This air conditioner uses new refrigerant HFC (R410A).
5 cm or over
The basic installation work procedures are the same as conventional refrigerant (R22) models.
However, pay careful attention to the following points:
INSTALLATION MANUAL
(PART NO. 9315342140)ENGLISH
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and operating standards.
As the installer or service person, it is an important part of your job to
install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state, and national electrical codes.
• Pay close attention to all danger, warning, and caution notices given in
this manual.
WARNING:
CAUTION:
• Hazel alerting symbols
This symbol refers to a hazard or unsafe practice which
can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which
can result in personal injury and the potential for product
or property damage.
Electrical
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units.
Get a partner to help, and bend your knees when lifting to reduce strain
on your back. Sharp edges or thin aluminum fins on the air conditioner
can cut your fingers.
When Installing...
...In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It
may be necessary to construct a strong wood or metal frame to provide
added support.
...In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that
can cause dripping and water damage to walls and floors.
...In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level
foundation for the outdoor unit. This prevents water damage and abnormal vibration.
...In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame.
Provide a suitable air baffle.
(1) Since the working pressure is 1.6 times higher than that of conventional refrigerant(R22) mod-
els, some of the piping and installation and service tools are special.(See the table below.)
Especially, when replacing a conventional refrigerant(R22) model with a new refrigerant R410A
model, always replace the conventional piping and flare nuts with the R410A piping and flare
nuts.
(2) Models that use refrigerant R410A have a different charging port thread diameter to prevent
erroneous charging with conventional refrigerant(R22) and for safety. Therefore, check
beforehand.[The charging port thread diameter for R410A is 1/2 threads per inch.]
(3) Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant(R22) models. Also, when storing the piping ,securely seal the opening by pinching,
taping, etc.
(4) When charging the refrigerant, take into account the slight change in the composition of the
gas and liquid phases, and always charge from the liquid phase side whose composition is
stable.
Special tools for R410A
Tool name
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous
mixing of other refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals-0.1 to 5.3 MPa (-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.
To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.
Contents of change
Safety / alert
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our
sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation
or maintenance service, including failure to follow the instructions in this
document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL
INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed
or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully
refer to the wiring diagram and these instructions when wiring. Improper
connections and inadequate grounding can cause accidental injuryor death.
• Ground the unit following local electrical codes.
...In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting
snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and
union tubes before connecting them, then tighten the nut with a torque
wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your
particular model is specified as either “small” or “large” rather than as
“liquid” or “gas”.
When Servicing
• Turn the power OFF at the main circuit breaker panel before opening
the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal
scraps or bits of wiring have been left inside the unit being serviced.
• After installation, explain correct operation to the customer, using the
operating manual.
Copper pipes
It is necessary to use seamless copper pipes and it is desirable
that the amount of residual oil is less than 40 mg/10m. Do not
use copper pipes having a collapsed, deformed or discolored
portion (especially on the interior surface). Otherwise, the expansion value or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than
CONNECTION PIPE REQUIREMENT
Nominal
diameter
3/8in
5/8in
Outer
diameter
9.52mm
15.88mm
Thickness
0.8mm
1.0mm
Maximum
length
50m(165ft)
Maximum height
(between indoor and
outdoor)
30m(99ft)
when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in the table. Never use copper pipes thinner than that in the
table even when it is available on the market.
WARNING
(1) Do not use the existing (for R22) piping and flare nuts.
• If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury,
etc.(Use the special R410A materials.)
(2) When installing and relocating the air conditioner, do not mix gases other than the specified refrigerant(R410A) to
enter the refrigerant cycle.
• If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value
and cause breakage, injury, etc.
CAUTION
When installing pipes shorter than 17ft (5m), sound of the outdoor unit will be transferred to the indoor unit, which
will cause large operating sound or some abnormal sound.
OUTDOOR UNIT
Lo
Hi
1
2
3
4
5
(L)
(N)
1
2
3
GG
GG
ELECTRICAL WIRING (OUTDOOR UNIT)
OUTDOOR UNIT INSTALLATION
WARNING
(1) Install the unit where it will not be tilted by more than 3°. However, do not install the unit with it tilted
towards the side containing the compressor.
(2) When installing the outdoor unit where it may exposed to strong wind, fasten it securely.
(1) Outdoor unit to be fasten with bolts at the four places indicated by the
arrows without fail.
Bottom side
370 mm
(14-9/16")
650 mm
(25-19/32")
Drain pipe
mounting place
4-ø 12 hole
(2) Fix securely with bolts on a solid block. (Use 4 sets of commercially
available M10 bolt, nut and washer.)
Bolt
Nut
Block
CAUTION
When connecting the power supply cord, make sure that
the phase of the power supply matches with the phase of
the terminal board. If the phases do not match, the
compressor will rotate in reverse and will not be able to
compress.
(1) Service cover removal
• Remove the two mounting screws.
• Remove the service cover by pushing downwards.
(2) Fasten the power supply cord and the connection cord to the conduit
holder using the lock nut.
(open the knock out holes if necessary)
(3) Connect the power supply cord and the connection cord to terminal.
(4) Fasten the power supply cord and connection cord with cord clamp.
Control box
Direction of the service
panel removal
Lock
nut
Hook
(3 places)
Service cover
Plug
Inter-unit line
AIR PURGE
(1) Remove the cap, and connect the gauge manifold and the vacuum
pump to the charging valve by the service hoses.
(2) Vacuum the indoor unit and the connecting pipes until the pressure
gauge indicates –0.1 MPa (–76 cmHg).
(3) When –0.1 MPa (–76 cmHg) is reached, operate the vacuum pump
for at least 60 minutes.
(4) Disconnect the service hoses and fit the cap to the charging valve to
the specified torque.
(5) Remove the blank caps, and fully open the spindles of the 3-way valves
with a hexagon wrench [Torque: 6~7 N·m (60 to 70 kgf·cm)].
Outdoor unit
Service hose
with valve core
Connecting pipe
3-way valve
Charging port
Blank cap
Hexagon wrench
Use a 4 mm
hexagon wrench.
Cord clamp
Connection cord
(indoor unit and
outdoor unit
connection cord)
Power supply cord
Terminal
Keep the earth wire longer than the other wires.
30 mm (1-3/16")
Earth wire
(6) Tighten the blank caps of the 3-way valve to the specified torque.
Tightening torque
Blank
cap
9.52 mm (3/8 in.)
15.88 mm (5/8 in.)
Charging port cap
20 to 25 N·m (200 to 250 kgf·cm)
30 to 35 N·m (300 to 350 kgf·cm)
10 to 12 N·m (100 to 120 kgf·cm)
CAUTION
1 Do not purge the air with refrigerants, but use a vacuum
Cap
Gauge manifold
t
Vacuum pump
CAUTION
Use a clean gauge manifold and charging hose
for R410A exclusively.
INDOOR UNIT
TERMINAL
INDOOR
DISCONNECT
SWITCH
(FIELD
SUPPLY)
14AWG
(Inter-unit)
Power lines
230/208 V
230/208 V
230/208 V
CIRCUIT
BREAKER
OR FUSE
(FIELD
SUPPLY)
OUTDOOR UNIT
TERMINAL
Disconnect switch and circuit breaker for over current protection given in the table below is to be installed between
the indoor unit and the outdoor unit.
Power supply line
Single-phase, 230/208 V
Disconnect switch
20A240 V - 5A
pump to vacuum the installation! There is no extra refrigerant in the outdoor unit for air purging!
2 Use a vacuum pump and gauge manifold and charg-
ing hose for R410A exclusively. Using the same vacuum
for different refrigerants may damage the vacuum
pump or the unit.
3 After connecting the piping, check the all joints for gas
leakage with gas leak detector.
4 When inspecting gas leakage, always use the vacuum
pump for pressure. Do not use nitrogen gas.
Service hose
Earth screw
Indoor unit
terminal block
12
3
G
4
Disconnect switch
Grounding
line
Earth screw
G
Outdoor unit
terminal block
12
45
3
Power supply line
Earth screw
G
Be sure to comply with local codes while running the wire
from the indoor unit to the outdoor unit (size of wire and
wiring method, etc. ).
Every wire must be connected firmly.
No wire should be allowed to touch refrigerant tubing, the
compressor or any moving part.
Loose wiring may cause the terminal to overheat or result
in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
Connect wires to the matching numbers of terminals.
Power supply
40 mm (1-9/16")
or more
WARNING
Circuit breaker (or Fuse)
CAUTION
Power supply
cord or connection cord
GENERAL
This INSTALLATION MANUAL briefly outlines where
and how to install the air conditioning system. Please
read over the entire set of instructions for the indoor
and outdoor units and make sure all accessory parts
listed are with the system before beginning.
1.
TYPE OF COPPER PIPE AND INSULATION MATERIAL
Copper tubing for connectin the outdoor unit to the indoor
unit and insulation material is available for purchase locally.
When you purchase them, please specify the following.
A.
Deoxidized annealed copper pipe for refrigerant piping as:
Small pipeLarge pipe
Outer diameterThicknessOuter diameterThickness
3/8”(9.52 mm)
0.031496 in
(0.8 mm)(1.0 mm)
5/8”(15.88 mm)
Cut each pipe to the appropriate length +12” (30 cm)
to16” (40 cm) to dampen vibration between units.
B. Foamed polyethylene insulation for copper pipes as
required to precise length of piping. Wall thickness
of the insulation should not be less than 5/16” (8 mm).
C. Use insulated copper wire for field wiring.
CAUTION
Check local electrical codes and regulations
before obtaining wire. Also, check any specified
instructions or limitations.
2. ADDITIONAL MATERIALS REQUIRED FOR INSTALLATION
A. Refrigeration (armored) tape
B. Insulated staples or clamps for connecting wire
(See your local electrical codes.)
C. Putty
D. Refrigeration lubricant
E. Clamps or saddles to secure refrigerant piping
3. OPERATING RANGE
Cooling/Dry Mode
Outdoor temperature
Indoor temperature
Indoor humidity
About 14 to 115 °F
About 64 to 90 °F
About 80% or less
ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 66 ft (20 m) is charged in
the outdoor unit at the factory.
When the piping is longer than 66 ft (20 m), additional charging is necessary.
For the additional amount, see the table below.
Pipe length
Additional
refrigerant
Between 66 ft (20 m) and 165 ft (50 m), when using a connection pipe
other than that in the table, charge additional refrigerant with 0.43 oz/
ft (40g/1 m) as the criteria.
99 ft (30 m)
14.2 oz (400 g)
131 ft (40 m)
1 lb 12 oz (800 g)
CAUTION
(1) When adding refrigerant, add the refrigerant from
the charging port at the completion of work.
(2) The maximum length of the piping is 165 ft (50
m). If the units are further apart than this, correct operation can not be guaranteed.
0.03937 in
165 ft (50 m)
2 lb 10 oz (1200 g)
STANDARD ACCESSORIES
The following installation accessories are supplied. Use them as
required.
Name and Shape Q’ty Name and Shape Q’ty
Wall hook bracket
Remote
control
unit
Battery
Remote control
unit holder
The following items are necessary to install this air conditioner. (The
items are not included with the air conditioner and must be purchased
separately.)
Name
Connection pipe assembly
Connection cord
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant
M10 bolt, nut
Cloth tape
1
Tapping screw (big)
1
Tapping screw (small)
2
Insulation (Drain hose)
1
1
8
2
1
Q’ty
1
1
1
1
1
1
1 set
1
1 set
1
4 set
ELECTRICAL REQUIREMENT
Always make the air conditioner power supply a special branch circuit and provide a special switch and receptacle. Do not extend the
power cord.
CAUTION
MINIMUM CIRCUIT AMPACITY22 A
MAXIMUM OVERCURRENT PROTECTION
(TIME DELAY FUSE OR HACR TYPE CIRCUIT BREAKER)
30 A
SELECTING THE MOUNTING
POSITION
Decide the mounting position with the customer as follows:
1. INDOOR UNIT
(1) Install the indoor unit level on a strong wall which is not subject
to vibration.
(2) The inlet and outlet ports should not be obstructed : the air should
be able to blow all over the room.
(3) Install the unit near an electric outlet or special branch circuit.
(4) Do not install the unit where it will be exposed to direct sunlight.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the drain pipe can be easily installed.
(7) Take servicing, etc. into consideration and leave the spaces shown
in the figure. Also install the unit where the filter can be removed.
2. OUTDOOR UNIT
(1) If possible, do not install the unit where it will be exposed to di-
rect sunlight. (If necessary, install a blind that does not interfere
with the air flow.)
(2) Do not install the unit where a strong wind blows or where it is
very dusty.
(3) Do not install the unit where people pass.
(4) Take your neighbors into consideration so that they are not dis-
turbed by air blowing into their windows or by noise.
(5)
Provide the space shown in the figure so that the air flow is not blocked.
Also for efficient operation, leave open three of the four direc-
tions front, rear, and both sides.
WARNING
Install at a place that can withstand the weight of the
indoor and outdoor units and install positively so that
the units will not topple or fall.
CAUTION
(1) Do not install where there is the danger of com-
bustible gas leakage.
(2) Do not install near heat sources.
(3) If children under 10 years old may approach the
unit, take preventive measures so that they can-
not reach the unit.
(4) Install the indoor unit on the wall where the height
from the floors more than 240 cm.
[Indoor unit piping direction]
The piping can be connected in the 7 directions in the figure. When
the piping is connected in direction 2, 3, 4 or 5, cut along the
piping groove in the side of the front panel with a hacksaw.
(Rear)
5 Left
outlet
7 Left rear
2 Right
outlet
3 Bottom outlet
1 Rear
outlet
6 Center
outlet
4 Left bottom
outlet
outlet
INSTALLATION DIAGRAM OF
INDOOR AND OUTDOOR UNITS
[INDOOR UNIT]
2-1/2”(6 cm)
2”(5 cm) or over
60”(150 cm)
or over
or over
95”(240 cm)
or over
Remote
control unit
[OUTDOOR UNIT]
24”(60 cm) or over
4”(10 cm) or over
24”(60 cm) or over
• Do not directly install it on
the ground, otherwise it
will cause failure.
• To obtain better operation
efficiency, when the outdoor
unit is installed, be sure to
open the front and left side.
2”(5 cm) or over
CAUTION
In the area with heavy snowfall, if the intake and outlet of outdoor unit is
blocked with snow it is likely to cause of the breakdown. Please construct a canopy and a pedestal or place the unit on a high stand (local
configured).
Wall hook bracket
2”(5 cm)
or over
(Wall cap)
Remote
control unit
holder
Tapping
screw(small)
4”(10 cm) or over
10”
(25 cm)
or over
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.