Friedrich YS09J10-1, YS13J33-1, ES12J33-1, ES12J33-3, ES15J33A-1 Service Manual

...
2000
®
TwinTemp
YS09J10-1 YS13J33-1
Series
ES12J33-3 ES15J33A-1
J
EL33J35-2
EK12J33A-1 YM18J34A-2 YL24J35A-1
ES12J33-1
EM18J34A-2 EM18J34A-3 EL24J35A-1
EL24J35A-3
EK12J33A-3
EK18J34A-2
EK18J34A-3
Manual
AMERICA’S BEST AIR CONDITIONER
TTJ0100 (1/00)
TABLE OF CONTENTS
GENERAL
Friedrich Room Model Number Code .........................................................................................................4
Application and Sizing ..............................................................................................................................5
Instructions For Using Cooling Load Estimate Form .................................................................................6
Cooling Load Estimate Form .....................................................................................................................7
Heat Load Form ........................................................................................................................................8
Heating Load Form Friedrich Unit Heat Pumps ..........................................................................................9
SPECIFICATIONS/PERFORMANCE DATA
Specifications "YS" - "YM" - "YL" Models ................................................................................................10
Performance Data (Cooling) "YS" - "YM" - "YL" Models ........................................................................... 11
Performance Data (Heating) "YS" - "YM" - "YL" Models ........................................................................... 11
Specifications "ES" - "EM" - "EL" - "EK" Models ..................................................................................... 12
Performance Data (Cooling & Heating) "ES" - "EM" - "EL" - "EK" Models ................................................13
REFRIGERANT REVERSE CYCLE
Refrigerant Flow Chart (Cooling Cycle) .................................................................................................... 14
Refrigerant Flow Chart (Heating Cycle) .................................................................................................... 14
PAG E
INSTALLATION INSTRUCTIONS
Installation Instructions for DC-2 Drain Kit ............................................................................................... 15
COMPONENTS OPERATION/TESTING
Compressors ........................................................................................................................................... 16
Thermal Overload (External) ....................................................................................................................16
Thermal Overload (Internal) ......................................................................................................................17
Fan Motor ................................................................................................................................................ 17
Capacitor, Run .........................................................................................................................................18
System Control Switch (Heat Pump & Electric Heat Models) ................................................................... 18
Thermostat .............................................................................................................................................. 19
Thermostat ("YQ" Model) .........................................................................................................................18
Thermostat Adjustment .......................................................................................................................... 20
Resistor (Heat Anticipator) ....................................................................................................................... 20
MoneySaver Switch ................................................................................................................................. 20
Heat Element ...........................................................................................................................................21
Defrost Thermostat (Heat Pump Models) ................................................................................................. 21
Defrost Bulb Location (Heat Pump Models) .............................................................................................22
Solenoid Coil (Heat Pump Models Only) ..................................................................................................22
Check Valve.............................................................................................................................................22
Drain Pan Valve........................................................................................................................................ 22
Reversing Valve (Heat Pump Models Only).............................................................................................. 23
Page 2
Sealed Refrigeration System Repairs....................................................................................................... 24
Hermetic Component Replacement ..........................................................................................................24
Special Procedure in the Case of Motor Compressor Burn-Out ................................................................ 25
Rotary Compressor Special Troubleshooting & Service ............................................................................ 25
Refrigerant Charge ................................................................................................................................... 25
TROUBLESHOOTING
Troubleshooting Touch Test Chart ............................................................................................................. 26
Troubleshooting Cooling ........................................................................................................................... 27
Troubleshooting Heating (Heat Pump Models) .......................................................................................... 31
Troubleshooting Heating (Cooling/Electric Models) ................................................................................... 34
WIRING DIAGRAMS
YS09J10-1 .......................................................... 618-200-04 .................................................................. 36
YS13J33-1 .......................................................... 618-200-02 .................................................................. 37
YM18J34A-2 ....................................................... 618-200-02 .................................................................. 37
YL24J35A-1 ........................................................ 618-200-02 .................................................................. 37
ES12J33-1, ES12J33-3 ...................................... 618-200-01 .................................................................. 38
ES15J33A-1 ....................................................... 618-200-01 .................................................................. 38
EM18J34A-2, EM18J34A-3................................. 618-200-01 .................................................................. 38
EL24J35A-1, EL24J35A-3 ................................... 618-200-01 .................................................................. 38
EL33J35-2 .......................................................... 618-200-01 .................................................................. 38
EK12J33A-1, EK12J33A-3.................................. 618-200-01 .................................................................. 38
EK18J34A-2 ....................................................... 618-200-01 .................................................................. 38
EK18J34A-3 ....................................................... 618-200-01 .................................................................. 38
TABLE OF CONTENTS (Cont.)
Page
PARTS LIST
"YS" - "YM" - "YL" Series Parts List ........................................................................................................ 39
"ES" - "EM" Series Parts List .................................................................................................................. 46
"EL" Series Parts List .............................................................................................................................. 51
"EK" Series Parts List ............................................................................................................................. 56
Page 3
FRIEDRICH ROOM MODEL NUMBER CODE
1st DIGIT - FUNCTION
S = Straight Cool, Value Series C = Straight Cool, Budget Series Y = Heat Pump E = Electric Strip K = Straight Cool, Challenger Series W = Thru-The-Wall, WallMaster Series
2nd DIGIT - TYPE
C = Casement P = PowerMiser “Portable Q = QStar S = Small Chassis M = Medium Chassis L = Large Chassis W = Built-In H = Hazardgard
3rd & 4th DIGITS - APPROXIMATE BTU/HR (Cooling)
Heating BTU/HR capacity listed in Specifications/Performance Data Section
E S 15 H 3 3 A
5th DIGIT - ALPHABETICAL MODIFIER
6th DIGIT - VOLTAGE
1 = 115 Volts 2 = 230 Volts 3 = 230-208 Volts
7th DIGIT
0 = Straight Cool & Heat Pump Models ELECTRIC HEAT MODELS
1 = 1 KW Heat Strip, Nominal 3 = 3 KW Heat Strip, Nominal 4 = 4 KW Heat Strip, Nominal 5 = 5 KW Heat Strip, Nominal 8 = 8 KW Heat Strip, Nominal
8th DIGIT
Major Change
Page 4
Printed in the U.S.A.
APPLICATION AND SIZING
In the application and sizing of room air conditioners for cooling, it is most important to give full consideration to all factors which may contribute to the heat loss or gain of the space to be conditioned. It is therefore necessary to make a survey of the space to be conditioned and calculate the load requirements before a selection of the size of the equipment needed can be made.
The load requirement may be determined very easily by simply using the standard "AHAM" Load Calculating Form, on Page 7. This form is very easy to use and is self explanatory throughout. It is necessary only to insert the proper measurements on the lines provided and multiply by the given factors, then add the result for the total load requirements.
Cooling load requirements are generally based on the cooling load for comfortable air conditioning which does not require specific conditions of inside temperature and humidity. The load calculation form is based on outside design temperature of 95° FDB and 75° FWB. It can be used for areas in the Continental United States having other outside design temperatures by applying a correction factor for the particular locality as determined from the map shown on Page 7.
When sizing a TwinTemp unit for cooling and heating, we must remember that the heating capacity of any given unit varies directly with the outdoor ambient temperature. Also, we must keep in mind the average low temperatures which might be experienced in the locality where the unit is to be installed. Therefore, when sizing a TwinTemp unit, both cooling and heating requirements must be calculated. Do not oversize, or undersize, one phase of the units capacity at the expense of the other. In those cases where the unit will provide satisfactory cooling at all times but will be inadequate for those few times that the outdoor temperature is below the maximum low for the unit, additional auxiliary heating facilities must be provided to insure that adequate heat is available at all times.
Page 5
INSTRUCTIONS FOR USING COOLING LOAD ESTIMATE
FORM FOR ROOM AIR CONDITIONERS
(AHAM PUB. NO. RAC-1)
A. This cooling load estimate form is suitable for estimating the cooling load for comfort air conditioning installations
which do not require specific conditions of inside temperature and humidity.
B. The form is based on an outside design temperature of 95°F dry bulb and 75°F wet bulb. It can be used for areas
in the continental United States having other outside design temperatures by applying a correction factor for the particular locality as determined from the map.
C. The form includes "day" factors for calculating cooling loads in rooms where daytime comfort is desired (such as
living rooms, offices, etc.)
D. The numbers of the following paragraphs refer to the corresponding numbered item on the form:
1. Multiply the square feet of window area for each exposure by the applicable factor. The window area is the area of the wall opening in which the window is installed. For windows shaded by inside shades or venetian blinds, use the factor for "Inside Shades." For windows shaded by outside awnings or by both outside awnings and inside shades (or venetian blinds), use the factor for "Outside Awnings." "Single Glass" includes all types of single thickness windows, and "Double Glass" includes sealed airspace types, storm windows, and glass block. Only one number should be entered in the right hand column for Item 1, and this number should represent only the exposure with the largest load.
2. Multiply the total square feet of all windows in the room by the applicable factor.
3a. Multiply the total length (linear feet) of all walls exposed to the outside by the applicable factor. Doors should
be considered as being part of the wall. Outside walls facing due north should be calculated separately from outside walls facing other directions. Walls which are permanently shaded by adjacent structures should be considered "North Exposure." Do not consider trees and shrubbery as providing permanent shading. An un­insulated frame wall or a masonry wall 8 inches or less in thickness is considered "Light Construction." An insulated wall or masonry wall over 8 inches in thickness is considered "Heavy Construction."
3b. Multiply the total length (linear feet) of all inside walls between the space to be conditioned and any
unconditioned spaces by the given factor. Do not include inside walls which separate other air conditioned rooms.
4. Multiply the total square feet of roof or ceiling area by the factor given for the type of construction most nearly describing the particular application (use one line only.)
5. Multiply the total square feet of floor area by the factor given. Disregard this item if the floor is directly on the ground or over a basement.
6. Multiply the number of people who normally occupy the space to be air conditioned by the factor given. Use a minimum of 2 people.
7. Determine the total number of watts for light and electrical equipment, except the air conditioner itself, that will be in use when the room air conditioning is operating. Multiply the total wattage by the factor given.
8. Multiply the total width (linear feet) of any doors or arches which are continually open to an unconditioned space by the applicable factor. NOTE: Where the width of the doors or arches is more than 5 feet, the actual load may exceed the calculated value. In such cases, both adjoining rooms should be considered as a single large room, and the room air conditioner unit or units should be selected according to a calculation made on this new basis.
9. Total the loads estimated for the foregoing 8 items.
10. Multiply the subtotal obtained in item 9 by the proper correction factor, selected from the map, for the particular locality. The result is the total estimated design cooling load in BTU per hour.
E. For best results, a room air conditioner unit or units having a cooling capacity rating (determined in accordance
with the NEMA Standards Publication for Room Air Conditioners, CN 1-1960) as close as possible to the estimated load should be selected. In general, a greatly oversized unit which would operate intermittently will be much less satisfactory than one which is slightly undersized and which would operate more nearly continuously.
F. Intermittent loads such as kitchen and laundry equipment are not included in this form.
Page 6
COOLING LOAD ESTIMATE FORM
HEAT GAIN FROM
1. WINDOWS: Heat gain from the sun.
Northeast East Southeast South Southwest West Northwest North
2. WINDOWS: Heat by conduction
(Total of all windows.) Single glass Double glass or glass block
3. WALLS: (Based on linear feet of wall) a. Outside walls
North Exposure Other than North exposure
b. Inside Walls (between conditioned and
unconditioned spaces only.)
4. ROOF OR CEILING: (Use one only) a. Roof, Un-insulated b. Roof, 1 inch or more insulation c. Ceiling, occupied space above d. Ceiling, insulated, with attic space above e. Ceiling, Un-insulated, with attic space above
* These factors are for single glass
only. For glass block, multiply the above factors by 0.5; for double glass or storm windows, multiply the above factors by 0.8.
QUANTITY
____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft.
____sq. ft. ____sq. ft.
____ ft. ____ ft.
____sq. ft.
____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft.
FACTORS
DAY
No
Shades*
60 80 75
75 110 150 120
0
Light Construction
30 60
Inside
Shades*
Outside
Awnings*
25 40 30 35 45 65 50
0
14
30
19
12
20 ____ 25 ____ 20 ____ 20 ____ 30 ____ 45 ____ 35 ____
0 ____
7
Heavy Construction
8 3 5
BTU/Hr.
(Quantity x Factor)
(Area
X Factor)
____
Use
____
only
____
the
Use only one.
____ ____ ____ ____ ____
_____ _____
_____ _____
_____
_____ _____ _____ _____ _____
largest
load.
20 30
5. Floor: (Disregard if floor is directly on ground or over a basement.
6. NUMBER OF PEOPLE
7. LIGHTS AND ELECTRICAL EQUIPMENT IN USE
8. DOORS AND ARCHES CONTINUOUSLY OPENED TO UNCONDITIONED SPACE: (TOTAL LINEAR FEET OF
WIDTH.)
9. SUBTOTAL
10. TOTAL COOLING LOAD (BTU per hour to be used for
selection of room air conditioner(s).)
____ Total in Item 9 X ____(Factor from Map) = _______
____sq. ft.
____
____watts
____ft.
*****
3
600
3
300
*****
_____
_____
_____
_____
_____
Page 7
HEAT LOAD FORM
The heat load form, Page 9, may be used by servicing personnel to determine the heat loss of a conditioned space and the ambient winter design temperatures in which the unit will heat the calculated space.
The upper half of the form is for computing the heat loss of the space to be conditioned. It is necessary only to insert the proper measurements on the lines provided and multiply by the given factors, then add this result for the total heat loss in BTU/Hr./°F.
The BTU/Hr. per °F temperature difference is the 70°F inside winter designed temperature minus the lowest outdoor ambient winter temperature of the area where the unit is installed. This temperature difference is used as the multiplier when calculating the heat loss.
The graph shows the following:
Left Hand Scale Unit capacity BTU/Hr. or heat loss
BTU/Hr.
Bottom Scale Outdoor ambient temperature,
base point.
Heat Pump Model BTU/Hr. capacity heat pump will
deliver at outdoor temperatures.
Balance Point Maximum BTU/Hr. heat pump will
deliver at indicated ambient tem­perature.
Below is an example using the heat load form:
A space to be conditioned is part of a house geographi­cally located in an area where the lowest outdoor ambi­ent winter temperature is 40°F. The calculated heat loss is 184 BTU/Hr./°F.
Subtract 40°F (lowest outdoor ambient temperature for the geographical location) from 70°F (inside design tem­perature of the unit) for a difference of 30°F. Multiply 184 by 30 for a 5500 BTU/Hr. total heat loss for the calcu­lated space.
On the graph, plot the base point (70°) and a point on the 40°F line where it intersects with the 5500 BTU/Hr. line on the left scale. Draw a straight line from the base point 70 through the point plotted at 40°F. This is the total heat loss line.
Knowing that we have a 5500 BTU/Hr. heat loss, and we expect that our heat pump will maintain a 70°F inside temperature at 40°F outdoor ambient, we plot the se­lected unit capacity BTU/Hr. of the unit between 35° and 60° on the graph and draw a straight line between these points. Where the total heat loss line and the unit capac­ity line intersect, read down to the outdoor ambient tem­perature scale and find that this unit will deliver the re­quired BTU/Hr. capacity to approximately 30°F.
Page 8
HEATING LOAD FORM
FRIEDRICH ROOM UNIT HEAT PUMPS
BTU/HR PER
WALLS: (Linear Feet °F. TEMP. DIFFERENCE
2" Insulation Lin. Ft. x 1.6 Average Lin. Ft. x 2.6
WINDOWS & DOORS (Area, sq. ft.
Single Glass: Sq. Ft. x 1.13 Double Glass: Sq. Ft. x 0.61
INFILTRATION - WINDOWS & DOORS: AVG. Lin. Ft. x 1.0
Loose L i n. Ft . x 2 . 0
CEILING: (Area, Sq. Ft.)
Insulated (6") Sq. Ft. x 0.07 Insulated (2") Sq. Ft. x 0.10 Built-up Roof (2" insulated Sq. Ft. x 0.10 Built-up Roof (1/2" insulated) Sq. Ft. x 0.20 No Insulation Sq. Ft. x 0.33
FLOOR: (Area, Sq. Ft.)
Above Vented Crawl space Insulated (1:) Sq. Ft. x 0.20 Un-insulated Sq. Ft. x 0.50 * Slab on Ground Lin. Ft. x 1.70 1" Perimeter insulation Lin. Ft. x 1.00
* Based on Linear Feet of outside wall TOTAL HEAT LOSS PER °F BTU/HR/°F
Multiply total BTU/HR/°F X 30 and plot on the graph below at 40°F. Draw a straight line from the 70 base point thru the point plotted at 40°F. The intersection of this heat loss line with the unit capacity line represents the winter design heating load.
Page 9
SPECIFICATIONS YS09J10-1 YS13J33-1 YM18J34A-2 YL24J35A-1
BTUH (Cooling) 9000 13000 17500 24000
BTUH (Heating) 8300 12400 16500 23000
E.E.R. (Cooling) 11.5 9.8 9.4 9.0
E.E.R. (Heating) 11.0 9.4 9.6 9.8
Volts 115 230 230 230
Amperes (Cooling) 7.2 6.0 8.3 12.0
Amperes (Heating) 6.7 6.0 7.6 10.4
Total Watts (Cooling) 760 1325 1860 2665
Her tz 60 60 60 60
Fuse/Breaker Size 15 20 30 30
Amps 16.0 19.5 24.0
Resistance
Watts 3500 4200 5500
Heater
BTUH 10700 13000 17300
Fan RPM 1110 1110 1120 1120
13000 17500 23800
12300 16300 22800
9.8 9.4 9.0
9.4 9.6 9.8
208 208 208
6.5 9.1 13.0
6.5 8.3 11.5
1325 1860 2645
14.7 17.0 22.4
2900 3500 4650
8900 10600 14300
Evaporator Air CFM 300 325 425 600
Exhaust Air CFM Yes Yes Yes Yes
Dehumidification Pts/Hr 1.7 3.5 5.2 7.0
Width 25
Height 15
Depth 27
Minimum Ext. Into Room 3
Minimum Ext. to Outside 16
15/16"2515/16"2515/16"28"
15/16"1515/16"1715/16"203/16"
3/8"273/8"273/8"335/8"
1/16"31/16"31/16"33/16"
15/16"1615/16"1615/16"1815/16"
Net Weight 113 117 166 198
Shipping Weight 124 128 153 217
Page 10
PERFORMANCE EVAPORATOR AIR OPERATING ELECTRICAL R-22 COMP. DATA* TEMP. °F. PRESSURES RATINGS REFRIG. OIL Cooling DISCHARGE TEMP. SUCTION DISCHARGE AMPS LOCKED CHARGE IN CHARGE IN
AIR DROP °F ROTOR AMPS O Z. FLUID OZ.
YS09J10-1 59.0 21.0 87.0 241 7.2 39.2 28.0 11.8
YS13J33-1 56.0 24.0 75.0 280 6.0 29.0 30.0 11.8
YM18J34A-2 53.0 27.0 74.0 277 8.7 42.0 54.0 30.0
YL24J35A-1 55.0 25.0 77.0 272 12.0 61.0 69.0 32.0
6.5
9.3
13.0
* Rating Conditions: 80°F Room Air Temperature and 50% Relative Humidity with
95°F Outside Air Temperature at 40% Relative Humidity.
PERFORMANCE DATA *YS09J10-1 **YS13J33-1 **YM18J34A-2 **YL24J35A-1 (Heating)
AHAM @ 70°F Inside 47°F Outside 8300 12400/12300 17200/17200 23000/22800
@ 70°F Inside 35°F Outside 10700/8900 13000/10600 17300/14300
Evaporator Air Temperature Rise
@ 70°F Inside 47°F Outside 19.62 31.38 24.74 31.71 @ 70°F Inside 35°F Outside 28.69/23.87 24.46/20.22 24.38/20.16
AMPS @ 70°F Inside 47°F Outside 6.7 6.0/6.5 8.5/9.0 10.4/11.5
@ 70°F Inside 35°F Outside 16.0/14.7 19.5/17.0 24.0/22.4
Watts @ 70°F Inside 47°F Outside 760 1340/1300 1880/1820 2350/2340
@ 70°F Inside 35°F Outside 3500/2900 5500/4650 5500/4650
Suction/Head PSIG
@ 70°F Inside 47°F Outside 53.5/222 52.5/251 53/225 54/236.5
* Do not operate below 37° ambient. ** Heating element comes on at 35°F outside ambient and compressor shuts off.
Page 11
SPECIFICATIONS ES12J33-1 ES15J33A-1 EM18J34A-2 EL24J35A-1 EL33J35-2 EK12J33A-1 EK18J34A-2
ES12J33-3 EM18J34A-3 EL24J35A-2 EK12J33A-3 EK18J34A-3
BTUH (Cooling) 12000 15000 18500 24000 33000 12500 18000
12000 15000 18300 24000 32500 12500 18000
BTUH (Heating) 10700 10700 13000 17300 17300 10700 13000
8900 8900 10600 14300 14300 8900 10600
E.E.R. (Cooling) 10.5 9.6 10.0 9.5 9.0 10.0 9.6
11.0 9.6 10.0 9.4 9.0 10.0 9.6
E.E.R. (Heating)
Volts 230 230 230 230 230 230 230
208 208 208 208 208 208 208
Amperes (Cooling) 5.5 6.9 8.4 12.0 17.0 5.8 8.3
5.7 7.5 9.0 13.3 18.0 6.2 9.1
Amperes (Heating) 16.0 16.0 19.5 24.0 24.0 16.0 19.5
14.7 14.7 17.0 22.4 22.4 14.7 17.0
Total Watts (Cooling) 1145 1665 1850 2610 3670 1250 1875
1090 1655 1830 2640 3610 1250 1875
Her tz 60 60 60 60 60 60 60
Fuse/Breaker Size 20 20 30 30 30 20 30
Fan RPM 1120 1100 1120 1100 1100 1080 1120
Evaporator Air CFM 325 330 425 560 700 325 440
Fresh Air CFM Yes Yes Yes Yes Yes Yes Yes
Exhaust Air CFM Yes Yes Yes Yes Yes Yes Yes
Dehumidification Pts/Hr 3.5 5.0 5.7 7.7 11.0 3.5 5.5
Width 25
Height 15
Depth 27
Minimum Ext. Into Room 3
Minimum Ext. to Outside 16
15/16"2515/16"2515/16" 28" 28" 2515/16"2515/16"
15/16"1515/16"1715/16"203/16"203/16"1515/16"1715/16"
3/8"273/8"273/8"335/8"335/8"273/8"273/8"
1/16"31/16"31/16"33/16"33/16"31/16"31/16"
15/16"1615/16"1615/16"1815/16"1815/16"1615/16"1615/16"
Net Weight 111 116 160 191 215 108 158
Page 12
PERFORMANCE EVAPORATOR AIR OPERATING ELECTRICAL R-22 COMP. DATA* TEMP. °F. PRESSURES RATINGS REFRIG. OIL Cooling DISCHARGE TEMP. SUCTION DISCHARGE AMPS LOCKED CHARGE IN CHARGE IN
AIR DROP °F ROTOR AMPS O Z. FLUID OZ.
ES12J33-1 58.0 22.0 77.5 266 5.5 26.3 25.0 11.8 ES12J33-3 5.7 26.3 26.0 11.8
ES15J33A-1 53.0 27.0 77.0 260 7.4 42.0 32.0 30.0
8.2
EM18J34A-2 55.0 25.0 73.0 262 8.2 42.0 47.0 30.0 EM18J34A-3 8.7 42.0 43.0 30.0 EL24J35A-1 55.0 25.0 73.5 280 12.0 61.0 53.0 32.0 EL24J35A-3 13.3 57.0 32.0 EL33J35-2 52.0 28.0 71.0 299 17.0 94.0 78.0 35.0
EK12J33A-1 57.0 23.0 79.0 293 5.8 26.3 26.5 11.8
EK12J33A-3 6.2 26.3 24.0 11.8 EK18J34A-2 55.0 25.0 73.0 262 8.2 42.0 46.0 30.0 EK18J34A-3 42.0 42.0 30.0
18.0
* Rating Conditions: 80°F Room Air Temperature and 50% Relative Humidity with
95°F Outside Air Temperature at 40% Relative Humidity.
PERFORMANCE DATA VOLTS BTUH CFM HEAT RISE Heating HIGH SPEED
ES12J33-1 230 10700 1120 30.5 ES12J33-3 208 8900 ES15J33A-1 230 10700 1100 30.5
208 8900 EM18J34A-2 230 13000 1120 28.3 EM18J34A-1 208 10600 EL24J35A-1 230 17300 1100 28.6 EL24J35A-3 208 14300 EL33J35 230 17300 1110 22.8
208 14300 EK12J33A-1 230 10700 1080 30.5 EK12J33A-3 208 8900 EK18J34A-2 230 13000 1120 27.5 EK18J34A-3 208 10600
Page 13
REFRIGERANT FLOW CHART — HEAT PUMP MODELS
Cooling Cycle (Refer to Chart Below)
In the cooling cycle, both capillary tubes feed the evaporator coil
Heating Cycle (Refer to Chart Below)
In the heating cycle, the one-way check is closed and the refrigerant flows through one capillary only to the condenser
Page 14
INSTALLATION INSTRUCTIONS
FOR DC-2 DRAIN KIT
STEP 1 Before sliding chassis into outer shell, turn chassis on its side and add drain hole by drilling ½"
diameter hole as shown in Figure 1.
STEP 2 DC-2 mounts to the bottom of the outer shell as shown in Figure 2 on the right side as you face
the unit. Use two (2) 10 - 24 x 3/8" long machine screws and 10 - 24 hex nuts provided.
STEP 3 SQ, KQ, YQ Models - Drill two ¼" holes in outer shell as shown in Figure 3. Also drill a 3/8"
diameter hole in the base pan 3½" from the back and 3½" from right side.
STEP 4 Small and Medium Chassis Models - Mount in second and third holes from the rear of shell; See
Figure 4.
STEP 5 Large Chassis Models - Mount in third and fourth holes from the rear of shell; see Figure 5.
STEP 6 Connect a suitable length of garden hose or other tubing to end of the drain tube to drain the
condensate away.
FIGURE 1 FIGURE 2
RIGHT SIDE
APPROXIMATE LOCATION OF EMBOSSMENT. DRILL 1/2" DIA. HOLE
BACK OF BASE PAN
FIGURE 3
FIGURE 4 FIGURE 5
2ND & 3RD HOLES FROM REAR OF SHELL
10-24X 3/8" LONG SCREWS
DRAIN PLATE
10X24 NUTS
3RD & 4TH HOLES FROM REAR OF SHELL
SQ, KQ, YQ MODELS
BOTTOM VIEW
SMALL & MEDIUM
CHASSIS MODELS
BOTTOM VIEW
LARGE
CHASSIS MODELS
BOTTOM VIEW
Page 15
COMPONENT OPERATION & TESTING
WARNING
DISCONNECT ELECTRICAL POWER TO
UNIT BEFORE SERVICING OR TESTING
COMPRESSORS
GROUND TEST
Use an ohmmeter set on its highest scale. Touch one lead to the compressor body (clean point of contact as a good connection is a must) and the other probe in turn to each compressor terminal (see Figure 2.) If a reading is obtained, the compressor is grounded and must be replaced.
Compressors are single phase, 115 or 230/208 volt, depending on the model unit. All compressor motors are permanent split capacitor type using only a running capacitor across the start and run terminal.
All compressors are internally spring mounted and externally mounted on rubber isolators.
COMPRESSOR WINDING TEST (See Figure 1)
Remove compressor terminal box cover and disconnect wires from terminals. Using an ohmmeter, check continuity across the following:
1. Terminal "C" and "S" - no continuity - open winding
- replace compressor.
2. Terminal "C" and "R" - no continuity - open winding
- replace compressor.
3. Terminal "R" and "S" - no continuity - open wind­ing - replace compressor.
Figure 2: Typical Ground Test
CHECKING COMPRESSOR EFFICIENCY
The reason for compressor inefficiency is normally due to broken or damaged suction and/or discharge valves, reducing the ability of the compressor to pump refrigerant gas.
This condition can be checked as follows:
1. Install a piercing valve on the suction and discharge or liquid process tube.
2. Attach gauges to the high and low sides of the system.
Figure 1: Compressor Winding Test
Page 16
3. Start the system and run a cooling or heating performance test.
If test shows:
A. Below normal high side pressure.
B. Above normal low side pressure.
C. Low temperature difference across coil.
The compressor valves are faulty - replace the compressor.
THERMAL OVERLOAD (External)
Some compressors are equipped with an external overload which is located in the compressor terminal box adjacent to the compressor body (see Figure 3.)
The overload is wired in series with the common motor terminal. The overload senses both major amperage and compressor temperature. High motor temperature or amperage heats the disc causing it to open and break the circuit to the common motor terminal.
Figure 3: External Overload
Should the internal temperature and/or current draw be­come excessive, the contacts in the overload will open, turning off the compressor. The overload will automati­cally reset, but may require several hours before the heat is dissipated.
CHECKING THE INTERNAL OVERLOAD (see Figure 4.)
Figure 4 INTERNAL OVERLOAD
Heat generated within the compressor shell is usually due to:
1. High amperage.
2. Low refrigerant charge.
3. Frequent recycling.
4. Dirty condenser.
TERMINAL OVERLOAD - TEST (Compressor - External Type)
1. Remove overload.
2. Allow time for overload to reset before attempting to test.
3. Apply ohmmeter probes to terminals on overload wires. There should be continuity through the over­load.
TERMINAL OVERLOAD (Internal)
1. With no power to unit, remove the leads from the compressor terminals.
2. Using an ohmmeter, test continuity between termi­nals C-S and C-R. If not continuous, the compres­sor overload is open and the compressor must be replaced.
FAN MOTOR
A single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A self-resetting overload is located inside the motor to protect against high temperature and high amperage conditions.
FAN MOTOR - TEST
1. Determine that capacitor is serviceable.
Some model compressors are equipped with an internal overload. The overload is embedded in the motor wind­ings to sense the winding temperature and/or current draw. The overload is connected in series with the com­mon motor terminal.
2. Disconnect fan motor wires from fan speed switch or system switch.
3. Apply "live" test cord probes on black wire and com­mon terminal of capacitor. Motor should run at high speed.
Page 17
Figure 5: Fan Motor
4. Apply "live" test cord probes on red wire and common terminal of capacitor. Motor should run at low speed.
5. Apply "live" test cord probes on each of the remaining wires from the speed switch or system switch to test intermediate speeds.
CAPACITOR, RUN
A run capacitor is wired across the auxiliary and main winding of a single phase permanent split capacitor motor such as the compressor and fan motor. A single capacitor can be used for each motor or a dual rated capacitor can be used for both.
The capacitor's primary function is to reduce the line current while greatly improving the torque characteristics of a motor. The capacitor also reduces the line current to the motor by improving the power factor of the load. The line side of the capacitor is marked with a red dot and is wired to the line side of the circuit (see Figure 6.)
CAPACITOR - TEST
1. Remove capacitor from unit.
2. Check for visual damage such as bulges, cracks, or leaks.
3. For dual rated, apply an ohmmeter lead to common (C) terminal and the other probe to the compressor (HERM) terminal. A satisfactory capacitor will cause a deflection on the pointer, then gradually move back to infinity.
4. Reverse the leads of the probe and momentarily touch the capacitor terminals. The deflection of the pointer should be two times that of the first check if the capacitor is good.
5. Repeat steps 3 and 4 to check fan motor capacitor.
NOTE: A shorted capacitor will indicate a low resistance
and the pointer will move to the "0" end of the scale and remain there as long as the probes are connected.
An open capacitor will show no movement of the pointer when placed across the terminals of the capacitor.
SYSTEM CONTROL SWITCH
(Heat Pump & Electric Heat Models)
An eight position control switch is used to regulate the operation of the fan motor and compressor. The compressor can be operated with the fan operating at low, medium or high speed in the cooling or heating mode. The fan motor can also be operated independently on medium speed. See switch section as indicated on decorative control panel (see Figure 7.)
Figure 6: RUN CAPACITOR HOOK-UP
Page 18
1. "Off" Position - everything is off.
2. "Lo Cool" Position - fan operates on low speed, compressor is on.
3. "Med Cool" Position - fan operates on medium speed, compressor is on.
4. "Hi Cool" Position - fan operates on high speed, compressor is on.
5. "Hi Heat" Position - fan operates on high speed, compressor or electric heater is on.
6. "Med Heat" Position - fan operates on medium speed, compressor or electric heater is on.
Loading...
+ 42 hidden pages