mounting position with the customer as follows:
1. INDOOR UNIT
(1) Install the indoor unit level on a strong wall which is not subject
to vibration.
(2) The inlet and outlet ports should not be obstructed : the air should
be able to blow all over the room. (3) Install the unit near an electric outlet or special branch circuit. (4) Do not install the unit where it will be exposed to direct sunlight. (5) Install the unit where connection to the outdoor unit is easy. (6) Install the unit where the drain pipe can be easily installed. (7) Take servicing, etc. into consideration and leave the spaces shown
in (Fig. 7). Also install the unit where the filter can be removed.
2. OUTDOOR UNIT
(1) If possible, do not install the unit where it will be exposed to di-
rect sunlight. (If necessary, install a blind that does not interfere
with the air flow.) (2) Do not install the unit where a strong wind blows or where it is
very dusty. (3) Do not install the unit where people pass. (4) Take you neighbors into consideration so that they are not dis-
turbed by air blowing into their windows or by noise. (5) Provide the space shown in Fig. 7 so that the air flow is not blocked.
Also for efficient operation, leave open three of the four direc-
tions front, rear, and both sides.
WARNING
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall.
CAUTION
(1) Do not install where there is the danger of com-
bustible gas leakage. (2) Do not install near heat sources. (3) If children under 10 years old may approach the
unit, take preventive measures so that they can-
not reach the unit. (4) Install the indoor unit on the wall where the height
from the floors more than 70”(180 cm).
[Indoor unit piping direction]
The piping can be connected in the six directions indicated in (Fig. 6). When the piping is connected in direction 2 , 3 , 4 or 5 , cut along the piping groove in the side of the front cover with a hacksaw.
Fig. 6
(Rear)
2 Right outlet
Fig. 8
1 Rear outlet
3 Bottom outlet
18” (45.4 cm)
4 Left bottom outlet
5 Left outlet
4 Left rear outlet
12-9/16” (32 cm)
INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS
Fig. 7
[INDOOR UNIT]
2”(5 cm)
2-2/5”(6 cm) or over
60”(150 cm) or over
Connection Cord
14AWG
or over
70” (180 cm) or over
Remote control unit
[OUTDOOR UNIT]
24”(60 cm) or over
4”(10 cm) or over
8”(20 cm) or over
• Do not directly install it on the ground, otherwise it will cause failure.
• To obtain better operation efficiency, when the outdoor unit is installed, be sure to open the front and left side.
When the outdoor temperature is 32°F (0°C) or less, do not use the
(1)
accessor y drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremety cold weather. (Reverse cycle model only)
(2)
In the area with heavy snowfall, if the intake and outlet of outdoor unit
is blocked with snow, it might become difficult to get warm and it is likely to cause of the breakdown. Please construct a canopy and a ped­estal or place the unit on a high stand (local configured).
2”(5 cm) or over
Drain hose
CAUTION
Wall hook bracket
3- 9/16”(9 cm) or over
(Wall cap)
Remote control unit holder
Tapping screw (small)
4”(10 cm) or over
Outdoor unit bottom
10”(25 cm) or over
OUTDOOR UNIT
OUTDOOR UNIT INSTALLATION
Set the unit on a strong stand, such as one made of concrete blocks
to minimize shock and vibration.
Do not set the unit directly on the ground because it will cause trou-
ble.
Connector cover removal
Remove the tapping screw.
Installing the connector cover
(1) After inserting the four hooks, then push upward. (2) Tighten the tapping screw.
WARNING
(1) Install the unit where it will not be tilted by more
than 5°.
(2) When installing the outdoor unit where it may ex-
posed to strong wind, fasten it securely.
AIR PURGE
Always use a vacuum pump to purge the air. Refrigerant for purging the air is not charged in the outdoor unit at the factory.
Close the high pressure side valve of the gauge manifold fully and do not operate it during the following work.
1. Check if the piping connections are secure.
2. Check that the stems of 2-way valve and 3-way valve are closed fully.
3. Connect the gauge manifold charge hose to the charging port of the 3-way valve (side with the projection for pushing in the valve core).
4. Open the low pressure side valve of the gauge manifold fully.
5. Operate the vacuum pump and start pump down.
6. Slowly loosen the flare nut of the 3-way valve and check if air enters, then retighten the flare nut. (When the flare nut is loosened the operating sound of the vacuum pump changes and the reading of the compound pressure gauge goes from minus to zero.)
7. Pump down the system for at least 15 minutes, then check if the compound pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).
8. At the end of pump down, close the low pressure side gauge of the gauge manifold fully and stop the vacuum pump.
9. Slowly loosen the valve stem of the 3-way valve. When the compound pressure gauge reading reaches 0.1-0.2 MPa, retighten the valve stem and disconnect the charge hose from the 3-way valve charging port. (If the stem of the 3-way valve is opened fully before the charge hose is disconnected, it may be difficult to disconnect the charge hose.)
Fig. 9
Tapping screw
Rear hook
Connector cover
Always use the screws as shown above. Do not select the top and bottom screws incorrectly.
10. Fully open the valve stems of the 2-way valve and 3-way valve using a hexagon wrench. (After the valve stem begins to turn, turn it with a torque of less than 2.17ftlbs (30 kgfcm) until it stops turning.)
11. Firmly tighten the 2-way valve and 3-way valve blank cap and the charging port cap.
Fig. 10
3-way valve
Charging port cap
2-way valve
Compound pressure gauge
Flare nut
Low pressure side valve
Valve stem
Blank cap
Charge hose
Charging port
-0.1 MPa (-76 cmHg
-1 bar)
Gauge manifold
Pressure gauge
High pressure side valve (closed)
Charge hose
Vacuum pump
Table 7
Tightening torque
Blank cap 14.47 to 18.08 ft
Charging port cap 9.04 to 11.57 ft
lbs (200 to 250 kgfcm)
lbs (125 to 160 kgfcm)
CAUTION
(1) Refrigerant must not be discharged into atmos-
phere.
(2) After connecting the piping , check the joints for
gas leakage with gas leak detector.
(3)
When adding refrigerant, add the refrigerant from the charging port at the completion of work.
(4)
The maximum length of the piping is 66 ft (20 m). If the units are further apart than this, correct
operation can not be guaranteed.
ELECTRICAL WIRING (OUTDOOR UNIT)
1. Remove the screws, then remove the control box cover.
2. Fasten the Inter unit wire harness and power supply to the conduit holder using the lock nut.
3. Connect inter-unit wire harness and power supply to the terminal. Refer to the wiring diagram
4. Use the screws to install the control box cover.
WARNING
Be sure to comply with local codes while run­ning the wire from the indoor unit to the out­door unit (size of wire and wiring method, etc.).
Every wire must be connected firmly.
No wire should be allowed to touch refrigerant tubing, the compressor or any moving part.
Loose wiring may cause the terminal to over­heat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
Connect wires to the matching numbers of terminals.
Fig. 11
Indoor unit
Terminal
Earth Screw
G
3
2
1
DISCONNECT SWITCH (FIELD SUPPLY)
G
Grounding line
Control line
(Inter Unit) Power line
12
208/230V
208/230V
208/230V
3
Outdoor unit
Terminal
G
L2
L1
3
2
1
Connection cord
NOTE:
Connector trade size for this unit is 1/2” (12.7 mm). The connec­tor can be bought at a hardware store. Refer to How to connect wiring to the terminals for instructions on connecting depend­ing on the wire type you are using.
The fuse located in the outdoor unit provides power supply pro­tection and may blow when power is applied if the system has been incorrectly wired.
POWER SUPPLY
Single-phase, 208/230V
12
Lock nut
terminal block
3
Earth Screw
Control box cover
Inter-unit wire harness
Power supply
Inter-unit wire harness
L1 L2
Earth Screw
G
ELECTRICAL WIRING (INDOOR UNIT)
HOW TO THE INSTALL THE INTER-UNIT WIRE HARNESS
1. Remove the screws, then remove the conduit holder.
2. Fasten the inter-unit wire harness to the conduit holder using the lock nut. IMPORTANT: Refer to Fig. 19 about the length of inter-unit wire harness.
3. Use the screws to install the conduit holder with which Inter-unit wire har­ness is included.
4. Remove the screws, then remove the wire clamper.
5. Connect inter-unit wire harness to the terminal. Refer to the wiring diagram.
6. Use the screws to install the wire clamper.
ELECTRICAL WIRING (INDOOR UNIT)
1. Remove the screws, then remove the cord clamp.
2. Connect connection cord to the terminal. Refer to the wiring diagram
3. Use the screws to install the cord clamp.
Fig. 13
Wire cover
Screw
Cord clamp
Screw
Fig. 12
Wire cover
Screw
LOCK NUT
SCREW
CONDUIT HOLDER
EARTH WIRE
CONDUIT CONNECTOR
Cord clamp
Screw
FINISHING
(1) Insulate between pipes.
For rear, right, and bottom piping, overlap the connection pipe
heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.
For left and left rear piping, butt the connection pipe heat insula-
tion and indoor unit pipe heat insulation together and bind them with and vinyl tape so that there is no gap.
For left and left rear piping, wrap the area which accommodates
the rear piping housing section with cloth tape.
For left and left rear piping, bind the connection cord to the top
of the pipe with vinyl tape.
For left and left rear piping, bundle the piping and drain hose
together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
(2) Temporarily fasten the connection cord along the connection pipe
with vinyl tape. (Wrap to about 1/3 the width of the tape from the
bottom of the pipe so that water does not enter.) (3) Fasten the connection pipe to the outside wall with a saddle, etc. (4) Fill the gap between the outside wall pipe hole and the pipe with
sealer so that rain water and wind cannot blow in. (5) Fasten the drain hose to the outside wall, etc.
Fig. 16
(Outside wall cap)
(Saddle)
(Sealer putty)
Fig. 15
Connection pipe (heat insulation)
Bind the pipes together to that there is no gap.
Pipe
Drain hose
Check the following:
GOOD
Overlap the insulation
Indoor unit pipe (heat insulation)
Vinyl tape
Wrap with cloth tape
Cloth tape
Left piping
Connection cord
Pipe
Drain hose
For connection from the left rear
Wall pipe
Drain hose
Connection cord
Connection pipe
View from indoors
BAD
BAD BAD
The method of adjusting inter-unit wire harness
To connect inter-unit wire harness to the terminal correctly, please refer to Fig. 19 to adjust the length of the part of Inter-unit Wire harness ahead from conduit holder.
EARTH WIRE
Fig. 19
14AWG
(1:1)
15/16" (25mm)
Connection cord
Connection cord
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 15/16 (25 mm) to expose the solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using pliers, bend the solid wire to form a loop suitable for the termi-
nal screw.
(4) Shape the loop wire properly, place it on the terminal board and
tighten securely with the terminal screw using a screwdriver.
B. For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 3/8 (10 mm) to expose the strand wiring.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using a round terminal fastener or pliers, securely clamp a round
terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the termi-
nal screw using a screwdriver.
Fig. 14
A. Solid wire
Insulation
Strip 15/16" (25 mm)
Wire
Insert the tab into the square hole of the indoor unit and fasten with a screw.
Loop
Strip 3/8" (10 mm)
Screw with special washer
Round terminal
Terminal board
Wire
Terminal block
B. Strand wire
Screw with special washer
Connection cord
Round terminal
Round terminal
(Outdoors)
Pipe
Wall
FRONT PANEL REMOVAL AND INSTALLATION
INTAKE GRILLE REMOVAL
(1) Open the intake grille. (2) Pull down the knob. (3) Lift the intake grille upward, until the axle at the top of the in-
take grille is removed.
INTAKE GRILLE INSTALLATION
(1) The fixing axle of the intake grille is installed on the Panel. (2) Lay down the intake grille.
FRONT PANEL REMOVAL
(1) Remove intake grille (Reference the intake grille removal.) (2) Remove wire cover. (3) Remove three screws. (4) The front panel is pulled to the front, raising the upper surface,
and a front panel is removed.
THE FRONT PANEL INSTALLATION
(1) Firstly, fit the lower part of the front panel, and insert top and
bottom hooks. (Three top sides, eight bottom sides) (2) Three screws is attached. (3) The wire cover is attached. (4) The intake grille is attached.
Bottom holes
Indoor unit
(two position)
Front panel
Screws (Wire cover)
Top hole (center)
Indoor unit
Drain hose
Saddle
Fig. 17
Wire cover
Lifted up
Intake grille
Mounting shaft
Bearing
Front panel
Screws (3 position)
Top holes (two sides)
Wave
Top hook (center)
End in water
Intake grille
Knob
Front panel
Top hooks (two sides)
Front panel
7-7/8" (200mm)
7-15/32" (190mm) 15/16" (25mm)
CONDUIT PLATE
CAUTION
(1) Match the terminal block numbers and connection
cord colors with those of the outdoor unit. Erroneous wiring may cause burning of the elec­tric parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
(3) Always fasten the outside covering of the connection
cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.) (4) Always connect the ground wire. (5) Do not use the earth screw for an external connector.
Only use for interconnection between two units.
TEST RUNNING
Perform test operation and check items 1 and 2 below.
For the test operation method, refer to the operating manual.
The outdoor unit, may not operate, depending on the room temperature. In this case, press the test run button on the remote control unit
while the air conditioner is running, (Point the transmitter section of the remote control unit toward the air conditioner and press the test run button with the tip of a ball-point pen, etc.)
To end test operation, press the remote control unit START/STOP button. (When the air conditioner is run by pressing the test run button, the OPERATION indicator lamp and TIMER indicator lamp will simultaneously flash slowly.)
1. INDOOR UNIT
(1) Is operation of each button on the remote control unit normal? (2) Does each lamp light normally? (3) Do the air flow-direction louver operate normally? (4) Is the drain normal?
Transmitter section
Fig. 18
2. OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation? (2) Will noise, wind, or drain water from the unit disturb the neighbors? (3) Is there any gas leakage?
Test run button
POWER
WARNING
(1) The rated voltage of this product is 208/230 V AC
60 Hz.
(2) Before turning on the power, check if the voltage
is within the 208 V-10% to 230V+10% range.
(3) Always use a special branch circuit and install a
special receptacle to supply power to the room air conditioner.
(4) Use a circuit breaker and receptacle matched to
the capacity of the air conditioner. (5) Do not extend the power cord. (6) Perform wiring work in accordance with stand-
ards so that the air conditioner can be operated
safely and positively. (7) Install a leakage circuit breaker in accordance with
the related laws and regulations and electric com-
pany standards.
(1) The power source capacity must be the sum of
the air conditioner current and the current of other electrical appliances. When the current contracted capacity is insufficient, change the contracted ca­pacity.
(2) When the voltage is low and the air conditioner is
difficult to start, contact the power company the voltage raised.
CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operat­ing manual: (1) Starting and stopping method, operation switching, temperature
adjustment, timer, air flow switching, and other remote control unit
operations. (2) Air filter removal and cleaning, and how to use the air louvers. (3) Give the operating and installation manuals to the customer.
CAUTION
Bottom holes (six position)
Bottom hooks (six position)
CAUTION
Install the front panel and INTAKE GRILLE securely. If installation is imperfect, the front panel or INTAKE GRILLE may fall off and cause injury.
REMOTE CONTROL UNIT INSTALLATION
CAUTION
(1) Check that the indoor unit correctly receives the
signal from the remote control unit, then install the remote control unit holder.
(2) Select the remote control unit holder selection
site by paying careful attention to the following: Avoid places in direct sunlight. Select a place that will not be affected by the heat from a stove, etc.
1. REMOTE CONTROL UNIT HOLDER INSTALLATION
Install the remote control unit with a distance of 23 ft
(7 m) between the remote control unit and the photocell as the criteria. However, when installing the remote con­trol unit, check that it operates positively.
Install the remote control unit holder to a wall, pillar,
etc. with the tapping screw (Fig. 20).
Fig. 20
Remote control unit holder fixing
Remote control unit holder
Tapping screw (small)
Remote control unit mounting
1 Set
2 Push
Remote control unit
IMPORTANT
This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropriate coil components. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufacturer's refrigerant charging and air flow instructions. Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life.
CONDUIT CONNECTOR
PUMP DOWN OPERATION (FORCED COOLING OPERATION)
To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation or forced cooling operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the forced cooling operation.)
(1) Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3 way valve and opening the
low-pressure valve slightly. (2) Close the valve stem of 2 way valve completely. (3) Start the cooling operation or following forced cooling operation.
Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds.
The operation indicator lamp and timer indicator lamp will begin to flash simultaneously during test run.
(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.) (4) Close the valve stem of 3 way valve when the reading on the compound pressure gage becomes 0.05~0 MPa (0.5~0 kg/cm (5) Stop the operation.
Press the START/STOP button of the remote control unit to stop the operation.
Press the MANUAL AUTO button when stopping the operation from indoor unit side.
(It is not necessary to press on keeping for more than 10 seconds.)
CAUTION
During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open. This may cause abnormal
pressure in the refrigeration cycle that leads to breakage and even injury.
2
).