Friedrich PE07K0SB, PE07K0XA, PE07K0XB, PE07K2CA, PE07K2CB Owner’s Manual

...
WallMaster®PTAC
PackagedTerminalAirConditioners& Heat Pumps
Standard
RemoteThermostat
SeacoastProtected
Installation& OperationManual
920-087-02 (9-03)
920-087-02(9-03)
UnitComponents......................................................................................................................................................................................... 2
P-SeriesAnnouncement/ModelNumberCode............................................................................................................................................ 3
InstallationRecommendations.................................................................................................................................................................... 4
DrainKit Installation ................................................................................................................................................................................ 5-6
Wall SleeveInstallation............................................................................................................................................................................ 7-8
DeepWall Installation .................................................................................................................................................................................. 9
Standard GrilleInstallation ........................................................................................................................................................................ 10
InstallationChecklist................................................................................................................................................................................. 11
Electrical RatingTables.............................................................................................................................................................................. 11
ChassisInstallation............................................................................................................................................................................. 12-13
Standard UnitOperations.......................................................................................................................................................................... 14
TemperatureLimitingThermostat .............................................................................................................................................................. 14
HeatingControl(Heat Pumps& Emergency Heat)..................................................................................................................................... 15
FanCycleSwitch....................................................................................................................................................................................... 15
FreshAirVent Control................................................................................................................................................................................ 15
AirDischargeGrille.................................................................................................................................................................................... 16
Start-up Checklist...................................................................................................................................................................................... 16
AppendixA: RemoteThermostatWiring............................................................................................................................................... 17-18
AppendixB: ElectricalWiringfor 265 V Models........................................................................................................................................ 19
RoutineMaintenance................................................................................................................................................................................ 20
BasicTroubleshootingTechniques............................................................................................................................................................. 21
Accessories......................................................................................................................................................................................... 22-23
Warranty................................................................................................................................................................................................... 24
TypicalUnit Components
Chassis
tcover
2
920-087-02 (9-03)
Announcing the FriedrichP-Series PackagedTerminalAir Conditioner.
A new approach to reliability and efficiency. A totally redesigned Friedrich PTAC.
Thank you for your decision to purchase the newly designed Friedrich Packaged Terminal Air Conditioner (PTAC). We are confident that you will find this unit a quiet and efficient example of Friedrich reliability.
This Installation and Operation Manual has been designed to insure maximum satisfaction in the performance of your unit. For years of trouble-free service, please follow the installation instructions closely. We cannot overemphasize the importance of proper installation. We have added new information to the basic instructions
to help you achieve success.
Remember, proper installation is not difficult but it is essential.
ModelNumberCode
Series
P= Pseries
System
X= Accessory E= Coolingwith or
withoutelectric heat
H =Heat Pumpwith
Auxiliary Heat
NominalCoolingCapac_y
07 = _000 Btuh 09 = 9,000 Btuh 12 = 12,000 Btuh
15 = 15,000 Btuh
PH07K 3 S A 1
L
I Engineering Digit I
I Designsedes I
Options
S = Standard
R = RemoteThermostat
C = SeacoastProtection X = RemoteThermostatand
SeacoastProtection
NominalHeaterSize
(@230V or 265V)
0 = NoHeater 2 = 2.5 KW
3 = 3.4 KW 5 = 5.0 KW
Voltage
K = 230/208V-1Ph.-60 Hz. R = 265V-1Ph.-60 Hz.
Please read this manual thoroughly prior to equipment installation or operation. Itisthe installer's responsibility to properly apply and install the equipment. Installation must be in conformance with the NFPA 70-2002
National Electric Code or current edition and Universal Mechanical Code current edition and applicable local or national codes.
3
920-087-02 (9-03)
PTACInstallation Recommendations
ForproperPTACunitperformanceandmaximumoperatinglifepleaserefertothe minimuminstallationclearancesbelow:
Figure I
PTAC units should be installed no closer than 12"apart when
two units are side by side. If three of more PTAC units are to
operate next to one another allow a minimum of 36" between units.
Also, a vertical clearance of 60" should be maintained between
units installed.
VIEW: OUTSIDE
BUILDING ELEVATION
60" VERTICAL M]MUMUM
BETWEEN PTACs
THREE OR MORE PTACs #,DJACENT 36" MINIMUM
GROUND FLOOR PTACs 6" MINIMUM FROM GRADE
Figure 2
ForPTACsonthegroundfloororanytimeobstructionsarepresent,usethefollowingguidelines:
For minor obstructions such as lamp poles or small
shrubbery a clearance of
12"from the outdoor louver
should be maintained.
For major obstructions such as a solid fence, wall or
other heat rejecting device
PTAC 7 PTAC r
like a condensing unit, a minimum distance of 36"
should be kept.
12" MINIMUM, MINOR
OBSTRUCTIONS _ 36"
36" MIMUMUM, MAJOR _
OBSTRUCTIONS _) ' ' ' FENCE OR WALL'
The above suggestions are for reference only and do notrepresent all possible installations. Please contact the factory for information regarding affects of other installation arrangements. By following these simple recommendations you
can be confident that your Friedrich PTAC will provide years of worry free operation.
TYP. BUILDING ( PLAN VIEW )
-- 36"_] [_ 36"--
I I I I
I I I I
CONDENSING UNIT
PTAC
4
920-087-02(9-03)
Installation Instructions PXDRIO DrainKit
NOTE: Determine whetherdrain willbe located within the wall,on the indoor side, orwill drain to the exteriorof the building. Follow
appropriate instructionsbelow depending on yourparticular type of installation.
Internal Drain (optional for new construction) NOTE: Ifinstalling an internaldrain,you MUST installa drainkit on
the wall sleeve before the wall sleeve is installed.
1,
Refer to Figure 3 below and locate the drain within the "Primary" area for best drainage. Maintain at least a 1/2"
clearance from the embossed area.
2.
Using the mounting plate with the 1/2" hole as a template, mark and drill two, 3/16" mounting holes and a 1/2" drain hole.
,
Removethe backingfrom thegasket and mount iton the flat side of the mounting plate. (See Figure 4.) Insert the drain tube through the hole in the gasket and mounting plate so the tube flange will beagainst the wall sleeve.
4. Position the assembly beneaththe drilled holes and secure itwith #10-24 x 1/2" machine screws and locknuts provided. Seal the tops of the screws with silicone caulking.
Figure 3
DrainKitLocationandInstallation
Secondary area Primary area _ no foam insulation -- If the drain must be located in the
secondary area, the foam insulation
must be cut away and removed to
allow access to the drain,
76 cm
5. Use 1/2" I.D.copper tube, PVCpipe, or vinyl hose (obtained locally) to connect the internaldrain tube to the drain system in the building.
6. Referring to Detail A on page 6, locate and assemble the (2) two cover plates and gaskets over the drain holes at the rear of the wall sleeve.Attach them with the #10 sheet metal
screws provided. Makecertain that the four overflow slotsat the rear of the wall sleeve are not blocked (See drawing of
the back of the sleeve on page 6).
7. If a deep wall extension (PXWE) is used, after installing the field supplied flashing, caulk as required. Be sure to caulk around the flashing and the wall sleevewhere the hole was
drilled for the drain tube.
Screw [_
Wail sleeve
Gasket t t
Mounting plateNut _ j _ I \\
i
)
5
920-087-02 (9-03)
ExtemalDrain(for newconstructionorunit replacement)
When usingan external drain system, the condensate is removedthrough eitherof two drain holes on the back of thewall sleeve. Select the drain hole which best meets your drainagesituation and install the drain kit. Seal offthe other with a cover plate.
Drain Tube Installation
1. Peelthe backing tape off thegaskets and apply thesticky side toone cover plateand one mounting plateas shown in Details A and B,
2. Placethedrain tube throughthe gasketand the mounting plate with the flange toward the wall sleeve.
3. Attach the drain tube assembly to one of the two drain holes at the rear of the wall sleeve. The large flange on themountingplateispositionedatthe bottomofthe sleeve facing toward thesleeve, Detail B. When thedrain tube is positioned at the desired angle,tighten the screws.
NOTE: Ifthe wallsleeve hasnot been installed,the draintube must
be rotated to a horizontal position until after the sleeve is installed. Tighten the mounting plate screws when the tube is in the proper position. Make certain that the four
overflow slotsat the rearof the wallsleeveare notblocked. (See the drawing below.)
Figure 4
DrainKitInstallation
Cover Plate Installation
4. Mountthefoamgaskettothecoverplate. Usingtwo#10x 1/2"sheet metal screws (provided),attachthe cover plate
tothe remaining drainhole. Make certain the largeflange on the plate is positioned at the bottom of the sleeve.
5. Discardtheadditionalcoverplate,gasket,machinescrews, and Iocknuts.
QUANTITY DESCRIPTION
2 1 1 3
4 2 2
COVER PLATES MOUNTING PLATE DRAIN TUBE
MOUNTING PLATE GASKETS
#10 X 1/2" MOUNTING SCREWS
10-24 X 1/2" MACH, SCREWS LOCKNUTS
gasket
plate
DETAIL A
Foam gasket _ _/2"O.D.tube
Mounting plate #10 sheet metal screws
_DETAIL B
NOTES:
The large flange on the mounting plate is positioned at the bottom of the sleeve facing toward the sleeve. The drain tube must be rotated to a horizontal position to allow for the wall sleeve to be installed into the wall. Once the wall sleeve is installed, return the drain tube to a downward angle.
6
920-087-02(9-03)
WallSleeveInstallation Instructions(PXWS)
NOTE: Insurethat theunit is only installed inawall structurallyadequatetosupport the unitincludingthe sleeve,chassis andaccessories. Ifthe sleeve projects more than 8" intothe room, a subbase or other means of support MUST be used. Please read these instructions
completely before attempting installation.
Figure 5
TypicalWall Sleeve Installation
Lintel to support masonry walls .--_.b_//_
10"
(25.4 cm
Electrical receptacle -
Wall opening Wall sleeve
ForDeep Wall Installation See Section II
1 1_ _ /]
/
41._m) _\_'[_ -- -- Electrical receptacle
Insulation --
Smoothsideofscrew
slip facing into room
The following instructions apply ONLY to walls less than
13 1/4" in depth.
1. Frominside thebuilding,positionthewall sleevein theopening and push it throughthe wall so itprotrudes at least 1/4"onthe
outside, note Figure 5.
2. Position thewall sleeve with a slight tilt towards the outsideto facilitate condensate drainage. It should be levelside-to-side
and the front should be 1/4 bubble higher than the back. DO
NOT allow any pitch towardthe inside.
Electricalshock hazard.
Turnelectric power OFFat the fuse box or service panel before making any electrical connections and ensure a
proper ground connectionis made before connecting line voltage. Failureto do so can result in property damage,
personalinjuryand/ordeath.
Figure 6
Dimensions
S
'_7€/////_ _ 6.4 cm
A
13¾ _
920-087-02 (9-03)
A B
Dimension*
in.
No Accessories ¼" ¼"
With Subbase 1¾" 3½" 5"
With Lateral Duct ¾" ¼"
Allow Allow for floor finishing
for wall
finishing
(Minimum) Min. Max
(6.4 ram)* (6.4 mm) ---
(4.5 cm) (8.9cm) (12.7cm)
(1.9 cm) (6.4 mm) ---
_ ...........Wall
,
Drill two 3/16" holes through each side of the sleeve approximately4" from top and4"from bottomof sleeve. Screw four#10x 1"screws (included)or appropriatefastenersfor your installation, through the holes inthe sides of the wall sleeve.
4. Apply sealant around thewall sleevewhere itprojectsthrough the insideand outside wall surfaces. Apply the sealant tothe screw headsor the tops of the fasteners used in Step #3.
NOTE: When sealing the sleeve on the outside of the building,
be careful NOT to let the sealant block the two condensate drain holes or the four overflow slots at the bottom flange of
the sleeve.
Rgure 7
LintelInstallation Jack studs
Main studs
* If mere than one accessory [sto be used, use the maximum dimension. If the wail thickness is more than 13¾" (35cm) -
(A + ¼" [6.4 mm]), a sleeve extension must be used.
5. Ifthe chassisandexteriorgrilleareto beinstanedlater,leavethe weatherboard and center support in place,otherwise remove and dispose of them.
6. Providea supportlintelifthewall sleeve isinstalledina concrete or masonry wall. (See Figure 7.)
Untel
Jack stud
Mounting screw holes
No holes in bottom of wall sleeve unless drain kit is used
NOTE: Construct wall opening to comply with all applicable building codes.
8
Loading...
+ 16 hidden pages