Friedrich VEB18, VEH24, VEH18, VEB24, VEB30 Installation & Operation Manual

...
920-164-02 (10-04)
VERT-I-PAK® B-SERIES
SINGLE PACKAGE VERTICAL AIR CONDITIONING SYSTEM
18,000 - 60,000 BTU/h
920-164-02 (10-04)
Table of Contents
Safety Considerations ............................................................................................................................................ 3
General Recommendations ................................................................................................................................... 3
Unpacking and Inspecting the Unit ........................................................................................................................ 3
Supplies Needed for Installation ............................................................................................................................ 3
Accessories ............................................................................................................................................................ 4
I. General Specifi cations
Model Number Identifi cation Guide ........................................................................................................................ 5
II. Dimensional Data
V(E,H)B18,24,30,36 Unit Dimensions .................................................................................................................... 5
V(E,H)B42,49 Unit Dimensions .............................................................................................................................. 6
V(E,H)B60 Unit Dimensions ................................................................................................................................... 6
III. Installation
1. Indoor and Outdoor Air Requirements
A. Outdoor Air System ................................................................................................................................... 7
B. Ducted Condenser Air ............................................................................................................................... 7
C. Indoor Air (Conditioned Supply Air) System ............................................................................................ 10
Outdoor Fan Performance ............................................................................................................................ 10
Indoor Fan Performance ............................................................................................................................... 11
2. Electrical
A. Grounding ................................................................................................................................................ 12
B. Power Supply .......................................................................................................................................... 12
3. Thermostat Mounting and Wiring
A. Thermostat Location ................................................................................................................................ 13
B. Thermostat Mounting & Wiring ................................................................................................................ 13
C. Wire Thermostat Cable to Unit Terminal .................................................................................................. 14
4. Condensate Drain Line ........................................................................................................................................ 14
Installation Final Checklist ................................................................................................................................ 14
Test Run .............................................................................................................................................................. 14
IV. Owners Manual & Operating Information
Identifying your System ........................................................................................................................................ 15
Important Facts .................................................................................................................................................... 15
Thermostat Operation .......................................................................................................................................... 16
Cooling Cycle ....................................................................................................................................................... 16
Heating Cycle ....................................................................................................................................................... 17
Defrost Cycle ....................................................................................................................................................... 17
Performing Routing Maintenance ........................................................................................................................ 17
Replace the Air Filter ............................................................................................................................................ 17
Inspect and Clean the Indoor Air Coil .................................................................................................................. 17
Inspect the Outdoor Air Intake and Exhaust ........................................................................................................ 17
Inspect and Clean the Condensate Drain ............................................................................................................ 17
2
Safety Considerations
920-164-02 (10-04)
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fi re, electrical shock, or other conditions which may cause personal injury or property damage. C onsult a qualifi ed installer, ser vice agency, or your distributor or dealer for information and assistance. The qualifi ed installer or agency must use factory-authorized parts or accessories when modifying this product. Refer to the
Follow all safety codes. Wear safety glasses and work gloves. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Always install units in accordance with local building codes, the National Electric Code (NEC), and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B for special installation requirements.
individual instructions packaged with the parts or accessories when installing.
General Recommendations (Do's And Don't's)
DO read the instructions completely before installation.
DO take time to perform a quality installation.
DO install drain heater accessory if outdoor design
temperature is 15°F or below.
DO NOT obstruct or restrict indoor or outdoor air paths.
When using fl ex duct: DO install properly. DO NOT crush
or make sharp bends in fl ex duct, use only gradual bends.
DO tape and seal all duct joints.
DO check the indoor conditioned air duct system static
pressure losses. It should not exceed those listed in Table
2. Consult your dealer or distributor for more information.
When designing indoor supply systems, DO NOT reduce
air intakes or discharge sizes.
DO insulate ALL conditioned air duct system components.
DO NOT locate room thermostat near conditioned air
diffusers.
DO locate thermostat on an interior wall.
DO check that condensate drain line drains freely.
DO NOT let debris fall and collect in indoor or outdoor
blowers.
DO NOT drill into unit (except for 1 in. fl anges for ducted
return units). This could cause a refrigerant leak.
DO handle unit with care.
DO provide minimum installation and service clearances.
DO build closet so that unit may be removed if necessary.
DO follow all guidelines for indoor and outdoor air system.
DO NOT substitute any components without checking
with your dealer or distributor. If you do substitute, get approval in writing. Substitutions without approval void unit warranty.
DO NOT guess, consult your dealer or distributor if any
portion of the installation procedure is unclear.
Unpack and Inspect Unit
Remove shipping protection and pallet from unit and inspect for damage. Be sure to check for concealed internal shipping damage. Do not install a damaged unit.
Supplies Needed For Installation
The following items are required to install unit:
Adhesive, aluminum duct tape
CAUTION: Incorrect type of duct tape may be a fi re hazard. A failure to follow this warning could result in a fi re and personal injury or death.
6-conductor thermostat cable (20 gage wire min.)
CAUTION: Do not use thermostat wire with less
than the recommended number of conductors.
Supplies to connect indoor air (conditioned air supply)
duct to unit
Supplies to connect power to unit
Supplies to connect outdoor-air duct to unit
Supplies to connect condensate drain line
Supplies to connect low-voltage thermostat to unit
3
920-164-02 (10-04)
Vert-I-Pak® B Series ACCESSORIES
MODEL DESCRIPTION PHOTO
Telescoping wall plenums adjust to exact wall depth. Models with -8 suffi xes adjust 41/2" - 8" deep; -14 models adjust 8" - 14".
WALL PLENUM- Used when chassis is positioned against an exterior wall for outdoor air infi ltration.
VPBWP3-8
VPBWP3-14
Recommended for use with 18,000 and 24,000 Btu/h units. DIMENSIONS: 18
1
/4" high x 281/4" wide.
CUTOUT DIMENSIONS: 181/2" high x 281/2" wide.
Recommended for use with 18,000, 24,000, 30,000 and 36,000
VPBWP4-8
VPBWP4-14
Btu/h units. DIMENSIONS: 24
1
/4" high x 30" wide.
CUTOUT DIMENSIONS: 241/2" high x 301/4" wide
VPBWP5-8
VPBWP5-14
VPBWP6-8
VPBWP6-14
Recommended for use with 42,000 and 49,000 Btu/h units.
1
DIMENSIONS: 24
/4" high x 38" wide.
CUTOUT DIMENSIONS: 241/2" high x 381/4" wide.
Recommended for use with 60,000 Btu/h units. DIMENSIONS: 34
1
/4" high x 40" wide.
CUTOUT DIMENSIONS: 341/2" high x 401/4" wide.
VPBWP3-8
ARCHITECTURAL LOUVER- Extruded aluminum outdoor louver that attaches to wall sleeve or outside of building.
VPAL3 VPSC3
VPAL4 VPSC4
Architectural louver for VPBWP3 plenums. Custom colored architectural louver for VPBWP3 plenums.
Architectural louver for VPBWP4 plenums. Custom colored architectural louver for VPBWP4 plenums.
VPAL5 VPSC5
VPAL6 VPSC6
RT3
Architectural louver for VPBWP5 plenums. Custom colored architectural louver for VPBWP5 plenums.
VPAL4
Architectural louver for VPBWP6 plenums. Custom colored architectural louver for VPBWP6 plenums.
THERMOSTAT Digital two-stage, manual changeover thermostat for B Series heat pumps only. For nonheat pump models, use RT2.
DISTRIBUTION BLOCK - Allows B Series Vert-I-Paks to be connected to a single-point power source. Block and
VPDB1
wiring is entirely contained within the unit electrical control box. For use on circuits up to 100 amps max. Larger requirements must use multiple circuits. VHB49K15 is the largest Vert-I-Pak approved for use with the VPDB1.
COLD CLIMATE KITS- The following kits are to be applied in climates where the outdoor design temperature is 15°F or below.
VPDPH5 VPDPH6
*No additional electrical service is required for these kits.
Outdoor coil drain pan/line heater for 18,000 – 36,000 Btu/h units.* Outdoor coil drain pan heater for 42,000 – 60,000 Btu/h units.*
4
920-164-02 (10-04)
Section I – Nomenclature
MODEL NUMBER V E A 09 K 50 RT A
SERIES V=Vertical Series
E=Cooling with or without electric heat H=Heat Pump
DESIGN SERIES
A = 32"/47" Cabinet B = 68" Cabinet
NOMINAL CAPACITY A Series (Btu/h)
09 = 9,000 12 = 12,000 18 = 18,000 24 = 24,000
VOLTAGE
K = 208/230V-1Ph-60Hz
B Series (Btu/h)
18 = 18,000 42 = 42,000 24 = 24,000 49 = 49,000 30 = 30,000 60 = 60,000 36 = 36,000
EN GI NEER ING CODE
OPTIONS
RT = Stan dard Re mote Op er a tion SP = Sea coast Pro tect ed
ELECTRIC HEATER SIZE A Series B Series
00 = No electric heat 00 = No electric heat 25 = 2.5 KW 05 = 5.0 KW 34 = 3.4 KW 10 = 10.0 KW 50 = 5.0 KW 15 = 15.0 KW 75 = 7.5 KW 20 = 20.0 KW 10 = 10.0 KW 25 = 25.0 KW
Section II – Dimensional Data
Figure 1 V(E,H)B18,24,30,36 Unit Dimensions (Inches)
INDOOR AIR RETURN (12" x 27" NOM.)
CONTROL BOX ACCESS
CONDENSATE DRAIN EXIT 2" ABOVE FLOOR
5
Figure 2 V(E,H)B42, 49 Unit Dimensions (Inches)
920-164-02 (10-04)
38.00
INDOOR AIR
RETURN 19" x 27"
NOM.
21.00
16.25
OUTDOOR
AIR
INTAKE
19.00
2.00
OUTDOOR
AIR
EXHAUST
12.00
14.00
22.5
23.25
11.6
2.0
2.00
V(E,H)B42
BACK VIEW
Figure 3 V(E,H)B60 Unit Dimensions (Inches)
OUTDOOR
AIR
INTAKE
19.1
V(E,H)B49
BACK VIEW
OUTDOOR
AIR
EXHAUST
9.5
11.6
22.5
1.5
68.00
CONTROL BOX ACCESS
SERVICE
PORT
ACCESS
INDOOR AIR SUPPLY
11.10
5.50
14.50
2.00
V(E,H)B42
BACK VIEW
6
INDOOR AIR SUPPLY
TOP VIEW
13.25
11.75
13.87
2.00