Friedrich PDXWS User Manual

Model PDXWS
Installation Instructions
WALL SLEEVE
For Use With Packaged Terminal Units
Please read these instructions completely before attempting installation.
NOTE: These instructions apply to installation of the wall sleeve only through walls structurally adequate to support the unit (i.e. sleeve, chassis, accessories.) If wall is not structurally adequate, a subbase or other means of support MUST be made.
Figure 1. Typical Wall Sleeve Installation
Electrical Receptacle
Lintel Used To Support Masonry Walls
42¼"
Minimum
16¼"
Maximum
50"
Insulation
Wall Opening
10" Maximum
13¾"
Electrical Receptacle
WARNING
Electrical shock hazard.
Turn OFF electric power at fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage.
Smooth side of clip on Room side.
Wall Opening
Failure to do so can result in property damage, personal injury and/or death.
920-078-01 (12-04)
SECTION I
Drain Kit
A field supplied condensate drain kit is required for total elimination of cooling or heat pump condensate.
When installing a condensate drain kit, (either internal or ex­ternal drain), it is recommended that installation of the drain kit be completed before installing the wall sleeve. Instructions for drain kit installation are shipped with the drain kit.
Wall Structure
3. Drill two 3/16" holes through each side of the sleeve approximately 4" from top and 4" from bottom of sleeve. Screw four #10 x 1" screws (included) or appropriate fasteners for your installation, through holes in sides of opening.
NOTE: Do NOT put any screws or drill any holes in the bottom of wall sleeve, unless required by the installation of a PXDR10 Condensate Drain Kit.
A subbase or other means of support MUST be used if sleeve projects more than 8" into room. Refer to subbase installation instructions for additional information.
Sleeve Installation
For Deep Wall Installation See Section II
The following instructions apply ONLY to walls less than 13 1/4"" in depth.
1. From inside the building, position wall sleeve in opening and push through the wall so it protrudes at least 1/4" on the outside, note Figure 2.
2. Position the wall sleeve so that it is positioned with a slight tilt towards the outside to facilitate condensate drainage. It should be level side-to-side. DO NOT allow
any pitch toward the inside.
Figure 2. Dimensions
4. Apply sealant around the wall sleeve where it projects through the inside and outside wall surfaces. Apply sealant to screw heads or tops of fasteners used in Step #3.
NOTE: When sealing sleeve on outside of building, be care-
ful NOT to let sealant block the two condensate drain holes or the four overflow slots at the bottom flange of the sleeve.
5. If chassis and exterior louver are to be installed later, leave the weatherboard and center support in place, otherwise remove and dispose of them.
Dimension* A (Minimum) B
(See Note)
Min. Max.
13¾"
Wall
** To allow for wall/fl oor fi nishing.
¼" Minimum
No Accessories
With
Outdoor Grille
Subbase 1 3/4" 3 1/2" 5"
With Lateral Duct 3/4" 1/4"
Caulking
NOTES
* If more than one accessory is to be
used, use the worst case dimension.
If the wall thickness is more than 13 3/4" - (A + 1/4"), a sleeve extension MUST be used.
**1/4" 1/4"
Figure 3. Lintel Installation
MAIN STUDS
JACK STUD
LINTEL
MOUNTING
SCREW HOLE
No holes are permitted in the bottom of the case. (Exception: PXDR10 Drain Kit)
Note the use of a lintel under the first course of bricks above the wall sleeve. Do not use the wall sleeve as a lin­tel. The mounting screw holes shown are to be made by the installer.
6. Provide a support lintel if the wall sleeve is installed in a concrete or masonry wall. (See Figure 3)
SECTION II
Deep Wall Installation
If wall is thicker than allowed in the notes in Figure 2, a sheet metal wall sleeve extension and flashing MUST be used. See Figure 4 for guidelines to use in fabricating a wall sleeve ex­tension.
Field Fabricating A Sleeve Extension
The Following points MUST be considered when designing a wall sleeve extension.
1. Provision must be made to direct excess condensate from the back of the wall sleeve to the outside of the build­ing.
2. Air baffles must be mounted to properly direct air flow from the condenser.
3. Wall Sleeve Extension design must allow for the proper mounting of the louvers.
4. Caulking of all potential sites where condensate or external water could infiltrate into building is required.
6. Condensate notches are clear of sealant so condensate flows freely into extension.
NOTE: Improper fabrication of a wall sleeve extension will impair PTAC performance. Regardless of your final extended wall sleeve design, provision MUST be made for proper direc­tion of air flow and condensate.
Extension Installation
Size wall sleeve extension to fit frame opening. Secure it to wall sleeve before installing in the wall. Refer to Figure 4
the
for a guide for fabrication of a condensate drip panel. Panel MUST extend the full depth of the wall sleeve and the wall sleeve extension. Pay particular care in sealing and caulking the panel where it makes contact with the wall sleeve (see Figure 4.) After installation in the wall, secure with fasteners through the sides. Seal around the sleeve extension with exterior caulking. Using a good grade of silicone sealant, seal all exposed screw heads. When installation is complete, outside louver may be attached to wall sleeve extension.
5. Seal strips must be attached to the outside edge of the vertical baffles.
Figure 4. Extended Wall Sleeve and Sealant Locations
IMPORTANT NOTE: The silicone bead MUST extend 3" up the side of the two flanges to prevent condensate from leaking.
Wall Sleeve
Outside Edge
Insulation
Air Baffles
Condensate
Width of wall
Drip
Edge
Drip Panel
(Field
Supplied)
Condensate Notches
Sealant inside (4) bottom corners
920-078-01 (12-04)
42 X 16" Frame, 20 gauge minimum, painted or aluminium
Loading...