Friedrich VHA24K25, VEA24K25, VHA24K34, VEA24K34, VHA24K50 Installation & Operation Manual

...
Page 1
920-159-02 (10-04)
VERT-I-PAK® A-SERIES
SINGLE PACKAGE VERTICAL AIR CONDITIONING SYSTEM
24,000 BTU/h
Page 2
920-159-02 (10-04)
Table of Contents
Installation Recommendations ......................................................................................................................................................... 3
I. General Specifi cations
Model Number Identifi cation Guide ................................................................................................................................... 4
VERT-I-PAK Chassis Specifi cations ...................................................................................................................................4
II. Installation
1. Utility Closet Dimensions ................................................................................................................................................... 5
2. Wall Plenum & Architectural Louver Installation ................................................................................................................ 6
3. Electrical Information ..................................................................................................................................................... 7-9
4. Indoor Re turn Air Grille Installation .................................................................................................................................. 10
5. Ductwork Preparation and CFM ....................................................................................................................................... 11
6. Chassis Installation .......................................................................................................................................................... 11
7. Chassis Final Connections (Electrical, Duct, Drain & Wall Thermostat) ............................................................................ 12
8. Final Installation Checklist ............................................................................................................................................... 12
III. Chassis Operation
9. Thermostat Control ..........................................................................................................................................................12
10. Low Ambient Protection for Compressor & Fan ................................................................................................................ 12
11. Heating Defrost (Heat Pump Models only) ........................................................................................................................ 12
12. Fresh Air Door ...................................................................................................................................................................13
13. Condensate Disposal System ..........................................................................................................................................13
IV. Service, Maintenance & Warranty
14. Servicing / Chassis Quick Changeouts ............................................................................................................................. 13
15. Routine Maintenance .......................................................................................................................................................13
16. Warranty .......................................................................................................................................................................... 14
V. Vert-I-Pak Accessories ....................................................................................................................................................15
Please read this manual thoroughly prior to equipment installation or operation. It is the installer’s responsibility to properly apply and install the equipment. Installation must be in conformance with the NFPA 70-2002 National Electric Code or current edition and Universal Mechanical Code current edition and applicable local or national codes.
Proper installation is not diffi cult but it is essential.
2
Page 3
920-159-02 (10-04)
Vert-I-Pak Installation Recommendations
For proper unit performance and maximum operating life please refer to the minimum installation clearances
below.
Fig ure 1
VERT-I-PAK® units must be installed on an outside wall. Confi ned spaces and/or covered areas should be avoided. Units should be installed no closer than 12" apart when two units are side by side. If three of more units are to operate next to one another allow a minimum of 60" between units or pairs of units. Also, a vertical clearance of 60" should be maintained between units. Units installed on the bottom fl oor should be mounted at least 6" off of the ground.
6"
SMALL RECESS OK
60"
60"
60"
60" 60"
60"
60"
B
A
LARGER RECESS OK. IF A> 5xB
60"
60"
60"60"
6"
6"
Fig ure 2
Any time obstructions are present use the following guidelines for proper spacing from the VERT-I-PAK louver:
• For minor obstructions such as lamp poles or small shrubbery a clearance of 24" from the outdoor louver should be maintained.
• For major obstructions such as a solid fence, wall or other heat rejecting device like a condensing unit, a mini­mum distance of 72" should be kept.
BUILDING
24"60"
VPAK VPAK VPAK
OUTDOOR CONDENSING UNIT
12"
POLE
MAJOR OBSTRUCTION
SHRUB
12"
24"
72"
FENCE
The above suggestions are for reference only and do not represent all possible installations. Please contact the factory for information regarding affects of other installation arrangements.
By following these simple recommendations you can be confi dent that your Friedrich Vert-I-Pak of worry-free operation.
®
will provide years
3
Page 4
920-159-02 (10-04)
Section I. General Specifi cations
VERT-I-PAK® MODEL IDENTIFICATION GUIDE
MODEL NUMBER V E A 24 K 50 RT A
SERIES
V=Vertical Series
E=Cooling with or without electric heat H=Heat Pump
EN GI NEER ING CODE
OPTIONS
RT = Stan dard Re mote Op er a tion SP = Sea coast Pro tect ed
DESIGN SERIES
A = 32" and 47" Cabinet
NOMINAL CAPACITY A-Series (Btu/h)
09 = 9,000 12 = 12,000 18 = 18,000 24 = 24,000
VOLTAGE
K = 208/230V-1Ph-60Hz
Vert-I-Pak® Chassis Specifications
MODEL: V(E,H)A24
Voltage ( V) 230/208
Refrigerant R-22
Chassis Width 23.125
Chassis Depth 23.125
Chassis Height ** 47.25
Supply Duct Collar *** 10"
Drain Connection 3/4" FPT
Min. Circuit Amps See Nameplate
CFM Indoor See chart, pg. 11
Max. Duct ESP .4 in. water
ELECTRIC HEATER SIZE A-Series
00 = No electric heat 25 = 2.5 KW 34 = 3.4 KW 50 = 5.0 KW 75 = 7.5 KW 10 = 10 KW
NOTES: ** Height includes 2" duct collar & isolators under unit. *** Factory collar accepts 10" fl ex duct.
4
Page 5
920-159-02 (10-04)
II. Installation
1) Utility Closet Dimensions
Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 1. Three inches minimum clearance on three sides of the unit must be allowed for return airfl ow, installation access and service access. See Figures 1 & 2 for clear anc es and ref er ence di men sions.
Fig ure 3
Typical Utility Closet
Chassis Shown in Closet, on Optional Platform
Field-supplied Filter (25" x 20")
29"
VPRG4 Access Panel & Return Air Filter Grille
58"
Power Disconnect
Optional field
installed drain pan
(refer to local codes)
Optional Platform
3" Clearance on all
three sides minimum for
service and installation
Rigid Ductwork
Chassis is shipped with vibration isolators installed
Exterior Wall
Flexible Ductwork
VPAWP1-8/1-14 Wall Plenum
Plenum
VPDP1 drain pan beneath unit is required on all VEA/VHA24 units. Drain pan must be installed prior to chassis installation
Fig ure 4
control box
Top View
electrical entrance
Vert-I-Pak Chassis 2-ton dimensions:
• 23" wide x 23" deep x 47 1/4" high.
VPAWP1-8/1-14 Wall Plenum cut-out
• dimensions 24 5/8" wide x 30 7/8" high.
VPRG4 Access Panel cutout dimensions:
• 27" wide by 55 3/4" high.
See Figure 8 (Page 10) for proper
• chassis installation.
NOTE: Drain pan must be installed in closet prior to chassis insertion into plenum. See Figure 7 (page 8) for drain pan installation details.
5
Page 6
920-159-02 (10-04)
2) Wall Plenum and Architectural Louver Installation
A. Install the wall plenum (VPAWP1-8/1-14) components in accordance with the in stal la tion instructions provided with each accessory.
IMPORTANT REMINDER: FRIEDRICH WALL PLENUM IS NOT DESIGNED TO CARRY STRUCTURAL LOADS. PROPER WALL HEADER CONSTRUCTION IS REQUIRED. THE PLENUM RE QUIRES PROP ER FLASHING, SHIM AND CAULK FOR A WEATH ER RESISTANT INSTALLATION.
B. Ensure that the divider is adjusted properly for the depth of the wall in accordance with the accessory installation manual
Fig ure 5
Wall Ple num & Outdoor Louver In stal la tion
Proper Flashing
Proper Caulking
Proper Header
Outside Wall
Caulk all 8 fl ange cor ners
Inside Wall Plenum (Part B)
Proper Caulking
Architectural louver VPAL2 mounted on the outside wall plenum (Part A)
Rough opening dimension 24 5/8" wide x 30 7/8" high.
Ensure that the bottom of the plenum is 1 1/2" from the fl oor of the closet. Note: 9,000 / 12,000 / 18,000 installation
• height may be different. Refer to specifi c installation manual for clarifi cation.
For proper airfl ow, maintain a minimum distance of 12" between Vert-I-Pak units. Consult the factory for any
• installation or application questions.
6
Proper Flashing
Page 7
3) Electrical Information
Electrical Data
920-159-02 (10-04)
MODEL
VHA/VEA24K25
230/208 230/208 230/208 230/208 230/208 230/208
68 68 68 68 68 68 Cooling Current (A) MIN. Ckt. Amps (A)
Max Branch Circuit Fust (Amps)
* Single circuit from main box. Based on copper wire, single in su lat ed conductor at 60°C.
NOTE: Use copper conductors ONLY. Wire sizes are per NEC. Check local codes for over seas applications.
13.7/12.4 13.7/12.4 13.7/12.4 13.7/12.4 13.7/12.4 13.7/12.4
17.2/15.9 22.1/20.3 30.7/28.1 44.3/40.3 57.9/52.7 15.6/15.6
25/25 25/25 35/30 45/45 60/60 20/20
HARD WIRED
Recommended Branch
14/14 12/12 8/10 6/6 4/6 14/14
AWG - American Wire Gauge
Voltage ( V)
LRA - Comp. (A)
Power Connection
Circuit Wire Sizes*
VHA/VEA24K34
VHA/VEA24K50
VHA/VEA24K75
VHA/VEA24K10
VHA/VEA24K00
Sample Name plate (see your chassis name plate)
SAMPLE
7
Page 8
IMPORTANT: ALL 208/230V CHASSIS MUST BE HARD WIRED WITH PROPERLY SIZED BREAKER. SEE NAMEPLATE FOR SPECIFIC CHASSIS ELECTRICAL REQUIREMENTS. SEE PAGE 9 - FIGURE 8 FOR UNIT WIRING AND WALL THERMOSTAT WIRING. SEE PAGE 7 FOR WIRE SIZE. USE HACR TYPE BREAKERS TO AVOID NUISANCE TRIPS. ALL FIELD WIRING MUST BE DONE IN ACCORDANCE WITH NEC AND LOCAL CODES.
3) Electrical Information (continued)
Figure 6
Electrical Requirements
Note: All fi eld wiring must comply with NEC and local codes. It is the responsibility of the installer to insure that the electrical codes are met.
920-159-02 (10-04)
CAUTION
Wire Size
Fuse /Circuit Breaker
Grounding
Wire Sizing
Use ONLY wiring size recommended for single out let branch circuit.
Use ONLY type and size fuse or HACR circuit breaker indicated on unit's rating plate (See sample on page 6). Proper current protection to the unit is the responsibility of the own er.
Unit MUST be grounded from branch circuit to unit, or through separate ground wire provided on permanently connec ted units. Be sure that branch circuit or general purpose outlet is ground ed.
Use recommended wire size given in tables and install a single branch circuit. All wiring must comply with local and national codes. NOTE: Use copper conductors only.
Figure 7
Drain Connection and Location
Elec tric shock haz ard.
Turn OFF ele c tric pow er be fore service or in stal la tion.
All electrical connections and wir ing MUST be in stalled by a qual i fi ed elec tri cian and con form to the Na tion al Elec tri cal Code and all local codes which have ju ris dic tion.
Failure to do so can result in prop er ty damage, per son al injury and/or death.
CAUTION: THE ACCESSORY DRAIN PAN (VPDP1) MUST BE INSTALLED BEFORE INSTALLING THE UNIT.
1. The accessory drain pan has two (2) provisions (left & right) for connecting an external condensate drain.
2. A fi eld supplied condensate drain system must be connected to one of the two 3/4" FPT connections.
3. The remaining connection must be plugged using the 3/4" pipe plug (provided) and fi eld suppled tefl on tape or pipe joint compound.
4. Failure to follow these procedures may result in serious property damage.
5. This is the primary drain pan. A fi eld supplied secondary condensate pan may be applied. Check with local codes.
8
Page 9
3) Electrical Data (continued)
Figure 8
Electrical & Thermostat Wiring Diagrams
RT2
THERMOSTAT
(FRONT)
920-159-02 (10-04)
FOR 208 VOLT MODELS ONLY
MOVE THE WHITE WIRE AS
SHOWN BELOW
BLACK
COM.
208V 240V
WHITE
THERMOSTAT CONNECTIONS
(EAR)
UP
G R
R
W
Y
WHITE
BROWN
TERM BOARD
BROWN
YELLOW
YWRGBC
TRANSFORMER
24V
BLACK
B
C
RED
RED
c
CAPACITOR
WHITE
HERM
QUICK DISCONNECT
L1
BLACK
BLUE
COM.
TRANSFORMER
24V
208V
L2
WHITE
240V
GREEN
TO MOTOR
MOUNT
RED
WHITE
SEE NOTE #6
RED
GREEN
BLACK
BLACK
BLACK
CONDENSER
MOTOR
RED
BLACK BLUE RED
"F"
S
COMP WIRE HARNESS
R
C
"F"
"F"
COMPRESSOR
FAN
BLACK
BLUE
GREEN
RED
YELLOW
WHITE
123
COMPR RELAY
4
LOW AMBIENT
RED
BLACK
WHITE
BROWN
RED
COIL, SOLENOID
RED
BLACK
WHITE
CONTROL
WIRE NUT (RED)
WHITE
RED
PRESSURE
SWITCH
YELLOW
CAPACITOR
YELLOW
FAN
2 4
1 3
BLACK
c
HEATER
2.5 KW & 3.4 KW 5 KW
WHITE
FAN
RELAY
2
BLACK
BROWN
M
ER
H
RED
REV VALVE
4
31
RELAY
WHITE
BLUE
HEAT
RELAY
(2.5KW/3.4KW
2 4
1 3 123
BLACK
BLACK
RED
C
H
L
GREEN
BLOWER
MOTOR
5 KW)
T-STAT DEFROST
INSULATOR
2-REQ'D
TO MOTOR MOUNT
WIRE NUT (RED)
SEE NOTE #4
BLACK
7.5 KW & 10 KW
RED
RELAY
2 4
1 3
HEATER
HEAT
(2.5KW/3.4KW
5 KW)
BLACK
BLACK
RED
RED
HEAT RELAY (7.5KW/10KW) (7.5KW/10KW)
2
4
1
BLACK
BLACK
HEAT RELAY
4
3
NOTE: THE DIAGRAM ABOVE ILLUSTRATES THE TYPICAL THERMOSTAT WIRING AND 208
VOLT TRANSFORMER WIRING. SEE THE UNIT CONTROL PANEL FOR THE ACTUAL UNIT WIRING DIAGRAM AND SCHEMATIC.
9
Page 10
920-159-02 (10-04)
4) Indoor Return Air Grille Installation
There are three Indoor Return Air Grille options as shown in Figure 9. Choose the option that best suits your needs. Use the installation instructions provided with accessories for installation details.
Figure 9
Return Air Grille Op tions
Option 1
VPRG4 Return Air Grille with Access Panel
A fi eld-supplied (25" x 20") fi lter is mounted inside the hinged access door.
Option 2
All Vert-I-Pak chassis are shipped with a 20" x 14" fi lter installed. If an accessory fi lter holder is to be used, you MUST remove the factory shipped fi lter from the chassis. Do NOT use two fi lters
VPRG2 Return Air Grille
Unit requires a fi eld-supplied access door or panel and a 16" x 20" fi lter.
Notes:
A. These are the Friedrich recommended return air grille / fi lter / access panel arrangements. Consult the factory on other
arrangements. Im prop er return air arrangements will cause per for mance problems.
B. Return air arrangements are shown from the front, but can also be installed from the right or left side of the unit.
10
Page 11
920-159-02 (10-04)
5) Indoor Airfl ow Data
The Vert-I-Pak A series units must be installed with a free return air confi guration. The table below lists the indoor airfl ow at corresponding static pressures. All units are shipped from the factory and are rated at low speed.
To change to high speed replace the low speed lead (blue) with the high speed lead (black) on the blower relay.
VEA/VHA24K
Low High
.1” ESP 750 815 .2” ESP 725 780 .3” ESP 700 745 .4” ESP 675 700
Figure 10
Slide-in View / Chassis Installation
All values listed are inches W.C. with a wet indoor coil with fi lter installed.
6) Chassis Installation
NOTE: Prior to installing the chassis, ensure that the drain pan and line are free from debris.
A. Ensure that the wall ple num is in stalled in ac cor dance with
the VPAWP1-8/1-14 Installation Manual.
B. Ensure that the VPDP1 drain pan is installed correctly (see
page 8). Using the 3/4" plugs supplied with the pan, plug the unused condensate drain hole. Connect a drain to the condensate exit location. Be sure to use tefl on tape or approved pipe sealant on all drain connections and plugs (see page 8).
C. Place the chassis into the closet with the outdoor side
facing the wall plenum opening.
D. Slide the chassis into the wall plenum until the plenum
divider seal is established and the factory-installed chassis to plenum gasket has sealed to the top fl ange of the plenum. (See Figure 10)
Chassis to plenum gasket
The Vert-I-Pak chassis must be inserted into the wall plenum so that the plenum divider gas ket makes contact with the condenser baffle in the unit. The chassis will fit ap prox i mate ly 2
NOTE: Prior to installing the chas sis, ensure that the drain pan and line are free from debris.
3
/8" into the wall plenum.
23/
8
11
Page 12
920-159-02 (10-04)
7) Chassis Final Connections
With the chassis in place, you are now ready to begin chassis connections:
A. Move the thermostat switches to "OFF" and "AUTO." This
will keep the ther mo stat from cy cling the chassis until fi nal connections are com plete.
B. Connect the ductwork onto the 10" collar. Plas tic wireties (fi eld
sup plied) are suggested to se cu re the ductwor k in pla ce. U se 2 wire ties, one for each inner and outer fl ex duct sleeve.
D. For 208 Volt pow er o nly: y ou mu st mo ve t he tran s form er wire
as shown in Fig ure 8, Page 9.
RT2 Digital Thermostat
III. Chassis Operation
E. Review the Fi nal Installation Check list on Page 12 before
re plac ing the pow er quick dis con nect, reconnecting power to the chassis, plug ging in the re mote ther mo stat har ness, or op er at ing the chassis.
Electrical shock and moving parts hazard can cause injury or death. If you have not done so, pull out the disconnect head found on the front of chas sis before continuing instal­lation! Disconnect external power at the breaker.
8) Final Installation Checklist
Correct line voltage?
Chassis deck level?
Plenum divider baffl e installed?
Wall plenum caulked? Level? Flashing?
HACR type breaker/fuse?
9) Remote Thermostat Control
The chassis requires a simple single stage heat-cool wall thermostat. Each chassis comes with a terminal strip located in the electrical control box. All internal chassis wiring (low & high voltage) is factory ready for 230 Volt operation. For 208 Volt operation a single wire MUST BE CHANGED ON THE TRANS FORM ER. Refer to Figure 8 on page 9.
10) Low Ambient Protection
Each chassis is equipped with Low Ambient Protection in the form of a suction line thermostat. This thermostat will prevent compressor operation at low suction line temperatures. Each chassis is also equipped with a factory in stalled bellows that will drain water from the base pan to prevent the fan slinger from freezing during winter weather.
11) Heating Defrost (Heat Pump Models Only)
All Heat Pumps have a passive heating defrost system. Defrost occurs as needed and automatically switches to electric heat during defrost. When the outdoor ambient temperature drops below a 45°F factory setting, the chassis au to mat i cal ly switch es to electric heat. As outdoor ambient temperatures rise above 45°F, the chassis returns to the heat pump mode. The changeover temperature is user adjustable from approximately 32°F - 55°F. The defrost thermostat may also be used to lock out the compressor in an emergency heat situation.
Single circuit only?
Ductwork connected?
Chassis weather seal in place?
Wall thermostat wired correctly?
Chassis inserted into plenum?
12
Page 13
920-159-02 (10-04)
12) Fresh Air Door
The Fresh Air Door is an "intake" system. The fresh air door is opened via a slide on the front of the chassis located just above the indoor coil. Move the slide left to open and right to close the fresh air door. The system is capable of up to 60 CFM of fresh air @ ~.3" H20 internal static pressure.
13) Condensate Disposal System
The VPDP1 drain pan features two ¾ female PVC fi ttings to attach a drain connection to on the left or right side of the drain pan. Condensate piping can be routed to the left, right or beneath
the unit platform.
See page 8 or the drain pan installation manual for more information.
Part 1: The system’s fi rst stage increases energy
effi ciency utilizing a factory installed fan that slings the cold condensate onto the hot outdoor coil.
Part 2: When high outdoor humidity prevents the slinger
from disposing of all the condensate, the excess condensate overfl ows into the condensate drain pan and out of the ¾" internal drain connections.
Part 3: If Parts 1 & 2 fail for any reason, excess
condensate overfl ows from a spillway directly into the wall plenum to the outside of the building. IF
THIS OCCURS, THIS IS YOUR WARNING THAT THE CHAS SIS OR DRAIN NEEDS SERVICING.
15) Routine Maintenance
Performing Routine Maintenance
With the proper maintenance and care, your system will operate economically and dependably. Maintenance can be accomplished easily by referring to the following directions. However, before performing any maintenance, consider these important safety precautions:
WARNING: Electrical Shock Hazard. Before attempting any service work or routine maintenance, turn off all electrical connections to the unit. Failure to do so may result in property damage, personal injury and/or death.
CAUTION: Although great care has been taken to minimize sharp edges in the construction of your unit, be extremely careful when handling parts or reaching into the unit.
Replace Air Filter
A dirty air fi lter reduces the effi ciency of your Vert-I-Pak and allows lint and dirt to accumulate on the indoor-air coil. Lint and dirt on the indoor-air coil can damage your unit and void the warranty. The air fi lter should be replaced as it becomes dirty.
To replace the fi lter (chassis mounted return air fi lter):
1. Slide the fi lter clear of the fi lter rails.
2. Remove the fi lter.
3. Install new disposable fi lter.
CAUTION: Do not operate your system without a fi lter in place, nor block the front of the unit return air opening.
IV. Service & Warranty
14) Servicing / Chassis Quick Changeouts
The chassis is designed for quick disconnect and change out. For minor electrical service, the control box cover lifts straight up after the screws & disconnect head are removed. For major electrical, refrigeration and fan service the chas sis may be removed from utility closet.
To Remove the Chassis from the Closet:
A. Switch the wall Ther mo stat off.
B. Pull the Power Disconnect located in the front of the chassis.
C. Disconnect the thermostat wiring harness.
D. Disconnect the electrical connection.
E. Disconnect the ductwork.
F. Slide the chassis out of the wall ple num.
G. Lift the chassis out of the utility closet.
Electrical shock and moving parts hazard can cause injury or death. Pull out the disconnect head found on the front of the chassis before servicing.
Inspect and Clean Indoor-air Coil
Eventually, minor amounts of lint and dirt may pass through the fi lter and collect on the indoor-air coil. These minor accumulations can be carefully vacuumed away with a brush attachment on a vacuum cleaner. Care must be taken to avoid bending the aluminum fi ns on the coil. Bent fi ns should be straightened using a special fi n tool available from most HVAC service technicians.
Inspect Outdoor-air Intake and Exhaust
The unit’s outdoor-air intake and outdoor-air exhaust paths must remain clear. Check the OA exhaust frequently. Keep it free of all debris, snow, or ice. The OA intake should also be kept free of obstructions. Blocking the OA exhaust or OA intake opening will reduce the effi ciency of your unit, could damage it, and may void your warranty.
Inspect and Clean Condensate Drain
The condensate drain must be routed to a suitable drainage area. Check the unit condensate drain periodically. Keep it free of anything that may block or impede the fl ow of condensate water. If there is any accumulation of foreign matter in the drain pipe, it should be removed and cleaned. The entire drain line must be protected from freezing.
16) Warranty
All service work must be done by a qualifi ed servicer. See Warranty on the next page, and consult your dealer or contractor for details
13
Page 14
920-159-02 (10-04)
Friedrich Air Conditioning Company
P.O. Box 1540
San Antonio, TX 78295
210.357.4400
www.friedrich.com
VERT-I-PAK® A SERIES
SINGLE PACKAGE VERTICAL AIR CONDITIONERS
LIMITED WARRANTY
SAVE THIS CERTIFICATE.
province to province.
In the event that your unit needs servicing, contact your nearest authorized service center. If you do not know the nearest service center, ask the company that installed your unit or contact us - see address and telephone number above. To obtain service and/or warranty parts replacement, you must notify an authorized FRIEDRICH Air Conditioning Co. service center, distributor, dealer, or contractor of any defect within the applicable warranty period.
When requesting service:
Unless specified otherwise herein, FRIEDRICH VERT-I-PAK A SERIES VERTICAL AIR CONDITIONERS AND HEAT PUMPS
LIMITED WARRANTY - FIRST YEAR (Twelve (12) months from the date of installation).
the material or workmanship will be repaired or replaced free of charge by our authorized service center during the normal working hours; and
LIMITED WARRANTY - SECOND THROUGH FIFTH YEAR (Sixty (60) months from the date of installation). ON THE SEALED REFRIGERATION SYSTEM.
will be repaired or replaced free of charge (excluding freight charges) by our authorized service center during normal working hours. The sealed refrigeration system consists of the compressor, metering device, evaporator, condenser, reversing valve, check valve, and the interconnecting tubing.
It gives you specific rights, you may also have other rights which may vary from state to state and
please have the model
the following applies:
Any part of the sealed refrigeration system that is defective in material or workmanship
and serial number from your unit readily available.
Any part found to be defective in
These warranties apply only while the unit remains at the original site and only to units installed inside the continental United States, Alaska, Hawaii, Puerto Rico and Canada. The warranty applies only if the unit is installed and operated in accordance with the printed instructions and in compliance with applicable local installation and building codes and good trade practices. For international warranty information, contact the Friedrich Air Conditioning Company ­International Division.
Any defective part to be replaced must be made available to proof must be presented to establish the date of install, otherwise the beginning date of this certificate will be considered to be our shipment date plus sixty days. Replacement parts can be new or remanufactured. Replacement parts and labor are only warranted for any unused portion of the unit’s warranty.
We will not be responsible for and the user will pay for:
1. Service calls to: A) Instruct on unit operation. B) Replace house fuses or correct house wiring. C) Clean or replace air filters. D) Remove the unit from its installed location when not accessible for service required. E) Correct improper installations.
2. Parts or labor provided by anyone other than an authorized service center.
3. Damage caused by: A) Accident, abuse, negligence, misuse, riot, fire, flood, or acts of God. B) Operating the unit where there is a corrosive atmosphere containing chlorine, fluorine, or any damaging chemicals (other than in a normal residential environment). C) Unauthorized alteration or repair of the unit, which in turn affects its stability or performance. D) Failing to provide proper maintenance and service. E) Using other than a “Seacoast Protected” unit in a coastal environment. F) Using an incorrect power source. G) Faulty installation or application of the unit.
We shall not be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure of this unit. We have not made and do not make any representation or warranty of fitness for a particular use or purpose and there is no implied condition of fitness for a particular use or purpose. We make no expressed warranties except as stated in this certificate. No one is authorized to change this certificate or to create for us any other obligation or liability in connection with this unit. Any implied warranties shall last for one year after the original purchase date.
above limitations or exclusions may not apply to you. The provisions of this warranty are in addition to and not a modification of or subtraction from the statutory warranties and other rights and remedies provided by law.
Some states and provinces do not allow limitations on how long an implied warranty or condition lasts, so the
FRIEDRICH
in exchange for the replacement part. Reasonable
In case of any questions regarding the provisions of this warranty, the English version will govern.
14
(10-04)
Page 15
920-159-02 (10-04)
IV. Vert-I-Pak Accessories
MODEL DESCRIPTION PHOTO
WALL PLENUM Two-part sleeve that telescopes in and out
1
from 5
/2" to 8" in depth. The wall plenum sits inside the
VPAWP1-8
exterior wall penetration.
3
DIMENSIONS: 30
/8" high x 241/8" wide.
CUTOUT DIMENSIONS: 30
7
/8" high x 245/8" wide.
VPAWP1-14
VPAL2
VPSC2
RT2
VPRG4
Same as VPAWP1-8, but telescopes 8" to 14" as required.
ARCHITECTURAL LOUVER Extruded aluminum louver that attaches to the outdoor section of the wall plenum.
1
DIMENSIONS: 31
/16" high x 259/16" wide.
Same as VPAL2 but can be ordered in a special color to match the exterior wall.
DIGITAL THERMOSTAT Digital electronic thermostat with "one touch" adjustment. Mounts to wall for control of unit.
ACCESS PANEL / RETURN AIR GRILLE – Serves as an access panel to chassis and interior return air grille. A field-supplied (25" x 20") filter is mounted inside the hinged access door. DIMENSIONS: 58" high x 29" wide. CUTOUT DIMENSIONS: 55
3
/4" high x 27" wide.
RETURN AIR GRILLE – Interior return air grille that hinges
VPRG2
to allow a field supplied (16" x 20") filter to slip inside. Must be used when an access door / panel already exists in closet. DIMENSIONS: 18
VPDP1
DRAIN PAN for VEA/VHA24 models. Drain pan may be installed prior to chassis for easy installation/removal.
7
/16" high x 223/8" wide.
15
Page 16
Use Factory Certifi ed Parts.
FRIEDRICH AIR CONDITIONING CO.
Post Office Box 1540 · San Antonio, Texas 78295-1540 4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212 (210) 357-4400 · Fax (210) 357-4480 www.friedrich.com
Printed in the U.S.A.
920-159-02 (10-04)
Loading...