Friedrich SS08N10C User Manual

Room Air Conditioners
AUTO
°F°C AUTO CONTINUOUS
AUTO
SYSTEM FAN MODE
SCHEDULE FAN SPEED
Window Installation Instructions
Standard Chassis Models
115-Volt:
208-230-Volt:
115-Volt:
208-230-Volt:
93001014_00
SS08, SS10, SS12, SS14 SS12, SM18,SM21
, SM15,
SL24, SL28, SL36
EQ08,YS10 ES12, ES16, YS12, EM18, YM18, EM24, EL24, EL36, YL24
Airflow Selection and Adjustment
Air flow direction adjustment
left or right side of the discharge opening. Each of the banks of louvers can be directed left, right, up or down in order to achieve the most optimum
move it in the direction that you would like the air to be directed. Please
louvers than the other.
Fresh air and exhaust control
Your air conditioner has the ability to bring fresh air into the room or exhaust stale air out of the room. The control slide is found on the upper part of the unit (See Figure 13).
TO BRING IN FRESH AIR – Move the lever to the Fresh Air which allows outside air to enter the room. This is useful in fall and spring as a means of bringing in fresh outside air when using FAN ONLY . It can also be used in the summer with the compressor in the Cooling Mode if you wish.
TO EXHAUST INDOOR AIR – Move the lever to the Exhaust position. This will allow stale air to be expelled to the outside of the dwelling. This is especially handy in the spring or fall when indoor air tends to get stale, or after a social gathering involving smokers, or to remove cooking odors.
BEST PERFORMANCE – Move the lever to the Re-Circulate Position
position
Figure 13
FRR008
17
Installation Instructions
READ THIS FIRST! Electrical Requirements
WARNING
Electrical Shock Hazard
Make sure your electrical receptacle has the same configuration as your air conditioner’s plug. If different, consult a Licensed Electrician.
Do not use plug adapters. Do not use an extension cord. Do not remove ground prong.
Always plug into a grounded 3 prong oulet. Failure to follow these instructions can result in death, fire, or electrical shock.
IMPORTANT: Before you begin the actual installation of your air
Your air conditioner must be connected to a power source with the same alternating current (A.C.) voltage and amperage as marked on the name plate located on the chassis. Only A.C. can be used. Direct Current (D.C.) cannot b
e used.
CIRCUIT PROTECTION – Use on single outlet circuit only. An overloaded circuit will invariably cause malfunction or failure of an air conditioner, therefore, it is necessary that the electrical protection is adequate. Due to momentary high current demand when the air conditioner starts, use a "TIME DELAY" fuse or a HACR type circuit breaker. Consult your dealer or power company if in doubt.
fer to the electrical name plate located on the air conditioner chassis
Re (See page 2) to determine the correct fuse or circuit breaker amperage for your model (See Table 1 on Page 6 for electrical receptacle types).
The power cord has a plug with a grounding prong and a matching receptacle is required.
The following instructions are for standard chassis model groups
sizes listed in Table 3.
Table 3
MODEL DESIGNATION CABINET SIZE (H x W x D)
SMALL CHASSIS - SS, ES, YS
MEDIUM CHASSIS - SM, EM, YM
LARGE CHA SS IS - SL, EL, YL
15
15
⁄16" x 25 15⁄16" x 29" (405 mm x
660 mm x 737 mm)
15
17
⁄16" x 25 15⁄16" x 29" (455 mm x
660 mm x 737 mm)
3
20
⁄16" x 28" x 35 1⁄2" (513 mm x 711
mm x 851 mm)
WARNING
MOVING PARTS HAZARDS
* Do not operate unit out of sleeve
or with front grille removed.
.woleb noitamrofni eht dna sedoc lacirtcele lacol kcehc ,renoitidnoc
* Do not place hands in blower or
fan blade areas. Failure to do so can result in serious injury.
CAUTION
Excessive Weight Hazard
Use two or more people when installing your air conditioner.
Failure to do so can result in back or other injury.
Recommended Tools
1. Power Drill
2. 5/32" Drill Bit
3. Gloves
4. Carpenters Level
5. 5/16" Wrench
6. 1/4" Wrench
7. #2 Phillips Screw Driver
8. Putty Knife or (wood stir stick)
18
4
1
5/16
2
3
ITEMS NOT TO SCALE
5/16
1/4
1/4
65
87
INSTALLATION HARDWARE AND ACCESSORY DETAIL
ITEM 10
ITEMS NOT TO SCALE
ITEM 1
ITEM 4
ITEM 7
ITEM 11
ITEM 2
ITEM 8
ITEM 12 ITEM 13
ITEM 3
ITEM 5 ITEM 6
ITEM 9
ITEM 14
FRR009
ITEM
DESCRIPTION QTY.
NO
SHELL MOUNTING PARTS
1 2 3 4
5 6 7
8 9
10
11
12 1 13 14
SUPPORT BRACKET SCREW, 10-24 x 1" HEX HEAD
10-24 FLAT WELD NUT
SCREW, SHEET METAL #12 x 2"
WINGBOARD ANGLE MOUNTING
WINGBOARD ANGLE, TOP WINGBOARD ANGLE, SIDE SCREW, SHEET METAL #8 x
WINGBOARD MOUNTING PARTS
WINGBOARD (MASONITE) "J" TYPE SPEED NUT WINGBOARD CLIP (SPRING STEEL) SCREW, #8 x ½" PHILLIPS TRUSS HD.
WINDOW SEALING
WINDOW SEAL GASKET (DARK FOAM) CHASSIS SEAL GASKET (LIGHT FOAM) R1 INSULATION PANEL (GREY FOAM)
3
8
"
ITEM
DESCRIPTION QTY.
NO
2 4 4 7
1 2 2
1 4 4 4
1 1
13
NOTE: Kühl + models do not come with window mounting
MOUNTING PARTS
4
SCREW, SHEET METAL #12A x 2” CHASSIS SEAL GASKET (LIGHT FOAM)
components. When mounting a cooling and heating model a window installation kit must be purchased separately.
KWIKS – For all ES and YS models. KWIKM – For all EM and YM models. KWIKL – For all EL and YL models.
7 1
19
Standard Window Installation
Figure 15
NOTE: Hardware and accessories used during installation are shown
STEP 1. Remove the chassis Entrygard retainer by removing the far
on page 18. Each part will be referred as Item No.
right screw (See Figure 14), save this screw to reattach the chassis retainer after installation (Step 12). Also, remove and discard the two retainer screws and washers located at the rear of the unit (See Figure 14).
CAUTION
Handle Use
Use handle on both sides to
eldnaH esU
pull unit from sleeve.
snoitacoL
]sedis htob[
Do not push, pull or lift from center of support.
STEP 2. Hold the cabinet stationary, then use the hand grips on both
STEP 3. Remove the large white foam blocks used to restrain the
ends of the control unit support bracket to pull the chassis out of the cabinet (See Figure 15).
compressor during shipment (See Figure 16). Inspect base pan for dislodged white foam blocks and remove. Do not remove any other foam parts.
CONTROL UNIT
SUPPORT BRACKET
STEP 4. Anchor the side angles (Item 6) by engaging the tabs of the
lo
wer sill plate (See Figure 17, Detail B-2) with the loops of the side angle. Engage the tabs of the top angle (Item 5) with the top loops of the side angle (See Figure 17, Detail B-1). Install two (2) screws (Item 7) to secure the top angle tabs and the side angle to the cabinet (See Figure 17, Detail B-1).
FRR012
Figure 14
RETAINER SCREWS AND WASHERS
ENTRYGARD RETAINER WIRE
FAR RIGHT
SCREW
20
FRR011
CAUTION
TOP VIEW OF UNIT
Remove Shipping Blocks
Prior to operating the unit remove the foam shipping blocks.
Failure to do so may result in damage to the unit which is not covered by the manufacturer’s warranty!
STEP 5. Check the window sill and frame to be sure they are in good
STEP 6. CABINET MOUNTING – Raise the lower window 1/4" more
STEP 7. OUTSIDE SUPPORT MOUNTING – Refer to Figures 19 and
Figure 16
than the height of the cabinet. Carefully slide the cabinet through the opening until the lower sill plate channel rests behind the window sill and the top angle rests against the window (See Figure 18). Center the cabinet within the opening. Drill three (3) 5/32" diameter pilot holes into window sill using the holes in the cabinet sill plate as a guide. Install
th
ree (3) #12 x 2" long screws (Item 4) (See Figure 18).
20. Assemble the support brackets (Item 1) to the bottom of the cabinet with four (4) 10-24 1” long screws (Item 2) and four
combination of the elongated holes of the bracket and different hole locations in the cabinet, to bring the bottom support bracket pads in contact with the wall. A 1" x 4" or 2" x 4" SPACER SHOULD BE USED BETWEEN THE WALL AND SUPPORT THE BRACKETS WHEN INSTALLED ON ALUMINUM OR VINYL SIDING. Drill 5/32" diameter pilot holes and secure the brackets to the wall with two (2) 12A x 2" long screws (Item 4).
NOTE: DO NOT LEVEL the cabinet from front to back. Make sure there
Adjust the support brackets to provide an inside-to-outside slope for excess condensation drainage (Refer to Standard Window Installation, Figures 19 through 23). Tighten all screws.
Alternate support method A: If you have a wide window sill which prevents
Using the elongated holes and different
Tighten all screws.
Alternate support method B: If the window ledge gap is narrow, try the
as shown in Figure 23. Bend the short piece so it will be vertical when
installed. Adjust the placement as required. Tighten all screws.
STEP 8.
is approximately 3/8” to 1/2” slope (1/8 to 1/4 bubble on level) toward the outside of the house.
hole locations in the cabinet,
Make sure you include the depth of the window channel.
NOTICE
For YOUR security and safety, YOU must provide a means of preventing the upper part of the window from opening.
STEP 9. To assemble the wingboard panels, push on the "J" type speed
nuts (Item 9) and spring steel clips (Item 10) (See Figures 25) on page 26. Secure each panel with two (2) screws (Item 11).
:gniwollof eht yrt ,22 erugiF ni nwohs sa stekcarb eht gnitnuom morf uoy
.)22 erugiF( thgiew s’tinu eht troppus ot tekcarb eht fo tnemecalp eht tes
.)42 erugiF( .tenibac dna slennahc edis wodniw eht neewteb
LEFT SIDE
REMOVE AND DISCARD
FOAM BLOCKS
COMPRESSOR
BACK
FAN MOTOR
EVAPORATOR COIL
FRONT
REMOVE AND DISCARD SCREWS
RIGHT SIDE
REMOVE AND SAVE SCREW FOR RE-INSTALLATION
FRR045
21
Figure 17
CABINET
#8 x 3/8” LONG SCREW (ITEM 7) 2 REQUIRED
TOP ANGLE (ITEM 5)
TAB
Figure 18
DRILL (3) 5/32” DIA.
PILOT HOLES AND
INSTALL (3) #12 x 2”
CENTER
CABINET
IN WINDOW
SIDE TO SIDE
LONG SCREWS
(ITEM 4)
SILL PLATE
TAB
SIDE ANGLE (ITEM 6) 2 REQUIRED
DETAIL B-2
DETAIL B-1
TAB
LOOP
FRR013
TOP ANGLE (ITEM 5)
PULL WINDOW SASH DOWN BEHIND TOP ANGLE
22
SIDE ANGLE (ITEM 6)
WINDOW SILL
LOCATE SILL PLATE GUIDE CHANNEL
JUST BACK OF WINDOW SILL
FRR014
Figure 19
3/8” SLOPE DOWN
#10-24 x 1” HEX HD. SCREW (ITEM 2)
SUPPORT BRACKET (ITEM 1)
SPACER SHOULD BE USED BETWEEN WALL AND BRACKET WHEN INSTALLED ON ALUMINUM OR VINYL SIDING.
Figure 20
#12 x 2” SCREW
(ITEM 4)
SUPPORT BRACKET (ITEM 1)
10-24 x FLAT WELD NUT (ITEM 3)
FRR015
3/8” SLOPE DOWN
CONDENSER AIR OUTLET
CONDENSER AIR INLETS
#10-24 SCREW #10-24 FLAT WELD NUT
#12 x 2” SHEET METAL SCREW (ITEM 4)
SPACER SHOULD BE USED BETWEEN WALL AND BRACKET WHEN INSTALLED ON ALUMINUM OR VINYL SIDING.
FRR016
23
Figure 21
STONE LEDGE
3/8” SLOPE DOWN
CONDENSER AIR INLETS
#10-24 SCREW
#10-24 FLAT WELD NUT
#12 x 2” SHEET METAL SCREW (ITEM 4)
SPACER
FRR017
Figure 22
3/8” SLOPE DOWN
#10-24 SCREW
STRAIGHTEN TAB TO LAY FLAT ALONG THE BOTTOM RAIL OF THE SHELL
#10-24 FLAT WELD NUT
SECURE THE LONGEST SIDE OF THE BRACKET TO THE SHELL
ADJUST IN OR OUT TO REST ON THE LEDGE
24
STONE LEDGE
FRR018
Figure 23
3/8” SLOPE DOWN
Figure 24
#10-24 SCREW
#10-24 FLAT WELD NUT
STONE LEDGE
OUTSIDE WALL
DIMENSION “A”
CUT HERE
CUT TO FIT DIMENSION “A” AND BEND DOWN TO FORM A VERTICAL LEG.
A
DISCARD SHADED AREA
MEASURE DISTANCE “B” TO INSIDE OF THE CHANNEL ON EACH SIDE.
FRR019
B
B
B
CUT HERE AND DISCARD CENTER WASTE MATERIAL.
WINGBOARD
B
SUBTRACT 1/8” FROM DIMENSION “B” AND MEASURE FROM THE EDGE OF THE WING­BOARD (ITEM 8), MARK, SCORE AND CUT WITH APPROPRIATE CUTTING TOOL.
FRR020
25
Figure 25
“J” TYPE SPEED NUT (ITEM #9) 2 REQUIRED
CUT
WINGBOARD
PANEL
SPRING STEEL CLIP (ITEM 10) 2 REQUIRED
3"
CUT EDGE
CENTER THE HOLE IN THE SPEED NUT OVER THE SLOT IN THE WINGBOARD PANEL
3"
SLIDE CLIP OVER CUT EDGE OF WINGBOARD PANEL
ROTATED 90°
FRR021
2
STEP
INSTALL THE R1 INSULATION PANEL – To
10.
minimize air leaks and ensure optimal insulation, install the included R1 insulation panel. (14 in parts list) (See Figure below A-C).
First, measure the width from one side of the cabinet/sleeve (covering the side angles where the wingboard was just secured) to the end of the wingboard. (See Figure A)
Next cut the R1 insulation panel to the measured width and remove protective cover, exposing adhesive on back panel (See Figure B)
Last, evenly apply the adhesive side of the panel across the entire height and width from side angle to wingboard panel. (See Figure C)
Repeat the steps above for the other wingboard panel.
STEP 11. INSTALL THE WINDOW SEALING GASKETS – Measure
the
and cut
Pull the window sash down behind the gasket. Measure and cut the dark foam window seal gasket (Item 13) and install it between the upper glass panel and the top part of the lower window sash (Figure 29).
vinyl window seal gasket (grey color, Item 12) to
CAUTION
Excessive Weight Hazard
Use two or more people when installing your air conditioner.
INSERT FOAM WINDOW SEAL GASKET (ITEM 12)
I
Failure to do so can result in back or other injury.
CAUTION
Cut/Sever
Although great care has been taken to minimize sharp edges in the construction of your unit, use gloves or other hand protection when handling unit
Failure to do so can result in minor to moderate personal injury.
STEP 12 Carefully team lift the chassis and set it into the cabinet. Slide
NOTE:
the chassis stopping approximately 3" from full insertion. Insert the chassis seal gasket (Item 14) one inch deep between the
A paint stir stick or ruler might be helpful here. Begin inserting the gasket at either bottom corner and go up the side, across the top, and down the opposite side. Then push the chassis all the way into the cabinet.
If the chassis seal gasket is not installed or installed improperly,
the operation of the unit will be negatively affected. Operational
.82 egap no nwohs sa )92 erugiF eeS( tenibac eht dna sissahc
26
STEP 13. Reattach the entry guard chassis entry guard retainer wire with
the same screw retained in Step 1 (See Figure 14).
C
FRR023
TOP OF CABINET
Figure 27Figure 26
PLACE WINGBOARD PANEL IN WINDOW JAM TO COMPRESS THE SPRINGS INSIDE THE RUNNERS, AND SWING THE WINGBOARD PANELS INTO PLACE AS INDICATED BY THE DASHED LINES.
WINDOW JAM
CLIP (ITEM 10)
SECTION A-A
INSERT VINYL WINDOW SEAL
GASKET OVER TOP ANGLE TO WINGBOARD (ITEM 12)
B
B
LOWER WINDOW SASH
INSERT FOAM WINDOW SEAL GASKET (ITEM 13)
A
SECURE THE SIDE WINGBOARD PANELS TO THE SIDE ANGLES WITH FOUR (4) #8 x 1/2” LONG SCREWS (ITEM 11), TWO ON EACH SIDE.
A
FRR022
VINYL
WINDOW
GASKET
TOP WINGBOARD ANGLE
SECTION B-B
27
OPTIONAL: The factory assembles the supply cord so that it exits the left
SECTION A-A
SCALE 1 / 3
side of the unit at the bottom. At the consumer’s discretion,
To do this, route the supply cord to the right side. Pull the supply cord taunt through the loops (Refer to Cord Routing Change, Figure 30) and route the cord down.
Use Tool Provided
.tinu eht fo edis thgir eht tixe ot detuor eb nac droc ylppus eht
Please use the provided tool to attach the decorative front to the chassis.
Figure 28
STEP 1
To attach and prevent damage to the front grille align the
4.
cord notch over the cord and center the fresh air lever, then align and tighten the four (4) captive screws as indicated by the arrows in Figure 28. Before closing the front panel, be sure the filter is in place. Make sure curtains do not block the side air intakes.
STEP 15. Refer to the Control Panel Operation section for instructions.
STEP 1
6. You are now ready to control the comfort level of the room.
Figure 29
USE HAND TOOLS
DO NOT O VER T IGHTE N
B
LOCATION OF GRILLE REMOVAL TOOL
FRR05 3
28
POWER CORD
CLIP
NOTE: WHEN INSTALLING THE CHASSIS SEAL GASKET; BEGIN AT EITHER BOTTOM CORNER AND GO UP THE SIDE & ACROSS THE TOP & DOWN THE OPPOSITE SIDE.
CHASSIS SEAL
GASKET (ITEM 14)
FRR024
Cord Routing Change
FRR054
Unplug unit.
STEP 17. Carefully pull out electrical control panel 1", but not all the way.
Figure 32
WARNING
Electrical Shock Hazard
Make sure your electrical receptacle has the same configuration as your air conditioner’s plug. If different, consult a Licensed Electrician.
Do not use plug adapters. Do not use an extension cord. Do not remove ground prong.
Always plug into a grounded 3 prong oulet. Failure to follow these instructions can result in death, fire, or electrical shock.
For convenience and optimum appearance the direction that the power cord exits the unit may be changed from left to right by following the procedure below. Select the exit location on the left or right based on proximity to the power outlet.
Figure 30
ELECTRICAL CONTROL PANEL
1 INCH
STEP 1
8. Pull electrical cord strain relief downward until free and rotate 90 degrees to the right.
Figure 33
FRR056
NOTE:
DECORATIVE FRONT REMOVED USE TOOL PROVIDED. (SEE FIGURE 28 FOR LOCATION OF TOOL).
Remove 3 screws as shown from the electrical control panel. Save to reinstall later.
Figure 31
ELECTRICAL CONTROL PANEL SCREWS (3)
FRR055
90°
ELECTRICAL CORD STRAIN RELIEF
STEP 1
9. Push electrical cord strain relief back upward into the electrical control panel.
Figure 34
ENSURE THE ELECTRICAL CORD STRAIN RELIEF IS FLUSH WITH THE TOP OF ELECTRICAL CONTROL PANEL
FRR057
FRR058
30
STEP 20. Carefully push electrical control panel back into chassis.
Figure 35
ELECTRICAL CONTROL PANEL
FRR059
STEP 2
2. If running power cord to the right of the unit install the cord into the cord retainer clips along the bottom front of the unit.
Figure 37
CORD RETAINER
CLIPS
STEP 21. Reinstall the 3
screws removed earlier to secure electrical
control panel.
Figure 36
ELECTRICAL CONTROL PANEL SCREWS (3) (RETAINED FROM STEP 1)
FRR060
FRONT GRILLE
POWER CORD
FRR061
31
THIS PAGE INTENTIONALLY LEFT BLANK
29
Friedrich Air Conditioning Co. Post Office Box 1540 • San Antonio, Texas 78295-1540 4200 N. Pan Am Expressway • San Antonio, Texas 78218-5212 (210) 357-4400 • FAX (210) 357-4480 www.friedrich.com
Printed in Mexico
Loading...