Friedrich VEA24 Operation Guide

920-159-02 (10-04)
VERT-I-PAK® A-SERIES
SINGLE PACKAGE VERTICAL AIR CONDITIONING SYSTEM
24,000 BTU/h
920-159-02 (10-04)
Table of Contents
Installation Recommendations ......................................................................................................................................................... 3
I. General Specifi cations
Model Number Identifi cation Guide ................................................................................................................................... 4
VERT-I-PAK Chassis Specifi cations ...................................................................................................................................4
II. Installation
1. Utility Closet Dimensions ................................................................................................................................................... 5
2. Wall Plenum & Architectural Louver Installation ................................................................................................................ 6
3. Electrical Information ..................................................................................................................................................... 7-9
4. Indoor Re turn Air Grille Installation .................................................................................................................................. 10
5. Ductwork Preparation and CFM ....................................................................................................................................... 11
6. Chassis Installation .......................................................................................................................................................... 11
7. Chassis Final Connections (Electrical, Duct, Drain & Wall Thermostat) ............................................................................ 12
8. Final Installation Checklist ............................................................................................................................................... 12
III. Chassis Operation
9. Thermostat Control ..........................................................................................................................................................12
10. Low Ambient Protection for Compressor & Fan ................................................................................................................ 12
11. Heating Defrost (Heat Pump Models only) ........................................................................................................................ 12
12. Fresh Air Door ...................................................................................................................................................................13
13. Condensate Disposal System ..........................................................................................................................................13
IV. Service, Maintenance & Warranty
14. Servicing / Chassis Quick Changeouts ............................................................................................................................. 13
15. Routine Maintenance .......................................................................................................................................................13
16. Warranty .......................................................................................................................................................................... 14
V. Vert-I-Pak Accessories ....................................................................................................................................................15
Please read this manual thoroughly prior to equipment installation or operation. It is the installer’s responsibility to properly apply and install the equipment. Installation must be in conformance with the NFPA 70-2002 National Electric Code or current edition and Universal Mechanical Code current edition and applicable local or national codes.
Proper installation is not diffi cult but it is essential.
2
920-159-02 (10-04)
Vert-I-Pak Installation Recommendations
For proper unit performance and maximum operating life please refer to the minimum installation clearances
below.
Fig ure 1
VERT-I-PAK® units must be installed on an outside wall. Confi ned spaces and/or covered areas should be avoided. Units should be installed no closer than 12" apart when two units are side by side. If three of more units are to operate next to one another allow a minimum of 60" between units or pairs of units. Also, a vertical clearance of 60" should be maintained between units. Units installed on the bottom fl oor should be mounted at least 6" off of the ground.
6"
SMALL RECESS OK
60"
60"
60"
60" 60"
60"
60"
B
A
LARGER RECESS OK. IF A> 5xB
60"
60"
60"60"
6"
6"
Fig ure 2
Any time obstructions are present use the following guidelines for proper spacing from the VERT-I-PAK louver:
• For minor obstructions such as lamp poles or small shrubbery a clearance of 24" from the outdoor louver should be maintained.
• For major obstructions such as a solid fence, wall or other heat rejecting device like a condensing unit, a mini­mum distance of 72" should be kept.
BUILDING
24"60"
VPAK VPAK VPAK
OUTDOOR CONDENSING UNIT
12"
POLE
MAJOR OBSTRUCTION
SHRUB
12"
24"
72"
FENCE
The above suggestions are for reference only and do not represent all possible installations. Please contact the factory for information regarding affects of other installation arrangements.
By following these simple recommendations you can be confi dent that your Friedrich Vert-I-Pak
®
will provide years
of worry-free operation.
3
920-159-02 (10-04)
Section I. General Specifi cations
VERT-I-PAK® MODEL IDENTIFICATION GUIDE
MODEL NUMBER V E A 24 K 50 RT A
SERIES
V=Vertical Series
E=Cooling with or without electric heat H=Heat Pump
EN GI NEER ING CODE
OPTIONS
RT = Stan dard Re mote Op er a tion SP = Sea coast Pro tect ed
DESIGN SERIES
A = 32" and 47" Cabinet
NOMINAL CAPACITY A-Series (Btu/h)
09 = 9,000 12 = 12,000 18 = 18,000 24 = 24,000
VOLTAGE
K = 208/230V-1Ph-60Hz
Vert-I-Pak® Chassis Specifications
MODEL: V(E,H)A24
Voltage ( V) 230/208
Refrigerant R-22
Chassis Width 23.125
Chassis Depth 23.125
Chassis Height ** 47.25
Supply Duct Collar *** 10"
Drain Connection 3/4" FPT
Min. Circuit Amps See Nameplate
CFM Indoor See chart, pg. 11
Max. Duct ESP .4 in. water
ELECTRIC HEATER SIZE A-Series
00 = No electric heat 25 = 2.5 KW 34 = 3.4 KW 50 = 5.0 KW 75 = 7.5 KW 10 = 10 KW
NOTES: ** Height includes 2" duct collar & isolators under unit. *** Factory collar accepts 10" fl ex duct.
4
920-159-02 (10-04)
II. Installation
1) Utility Closet Dimensions
Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 1. Three inches minimum clearance on three sides of the unit must be allowed for return airfl ow, installation access and service access. See Figures 1 & 2 for clear anc es and ref er ence di men sions.
Fig ure 3
Typical Utility Closet
Chassis Shown in Closet, on Optional Platform
Field-supplied Filter (25" x 20")
29"
VPRG4 Access Panel & Return Air Filter Grille
58"
Power Disconnect
Optional field
installed drain pan
(refer to local codes)
Optional Platform
3" Clearance on all
three sides minimum for
service and installation
Rigid Ductwork
Chassis is shipped with vibration isolators installed
Exterior Wall
Flexible Ductwork
VPAWP1-8/1-14 Wall Plenum
Plenum
VPDP1 drain pan beneath unit is required on all VEA/VHA24 units. Drain pan must be installed prior to chassis installation
Fig ure 4
control box
Top View
electrical entrance
Vert-I-Pak Chassis 2-ton dimensions:
• 23" wide x 23" deep x 47 1/4" high.
VPAWP1-8/1-14 Wall Plenum cut-out
• dimensions 24 5/8" wide x 30 7/8" high.
VPRG4 Access Panel cutout dimensions:
• 27" wide by 55 3/4" high.
See Figure 8 (Page 10) for proper
• chassis installation.
NOTE: Drain pan must be installed in closet prior to chassis insertion into plenum. See Figure 7 (page 8) for drain pan installation details.
5