Friedrich VEB42, Vert-I-Pak VEB42, Vert-I-Pak VHB42, Vert-I-Pak VEB48, Vert-I-Pak VHB48 Installation Instructions Manual

Page 1
VEB42, VHB42, VEB48, VHB48
FRIEDRICH AIR CONDITIONING CO.
P.O. BOX 1540 • San Antonio, TX 78295
Ph: 210-357-4400 • FAX: 210-357-4485
www.friedrich.com
SELF-CONTAINED INDOOR AIR CONDITIONER / HEAT PUMP
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or dealer for information and assistance. The qualified installer or agency must use factory-authorized parts or accessories when modifying this product. Refer to the individual instructions packaged with the parts or accessories when installing.
INSTALLATION
INSTRUCTIONS
Date: July 2000 Part No: 84016326 (IM010-01)
Follow all safety codes. Wear safety glasses and work gloves. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes, the National Electric Code (NEC), and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B for special installation requirements.
Recognize safety information. This is the safety-alert symbol. When you see this symbol on the unit or in instructions and manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor
personal injury or product and property damage. NOTE is used to convey special or supplemental information or to repeat and emphasize information previously provided.
Table 1 - Unit Sizes And Available Electric Heat
UNIT COOLING HEATING AVAILABLE SIZE BTUH BTUH AT 47ºF KW
V(E,H)B42 42,000 41,000 10 or 15
V(E,H)B48 48,000 47,000 15 or 20
Figure 1 — B-Series VERT-I-PAK
DANGER: Before installing or servicing system, always turn off main
power to system. There may be more than one (1) disconnect switch. Turn off auxiliary heater power if applicable. Electrical shock can cause personal injury or death.
INTRODUCTION
The VERT-I-PAK is ETL and c-ETL listed and is available in the cooling/ electric heating sizes shown in Table 1. The VERT-I-PAK units are approved for upflow installations. They are designed to be installed in closets.
The VERT-I-PAK is a self-contained unit. All components including outdoor coil, compressor, and refrigerant tubing are located in a single package. The units are already piped, charged, and wired. Refer to Figure 2 for basic unit dimensions.
1
Page 2
Figure 2 — V(E,H)B-Series Unit Dimensions (Inches)
2
Page 3
INSTALLATION
The VERT-I-PAK was designed for installation in residential and light commercial applications. These instructions detail a typical method of installation. Figure 3 shows the typical component location and airflow paths through the unit.
The VERT-I-PAK B-Series units are available in three return air configurations: front "free-return" with filter frame; front ducted return
Figure 3 – Component Location and Air Flow Paths
Indoor Air Exhaust
Optional Return Air
with 1" duct flange; and left side ducted return with 1" duct flange. See Figures 4, 5 & 6.
NOTE: Ducted return air configurations require field fabrication of a duct mounted filter box. Filters are not supplied with units configured for ducted return.
Indoor Coil
Auxillary Electric Heat
Indoor Blower
Return Air
To remove filter, slide it to the right side of the unit as shown
Filter Rails
Air Filter
Control Box
Compressor
Reversing Valve
Outdoor Air Exhaust
Outdoor Air Intake
Outdoor Blower
Expansion Valve
Condenser Coil
(Heat Pump)
Condensate Drain
Air Filter
Figure 4 — Front Free Return Figure 6 — Side Ducted
Figure 5 — Front Ducted Return
Return
3
Page 4
I. GENERAL RECOMMENDATIONS (DO'S AND DO NOT'S)
DO read the instructions completely before installation.
DO take time to perform a quality installation.
DO NOT obstruct or restrict indoor or outdoor air paths.
When using flex duct: DO install properly. DO NOT crush or make sharp bends in flex duct, use only gradual bends.
DO tape and seal all duct joints.
DO check the indoor conditioned air duct system static pressure losses. It should not exceed those listed in Table 2. Consult your dealer or distributor for more information.
When designing indoor supply systems, DO NOT reduce air intakes or discharge sizes.
DO insulate ALL conditioned air duct system components.
DO NOT locate room thermostat near conditioned air diffusers.
DO locate thermostat on an interior wall.
DO check that condensate drain line drains freely.
DO NOT let debris fall and collect in indoor or outdoor blowers.
DO NOT drill into unit (except for 1 in. flanges for ducted return units). This could cause a refrigerant leak.
DO handle unit with care.
DO provide minimum installation and service clearances.
DO follow all guidelines for indoor and outdoor air system.
DO NOT substitute any components without checking with your dealer or distributor. If you do substitute, get approval in writing. Substitutions without approval void unit warranty.
DO NOT guess, consult your dealer or distributor if any portion of the installation procedure is unclear.
OUTDOOR AIR
EXHAUST
28"
40"
OUTDOOR AIR
INTAKE
INDOOR AIR
40"
REQUIRED
SERVICE
CLEARANCE
SUPPLY
Figure 7 — Recommended Service Clearance
V. INDOOR AND OUTDOOR AIR REQUIREMENTS
The indoor and outdoor air systems are designed to operate at specified airflow rates and external static pressures. The supply and return air duct system pressure losses (including filter, louver/grille and registers) must not exceed the listed external static pressures for either the indoor or outdoor air systems. CAUTION: Failure to adhere to indoor air and outdoor air requirements as listed in the following sections will void unit warranty.
II. UNPACK AND INSPECT UNIT
Remove shipping protection and pallet from unit and inspect for damage. Be sure to check for concealed internal shipping damage. Do not install a damaged unit.
III. SUPPLIES NEEDED FOR INSTALLATION
The following items are required to install unit.
Adhesive duct tape, UL 181 aluminum or equivalent. CAUTION: Incorrect type of duct tape may be a fire hazard. A failure
to follow this warning could result in a fire or explosion, and personal injury or death.
8-conductor thermostat cable (20 gage wire minimum). CAUTION: Do not use thermostat wire with less than the recommended
number of conductors.
Supplies to connect indoor air (conditioned air supply) duct to unit.
Supplies to connect power to unit.
Supplies to connect outdoor-air duct to unit.
Supplies to connect condensate drain line.
Supplies to connect low-voltage thermostat to unit.
IV. SERVICE CLEARANCE AND UNIT LOCATION
For serviceability and to minimize transmitted noise and vibration, unit should be installed with at least 1 inch clearance from walls. (See Figure 7) A minimum of 30 in. service clearance must be allowed in front of the unit. All serviceable components are accessible from the front of the unit with the front panels removed. The condensate drain fitting is located in the front right hand corner post.
A. Indoor-Air (Conditioned Supply Air) System
The unit may be applied in either a free return air configuration or a ducted return air configuration. The supply air path is intended to be ducted. The design and construction of the indoor-air system must provide adequate air distribution to ensure comfort levels throughout the structure.
The combined pressure losses of the return and supply air paths must not exceed the external static capabilities of the system at the design airflow (See Table 2).
If the unit is installed in a closet behind a door and the return air louver or grille is directly opposite the unit RA opening, 2-in. clearance is required between the front of the unit and the back side of the louver or grille. If the louver or grille is located elsewhere on the door so it is not directly in front of the RA opening, a minimum of 7-in. clearance is required between the front of the unit and the back side of the door. The minimum "net free open area" required for the RA louver or grille is listed in Table 2.
Table 2 — Indoor Air System Data
UNIT SIZE
Airflow
(CFM)
ESP
(in WG)
RA Grille
Minimum Net
Free Open Area
(Sq. In.)
42
48
1,400
1,400
0.50
0.50
525
525
4
Page 5
B. Outdoor Air System
As a completely self-contained system, the Vert-I-Pak requires an adequate supply of outdoor air to exchange heat from the outdoor air coil. The outdoor air intake and discharge openings are located on the back side of the unit. The unit may be installed where the outdoor air path runs through the wall of the building directly behind the unit or where the outdoor air intake and discharge paths are ducted separately away from the unit. Figure 8 shows two typical ducted OA designs.
CAUTION: To ensure proper operation, the outdoor air intake and discharge air paths must be free and unobstructed. The two air paths must be situated to ensure that the intake and discharge air do not recirculate (also called short-circuit).
For ducted outside air applications, the combined pressure losses of the intake and discharge air paths must not exceed the external static capabilities of the system at the design airflow (See Table 3).
VI. LINE VOLTAGE ELECTRICAL WIRING
DANGER: Electrical shock hazard. Turn OFF electric power at the
fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage. Failure to do so can result in property damage, personal injury and/or death.
A. Grounding
CAUTION: The unit must be electrically wired and grounded in
accordance with all state and local codes, national electric code, and NFPA
70. Unit and controls will NOT operate unless properly grounded. A ground lug is provided for ground connection. Use only approved copper wire and connectors from unit to service panel.
B. Power Supply
NOTE: Line voltage circuit is completely factory wired. Make all line voltage connections inside circuit breaker junction box.
For through-the-wall applications, a wall sleeve and louver kit is available. Follow the installation instructions provided with the kit.
Table 3 — Outdoor Air System Data
UNIT SIZE
42
48
Airflow
(CFM)
1,800
1,800
ESP
(in WG)
0.25
0.25
Figure 8 — Typical Configurations for Ducted Outside Air Applications
INTAKE
EXHAUST
The circuit breakers or fuses used for branch circuit protection should be UL recognized. If circuit breakers are used, the circuit breaker for the compressor circuit must have a UL HACR rating. If fuses are used, the fuse for the compressor circuit MUST be time delay type.
CAUTION: Units are dual voltage rated 208-230/1/60. The 24V
control transformer must be connected for either 208V or 240V power source for proper operation. Line voltage must not exceed 253V or go below 197V. The transformer connection must be changed for 208V operation.
Depending on auxiliary heater size, unit must be supplied with 2 or 3 separate 208V or 240V circuits from structure’s fuse box or service panel. Each circuit is internally connected to a circuit breaker located in the unit control box located at the front center of the unit. Refer to Table 4 and Table 5 for required circuits and recommended wire size for each circuit.
EXHAUST
OUTDOOR AIR INTAKE
OUTSIDE WALL
FLOOR
CEILING
OUTSIDE WALL
OUTDOOR AIR EXHAUST
5
OUTDOOR AIR INTAKE
FLOOR
BACK
OF UNIT
CEILING
OUTSIDE WALL
OUTDOOR AIR EXHAUST
INTAKE
Page 6
Romex Wiring Bushings
C. Electrical Connections
Ground lug and line voltage connection terminals are located behind the circuit breaker panel of the control box. See Figure 9. Complete the ground wire connection. After completing ground wire connection, complete line voltage connections. See Figure 10.
WARNING: Failure to adhere to minimum wire sizes, maximum over-
current protection, disconnect, and grounding requirements can cause personal injury, electric shock, or a fire hazard. All wiring MUST comply with requirements of state and local codes and ordinances and the national electric code.
Control Box
Figure 9 — Gaining Access to Wiring Compartment
Unit
Size
42
48
Compressor
Amps
20.4
26.4
Outdoor Fan
Amps
4.5
4.5
Auxillary
Heater #1
(Field Wiring)
Ground
(Field Wiring)
Figure 10 — Line Voltage And Ground Connections
Note: Figure 10 reflects a typical 3 ton 15KW unit. Actual layout is based on unit size and auxiliary heater size.
Table 4 — Heat Pump Electrical Data
Compressor
Indoor Fan
Amps
3.0
3.0
Circuit
Ampacity
33.0
40.5
Ground Lug
Minimum
Wire
Size
Heat Pump
(Field Wiring)
1
8
6
Auxillary Heater #2
(Field Wiring)
Max. Wire
Length
(Ft.2)
60
100
Heat Pump
Auxillary
Heater #1
Auxillary
Heater #2
Max. Fuse
or Breaker
Size Amps
50
60
3
Table 5 — Auxiliary Electric Heat Electrical Data
Ckt. #1
Electric
Heater
(KW)
Unit
Size
Ckt.# 1
Amps
Ckt. #1
Ampacity
Ckt. #1
Wire
Size
Max
Fuse
Size
Amps
10
15
20
1
If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetalic-sheathed
42
42, 48
48
41.6
20.8
41.6
52.0
26.0
52.0
10
6
60
30
6
60
3
Ckt. #1
Max
Wire
Length
(Ft)
100
100
100
2
Ckt. #2
Amps
N/A
52.0
52.0
Ckt. #2
Ampacity
N/A
52.0
52.0
Ckt. #2
Wire
Size
N/A
6
6
Ckt. #2
Max
Fuse3
1
Size
Amps
N/A
60
60
Ckt. #2
Max
Wire
Length
(Ft.)
N/A
100
100
cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-30. If other than uncoated (non-plated), 60°C or 75°C (140°F or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
2
Length shown is as measured 1 way along the wire path between the unit and the service panel for voltage drop not to exceed 10v, consult the factory for longer wire lengths if needed.
6
2
Page 7
VII. THERMOSTAT MOUNTING AND WIRING
A. Thermostat Location
Locate the thermostat about 5 ft. above the floor in an area with good circulation at average indoor temperature.
Figure 11 — Thermostat
Do not mount the thermostat where it may be affected by:
drafts or dead-air spots behind doors and in corners.
hot or cold air flow from ducts.
radiant heat from sun or appliances.
concealed pipes or chimneys.
unheated (uncooled) areas behind thermostat, such as an outside
wall.
5. Level the thermostat. Tighten the two mounting screws.
6. Replace the thermostat cover.
Figure 4 — Terminal and Switch Location
Figure 5 — Anticipation selection switch settings
The thermostat is a precision instrument and was carefully adjusted at the factory. Handle it carefully.
CAUTION: Disconnect power supply before beginning installation of thermostat to prevent electrical shock or equipment damage. Do not short
across thermostat terminals. This can burn out the thermostat anticipator.
B. Thermostat Mounting and Wiring
All wiring for the thermostat circuit must comply with NEC, state and local codes. Use No. 20 AWG color-coded, insulated (35°C minimum) wire. If thermostat is located more than 100 ft from unit (as measured along the control voltage wires), use No. 18 AWG color-coded wires to avoid excessive voltage drop.
1. In replacement applications, check the existing thermostat wiring for
cracked or frayed insulation. Replace any wiring in poor condition. All wiring must comply with local codes and ordinances.
2. Run wiring (if necessary) to the location. Thread wires through hole
in the packing material saved in step 2. Connect the wires to the terminals on the back of the thermostat. (See Figure 12.)
3. Push the excess wire back through the hole and plug any opening with
packing material to prevent drafts that may affect thermostat perfor­mance.
4. Loosely secure the thermostat to the wall with screws through the two
mounting holes in the middle of the thermostat. The sheetmetal screws included with the thermostat are designed for use in a plas­ter wall and anchors are not needed.
Table 1 — First Stage Heat and Cool
Anticipation
Reference
Number
10
14
16
Approximate Temperature
Differential
0.8°F
1.1°F
1.3°F
2.4°F
30
Table 2 — Second Stage Heat and Emergency Heat
Anticipation
Reference
Number
10
14
16
30
Approximate Temperature
Differential
0.3°F
0.4°F
0.5°F
0.9°F
7
Page 8
C. Wire Thermostat Cable to Unit Terminal Strip
Attach thermostat wires to low-voltage terminal block on left side of control box in locations indicated in Figure 12.
Figure 17 — Terminal and Switch Location
NOTE: Do not connect any unused thermostat cable wires.
CAUTION: Recheck wiring color code schedule to be certain proper terminals are connected before applying power. Improper wiring or
installation may damage thermostat.
VIII. CONDENSATE DRAIN LINE
The condensate drain exits the unit just above floor level at the right side front corner of the unit. The condensate drain line is already internally trapped therefore, no external condensate trap is required.
WARNING: Do not vent refrigerant to atmosphere. Recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow-control devices.
X. MAINTENANCE
NOTE: It is recommended that the Vert-I-Pak be inspected and serviced on an annual basis by a qualified technician.
If you perform maintenance on the unit yourself, remember that certain mechanical and electrical skills, plus specialized tools are required to properly perform maintenance. Personal injury or death may result if you are NOT properly trained. You should call your installing dealer if you are uncertain about your ability to perform maintenance.
WARNING: Electrical shock hazard. Turn OFF power to the system before performing any maintenance or removing panels. Failure to do so can result in personal injury and/or death.
A. Filters
NOTE: Dirty filters are the most common cause of inadequate heating and cooling performance.
Inspect filters monthly
Replace disposable type filters before they become clogged
Use water and mild detergent to clean washable type filters
NOTE: Some filters are marked with an arrow to indicate the proper direction of air flow through the filter. The arrow MUST point in the direction of air flow.
Install a condensate drain line of the same size as the drain fitting on the unit. PVC plastic pipe (3/4 in. I.D.) makes an ideal condensate line (if local codes allow).
Run condensate drain line from unit to floor drain or outside perimeter of building per local codes.
The condensate line must have a minimum drop of 1/4" per running foot as it leaves the unit. When a horizontal run of 15 ft. or longer is required, it may be necessary to install a vent tee in the drain line near the unit or use a larger diameter drain line. This is to eliminate air trapping and allow proper condensate drainage.
Heat pumps generate condensate during both cooling and heating modes. Condensate drain line must be protected from freezing to prevent condensate from backing up in unit during freezing outdoor conditions.
IX. REFRIGERANT
The unit is pre-charged at the factory to the correct operating charge and should not require adjustment. However, should an adjustment be required or if the unit requires service, adhere to the following precautions.
WARNING: Gage ports are equipped with schrader valves. To prevent
personal injury, wear safety glasses and gloves when handling refrigerant.
CAUTION: Compressor damage may occur if system is overcharged.
See unit serial tag for amount and type of refrigerant.
XI. INSTALLATION - FINAL CHECKLIST
1. Check to see if all duct work is sealed to unit for an airtight fit.
2. Insure that the condensate drain line is installed and run to an
appropriate disposal site.
3. Make sure the circuit breakers inside the unit are ON.
4. Insure that the thermostat is level and properly installed. Heat
anticipator indicator is set to the correct setting.
5. Test run in Heating, Cooling, and Emergency Heat mode as follows:
a. Set fan control to ON. If fan runs, return control to AUTO setting.
This verifies fan is working properly.
b. Set system control from OFF to COOL. Lower temperature
selector to 50°F or lower. The compressor should energize and cool air should flow from room registers. Once cooling test is complete, return system control to OFF setting. Wait 5 minutes.
c. Set system control to HEAT and raise temperature selector to 80°F
or higher. Compressor should energize, and warm air should flow from room registers.
d. Set system control to EM HEAT (Emergency Heat). Compressor
should turn off and warm air should continue to flow from registers.
NOTE: During EM HEAT operation, temperature of air flowing from room registers may be slightly warmer than during normal HEAT mode operation.
7. Leave both Installation Manual and Users Manual with owner or user
of equipment.
8. After 72 hours of operation, the unit will achieve full rated operating
performance.
8
Loading...