Friedrich PVH12K, PVH09K, PVH09R, PVH12R User Manual

PTAC Packaged Terminal Air Conditioners & Heat Pumps
Installation and Operation Manual
FreshAire
TM
2
Congratulations········································································································································3
General Instructions
General Specifications
PTAC Installation Recommendations···········································································································5
Wall Sleeve Installation Instructions (PDXWSA)···························································································· 6
Alternate Wall Installations
PXDR10 Drain Kit Installation Instructions (optional for new construction)
External Drain (for new construction or unit replacement)··············································································11
PXGA Standard Grille Installation Instructions····························································································· 12
Chassis Install Preparation
Chassis Installation
Friedrich PTAC Digital Control and Unit Features·························································································19
System Configuration······························································································································ 21
Digital Control User Input Configuration
Digital Control Operation
Remote Control Thermostat Installation······································································································26
··································································································································
·······························································································································
·························································································································
························································
·······················································································································
·································································································································
······································································································
··························································································································
10
16
18
22
24
3
4
7
Remote Thermostat and·························································································································· 26
Low Voltage Control Connections
Final Inspection & Start-up Checklist
Basic Troubleshooting····························································································································· 29
Service & Assistance·······························································································································31
Accessories
···········································································································································
··············································································································
··········································································································
26
28
32
NOTE: All PTAC 9000units come with a universal 2.5+1.0kW electric heater(standard 20A power cord for 3.5kW ,optional 15A power cord for 2.5kW). All PTAC 12000units come with a universal 3.5+1.5kW electric heater(standard 20A power cord for 3.5kW,optional 30A power cord for 5kW,optional 15A power cord for 1.5kW).
3

Congratulations

Thank you for your decision to purchase Friedrich. Your new Friedrich has been carefully engineered and manufactured to give you many years of
dependable, efficient operation, maintaining a comfortable temperature and humidity level. Many extra features have been built into your unit to assure quiet
operation, the greatest circulation of cool, dry air, and the most economic operation.
This Installation and Operation Manual has been designed to insure maximum satisfaction in the performance of your unit. For years of trouble-free service,
please follow the installation instructions closely. We cannot overemphasize the importance of proper installation.

WARNING

Refrigeration system
under high pressure
Do not puncture, heat, expose to flame or
incinerate.
Only certified refrigeration technicians should
service this equipment.
R410A systems operate at higher pressures
than R22 equipment. Appropriate safe
service and handling practices must be used.
Only use gauge sets designed for use with
R410A. Do not use standard R22 gauge sets.
Here are some suggestions to help you use your new Friedrich most efficiently:
1. Carefully read and follow the installation instructions.
2. Make sure the unit is the right capacity for the area being cooled.
An undersized unit makes the unit work too hard, using more
electricity than needed and increases wear. An oversized unit
will cycle on and off too rapidly, and therefore cannot control
humidity as well.
3. Clean the filter frequently (See Routine Maintenance, Page 27).
4. Do not block the air flow to and from the unit.
5. A dirty filter or improperly set controls can affect the cooling
ability of the unit.
6. If cooling is weak and you have verified that the filter is clean
and the controls are properly set, the unit may need service and
you should call your Friedrich service provider to check the unit.
7. Keep blinds, shades and drapes closed on the sunny side of the
room being cooled to reduce radiant heat.
8. Proper insulation helps your unit maintain the desired inside
temperature.
9. Whenever possible, shade south and west facing windows.
10. Keep window coverings awayfrom the unit to provide free airflow.

WARNING

Read Installation Operation Manual

Please read this manual thoroughly prior to equipment installation or operation.
It is the installer’s responsibility to properly apply and install the equipment. Installation must be in conformance with the NFPA 70
-2008 National Electric Code or current edition, International Mechanic Code 2009 or current edition and any other applicable local or national codes.
Failure to do so can result in property damage, personal injury or death.
WARNING
CAUTION
Indicates a hazard which, if not avoided, can result in severe personal injury or
death and damage to product or other property.
Indicates a hazard which, if not avoided, can result in personal injury and
damage to product or other property.
NOTICE
Indicates property damage can occur if instructions are not followed.

General Instructions

Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is a safety Alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol with the word “WARNING” or “CAUTION”. These words mean:
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what will happen if the instructions are not followed.
4

GeneralSpecifications

WALL SLEEVE
DISCHARGE GRILLE
FILTERS
RETURN AIR GRILLE
OUTDOOR GRILLE
CHASSIS
FRONT COVER
PDXWS Wall Sleeve Dimensions: 16" H x 42" W x 13-¾" D Front Cover Dimensions: 16" H x 42" W x 7-¾" D
Cut-Out Dimensions: 16-¼" x 42-¼"
MODEL NUMBER
V
H
09
3 F
Series
PV = Friedrich Digital PTAC
System
E = Cooling with electric heat H = Heat Pump with Auxiliary Heat
Nominal Capacity
Engin eering Digit
Design Series
Chassis
F= FreshAire
07 = 7,000 Btuh 09 = 9,000 Btuh
Voltage
12= 12,000 Btuh 15= 15,000 Btuh
Nominal Heater Size (230V or 265V)
3=3kW

Installation Checklist

. Inspect all components and accessories for damage before and
after installation.
. Remove the cardboard wall sleeve support and grill weatherboard.
. Check for proper wall sleeve installation in accordance with the wall
sleeve installation instructions.
. Check for a subbase kit or other means of structural support which
is required for ALL installations projecting more than 8" into room.
. Install th e recommended Condensate Drain Kits for complete
condensate removal.
. Ensure that chassis and chassis front cover are installed and secured
properly.
. Ensure that drapes,bed,bedspread,furniture,etc DO NOT block
either return or discharge air grilles.
. Inspect the condenser air inlet and outlet for any obstructions
(shrubbery,etc).
. Ensure that 'reset' button is pressed on LCD device(only on cord
connected models).

Typical Unit Components and Dimensions

K = 230/208V - 1 Ph. - 60 Hz. R = 265V - 1 Ph. - 60 Hz.
A
. Ensure that the chassis is installed in a 16" highx4'' wide wall sleeve
that is no deeper than 13-¾".A baffle kit is required if the sleeve exceeds that depth.
5

PTACInstallationRecommendations

FRP001
Fo r mi nor o bs truc t ion s
such as lamp poles or small
shrubbery a clearance of
12" from the outdoor louver
should be maintained.
TYPICAL BUILDING ( PLAN VIEW )
For major obstructions such
as a solid fence, wall or
other heat rejecting device
like a condensing unit, a
minimum distance of 36"
should be kept.
PTAC
12" MINIMUM, MINOR
OBSTRUCTIONS
36" MIMUMUM, MAJOR
36"
POLE
PTAC
12"
36"
36"
SHRUB
PTAC
OBSTRUCTIONS
CONDENSING UNIT
FENCE OR WALL
FRP002
The above suggestions are for reference only and do not represent all possible installations.Please contact Friedrich for information regarding affects of other
installation arrangements.By following these simple recommendations youcan be confident that your Friedrich PTACwill provide years ofworry free operation.
For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances below:
Figure 1
PTAC units should be installed no closer than 12" apart when two units are side by side. If three or more PTAC units are to operate next to one another allow a minimum of 36" between units. Also,a vertical clearance of 60" should be maintained between units installed. In the interior of the room the unit should be located a minimum of 1/4" from the floor and a minimum of 36" from the ceiling.
TYPICAL WINDOW
36"
THREE OR MORE PTACs ADJACENT 36" MINIMUM
TWO ADJACENT PTACs 12" MINIMUM
GROUND FLOOR PTACs 6" MINIMUM FROM GRADE
60" VERTICAL MINIMUM BETWEEN PTACs
60"
12"
6"
VIEW: OUTSIDE BUILDING ELEVATION
For PTACs on the ground floor or anytime obstructions are present, use the following guidelines:
Figure 2
6

Wall Sleeve Installation Instructions (PDXWSA)

NOTE: Insure that the unit is only installed in a wall structurally adequate to support the unit including the sleeve, chassis and accessories.If the sleeve
projects more than 8" into the room, a subbase or other means of support MUST be used. Please read these instructions completely
before attempting installation.

WARNING

Falling Object Hazard

Not following Installation Instructions for
mounting your air conditioner can result
in property damage, injury, or death.
NOTICE
DO NOT allow any pitch toward the inside.
Flashing on all 4 sides of the opening is recommended.
Potential property damage can occur if instructions are not followed.
For Deep Wall Installation (Greater than 13 1/4") See Page 9
The following instructions apply ONLY to walls less than 13 ¼" in depth.
1 The PXDR10 Drain Kit,(optional for new construction) see page 10
if applicable, must be installed before the wall sleeve is installed
into the wall.
2 The External Drain (for new construction or unit replacement) see
page 11 if applicable, must be installed before the wall sleeve is
installed into the wall.
Figure 3
Typical Wall Sleeve Installation
3 Frominside the building, positionthe wall sleeve inthe opening and
push itinto the wall until it protrudes at least ¼” on the outside
(See Figure 9, Page 8).
4 Position the wall sleeve with a slight tilt towards the outside to
facilitate condensate drainage. It should be level side-to-side and
the front should be ¼ bubble higher than the back.
ELECTRICAL
RECEPTACLE
LINTEL TO SUPPORT MASONRY WALLS
42-¼" MIN.
16-¼"
60" MAX.
20" MAX.
13-¾"
SMOOTH SIDE OF SCREW CLIP FACING INTO ROOM
ELECTRICAL RECEPTACLE
INSULATION
WALL OPENING
WALL SLEEVE
INSULATION
NOTE:
All 230/208V units are manufactured with a 60” power cord and all 265V units with a 18” power cord.
FRP003
7

AlternateWall Installations

Figure 4
Panel Wall
Figure 6
CurtainWall
WALL OR WINDOW
1/4" MIN PROJECTIO N
CASE FLANGE
OPTIONAL SUBBASE
LEVELING SCREW
OPTIONAL SUBBASE
FRP004
LEVELING SCREW
FRP006
Figure 5
Frame and Brick Veneer
Figure 7
Block and Brick Veneer
1/4" MIN PROJECTION
1/4" MIN PROJECTION
WOOD FRAME
CONCRETE LINTEL
STEEL
LINTEL
13-3/4" MIN.
STEEL LINTEL
11" MIN. WITH SUBBASE
WITHOUT SUBBASE
OPTIONAL SUBBASE
LEVELING SCREW
FRP005
RECEPTACLE
FINISHED FLOOR
POWER SUPPLY CONDUIT (SUPPLIED BY INSTALLER)
FRP007
NOTE: Follow all wall system manufacturer installation instructions. For sunrooms and modular buildings, adhere to their installation instructions for
supporting and sealing sleeve to their frames. All wall and window/wall installations must provide for proper drainage. In applications where the
drain holes on the PTAC wall sleeve are not exposed beyond the wall an internal drain system is recommended. It is the installer's responsibility
to ensure there is adequate drainage for the PTAC unit.
(BY OTHERS)
8
13-¾
"
Figure 8
WALL SLEEVE
ALTERNATE FASTENING METHODS (Field Supplied)
WOOD SCREW
TOGGLE BOLT
NOTE: The Wall Sleeve must be
horizontally level (side-to-side) and pitched 1/4 bubble to the outside when installed in an opening.
The mounting hole location
EXPANSION
ANCHOR BOLT
should be approximately 2-4” from the top and bottom of the sleeve.
PLASTIC ANCHORS
SCREWS
FRP008
A ¼" MIN.
A B C
Dimension*
Allow for wall finishing
Allow for floor finishing
Allow for proper drainage
(Minimum) Min. Max.
(Front-to-Back)
C
No Accessories
¼" ¼"
---
---
With Subbase 1-¾" 3-½" 5"
---
With Lateral Duct ¾"
¼"
---
---
Wall Sleeve Tilt
B
---
---
---
¼"
WALL
* If more than one accessory is to be used, use the maximum
dimension. If the wall thickness is more than 13-¾" - (A+ ¼"), a sleeve extension must be used.
Wall Sleeve Attachment
MOUNTING
HOLES
Figure 9
Dimensions
FRP009
9
5. Drill two 3/16" holes through each side of the sleeve approximately
4" from top and 4" from bottom of sleeve. Screw four #10 x 1"
screws (included) or appropriate fasteners for your installation,
through the holes in the sides of the wall sleeve.
6. Apply sealant around the wall sleeve where it projects through the
inside and outside wall surfaces. Apply the sealant to the screw
heads or the tops of the fasteners used in Step #5.
7. If the chassis and exterior grille are to be installed later, leave the
weatherboard and center support in place, otherwise remove and
dispose of them. (See Figure 13, Page 12).
8. Provide a support lintel if the wall sleeve is installed in a concrete
or masonry wall (See Figure 10, Page 9).
Figure 10
Lintel Installation
MAIN STUDS
JACK STUDS
JACK STUDS
MAIN STUDS
LINTEL
MOUNTING SCREW HOLES
NO HOLES IN BOTTOM OF WALL SLEEVE UNLESS DRAIN KIT IS USED
NOTE: Construct wall opening to comply with all applicable building codes.
FRP010
One-Piece Deep Wall Sleeve
If the wall is thicker than 13 1/4” a deep wall sleeve or wall sleeve extension
MUST be used. The deep wall sleeve may be special ordered through
your Sales Representative.
Installation (PDXWSEXT)
10
PXDR10DrainKitInstallation Instructions(optionalfornew construction)
NOTE: Determine whether drain will be located within the wall, on the
indoor side, or will drain to the exterior of the building. Follow
appropriate instructions below depending on your particular
type of installation.

Internal Drain

NOTE: If installing an internal drain, you MUST install a drain kit on
the wall sleeve before the wall sleeve is installed.
1. Refer to Figure 11 and locate the drain within the “Preferred”
area of best drainage.Maintain at least a ½” clearance from the
embossed area.
2. Using the mounting plate with the ½” hole as a template, mark
and drill two, 3/16” mounting holes and a ½” drain hole in the
sleeve bottom.
Figure 11
DrainKitLocationand Installation
OPTIONAL AREA
PREFERRED AREA­NO FOAM INSULATION
3. Remove the backing from the gasket and mount it on the flat
side of the mounting plate (See Figure 12, Page 11). Insert the
drain tube through the hole in the gasket and mounting plate so the
tube flange will be against the wall sleeve.
4. Position the assembly beneath the drilled holes and secure it with
#10-24 x ½" machine screws and lock nuts provided. Seal the tops
of the screws with silicone caulking.
5. Use ½" I D copper tube, PVC pipe, or vinyl hose (obtained locally)
to connect the internal drain tube tothe drain system in thebuilding.
6. Referring to Figure 12, Detail A, Page 11, locate and assemble
the two cover plates and gaskets over the drain holes at the
rear of the wall sleeve. Attach them with the #10 sheet metal
screws provided. Make certain that the four overflow slots at
the rear of the wall sleeve are not blocked (See drawing of the
back of the sleeve Figure 12, Page 11).
7. If a deep wall extension (PDXWSEXT) is used, after installing the
field supplied flashing,caulk as required. Be sure to caulk around
the flashing and the wall sleeve where the hole was drilled for the
drain tube.
DRAIN TUBE
NUT
IF THE DRAIN MUST BE
REMOVED TO ALLOW ACCESS
3"

FRONT VIEW

FRP011
PXDR10
QUANTITY
DESCRIPTION
2
COVER PLATES
1
MOUNTING PLATE
1
DRAIN TUBE
3
MOUNTING PLATE GASKET
4
#10 X ½” SHEET METAL SCREWS
2
#10-24 X ½ ” MACH. SCREWS
2
#10-24 X ½" LOCKNUTS
LOCATED IN THE OPTIONAL AREA, THE FOAM INSULATION MUST BE CUT AWAY AND
TO THE DRAIN.
WALL SLEEVE
SCREW
GASKET
MOUNTING PLATE
SIDE VIEW
11
External Drain (for new construction or unit replacement)
When using an external drain system, the condensate is removed through either of two drain holes on the back of the wall sleeve. Select the drain
hole which best meets your drainage situation and install the drain kit.
Seal off the other with a cover plate.

Drain Tube Installation (See Figure 12)

1. Peel the backing tape off the gaskets and apply the sticky side
to one cover plate and one mounting plate as shown in Details
A and B.
2. Place the drain tube through the gasket and the mounting plate
with the flange toward the wall sleeve.
3. Attach the drain tube assembly to one of the two drain holes at the
rear of the wall sleeve. The large flange on the mounting plate is
positioned at the bottom of the sleeve facing toward the sleeve,
Detail B. When the drain tube is positioned at the desired angle,
tighten the screws.

Cover Plate Installation

4. Mount the foam gasket tothe cover plate. Using two #10 x ½" sheet
metal screws (provided), attach the cover plate to the remaining
drain hole. Make certain the large flange on the plate is positioned
at the bottom of the sleeve.
5. Discard the additional cover plate, gasket, machine screws, and
locknuts.
NOTICE
If the wall sleeve has not been installed, the drain tube must be rotated to a horizontal position until after the sleeve is installed. Tighten the mounting plate screws when the tube is in the proper position. Make certain that the four overflow slots at the rear of the wall sleeve are not blocked (See Figure 12).
When sealing the sleeve on the outside of the building, be careful NOT to let the sealant block the two condensate drain holes or the four overflow slots at the bottom flange of the sleeve.
Potential property damage can occur if instructions are not followed.
Figure 12
Drain Kit Installation
COVER PLATE
NUT
MOUNTING PLATE
FOAM GASKET
DETAIL A
FOAM GASKET

DETAIL B

SCREWS
½” O.D. TUBE
FRP012
NOTE: The large flange on the mounting plate is positioned at the bottom of the sleeve facing toward the sleeve. The drain tube must be rotated to a
horizontal position to allow for the wall sleeve to be installed into the wall. Once the wall sleeve is installed, return the drain tube to a downward
angle.
OVERFLOW
SLOTS
Loading...
+ 23 hidden pages