Friedrich SS16N30, SQ10N10 User Manual

Page 1
Room Air Conditioners
Service Manual
AUTO
°F°C AUTO CONTINUOUS
AUTO
SYSTEM FAN MODE
SCHEDULE FAN SPEED
Standard Chassis R-410A Models
Cool Only
115-Volt:
208-230-Volt:
208-230-Volt: ES12M33, ES15M33, EM18M34, EM24M35, EL36M35
208-230-Volt: YS12M33, YM18M34, YL24M35
115-Volt: YS10M10
Kuhl-ServMan (5-10)
SS08M10, SS10M10, SS12M10, SS14M10 SS12M30, SS15M30, SM18M30, SM21M30
Cool with Electric Heat
Heat Pump with Electric Heat
Heat Pump
Page 2
Table Of Contents
Important Safety Information ..................................................................................................................................... 2-4
Introduction ................................................................................................................................................................... 5
Model and Serial Number Location .............................................................................................................................. 5
Unit Identifi cation .......................................................................................................................................................... 6
Performance Data and Specifi cations .......................................................................................................................... 7
Installation Information/Sleeve Dimensions/Circuit Rating ........................................................................................... 8
Electrical Data ............................................................................................................................................................... 9
Before Operating the Unit ............................................................................................................................................10
Control Panel Operation ..............................................................................................................................................11
Alerts ......................................................................................................................................................................12-14
Remote Control Operation ......................................................................................................................................15-16
Electronic Control System Maintenance Operation .................................................................................................17-20
Unit Operation .............................................................................................................................................................. 21
Cool-Heat Set Points .................................................................................................................................................. 22
Electronic Control Sequence of Operation ............................................................................................................ 23-29
Unit Operation with a Wall-Stat ................................................................................................................................... 29
Removing the Front Cover and Unit Chassis ................................................................................................................ 30
Replacing the ID Coil Thermistor ................................................................................................................................ 31
Replacing the Control Board ....................................................................................................................................... 31
Low Voltage Interface Connector ................................................................................................................................ 32
Replacing the ID Coil Thermistor ................................................................................................................................ 31
Remote Wall Thermostat ....................................................................................................................................... 32-33
Airfl ow Selection and Adjustment ............................................................................................................................... 33
Components Testing .............................................................................................................................................. 34-35
Refrigeration Sequence of Operation .................................................................................................................... 36-37
Sealed Refrigeration System Repairs ................................................................................................................... 38-41
Hermetics Components Check ................................................................................................................................... 42
Reversing Valve Description/Operation ...................................................................................................................... 43
Testing the Coil ........................................................................................................................................................... 44
Checking the Reversing Valve ............................................................................................................................... 44-45
Compressor Checks .............................................................................................................................................. 46-47
Compressor Replacement ..................................................................................................................................... 48-49
Routine Maintenance / Battery Check / Change ...................................................................................................... 50-53
Service and Assistance ............................................................................................................................................... 54
Performance Test Data Sheet and Sizing Guide .......................................................................................................... 55
Error Codes and Alarm Status .................................................................................................................................... 56
Troubleshooting ..................................................................................................................................................... 57-66
Electronic Control Board Components Identifi cation ................................................................................................... 67
Wiring Diagrams .................................................................................................................................................... 68-75
Thermistors' Resistance Values .................................................................................................................................. 76
Remote Control Replacement Instructions ........................................................................................................... 77-78
User Interface Service Kit ........................................................................................................................................... 79
Instructions for Using Cooling Load Estimate Form ................................................................................................... 80
Cooling Load Estimate Form ...................................................................................................................................... 81
Heat Load Form .................................................................................................................................................... 82-83
Warranty ..................................................................................................................................................................... 84
1
Page 3
IMPORTANT SAFETY INFORMATION
The information contained in this manual is intended for use by a qualifi ed service technician who is familiar with the safety procedures required for installation and repair, and who is equipped with the proper tools and test instruments required to service this product.
Installation or repairs made by unqualifi ed persons can result in subjecting the unqualifi ed person making such repairs as well as the persons being served by the equipment to hazards resulting in injury or electrical shock which can be serious or even fatal.
Safety warnings have been placed throughout this manual to alert you to potential hazards that may be encountered. If you install or perform service on equipment, it is your responsibility to read and obey these warnings to guard against any bodily injury or property damage which may result to you or others.
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is a Safety Alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol with the word “WARNING”
or “CAUTION”. These words mean:
WARNING
CAUTION
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what will happen if the instructions are not followed.
NOTICE
You can be killed or seriously injured if you do not follow instructions.
You can receive minor or moderate injury if you do not follow instructions.
A message to alert you of potential property damage will have the
word “NOTICE”. Potential property damage can occur if instructions
are not followed.
PERSONAL INJURY OR DEATH HAZARDS
ELECTRICAL HAZARDS:
Unplug and/or disconnect all electrical power to the unit before performing inspections, • maintenance, or service.
M ake sure to follow proper lockout/tag out procedures.
A lways work in the company of a qualifi ed assistant if possible.
C apacitors, even when disconnected from the electrical power source, retain an electrical charge potential capable of causing electric shock or electrocution.
H andle, discharge, and test capacitors according to safe, established, standards, and approved procedures.
E xtreme care, proper judgment, and safety procedures must be exercised if it becomes necessary to test or troubleshoot equipment with the power on to the unit.
2
Page 4
D o not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel, and sleeve on the room side of the air conditioning unit while cleaning.
E lectrical component malfunction caused by water could result in electric shock or other electrically unsafe conditions when the power is restored and the unit is turned on, even after the exterior is dry.
N ever operate the A/C unit with wet hands.
U se air conditioner on a single dedicated circuit within the specifi ed amperage rating.
U se on a properly grounded outlet only.
D o not remove ground prong of plug.
D o not cut or modify the power supply cord.
D o not use extension cords with the unit.
F ollow all safety precautions and use proper and adequate protective safety aids such as: gloves, goggles, clothing, adequately insulated tools, and testing equipment etc.
F ailure to follow proper safety procedures and/or these warnings can result in serious injury or death.
REFRIGERATION SYSTEM REPAIR HAZARDS:
U se approved standard refrigerant recovering procedures and equipment to relieve pressure before opening system for repair.
D o not allow liquid refrigerant to contact skin. Direct contact with liquid refrigerant can result in minor to moderate injury.
B e extremely careful when using an oxy-acetylene torch. Direct contact with the torch’s fl ame or hot surfaces can cause serious burns.
M ake sure to protect personal and surrounding property with fi re proof materials.
Have a fi re extinguisher at hand while using a torch.
Pr ovide adequate ventilation to vent off toxic fumes, and work with a qualifi ed assistant whenever possible.
A lways use a pressure regulator when using dry nitrogen to test the sealed refrigeration system for leaks, fl ushing etc.
M ake sure to follow all safety precautions and to use proper protective safety aids such as: gloves, safety glasses, clothing etc.
F ailure to follow proper safety procedures and/or these warnings can result in serious injury or death.
MECHANICAL HAZARDS:
E xtreme care, proper judgment and all safety procedures must be followed when testing, troubleshooting, handling, or working around unit with moving and/or rotating parts.
B e careful when, handling and working around exposed edges and corners of the sleeve, chassis, and other unit components especially the sharp fi ns of the indoor and outdoor coils.
U se proper and adequate protective aids such as: gloves, clothing, safety glasses etc.
F ailure to follow proper safety procedures and/or these warnings can result in serious injury or death.
3
Page 5
PROPERTY DAMAGE HAZARDS
FIRE DAMAGE HAZARDS:
R ead the Installation/Operation Manual for the air conditioning unit prior to operating.
U se air conditioner on a single dedicated circuit within the specifi ed amperage rating.
Connect to a properly grounded outlet only.
D o not remove ground prong of plug.
D o not cut or modify the power supply cord.
D o not use extension cords with the unit.
Be extremely careful when using acetylene torch and protect surrounding property.
Fa ilure to follow these instructions can result in fi re and minor to serious property damage.
WATER DAMAGE HAZARDS:
I mproper installation, maintenance or servicing of the air conditioner unit can result in water damage to personal items or property.
In sure that the unit has a suffi cient pitch to the outside to allow water to drain from the unit.
D o not drill holes in the bottom of the drain pan or the underside of the unit.
F ailure to follow these instructions can result in damage to the unit and/or minor to serious property damage.
4
Page 6
INTRODUCTION
This service manual is designed to be used in conjunction with the installation and operation manuals provided with each air conditioning system.
This service manual was written to assist the professional RAC (Room Air Conditioner) service technician to quickly and accurately diagnose and repair malfunctions.
This manual will deal with subjects in a general nature.
Accumulator
Compressor
Outdoor Grille
Discharge Air
Fresh Air Vent
Reversing Valve
Evaporator Coil
Condenser Coil
Electronic Control
Board
Control Key Pad
Support Bar
Blower Wheel
Air Intake From
Sides and Bottom
Control Key Pad
(User Interface)
IMPORTANT: It will be necessary for you to accurately identify the unit you are servicing, so you can be certain of a proper diagnosis and repair (See Unit Identifi cation code on page 6).
Chassis Pull
Out Handle
Fan/Blower Motor
Base Pan
Sleeve
Air Intake Vents
Fan Blade
MODEL AND SERIAL NUMBER LOCATION
Register the air conditioner
Model information can be found on the name plate behind the front cover.
For your future con ve nience, record the model information here.
AIR CONDITIONING CO. SAN ANTONIO, TEXAS ASSEMBLED IN MEXICO
COOLING
VOLTS 115
MODEL NUMBER
HEATING
REFRIGERANT
XXXXXXXXX
XXXXXXXXXX
FUSE PROTECTED
U
30.1 OZ R410A
600 PSIG HS
XXXXXXXXX
CIRCUITS USE 15A
300 PSIG LS
XXXXXXXXXX
TIME DELAY FUSE
XXXXXXXXXX
L
X XX XXXXX XXXXXXXXXX
AIR CONDITIONING CO.
SAN ANTONIO, TEXAS
ASSEMBLED IN MEXICO
MODEL NUMBER YS10M10A SERIAL NUMBER LICY00008
BTH/HR 6500
60 HZ / 1 PH
YS10M10A
BTH/HR 6500
EER 12.0
VOLTS MIN 108
SERIAL NUMBER
EER 10.4
AMPS 8.0
LICY00008
AMPS 7.0
MODEL NUMBER
SERIAL NUMBER
PURCHASE DATE
5
Page 7
UNIT IDENTIFICATION
1st Digit – Function
S = Straight Cool, Value Series Y = Heat Pump E = Electric Heat
2nd Digit
S = Small Chassis M = Medium Chassis L = Large Chassis
Model Number Code
S S 08 M 1 0 A
8th Digit – Engineering
Major change
7th Digit – Options
0 = Straight Cool & Heat Pump Models 3 = 3 KW Heat Strip, Nominal 4 = 4 KW Heat Strip, Nominal 5 = 5 KW Heat Strip, Nominal
3rd and 4th Digit - Approximate BTU/HR in 1000s (Cooling)
Heating BTU/Hr capacity listed in the Specifi cation/Performance Data Section
RAC Serial Number Identifi cation Guide
Serial Number Decade Manufactured L=0 C=3 F=6 J=9 A=1 D=4 G=7 B=2 E=5 H=8
Year Manufactured A=1 D=4 G=7 K=0 B=2 E=5 H=8 C=3 F=6 J=9
A K A R 00001
6th Digit – Voltage
1 = 115 Volts 3 = 230-208 Volts
5th Digit
Alphabetical Modifi er
Production Run Number
Product Line R = RAC
Month Manufactured A=Jan D=Apr G=Jul K=Oct B=Feb E=May H=Aug L=Nov C=Mar F=Jun J=Sept M=Dec
6
Page 8
PERFORMANCE DATA
SL36M30-A 51 29 129 188 56 12 31 122 470 19.0 96.0 77.0 230/208v 30
p
p
COOLING
PERFORMANCE
DATA*
SS08M10-A 53 27 115 157 62 12 31 151 400 6.1 32.0 24.0 115 15 SS10M10-A 52 28 119 150 65 15 28 145 455 8.0 50.0 51.0 115 15 SS12M10-A 50 30 118 163 60 12 23 137 435 10.0 57.0 35.0 115 15 SS14M10-A 49 31 121 170 56 10 22 132 425 12.0 63.0 29.0 115 15 YS10M10-A 56 24 114 150 64 12 14 152 395 7.8 7.6 34.5 33.0 115 15
SS12M30-A 49 31 116 158 62 13 21 142 405 4.8 30.0 33.0 230/208v 15 ES12M33-A 51 29 115 158 62 13 18 140 400 4.8 16.0 30.0 33.0 230/208v 15 YS12M33-A 49 31 116 167 65 16 21 140 455 5.2 5.1 26.0 34.5 230/208 SS15M30-A 53 27 121 171 62 14 28 138 430 6.4 32.0 32.5 230/208v 15 ES15M33-A 53 27 121 171 62 14 28 138 430 6.4 16.0 32.0 32.5 230/208v 15 SM18M30-A 54 26 122 160 62 9 31 145 450 7.4 42.0 55.0 230/208v 15 EM18M34-A 54 26 122 160 62 9 31 145 450 7.4 19.5 42.0 55.0 230/208v 30 YM18M34-A 50 30 118 168 60 15 24 130 410 8.5 8.5 44.0 49.5 230/208v 15 SM21M30-A 48 32 124 170 55 10 28 137 455 9.4 46.0 55.0 230/208v 15 SM24M30-A 46 34 129 179 55 12 34 123 495 11.0 47.0 40.0 230/208v 20 EM24M34-A 46 34 129 179 55 1 YL24M34-A 56 24 121 176 62 18 25 135 480 11.1 12.2 47.0 74.0 230/208V 30 SL28M30-A 47 33 126 181 58 12 26 133 430 13.5 60.0 78.5 230/208v 20
EVAP. AIR TEMP. DEG.
F
Discharge Air
Temp.
Dro
F.
CONDENSER TEMP DEG. F
Discharge
Temp
Suction
Temp
Super Heat
Sub-
Cooling
2 34 123 495 11.0 47.0 40.0 230/208v 30
OPERATING
PRESSURES
Suction Discharge
ELECTRICAL RATINGS
Amps
Amps
Heat
Locked Rotor
Cool
Amps
R-410A
REF.
Charge in
OZ.
Voltage
v15
*Rating Conditions: 80 degrees F, room air temp. & 50% relative humidity, with 95 degree F, outside air temp & 40% relative humidity, all systems use R-410A.
SPECIFICATIONS
Model
Cooling
Capacity Btu
Heating
Capacity Btu
Volts
Rated
Cooling
Amps
Cooling
Watts
Heating
Amps
Heating
Watts COP
Energy
Effi ciency
Ratio
EER
NERGY STAR
E
Estimated
Yearly
Operating
Cost
®
qualifi ed
Moisture Removal Pints/HR
Room Side
Air
Circulation
CFM Sleeve
Kühl
SS08M10 7900 115 6.1 677 11.7 $54 1.0 265 S 99
SS10M10 9500 115 7.7 848 11.2 $68 2.0 260 S 106
SS12M10 12000 115 10.0 1071 11.2 $86 3.0 300 S 112
SS14M10 14000 115 12.0 1444 9.7 $115 3.5 325 S 116
SS12M30 11700/11200 230/208 4.8/4.9 1026/982 11.4/11.4 $82 2.8 275 S 112
SS15M30 14500/14300 230/208 6.4/6.8 1405/1385 — 10.3/10.3 $112 3.5 360 S 116
SM18M30 17500/17200 230/208 7.4/8.0 1635/1617 — 10.7/10.7 $131 4.6 350 M 140
SM21M30 20800/20700 230/208 9.4/10.3 2080/2070 10.0/10.0 $166 6.0 425 M 132
SM24M30 23500/23300 230/208 11.2/11.9 2500/2479 9.4/9.4 $200 10.0 390 M 152
SL28M30 27800/27000 230/208 13.5/14.4 2865/2812 9.7/9.6 $229 8.5 600 L 193
SL36M30 36000/35700 230/208 19.0/20.5 4235/4200 8.5/8.5 $338 12.0 725 L 212
Kühl +
Heat Pump
YS10M10* 9500 7500 115 7.8 812 7.6 743 3.0 11.7 $65 1.9 285 S 109
YS12M33 12100/12100
YM18M34 18200/17800
YL24M35 24000/23600
Kühl +
Electric Heat
ES12M33 11700/11200 10700/8900 230/208 4.8/4.9 1026/982 16.0/14.7 3500/2900 3.3 11.4/11.4 $82 2.8 275 S 113
ES15M33 14500/14300
EM18M34 17500/17200
EM24M34 23500/23300
EL36M35 36000/35700
9400/9000 230/208 5.2/5.4 1120/1120 5.6/5.8 1132/1139 2.4 10.8/10.8 $89 3.0 265 S 115
15500/15400 230/208 8.5/8.9 1838/1798 8.5/8.7 1833/1761 2.6 9.9/9.9 $147 5.4 370 M 141
23500/23200 230/208 11.1/12.0 2474/2433 12.2/14.3 2610/2575 2.6 9.7/9.7 7.0 600 L 197
10700/8900 230/208 6.4/6.8 1405/1385 16.0/14.7 3500/2900 3.0 10.3/10.3 $112 3.5 360 S 117
13000/10600 230/208 7.4/8.0 1635/1617 19.5/17.0 4200/3500 3.1 10.7/10.7 $131 4.6 350 M 141
13000/10600 230/208 11.2/11.9 2500/2479 19.5/17.0 4200/3500 3.1 9.4/9.4 $200 10.0 390 M 153
17300/14300 230/208 19.0/20.5 4235/4200 24.0/22.4 5500/4650 2.5 8.5/8.5 $338 12.0 725 L 213
BREAKER
FUSE
60 Hertz
Am
s
Weight
Net
Lbs
* Operates on 115 volt and is not equipped with supplemental heat. Will not provide heat at temperatures below 40°F. Friedrich room air conditioners are designed to operate in outdoor temperatures from 60°
F to 115° F.
Due to continuing research in new energy-saving technology, specifi cations are subject to change without notice.
As an ENERGY STAR
®
guidelines for energy effi ciency.
STAR
®
partner, Friedrich Air Conditioning Co. has determined that the selected ENERGY STAR® () models meet the ENERGY
The consumer- through the AHAM Room Air Conditioner Certifi cation Program- can be certain that the AHAM Cer tifi cation Seal accurately states the unit’s cooling and heating capacit y rating, the amperes and the energy effi ciency ratio.
Estimated yearly operating cost based on a 2007 national average electricity cost of 10.65 cents per kWh. † The estimated yearly operating cost of this model was not available at the time the range was published.
R-410A
All models use
environmentally
friendly R-410A
refrigerant.
7
Page 9
Installation Information / Sleeve Dimensions
Shell Depth to
Louvers
8
¾"
8
¾"
16
½"
Minimum
Extension
Into Room*
5
¾”
5 ¾”
3
5
/8
”18
Minimum
Extension
Outside*
15
16
”27
/16
15
/16
”27
16
15
/16
”29
Minimum** Maximum Height Width Max. Depth
Sleeve
S15
M17
L20
Height Width
15
"25
/16
15
/16
"25
3
/16"
Depth
with Front
15
"29"
/16
15
/16
"29"
28" 35 ½”
* Minimum ex tensions when mounted in a window.
** Minimum widths achieved using one side curtain assembly as opposed to both in a standard installation. NOTE: S,M and L sleeves may be installed in window with no side kits if properly installed.
Circuit Rating/ Breaker
Model
SS08M10, SS10M10, SS12M10 and SS14M10. YS10M10.
SS12M30, SS15M30, SM18M30 and SM21M30.
SM24M30, SL28M30. ES12M33, ES15M33. YS12M33
Circuit Rating
Breaker or
T-D Fuse
125V - 15A 5 - 15P 6
250V - 15A 6 - 15P 4
250V - 20A 6 - 20P 4
Plug Face
(NEMA#)
Power Cord
Length (ft.)
Wall Outlet
Appearance
Window Width
3
"42"16
/8
3
/8
"42"18
7
/8
”42"20
(C)
Front
(B)
Thru-the-wall Installation
Finished Hole
3
/16”
3
/16”
3
/8
3
26
/16”
3
26
/16”
" 28 ¼" 15
SIDE VIEW
3
7
"
/8
3
7
/8
1
/8
SL36M30. EM18M34, EM24M34, EL36M35. YM18M34 and YL24M35
250V - 30A 6 - 30P 4
For the best cooling performance and highest energy efficiency
Keep the filter clean
Make sure that your air conditioner is always in top performing condition
.ylralugerretlifehtgninaelcyb
Provide good air flow
Make sure the airflow to and from the unit is clear. Your air conditioner puts the conditioned air out at the top of the unit, and takes in unconditioned air at the bottom. Airflow is critical to good operation. It is just as important on the outside
.dekcolbtonsiroiretxetinuehtdnuorawolfriaehttahtgnidliubehtfo
Unit placement
If your air conditioner can be placed in a window or wall that is shaded by a tree
rosepardgnisU.yltneiciffeeromneveetarepolliwtinueht,gnidliubre hto naro
blinds on the sunny side of the dwelling will also add to your unit’s efficiency.
Insulation
Good insulation will be a big help in maintaining desirable comfort levels. Doors should have weather stri
pping.
Be sure to caulk around doors and
windows.
Proper installation of seal gasket
Make sure the seal gasket has been installed properly to minimize noise and improve effi ciency. If the seal gasket has not been installed, please refer to the installation instructions.
8
Page 10
ELECTRICAL DATA
Not following the above WARNING could result in fi re or electically unsafe conditions which could cause moderate or serious property damage. Read, understand and follow the above warning.
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before service or installation.
All electrical connections and wiring MUST be installed by a qualifi ed electrician and conform to the National Electrical Code and all local codes
which have jurisdiction. Failure to do so can result in personal injury or
death.
NOTICE
FIRE HAZARD
Wire Size Use ONLY wiring size recommended for single outlet branch circuit.
Fuse/Circuit Breaker Use ONLY the correct HACR type and size fuse/circuit breaker. Read electrical ratings on unit’s
Grounding Unit MUST be grounded from branch circuit through service cord to unit, or through separate
Receptacle The fi eld supplied outlet must match plug on service cord and be within reach of service cord.
*HACR: Heating Air Conditioning and Refrigeration
rating plate. Proper circuit protection is the responsibiity of the homeowner.
ground wire provided on permanently connected units. Be sure that branch circuit or general purpose outlet is grounded.
Do NOT alter the service cord or plug. Do NOT use an extension cord. Refer to the table above for proper receptacle and fuse type.
The consumer - through the AHAM Room Air Conditioner Certifi cation Program - can be certain that the AHAM Certifi cation Seal accurately states the unit’s cooling and heating capacity rating, the amperes and the energy effi ciency ratio.
9
Page 11
WARNING: Before Operating Your Unit
WARNING
Electrical Shock Hazard
Make sure your electrical receptacle has the same configuration as your air conditioner’s plug. If different, consult a Licensed Electrician.
Do not use plug adapters. Do not use an extension cord. Do not remove ground prong.
Always plug into a grounded 3 prong oulet. Failure to follow these instructions can result in death, fire, or electrical shock.
Make sure the wiring is adequate for your unit.
If you hav e fus es, they sho uld b e of the t ime dela y ty pe. B efo re yo u in stal l or relocate this unit, be sure that the amperage rating of the circuit breaker or time delay fuse does not exceed the amp rating listed in Table 1.
DO NOT use an extension cord.
The cord provided will carry the proper amount of electrical power to the unit; an extension cord may not.
Make sure that the receptacle is compatible with the air conditioner cord plug provided.
Proper grounding must be maintained at all times. Two prong receptacles
The grounded receptacle should meet all national and local codes and ordinances. You must use the three prong plug furnished with the air conditioner. Under no circumstances should you remove the ground prong from the plug.
Test the power cord
All Friedrich room air conditioners are shipped from the factory with a Leakage Current Detection Interrupter (LCDI) equipped power cord. The LCDI device on the end of the cord meets the UL and NEC requirements for cord connected air conditioners.
To test your power supply cord:
1. Plug power supply cord into a grounded 3 prong outlet.
2. Press RESET (See Figure 1).
3. Press TEST, listen for click; the RESET button trips and pops out.
4. Press and release RESET (Listen for click; RESET button latches
and remains in). The power cord is ready for use.
NOTICE
Do not use the LCDI device as an ON/OFF switch. Failure to adhere to this precaution may cause
premature equipment malfunction.
Once plugged in, the unit will operate normally without the need to reset th e LC DI d evic e. I f the LCD I de vic e fai ls t o tri p whe n te ste d or i f th e pow er su pply cord is d amag ed, it mu st b e rep lac ed wit h a n ew po wer supp ly c or d from the manufacturer. Contact our Technical Assistance Line at (800) 541-6645. To expedite service, please have your model number available.
Table 1.
MODEL
SS08M10, SS10M1 0, SS1 2M 10, SS1 4M10, YS10M10
SS1 2M30, SS 1 5M30, SM1 8M30, SM2 1M30
SL25M30, SL28M30, ES12M33, ES15M33, YS12M33
SL36M30, EM1 8M34, EL25M35, EL36M35, YM1 8M34 , YL2 4M 35
Figure 1
RESET
WARNING
TEST BEFORE EACH USE
1. PRESS RESET BUTTON
2. PLUG LCDI INTO POWER RECEPTACLE
3. PRESS TEST BUTTON, RESET BUTTON SHOULD POP UP
4. PRESS TEST BUTTON, FOR USE DO NOT USE IF ABOVE TEST FAILS
WHEN GREEN LIGHT IS ON IT IS WORKING PROPERLY
CIRCUIT RATING
OR TIME DELA Y
AMP VOLT
15 125 5-15R
15 250 6-15R
20 250 6-20R
30 250 6-30R
TEST
FUSE
TEST BEFORE EACH USE
1. PRESS RESET BUTTON
2. PLUG LCDI INTO POWER RECEPTACLE
3. PRESS TEST BUTTON, RESET BUTTON SHOULD POP UP
4. PRESS TEST BUTTON, FOR USE DO NOT USE IF ABOVE TEST FAILS
WHEN GREEN LIGHT IS ON IT IS WORKING PROPERLY
REQUIRED
WALL
RECEPTACLE
NEMA
NO.
TEST
RESET
WARNING
10
15/20A LCDI Device 30A LCDI Device
FRR001
Page 12
Control Panel Operation
Let’s check out how to control your air conditioner. On the control panel, just to the left of the POWER control panel function buttons and mode icons can be viewed in Figure 1.
Power On – Press the
power button will illuminate to indicate the power is on. The backlight on the power switch will automatically dim to 20% intensity after of inactivity. The remote control can also be used to turn power ON / OFF (See Remote Control).
Display
light. The back light has an automatic two (2) step dim function. seconds of inactivity, the display dims to 20% intensity. After an additional 120 seconds, the display switches off. Touching buttons will automatically bring the display to full brightness.
There are four control push buttons on each side of the display.
SYSTEM B utton – Allows the user to sequentially select,
, HEAT , and FAN ONLY operation. Press the button and the display advances to the next mode. A new icon appears. At the same time, the mode displays for two (2) seconds, then returns the display to th
e temperature set point for modes other than FAN. Note that on cool
only units, there are no
FAN MO DE B ut to n – Selects between automatic
operation. In the compressor operates or the heat function is enabled.
In the SYSTEM FAN ONLY Mode, mode, fans speed is determined by your
Figure 1
, is a liquid crystal display (LCD). All of the
button to turn on the air conditioner. The
120
seconds
After 120
Cool
HEAT
and modes.
or
mode, the fan only turns on and off when the
is not available.
selection on the
In the
button.
FAN SPEED Butto n .sdeeps naf neewteb tceles yllaitneuqes ot desU –
Depending on your model, you can select between LOW, MED, HIGH,
t available on SL and Kuhl+ models.on gnittes xaM .OTUA dna XAM dna When the button is pressed, the fan speed is temporarily displayed in the display window, plus a fan speed icon (triangle) changes to indicate the new speed level. W depending on t
he set temperature on the control panel and the actual
hen auto is selected,
fan speed automatically varies
room temperature. Let me explain. Say for example you’re working in your garage and you need to open the big door for several minutes. The air conditioner will sense a wide difference between the set temperature and the actual room temperature when this occurs the system fan speed increases to MAX. The fan speed decreases (in step) as the temperature difference decreases. When the set point temperature is reached the FAN speed returns to the original setting.
SCHEDULE Button – The
button turns the schedule function on and off. The current day of the week is indicated as a dot underneath the day symbol. Pressing the
button a second time turns the schedule function off. The schedule function comes preprogrammed with recommended energy savings values (Addendum 1). The values may be changed through the schedule program function (See Programmable Thermostat).
UP and DOWN arrows – Pressing either
(UP) or (DOWN) button changes the desired room temperature. The factory preset lower and upper limits are 63° F (16° C) and 99° F (37° C). These buttons are also used to navigate between function options when using the User Menu or Maintenance Mode.
BACK Button .detceles neeb sah meti unem a retfa desu si nottub sihT –
It takes the user back to the previous menu level and to save and exit.
DISPLAY/ENTER Button
This button is used in conjunction with User Menu and Maintenance Mode operation to select items. This button may also be used to alternatively display the ROOM TEMPERATURE, OUTDOOR TEMPERATURE, and TIME. If the display is left inactive for 10 seconds it will reset to the TEMPERATURE SET POINT.
AWAY
FRONT PAN E L LOCK
CHECK FI LT ERONOFF
HE AT ->
R ET URN NIGHT
SCHEDULE
PERIODS
FILTER MAINTENANCE
EXIT RESET
<- COOLROOM TEMP SE T POINT
F
A
M
P
M
C
WAIT
BACK
DISPLAY
ENTER
AUTO MODE
SYSTEM
FAN
MODE
FAN
COOL
MODE
HEAT
MODE
AUTO
AUTO
CONTINUOUS
AUTO
FAN ONLY MODE
MAINTENANCE
REQUIRED
OUTDOOR TEMP
% RH
SPEED
M
SCHEDULE
BUTTONS BUTTONS
SCHEDULE
ON/OFF
TW
TFS
S
WAKE
POWER
11
Page 13
ALERTS (The control system has five (5) customer alerts)
CHECK FILTER
appears on screen. The word “ The
alert is issued when the fan run .sruoh 005 naht retaerg si emit
This alert may be reset by the user (Refer to Special Functions, Filter Reset).
Maintenance Required – When maintenance is required, a service icon
appe ars on scre en. T his icon wi ll not be dismissed until maintenance
has been performed. If the service icon
” appears next to the .nottub
the icon
is established the service icon
goes away.
Wait – The WAIT icon
Whenever the compressor shuts off, system pressures must be allowed to equalize. At this time, an internal timer begins a count-down from up to 240 seconds. If a demand for heat or cool occurs during this count-down the WAIT icon
displays letting you know that the compressor will not operate until the count-down has completed. This timer prevents damage to the unit if it tries to start too quickly after it stops running. Normally the WAIT icon
is off. Once the timer has cleared, the air conditioner will he at o r coo l ba sed on t he t empe rat ure set ting . El ect ric h eat is n ot a ffec ted by this timer.
Protection Alert (Freeze) – If the room freeze protection is active, the
display indicates this by showing Room Freeze Protection "FRZ". Once
temperature is less than 40° F (4° C), and the air conditioner is equipped with electric heat, the room freeze protection will activate. The air conditioner will run high fan and electric heat until the room temperature reaches 46° F (8° C). Pressing the
Low Battery – When the battery is low a warning display
button delays the freeze protection function
will be
inserted before other messages such as “COOL”. If the Low Battery
alert is on, the battery in the control unit must be changed. Refer to the changing the battery procedure. Once the battery is changed, the alert message will go off. Refer to Troubleshooting Tips. Under normal conditions the battery life should be greater than 7 years.
.noitidnoc lamronba na desnes sah metsys eht ybdnats no si
.evitca si tuokcol rosserpmoc eht nehw setanimulli
The hour digits flash first. The user presses the or to change the hours. To change AM-PM, the hours must be advanced 12 hours. Press the key to change to the minutes. To exit the selection process, user presses the key which will go to the time screen.
The minutes digits flash. The user presses the or to change the minutes. Press the key to change the days. To exit the selection process, the user presses the key which will go to the time screen.
The dot underneath the days of the week begins to blink to indicate which day it is. If the user has not set the date before, the dot starts on Monday. If the user is making a correction to previously set information the dot appears under whichever day the unit thinks it is. The user can press or to move the dot left or right (respectively) along the week. The user presses to loop back to the hours setting. To exit the selection process, the user presses the key which will go to the time screen.
Tuesday has been selected. The user presses to loop back to the hours setting. To exit the selection process and accept the changes, the user presses the key which will go to the time screen.
BACK
Sp
ecial Functions
Panel Lock – The front panel push buttons can be locked to prevent
inadvertent operation. To lock the front panel, press and hold the
SCHEDULE
+
buttons for three (3) seconds. A double beep indicates your mode change was successful and a the display, press and hold the The
icon will no longer be visible.
Filter Reset
and holding the
button for three (3) seconds. A beep indicates the
system timer was reset and the
icon appears on the display. To unlock
SCHEDULE
+ .sdnoces )3( eerht rof snottub
icon displays, the timer may be reset by pressing
icon and the word "
RESE T
" will
no longer be visible.
User Menu Functions – The User Menu Functions allows you to change
the following selections: Set TIME, 12/24 Hour Clock Format, BEEP ON / OFF, DIM ON / OFF, Emergency Heat (EMHT) ON / OFF, Auto BAND Adjust, F/ C Select, FRZ ON / OFF, Temp Offset (TO) and the Automatic Temperature
Sensing Feature (ATSF).
To enter the User Menu, press and hold selection appears. Use the
(UP) or (DOWN) buttons to scroll
through the User Menu. Press the
for 3 seconds, the TIME
button to enter the displayed function. If left inactive for 15 minutes the User Menu display will no longer be visible and it returns to normal operation mode display. To manually exit the User Menu, press the
button.
Time Setting – When in the User Menu, on the Control Panel, use the
(UP) and (DO WN) to se lec t TIME . Push , the hours segment
(UP) and hsup neht ,ruoh eht tes ot )NWOD(
(UP) and
to set the minutes, then push
.
NOTE: If the AM or PM indicator is incorrect, push
(DOWN)
until the hours
(UP) or (DOWN) to advance the hour segment 12 hours, then push displays. Use the day. Press the
Press
(UP) to go to the next menu 1224.
NOTE: Pressing the
(UP) or (DOWN ) to s elect th e curr ent
key to
save and go back to the TIME screen.
button again will exit the user menu function
. The day of the week
mode. Or simply leave the control inactive for 15 minutes and the control will return back to normal operation.
12
Page 14
SYSTEM
FAN
MODE
FAN
SPEED
SCHEDULE
BACK
EXIT
DISPLAY
ENTER
SYSTEM
FAN
MODE
FAN
SPEED
SCHEDULE
BACK
EXIT
DISPLAY
ENTER
User presses or to toggle the format between 12HR and 24HR display. To exit the selection process and accept the change, press the key.
Clock Type – You may select between a 12 hr and 24 hr clock. When
1224 is displayed press the
key then press (UP) or (DOWN)
to toggle between 12 hr and 24 hr clock. To accept the change, press the
key to return to the 1224 screen. Press the (UP) to go to the
next menu BEEP.
BACK
SYSTEM
FAN
MODE
FAN
SPEED
SCHEDULE
EXIT
DISPLAY
ENTER
User presses or to toggle between Beep On and Beep Off. Press the key to accept the change and exit the selection process.
Audible Alerts – You can select to have the control beep when entering
menus.
When BEEP is displayed press the
or
(DOWN) to toggle between ON and OFF. To accept the change,
press the
key to return to the BEEP screen. Press the (UP) to go
key then press (UP)
to the next menu EMHT on Kühl+ models or F C for Kühl models.
FAN
SPEED
SCHEDULE
User presses or to select between AUTO, DM 20, OFF. Press the key to accept the change and exit the selection process.
The Dim Auto automatically dims the display to 20% and then turns it off after a period of time. The Dim 20 setting behavior is similar to AUTO, but prevents the display from turning off. Minimum brightness is 20%. The Dim Off setting forces the display to run at full brightness.
DISPLAY
ENTER
User presses or to toggle between Emergency Heat On and Emergency Heat Off. Press the key to accept the change and exit the selection process.
Emergency Heat – The Kühl+ heat pump models (YS, YM, YL) have
a special feature that is designed to keep the unit providing heat.
When EMHT is displayed press the
key then press (UP) or
.FFO dna NO neewteb elggot ot )NWOD(
To accept the change, press the Press the
(UP) to go to the next menu BAND
.
In the unlikely event of a compressor failure, the heat pump unit may be switched to operate in the electric heat mode only until repairs can be made.
BACK
SYSTEM
FAN
MODE
FAN
SPEED
SCHEDULE
EXIT
DISPLAY
ENTER
The menu allows the user to adjust the minimum spread between the Auto Cool set point and the Auto Heat set point. Press the or key to adjust. The adjust range is 3 to 10.
Auto Changeover ‘Dead Band’ – A buffer Zone between heating and
cooling in which no conditioning occurs. For Kühl+ models with the auto changeover feature you can select the temperature band between heating and cooling. From the factory the band is set at 3° F (-16° C). The band is adjustable from 3° F (-16° C) to 10° F (-12° C). When BAND is displayed press the key then press (UP) or (DOWN) to toggle between 3 and 10. To accept the change, press the key to return to the BAND screen. Press the (UP) to go to the next menu F C.
BACK
SYSTEM
FAN
MODE
FAN
SPEED
SCHEDULE
User presses or at the same time to toggle between Fahrenheit or Celsius as their temperature unit of choice. Press the key to accept the change and exit the selection process.
EXIT
DISPLAY
ENTER
.neercs THME eht ot nruter ot yek
Fahrenhei t / Celsius Sel ection – You may select between displaying
temperature in F or C. When F C is displayed press the press change, press the
(UP) or (DOWN) to toggle between F and C. To accept the
key to return to the F C screen. Press the
key then
(UP) to go to the next menu FRZ.
13
Page 15
BACK
SYSTEM
FAN
MODE
FAN
SPEED
SCHEDULE
EXIT
DISPLAY
ENTER
User presses or to select between Freeze Protection On & Freeze Protection Off. Press the key to accept the change and exit the selection process.
Free ze Pro tec tion The Kühl+ models have a special feature that is
designed to keep the interior space above freezing by energizing the electric heater anytime the indoor room temperature falls to 40° F (4° C) . With the freeze protection feature turned on, when the unit senses the indoor temperature fall to 40° F (4° C) the unit will run the heater and high fan until the space reaches 46° F (8° C) When FRZ is displayed press the
key then press (UP) or (DOWN) to toggle between ON
and OFF. To accept the change, press the key to return to the FRZ screen. Press the
(UP) to go to the next menu TO.
SYSTEM
FAN
MODE
FAN
SPEED
SCHEDULE
BACK
EXIT
DISPLAY
ENTER
F
F
Y R
User presses or to select between ATSF On or Off. Press the key to accept the change and exit the selection process.
Automatic Temperature Sampling Feature - The automatic temperature
sampling feature maintains a balanced temperature throughout the room by circulating the air for 30 seconds once every 9 minutes that the unit is not running when it is set to cooling or heating mode. By circulating the air the unit can detect hot or cold areas in the room and operate the unit to cool or warm the room as necessary. This function is only available when the fan mode is set to ‘AUTO’ or in COOL or HEAT Mode. (Heating function only available on Kuhl+ units)
User presses or to increment/decrement the temperature offset (TO) for the room temperature sensor. (Maximum offset = +/- 8 degrees F). Press the key to accept the change and exit the selection process
Temperature Offset – In some cases the built in thermostat on the unit
For display only. No user selectable options.
Y
may not display the temperature as it is felt in the room. This can be caused by many things including the size of the unit, the heat load on the room or other factors. Friedrich allows you to select the appropriate temperature offset to make the temperature readout as accurate as possible for your application.
In many cases the factory 0° F (-18° C) offset will provide
F
F
an accurate temperature readout. To change the offset follow these instructions. When TO is displayed press the (UP) or
(DOWN) to toggle between 0° F (-18° C) and 8° F (-13° C) .
key then press
In most instances an offset from 0° F (-18° C) to 2° F (-17° C) is all that is necessary. To accept the change, press the screen. Press the
(UP) to go to the next menu ATSF.
You may cycle through the menus using the (UP) or (D OWN) keys to access any of the menus.
key to return to the TO
Firmware Version - When VER is displayed press Display /
Enter key. The firmware version is displayed as left digit (Major) and right digit (Minor). This version number should be used along with Model and Serial numbers for service.
DIGITAL CONTROL PANEL'S ACCESS CODES SUMMARY
Key Sequence
Filter Reset Press BACK key for 3 sec + play double beep ( ) Enter User Menu Press DISPLAY/ENTER key for 3 sec + play double beep ( ) Enter Maintenance Menu Press SYSTEM + SCHEDULE + BACK + DISPLAY/ ENTER for 3 sec + play double beep () Schedule ON/OFF Press SCHEDULE once each time Enter & Exit Schedule Programming Press SCHEDULE for 3 sec + play double beep () Reset Error Codes & Error History Press  +  for 3 sec + play double beep ( ) Lock Control Panel Press SCHEDULE + DISPLAY/ENTER f
14
Action
or 3 sec + play double beep ()
Page 16
Remote Control Operation
Remote Control – Refer to Figures 11 and 12 during operation description. Getting Started – Install two (2) AAA batteries in the battery compartment
located on the back of the unit.
Operation – The remote control should be within 25 feet of the air
conditioner for operation (Refer to Figure 10 for effectiveness). Press the
button to turn the remote on. The remote will automatically power off after 15 seconds if the buttons are not being pressed. The remote must be on to control the unit.
POWER Button – Turns remote and unit on and off. SYSTEM Button – Allows the user to sequentially select,
HEAT
, and FAN ONLY operation. When the button is pressed, the
Note that when the heating function is not available, the system will automatically skip the HEAT and AUTO modes.
FAN MODE B ut ton – Selects between automatic (
operation. In the AUTO mode, the fan only turns on and off when the compressor operates or the heat function is enabled.
NOTE: AUTO is not available in the FAN ONLY Mode, the display
indicates determined by your selection on the
. In the mode, fan speed is
button.
Cool ,
) or
FAN SPEED Butto n – Used to sequentially select new fan speed, plus
AUTO operation. When the
FA N
button is pressed, the fan speed is
SPEED
temporarily displayed in the display window, plus a fan speed icon (triangle) changes to indicate the new speed level. Fan speed automatically varies depending on the set temperature on the control panel and the actual room temperature. Let me explain. Say for example you’re working in your garage and you need to open the big door for several minutes. Since there is a big diffe rence between your set temperature and the actual room temperature the system fan speed increases to MAX. It remains at this speed until the room temperature matches the set temperature.
SCHEDULE
SCHEDULE Button
off. Pressing the off. Only the schedule icon
UP and DOWN Arrows – Pressing either the
.egassem yalpsid a aiv detceles neeb sah edom hcihw setacidni yalpsid
button changes the desired room temperature. The factory preset lower
– The
SCHEDULE
button a second time turns the schedule function
button turns the schedule function on and
will be displayed.
(UP) or (DOWN)
and upper limits are 60° F (16° C) and 99° F (37° C). These buttons are also used to navigate between function options when using the User Menu or Maintenance Mode.
Remote Effectiveness
Hand Held Remote – Has an operating range of up to 25 ft. The infrared
remote control signal must have a clear path to transmit the command to the air conditioning unit. The remote signal has some ability to "bounce" off of walls and furniture similar to a television remote control. The diagram below shows the typical operating range of the control in a standard room with 8 ft high ceilings.
SIDE VIEW
7.5ft
60°
60°
TOP VIEW
25ft
25ft
30°
45°
25ft
45°
30°
8ft
25ft
25ft
25ft
4ft
8ft
60°
60°
45°
45°
30°
30°
25ft
6ft
16ft
25ft
Changing Temperature from F˚ (Fahrenheit) To C˚ (Celsius) or Reverse
Be within 25' of unit with the remote control. Press the SYSTEM and FAN MODE buttons at the same time and hold for 3 seconds. The display will show the temperature in Celcius. Do the same to reverse temperature to F
˚ (Fahrenheit).
15
Page 17
Remote Control Operation (Continued)
Figure 1
DISPLAY
Figure 2
SYSTEM
TEMPERATURE
UP
SCHEDULE
AUTO ICON
COOL
ICON
HEAT
ICON
FAN MODE
POWER
TEMPERATURE DOWN
FAN SPEED
FRR005
FAN ONLY
ICON
16
SYSTEM
MODE
FAN
MODE
FAN
SPEED
SCHEDULE
ICON
°F / °C ICONs
2 X 16 SEGMENT
DISPLAY
FRR006
Page 18
ELECTRONIC CONTROL SYSTEM MAINTENANCE
Introduction
This section contains information on the maintenance alerts, temperature limiting, diagnostic test and how to access. The electronic control system has a built in maintenance sub system which works constantly behind the scenes to help identify problems with the air conditioner or control system. When maintenance is required, a service icon appeasrs on the display screen.
This icon will not be dismissed until maintenance has been performed or the problem cleared.
Note: The wrench icon may be on steady or flash, depending on severity. Maintenance should only be performed by qualified service
personell.
Display
T esting the Display
Press the FAN MODE and FAN SPEED buttons at the same time for 3 seconds. All of the display's icons and functions should light up. If any of them do not light up, the display should be replaced. When the buttons are released, the display reverts to the original display.
17
Page 19
Electronic Control System Maintenance Operation
To Enter the Maintenance Section:
Press SYSTEM+SCHEDULE+BACK+DISPLAY/ENTER for 6 seconds.
There are 5 maintenance sub-menus M1 through M5.
Access
Maintenance Sub-Menus
M1
– Temperature High Limit – Temperature Low Limit
M2
– Test Mode Access
M3
– Provision Switch Setting & State
M4 M5
– Alarms & History
M6
Pressing the or key cycles through the sub-menus. Press DISPLAY/ENTER to enter a sub-menu. The BACK key is used to exit the menu.
be taken when modifying parameters in the maintenance menus.
Service Only
Factory Use Only
Factory Use OnlyFactory Use Only
Service Only Service Only
Service Only
Extreme care must
18
Page 20
Temperature High Limit
Maintenance function 1 is ready to be selected. Press DISPLAY/ENTER to access the function.
User presses is the maximum upper limit. The current stored high limit is displayed when the screen is selected. Press the BACK key to accept the value, and exit the sub-menu to the M1 screen.
or  to increment or decrement the upper temperature limit. 99°F
Temperature Low Limit
Maintenance funtion 2 is ready to be selected. Press DISPLAY/ENTER to access the fuction
User presses minimum lower limit. The current stored lower limit must be displayed when the screen is selected. Press the BACK key to accept the value, and exit the sub-menu to the M2 screen.
or  to increment or decrement the lower temperature limit. 60°F is the
M3 – Test Mode Access
Maintenance function 3 is ready to be selected. Press
DISPLAY/ENTER to access the function.
User presses the or key to toggle the Test Mode
ON/OFF. Press the BACK key to accept the change
and exit the sub-menu to the M3 screen.
This test selects the system mode of operation directly.
The Following functions Can be Tested
1. System Mode: Cool/Heat Pump Compressor, Electric Heat, Fan Only
2. Fan operation and speeds
Test mode Bypasses:
1. Compressor lock out (time delay)
2. All relay switch’s delays
3. All thermistors delay
4. Automatic heat/cool changeover delay
5. System settings
If M3 switch is left ON it will reset to OFF automatcally after 15 minutes of inactivity.
19
Page 21
M4 – Switch Access (Unit Configuration)
FACTORY USE ONLY
M5 – Error Codes & History
Maintenance funtion 5 is ready to be selected. Press DISPLAY/ENTER to access the function.
The error code display shows the error code number on the left, and the error code history on the right. User presses the
The current state of the error code is shown with the On/Off icon. To exit the maintenance sub-menu, press the BACK key to return to the M5 screen. Shown on this display is error code 1 with 4 occurances. The current state is on.The error code display shows the error code number on the left, and the error code history
on the right. User presses the current state of the error code is shown with the On/Off icon. To exit to the maintenance sub-menu, press the BACK key to return to the M5 screen. Shown on this display is error code 6 with 3 occurances. The current state is off.
or  keys to cycle through the error codes.
or  keys to cycle through the error codes. The
Number of Errors
Error Code
Error Code On/Off
To Clear Error Codes’ History:
Hold the
or  keys simultaneously for 3 seconds. See page 56 for alarm status and error codes.
M6 – Factory Use Only
20
Page 22
UNIT OPERATION
There are two basic ways to operate the unit - Front Panel and Wallstat. The Front Panel and Wallstat are never active at the same time. Switching between these modes is controlled via the (FP) jumper on the Wallstat connector. When the jumper is ON, the mode = Front Panel.
Front Panel
System Mode Sequence (SCHEDULE = OFF)
There are two system modes of operation. One for a cool only unit (see figure 1) and one for a heat-cool unit (see figure 2). System parameters for each system mode are saved when exiting a system mode, and retrieved when entering a new system mode.
Figure 1
System Mode: Cool Only Units
Figure 2
System Mode: Heat - Cool Units
21
Page 23
COOL-HEAT SET POINTS
The air conditioner control system is designed to control different product configurations with a select set of features. Some models just cool, some cool and heat with electric heat, and others cool and heat with a heat pump and/or electric heat.
The system set points are mapped to the internal controls as shown below.
1.5
1.5
Deadband
Control
There are 8 stored & variable set points in the system:
System Set Point Mapping Figure
1 - ASPC: Auto Set Point Cool 2 - ASPH: Auto Set Point Heat 3 - CSP: Cool Only Set Point 4 - HSP: Heat Only Set Point 5 - SASPC: Scheduler Auto Set Point Cool 6 - SASPH: Scheduler Auto Set Point Heat 7 - SSPC: Scheduler Set Point Cool Only 8 - SSPH: Scheduler Set Point Heat Only
22
Page 24
ELECTRONIC CONTROL SEQUENCE OF OPERATION
Compressor and Rev ersing V alve Control
Active Mode Compressor
Cooling De-Energized Heat - Heat Pump
Heat - Electric Fan Only
* The Reversing valve stays in the last state until a call for heat or cooling (see fi gure below)
On
On Off Off
Reversing Valve State
Energized
Compressor Operation:
The reversing valve only changes when required
to provide cooling or heat pump. The RV valve
stays in it's last state until required to change.
Cooling Mode
Once the ambient temperature rises past the cool demand threshold (Cool Set Point + 1.5 ˚F) (see fi gure below), and the compressor is not locked out, the cooling cycle begins. As shown in the fi gure below, the fan is started 5 seconds prior to the compressor. Once the ambient temperature has been lowered to the cool set point (Cool Set Point minus .25 ˚F), the cooling cycle starts to terminate by shutting off the compressor. After a 30 seconds delay, the fan is shut off. (See fi gure below for graphic details)
23
Page 25
Heating Mode Control Operation
There are two heating methods: Heat Pump and Electric Resistance Heat. There are 3 types of units that provide heating: Heat Pump Only (Model YS10M10) Heat Pump with Electric Heat and Cool with Electric Heat.
Heat Control Operation Heat Pump Only
Once the ambient temperature falls below the Heating Demand Threshold (1.5 ˚F Below the Heat Set Point Temperature), the heating cycle begins. The fan is turned on 5 seconds later. Once the ambient temperature has been raised to the Heat Satisfi ed Point (Set point + .25 ˚F), the compressor is turned off. The fan is turned off 30 seconds later. The fi gure below illustrates the basic heat pump operation.
24
Heat Control (Heat Pump Only)
Page 26
Heat Pump With Electric Heat Operation
This heating is more complex due to the possibility of two heating methods. If the ambient indoor temperature is be­low the heat demand threshold (1.5˚F below the heat set point temperature), and the compressor is not locked out, turn on compressor. If the ambient indoor temperature is 0.25˚F above the heat set point turn off the compressor.
If the compressor is locked out & electric heat is available:
1. Turn on the electric heat until the compressor is not locked out.
2. After lockout, turn off the electric heat, wait 5 seconds, then turn on the compressor.
If Electric Heat is Available
After the Heat button is initially pressed, the unit will run the electric heater until the initial set point is satis ed (Hot Start Feature). After the initial start, the unit will switch to Heat Pump heat and decide between Heat Pump heat and Electric
heat based on the following two monitored conditions:
Condition 1
If the outdoor coil temperature sensor drops to 30 ˚F or less for 2 consecutive minutes, the unit will switch to electric heat if available. Thereafter, the unit will switch back to Heat Pump heat if the outdoor coil temperature sensor rises to 45 ˚F or greater.
If Electric Heat is not available (out of order) and the outdoor coil temperature sensor drops to 30 ˚F or less for 2 consecutive minutes, then the compressor and fan will turn off. Thereafter, the unit will switch back to Heat Pump heat if the outdoor coil temperature rises to 45 ˚F or greater.
25
Page 27
Heat Pump With Electric Heat Operation (Continued)
Condition 2
If the Δ (delta) (set point temperature minus the ambient indoor temperature) is greater than 5 ˚F, then the unit will switch to electric heat, if available. The unit will continue to operate with electric heat until the heat demand is satisfi ed. Note that the electric heat switches on after the Δ temp passes 5°F and the heat pump switches off. Also note that the electric heat will run until the heat demand is satisfi ed. When another heat demand cycle is initiated, the heat pump will run unless the Δ temp is greater than the electric heat threshold.
Emergency Heat
If a compressor fails in the heating season, the Emergency Heat allows the user to override the Heat Pump and heat with electric heat only. This is controlled via the user interface (See the User Menu Functions page 12).
Note that if heat is the fi rst demand cycle (demand cycle = call for heat or call for cooling) after power restoration, the control system will run electric heat for the entire cycle if the unit is equipped with electric heat.
Electric Heat Operation in Cool with Electric Heat Units
When in the Heat mode, with and without Fan Mode Auto (Fan cycling): If the indoor ambient temperature is below the Heat Demand Threshold (Heat Set Point minus 1.5 ˚F), turn on electric heat. If Ambient is 0.3 ˚F above the Heat Set Point turn off the electric heat.
System Mode Auto
This mode provides automatic change over between cool and heat. The auto mode runs based on the room ambient temperature vs. the Demand Thresholds. It is only available in Heat-Cool Unit.
Notes:
The Heat Demand Threshold and the Cool Demand Threshold values are derived from the Auto Set Point in the Auto Mode (refer to page 22). There is a buffer zone as shown in fi gure , where no heating or cooling is allowed to occur. It is critical that the Cool Demand Threshold be greater than the Heat Demand Threshold by a minimum of 3° while in the Auto System Mode. For example, if a user enters a value for the Auto Cooling Set Point that violates the minimum Δ 3° rule, the Auto Heating Set Point will adjust accordingly. This buffer zone (BAND) can be manually adjusted from 3 to 10° (see the BAND section page 13).
When programming the schedule, the user has the fl exibility to enter the schedule automatic set point cooling (SASPC) and the schedule automatic set point heating (SSPH) set points directly. These values are monitored to ensure that they do not violate the minimum 3° Δ rule. If a violation is detected, the opposite set point will adjust to compensate. The individual heating and cooling rules apply to the auto mode.
Automatic Change Over Delay (Cool with Heat Units)
The change over delay ensures that any system heating or cooling over shoot does not trigger an opposite demand cycle. The change over delay = 15 min. This timer blocks the opposite demand cycle from running until the timer expires. As an example, if the last demand was a cool cycle, and another cool cycle is requested, the timer will not block the request. However, if the last demand cycle was a cool cycle, and heat cycle is requested, the timer will block the request until the change over delay is expired.
26
Page 28
Compressor Lock Out Time
The lockout feature ensures that the compressor is de-energized for a period of time. The timer varies randomly from 180 to 240 seconds The compressor lockout is initiated every time the compressor is “off” due to:
(1) Satisfying the temperature set point (2) Changing mode to fan only or heat (3) Turning the unit off (4) Control is fi rst plugged in or power is restored after failure (5) Line power is restored from a brown out condition
Wait ICON (Hour Glass )
The wait icon will be turned on when the compressor is locked out and during demand for cooling or heat pump compressor operation. The Wait ICON will be turned off when the condition clears.
Cooling Fan Dela y
Fan cycle/Auto mode only When unit cycles cooling ON – starts the fan 5 seconds EARLY. When unit cycles cooling OFF – DELAYS the fan off for 30 seconds
Note: this fan delay is disabled during Test Mode
Heating Fan Delay
This is only for fan Mode Auto (Fan cycles with cool/heat operation) and not for continuous fan mode. When unit cycles Heating ON – starts the fan 5 seconds EARLY. When unit cycles Heating OFF – DELAYS the fan off for 15 seconds Note: the fan delay is disabled during Test Mode
Fan Speed Change Delay
Relay activation is delayed by a minimum number of seconds. The default for this value is 2 seconds and is used to eliminate relay chatter.
Fan Only System Mode
The fan is turned on and runs at the specifi ed manually set speed. Only the Fan is turned on. Cool or Heat operation are off. (This is different than FAN MODE CONTINUOUS where the fan is on with the cool or heat operation).
Fan Only R ules
1. If the SYSTEM FAN ONLY MODE is selected, the Auto fan mode is disabled, and the fan mode is forced to continuous. In addition, the auto fan speed is disabled. If the user presses the fan speed key, the menu will skip over the auto selection. The set point temperature display is off.
2. Any fan speed may be manually selected during Fan Only Mode.
27
Page 29
Fan Operation (Front Panel Mode)
Heat – Cool – Auto – Fan Only Models starting with SS, SM have 4 speeds. Models with SL, and all Kuhl+ have 3 speeds
Speed Selection
1 2 3 4 AUTO
AUTO Operation, but never turns Off. Uses cool set point or heat set point vs. ambient temperature. When there is no demand, operate at the lowest available speed.
AUTO operation turns On or Off with heat or cool demand Uses cool set point or heat set point vs. ambient temperature
Fan
Mode
Continuous
AUTO
Fan Only
"On" " On" "On" " On"
Turns On or Off with heat or cool demand
"On" " On" "On" " On" Disabled
Turns On or Off with heat or cool demand
Turns On or Off with heat or cool demand
Turns On or Off with heat or cool demand
Table
Fan ICON Detail
The system may have a 3 or 4 speed fan. The Fan Speed ICON will Display as per the table below.
Note that in the AUTO mode, the speed of the fan will be shown by illuminating the number of bars in the speed triangle.
Fan Mapping
28
Page 30
UNIT OPERA TION WITH A WALL -ST A T
Front Panel Display Operation in Wall-Stat Mode
The indoor ambient temperature sensor is disabled. All buttons are disabled with the following exception: A. Maintenance commands. B. The user menu for Freeze protection (Display/Enter button for Kuhl+ only units). C. First Button push to illuminate the back light (display will dim).
Maintenance features are operational. This includes the Check Filter, Lock Panel, M3, M4, M5, and the Service wrench icon. Under T-stat operation, as a default, the selected operating Mode (Cool, Heat or Fan) will not show on the front panel. The Service ICON ( ) is displayed if a malfunction is detected.
Cool/Heat/Fan modes and Fan speed operations are controlled by the remote wall thermostat. The fan speeds can be Low or Max for 4 speed units and Low or High for 3 speed units. (T-stat selected must have 2 speed capabilities)
Thermostat terminals requirements:
Must be single stage heat/cool. For cooling only units: C, R, G, Y. For cooling with electric heat units: C, R, G, Y, W. For heat pump units: C, R, G, Y, W, B. (See page 68 for RT5 T-Stat wiring diagrams)
During Heat Mode: The B terminal must be continuously energized. The W terminal from the T-Stat must have 24 V AC output to call for heat. The control board decides on whether to turn on the Heat Pump Heat (compressor) or Electric Resistance Heat. The Y terminal should not have 24 VAC output during Heat Mode.
29
Page 31
REMOVING THE FRONT COVER
REMOVING THE CHASSIS
WARNING
ELECTRIC SHOCK HAZARD
Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.
Remove the decorative front cover by using the tool provided (see fi gure below).
WARNING
ELECTRIC SHOCK HAZARD
Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.
Remove the decorative front cover. (See fi gure at left). Remove the chassis Entrygard Retainer Wire by removing the screw at the front right bottom corner screw (See Figure below). Save this screw for reattachment after reinstalling the chassis.
Tighten the four (4) captive screws as indicated by the arrows in the fi gure above before closing the front panel (do not over tighten). Ensure the fi lter is in place. Make sure curtains do not block the side air intake
Notes on reattaching the decorative front cover: Align the cord notch over the cord and center the fresh air lever. Align the cover over the User Interface
(UI) to ensure it is clear around it and it does not depress any buttons. If not installed correctly the wrench alert symbol could fl ash.
Hold the cabinet stationary then use the hand grips on both ends of the control unit support bracket to pull the chassis out of the cabinet (see below).
Before reinserting the chassis into the sleeve ensure to properly reinstall the chassis seal gasket.
30
Page 32
REPLACING THE INDOOR COIL THERMISTOR
WARNING
ELECTRIC SHOCK HAZARD
Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.
Remove the decorative front cover (see page 30). Remove all indicated screws below (8 total, see fi gure below). Remove the Discharge Sensor and the User Interface plugs from the control board.
Replace the indoor coil sensor. Ensure to properly clip and insulate it at the same location (see fi gure below).
Remove the screws indicated at the side and back plate (6 total, see fi gure below). Partially lift the top cover and at the same time carefully swing out from the top, the back and side plate.
Up
Swing
Out
REPLACING THE CONTROL BOARD
WARNING
ELECTRIC SHOCK HAZARD
Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.
Remove the decorative front cover (see page 30). Disconnect discharge sensor plug (red) Disconnect the User Interface plug (white) Remove the 3 screws indicated below. Pull control board and mount plate out and disconnect the following connectors from it: Power, capacitor, thermistors, fan, reversing valve and heater. Remove the hex screw holding the control board to its mount plate. Pull out the control board (see fi gure below).
31
31
Page 33
Low Voltage Interface Connector
WARNING
ELECTRIC SHOCK HAZARD
Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.
All Kuhl and Kuhl + units have a low voltage interface connector through which a Remote Wall Thermostat, Desk Control and Auxiliary Fan’s Relay can be connected. The interface connector is located on the left side behind the decorative front cover.
Interface Connector Location
Figure 1
Adding a Remote Wall Thermostat
An external thermostat may be added to the air conditioner to provide remote temperature sensing and control.
Thermostat Selection
Friedrich recommends the use of either the Friedrich RT4 or RT5. These thermostats are single stage heat/cool, manual changeover. The RT4 is a digital display thermostat with single speed fan control. The RT5 features
a digital display, two fan speed selection, fi lter check light, temperature limiting, status indicator light, room temperature offset, backlight and battery backup. Other thermostats may be used as long as they are single stage heat/cool and are confi gured correctly for the unit.
Thermostat terminals requirements:
For cooling only units: C, R, G, Y. For cooling with electric heat units: C, R, G, Y, W. For heat pump units: C, R, G, Y, W, B.
For two fan speeds, thermostat must have 2 fan speed selection.
During Heat Pump Mode:
The B terminal must be continuously energized. The W terminal must have 24 VAC output to call for heat. The control board decides on whether to turn on the Heat Pump Heat (compressor) or Electric Heat. The Y terminal should not have 24 VAC output during heat mode.
32
Table 1
FP
F2
F1
D2
D1
C
GH
GL
B
Y
W
R
Interface Connector Definitions
Front Panel. Wire jumper between FP and F2 enables front panel operation. Jumper off enables remote wall t-stat operation.
Used with F1 to provide 24 VAC to external fan relay. (See above for use with FP)
Used with F2 to provide 24 VAC to external fan relay.
Used with D1 for desk control on or off operation.
Used with D2 for desk control on or off operation.
Common Ground Terminal
Call for high fan
Call for low fan
Call for heat pump reversing valve
Call for compressor
Call for heating
24V Power from Electronic Control to Wall
Connecting a Remote Wall Thermostat
To enable the remote thermostat operation, remove the jumper between terminals FP & F2 on the interface connector. Connect the thermostat using Figure 1 and Table 1 as a guide.
Procedure
1) Unplug the unit.
2) Unscrew and remove the decorative front cover. (Page 30)
3) Locate the Interface Connector (24 VAC terminal strip (See fi gure 1 at left) and remove the jumper wire at FP and F2.
4) Make the wire connections according to the confi guration needed for your unit (see above or page 68 for wiring diagrams).
5) Once each wire is matched and connected, the unit is now ready to be controlled by the thermostat.
6) Reattach the decorative front cover (see page 30).
Note: Under T-Stat operation the front panel is disabled
except the Maintenance functions (see page 29 for details).
Page 34
Remote Wall Thermostat Location
The thermostat should not be mounted where it may be affected by drafts, discharge air from registers (hot or cold), or heat radiated from the sun appliances, windows etc.. The thermostat should be located about 5 Ft. above the fl oor in an area of average temperature, with good air circulation.
Mercury bulb type thermostats MUST be level to control temperature accurately to the desired set-point. Electronic digital type thermostats should be level for aesthetics.
Airflow Selection and Adjustment
Air flow direction adjustment
left or right side of the discharge opening. Each of the banks of louvers can be d ire cted left , r igh t, u p or d own in o rder to a chie ve t he m ost o pti mum
move it in the direction that you would like the air to be directed. Please
louvers than the other.
Fresh air and exhaust control
Your air conditioner has the ability to bring fresh air into the room or exhaust stale air out of the room. The control slide is found on the upper part of the unit (See Figure).
Note: An improperly operating or poorly located remote wall thermostat
can be the source of perceived equipment problems. A careful check of the thermostat’s location and wiring must be made then to ensure that it is not the source of problems.
Desk Control
The unit’s electronic control has built-in provisions for connection to an external switch to control power to the unit. The switch can be a central desk control system or even a normally open door switch.
For desk control operation, connect one side of the switch to the D1 terminal and the other to the D2 terminal (See page 32). Whenever the switch closes, the unit operation will stop.
Maximum Wire Length for Desk Control Switch
TO BRING IN FRESH AIR – Move the lever to the Fresh Air
which allows outside air to enter the room. This is useful in fall and spring as
a means of bringing in fresh outside air when using FAN ONLY . It can also
be used in the summer with the compressor in the Cooling Mode if you wish.
TO EXHAUST I NDOOR AIR – Move the lever to the Exhaust
position. This will allow stale air to be expelled to the outside of the dwelling. This is especially handy in the spring or fall when indoor air tends to get stale, or after a social gathering involving smokers, or to remove cooking odors.
BEST PERFORMANCE – Move the lever to the Re-Circulate Position
position
Auxiliary Fan Control
The electronic control also has the ability to control a 24 VAC relay to activate an auxiliary, or transfer fan. The outputs are listed as F1 and F2 on the interface connector (See page 32).
To connect the relay, simply wire one side of the relay to F1 and the other side to F2. Anytime that the fan runs, the terminals will send a 24 VAC signal to the relay. The relay must be 24 VAC, 50mA or less.
Note: The Desk Control, Auxiliary Fan relay and wires must be fi eld supplied.
FRR008
33
Page 35
COMPONENTS TESTING
FAN MOTOR
A single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A self-resetting overload is located inside the motor to protect against high temperature and high amperage conditions. (See Figure 23)
WARNING
ELECTRIC SHOCK HAZARD
Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.
BLOWER/FAN MOTOR - TEST
1 . Determine that capacitor is serviceable.
2. Disconnect fan motor wires from fan speed switch or system switch.
3. Apply “live” test cord probes on black wire and common terminal of capacitor. Motor should run at high speed.
4. Apply “live” test cord probes on red wire and common terminal of capacitor. Motor should run at low speed.
5. Apply “live” test cord probes on each of the remaining wires from the speed switc h or system switch to test
intermediate speeds. If the control is in the “MoneySaver” mode and the thermostat calls for cooling, the fan will start - then stop after approximately 2 minutes; then the fan and compressor will start together approximately 2 minutes later.
CAPACITORS
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before servicing. Discharge capacitor with a 20,000 Ohm 2 Watt resistor before handling.
Failure to do so may result in personal injury, or death.
Many motor capacitors are internally fused. Shorting the terminals will blow the fuse, ruining the capacitor. A 20,000 ohm 2 watt resistor can be used to discharge capacitors
safely. Remove wires from capacitor and place resistor across terminals. When checking a dual capacitor with a capacitor analyzer or ohmmeter, both sides must be tested.
Capacitor Check with Capacitor Analyzer
The capacitor analyzer will show whether the capacitor is “open” or “shorted.” It will tell whether the capacitor is within its micro farads rating and it will show whether the capacitor is operating at the proper power-factor percentage. The instrument will automatically discharge the capacitor when
the test switch is released.
Capacitor Connections
The starting winding of a motor can be damaged by a shorted and grounded running capacitor. This damage usually can be avoided by proper connection of the running capacitor terminals.
Figure 23 Blower/Fan Motor
From the supply line on a typical 230 volt circuit, a 115 volt potential exists from the “R” terminal to ground through a
possible short in the capacitor. However, from the “S” or start terminal, a much higher potential, possibly as high as 400 volts, exists because of the counter EMF generated in the start winding. Therefore, the possibility of capacitor failure is much greater when the identifi ed terminal is connected to the “S” or start terminal. The identifi ed terminal should always be connected to the supply line, or “R” terminal, never to the “S” terminal.
When connected properly, a shorted or grounded running capacitor will result in a direct short to ground from the “R”
terminal and will blow the line fuse. The motor protector will protect the main winding from excessive temperature.
Dual Rated Run Capacitor Hook-up
34
Page 36
COMPONENTS TESTING
HEATING ELEMENT
All heat pumps and electric heat models are equipped with a heating element with the exception of model YS10M10. The other “YS” and “ES” models are equipped with a 3.3 KW element. The “YM” and “EM” models are equipped with a 4.0 KW element. The “YL” and “EL” models are equipped with a 5.2 KW element.
Heating Element Sample
The heating element contains a fuse link and a heater limit switch. The fuse link is in series with the power supply and will open and interrupt the power when the temperature reaches 199°F or a short circuit occurs in the heating element. Once the fuse link separates, a new fuse link must be installed.
NOTE: Always replace with the exact replacement.
The heater element has a high limit control. This control is a bimetal thermostat mounted in the top of the heating element.
Should the fan motor fail or fi lter become clogged, the high limit control will open and interrupt power to the heater before reaching an unsafe temperature condition.
The control is designed to open at 110°F ±6°F. Test continuity below 110°F and for open above 110°F.
TESTING THE HEATING ELEMENT
WARNING
ELECTRIC SHOCK HAZARD
Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.
Testing of the elements can be made with an ohmmeter across the terminals after the connecting wires have been removed. A cold resistance reading of approximately 14.5 ohms for the 3.3 KW heater, 11.9 ohms for the 4.0 KW heater and 9.15 ohms for the 5.2 KW heater should be registered.
DRAIN PAN VALVE During the cooling mode of operation, condensate which collects in the drain pan is picked up by the con­denser fan blade and sprayed onto the condenser coil. This assists in cooling the refrigerant plus evaporating the water.
During the heating mode of operation, it is necessary that water be removed to prevent it from freezing during cold outside temperatures. This could cause the con­denser fan blade to freeze in the accumulated water and prevent it from turning.
To provide a means of draining this water, a bellows type drain valve is installed over a drain opening in the base pan.
This valve is temperature sensitive and will open when the outside temperature reaches 40°F. The valve will close gradually as the temperature rises above 40°F to fully close at 60°F.
HEATING ELEMENT (Heat Pump Models) The heating element for the “Y” model is energized by an outdoor thermistor via the electronic control board. The outdoor defrost thermistor is adjusted at a predetermined temperature to bring on the heating element and turn off the compressor. The room
Bellows Assembly Drain Pan Valve
35
Page 37
REFRIGERATION SEQUENCE OF OPERATION
A good understanding of the basic operation of the refrigeration system is essential for the service technician. Without this understanding, accurate troubleshooting of refrigeration system problems will be more diffi cult and time consuming, if not (in some cases) entirely impossible. The refrigeration system uses four basic principles (laws) in its operation they are as follows:
1. “Heat always fl ows from a warmer body to a cooler body.”
2. “Heat must be added to or removed from a substance before a change in state can occur”
3. “Flow is always from a higher pressure area to a lower pressure area.”
4. “The temperature at which a liquid or gas changes state
is dependent upon the pressure.”
The refrigeration cycle begins at the compressor. Starting the compressor creates a low pressure in the suction line which draws refrigerant gas (vapor) into the compressor. The compressor then “compresses” this refrigerant, raising its pressure and its (heat intensity) temperature.
The refrigerant leaves the compressor through the discharge Line as a hot High pressure gas (vapor). The refrigerant enters the condenser coil where it gives up some of its heat. The condenser fan moving air across the coil’s fi nned surface facilitates the transfer of heat from the refrigerant to the relatively cooler outdoor air.
When a suffi cient quantity of heat has been removed from the refrigerant gas (vapor), the refrigerant will “condense” (i.e. change to a liquid). Once the refrigerant has been condensed (changed) to a liquid it is cooled even further by the air that continues to fl ow across the condenser coil.
The RAC design determines at exactly what point (in the condenser) the change of state (i.e. gas to a liquid) takes place. In all cases, however, the refrigerant must be totally condensed (changed) to a Liquid before leaving the condenser coil.
The refrigerant leaves the condenser Coil through the liquid line as a warm high pressure liquid. It next will pass through the refrigerant drier (if so equipped). It is the function of the drier to trap any moisture present in the system, contaminants, and large particulate matter.
The liquid refrigerant next enters the metering device. The metering device is a capillary tube. The purpose of the metering device is to “meter” (i.e. control or measure) the quantity of refrigerant entering the evaporator coil.
In the case of the capillary tube this is accomplished (by design) through size (and length) of device, and the pressure difference present across the device.
Since the evaporator coil is under a lower pressure (due to the suction created by the compressor) than the liquid line, the liquid refrigerant leaves the metering device entering the evaporator coil. As it enters the evaporator coil, the larger area and lower pressure allows the refrigerant to expand and lower its temperature (heat intensity). This expansion is often referred to as “boiling”. Since the unit’s blower is moving indoor air across the fi nned surface of the evaporator coil, the expanding refrigerant absorbs some of that heat. This results in a lowering of the indoor air temperature, hence the “cooling” effect.
The expansion and absorbing of heat cause the liquid refrigerant to evaporate (i.e. change to a gas). Once the refrigerant has been evaporated (changed to a gas), it is heated even further by the air that continues to fl ow across the evaporator coil.
The particular system design determines at exactly what point (in the evaporator) the change of state (i.e. liquid to a gas) takes place. In all cases, however, the refrigerant must be totally evaporated (changed) to a gas before leaving the evaporator coil.
The low pressure (suction) created by the compressor causes the refrigerant to leave the evaporator through the suction line as a cool low pressure vapor. The refrigerant then returns to the compressor, where the cycle is repeated.
36
Suction Line
Evaporator Coil
Metering Device
Refrigerant Strainer
Discharge Line
Condenser Coil
Compressor
Refrigerant Drier
Liquid Line
Page 38
R-410A SEALED SYSTEM REPAIR CONSIDERATIONS
WARNING
Refrigeration system under high pressure
Do not puncture, heat, expose to fl ame or incinerate. Only certifi ed refrigeration technicians should
service this equipment. R410A systems operate at higher pressures than
R22 equipment. Appropriate safe service and handling practicces must be used.
Only use gauge sets designed for use with R410A. Do not use standard R22 gauge sets.
The following is a list of important considerations when working with R-410A equipment
R-410A pressure is approximately 60% higher than R-22 pressure.
R-410A cylinders must not be allowed to exceed 125 F, they may leak or rupture.
R-410A must never be pressurized with a mixture of air, it may become fl ammable.
Servicing equipment and components must be specifi cally designed for use with R-410A and dedicated to prevent contamination.
Manifold sets must be equipped with gauges capable of reading 750 psig (high side) and 200 psig (low side), with a 500-psig low-side retard.
Gauge hoses must have a minimum 750-psig service pressure rating
Recovery cylinders must have a minimum service pressure rating of 400 psig, (DOT 4BA400 and DOT BW400 approved cylinders).
POE (Polyol-Ester) lubricants must be used with R-410A equipment.
To prevent moisture absorption and lubricant contamination, do not leave the refrigeration system open to the atmosphere longer than 1 hour.
Weigh-in the refrigerant charge into the high side of the system.
Introduce liquid refrigerant charge into the high side of the system.
For low side pressure charging of R-410A, use a charging adaptor.
Use Friedrich approved R-410A fi lter dryers only.
37
Page 39
R-410A SEALED REFRIGERATION SYSTEM REPAIRS
IMPORTANT
SEALED SYSTEM REPAIRS TO COOL-ONLY MODELS REQUIRE THE INSTALLATION OF A LIQUID LINE DRIER.
EQUIPMENT REQUIRED:
1. Voltmeter
2. Ammeter
3. Ohmmeter
9. High Pressure Gauge - (0 to 750 lbs.)
10. Low Pressure Gauge - (-30 to 200 lbs.)
11. Vacuum Gauge - (0 - 1000 microns)
4. E.P.A. Approved Refrigerant Recovery System
5. Vacuum Pump (capable of 200 microns or less vacuum.)
6. Acetylene Welder
7. Electronic Halogen Leak Detector capable of detecting HFC (Hydrofl uorocarbon) refrigerants.
8. Accurate refrigerant charge measuring device such as:
a. Balance Scales - 1/2 oz. accuracy
b. Charging Board - 1/2 oz. accuracy
WARNING
RISK OF ELECTRIC SHOCK
Unplug and/or disconnect all electrical power to the unit before performing inspections, maintenances or service.
Failure to do so could result in electric shock, serious injury or death.
WARNING
HIGH PRESSURE HAZARD
Sealed Refrigeration System contains refrigerant and oil under high pressure.
Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.
Failure to follow these procedures could result in serious injury or death.
12. Facilities for fl owing nitrogen through refrigeration tubing during all brazing processes.
EQUIPMENT MUST BE CAPABLE OF:
1. Recovering refrigerant to EPA required levels.
2. Evacuation from both the high side and low side of the system simultaneously.
3. Introducing refrigerant charge into high side of the system.
4. Accurately weighing the refrigerant charge introduced into the system.
Proper refrigerant charge is essential to proper unit operation. Operating a unit with an improper refrigerant charge will result in reduced performance (capacity) and/or effi ciency. Accordingly, the use of proper charging methods during servicing will insure that the unit is functioning as designed and that its compressor will not be damaged.
Too much refrigerant (overcharge) in the system is just as bad (if not worse) than not enough refrigerant (undercharge). They both can be the source of certain compressor failures if they remain uncorrected for any period of time. Quite often, other problems (such as low air fl ow across evaporator, etc.) are misdiagnosed as refrigerant charge problems. The refrigerant circuit diagnosis chart will assist you in properly diagnosing these systems.
An overcharged unit will at times return liquid refrigerant (slugging) back to the suction side of the compressor eventually causing a mechanical failure within the compressor. This mechanical failure can manifest itself as valve failure, bearing failure, and/or other mechanical failure. The specifi c type of failure will be infl uenced by the amount of liquid being returned, and the length of time the slugging continues.
Refrigerant Charging
NOTE: Because the RAC system is a sealed system, service
process tubes will have to be installed. First install a line tap and remove refrigerant from system. Make necessary sealed system repairs and vacuum system. Crimp process tube line and solder end shut. Do not leave a service valve in the sealed system.
38
Not enough refrigerant (undercharge) on the other hand, will cause the temperature of the suction gas to increase to the point where it does not provide suffi cient cooling for the compressor motor. When this occurs, the motor winding temperature will increase causing the motor to overheat and possibly cycle open the compressor overload protector. Continued overheating of the motor windings and/or cycling of the overload will eventually lead to compressor motor or overload failure.
Page 40
Method Of Charging / Repairs
The acceptable method for charging the WallMaster system is the Weighed in Charge Method. The weighed in charge method is applicable to all units. It is the preferred method to use, as it is the most accurate.
The weighed in method should always be used whenever a charge is removed from a unit such as for a leak repair, compressor replacement, or when there is no refrigerant charge left in the unit. To charge by this method, requires the following steps:
1. Install a piercing valve to remove refrigerant from the sealedsystem. (Piercing valve must be removed from the system before recharging.)
2. Recover Refrigerant in accordance with EPA regulations.
WARNING
BURN HAZARD
Proper safety procedures must be followed, and proper protective clothing must be worn when working with a torch.
Failure to follow these procedures could result in moderate or serious injury.
3. Install a process tube to sealed system.
CAUTION
FREEZE HAZARD
Proper safety procedures must be followed, and proper protective clothing must be worn when working with liquid refrigerant.
Failure to follow these procedures could result in minor to moderate injury.
4. Make necessary repairs to system.
5. Evacuate system to 200 microns or less.
6. Weigh in refrigerant with the property quantity of R-410A refrigerant.
7. Start unit, and verify performance.
WARNING
BURN HAZARD
Proper safety procedures must be followed, and proper protective clothing must be worn when working with a torch.
Failure to follow these procedures could result in moderate or serious injury.
8. Crimp the process tube and solder the end shut.
39
Page 41
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before service or installation.
WARNING
HIGH PRESSURE HAZARD
Sealed Refrigeration System contains refrigerant and oil under high pressure.
Extreme care must be used, if it becomes necessary to work on equipment with power applied.
Failure to do so could result in serious injury or death.
Undercharged Refrigerant Systems
An undercharged system will result in poor performance (low pressures, etc.) in both the heating and cooling cycle.
Whenever you service a unit with an undercharge of refrigerant, always suspect a leak. The leak must be repaired before charging the unit.
To check for an undercharged system, turn the unit on, allow the compressor to run long enough to establish working pressures in the system (15 to 20 minutes).
During the cooling cycle you can listen carefully at the exit of the metering device into the evaporator; an intermittent hissing and gurgling sound indicates a low refrigerant charge. Intermittent frosting and thawing of the evaporator is another indication of a low charge, however, frosting and thawing can also be caused by insuffi cient air over the evaporator.
Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.
Failure to follow these procedures could result in serious injury or death.
A check of the amperage drawn by the compressor motor should show a lower reading. (Check the Unit Specifi cation.) After the unit has run 10 to 15 minutes, check the gauge pressures. Gauges connected to system with an undercharge will have low head pressures and substantially low suction pressures.
Checks for an undercharged system can be made at the compressor. If the compressor seems quieter than normal, it is an indication of a low refrigerant charge.
Overcharged Refrigerant Systems
Compressor amps will be near normal or higher. Noncondensables can also cause these symptoms. To confi rm, remove some of the charge, if conditions improve, system may be overcharged. If conditions don’t improve, Noncondensables are indicated.
Whenever an overcharged system is indicated, always make sure that the problem is not caused by air fl ow problems. Improper air fl ow over the evaporator coil may indicate some of the same symptoms as an over charged system.
An overcharge can cause the compressor to fail, since it would be “slugged” with liquid refrigerant.
The charge for any system is critical. When the compressor is noisy, suspect an overcharge, when you are sure that the air quantity over the evaporator coil is correct. Icing
of the evaporator will not be encountered because the refrigerant will boil later if at all. Gauges connected to system will usually have higher head pressure (depending upon amount of over charge). Suction pressure should be slightly higher.
40
Page 42
Restricted Refrigerant System
Troubleshooting a restricted refrigerant system can be diffi cult. The following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions.
A partial restriction allows some of the refrigerant to circulate through the system.
With a complete restriction there is no circulation of refrigerant in the system.
Restricted refrigerant systems display the same symptoms as a “low-charge condition.”
When the unit is shut off, the gauges may equalize very slowly.
Gauges connected to a completely restricted system will run in a deep vacuum. When the unit is shut off, the gauges
will not equalize at all.
A quick check for either condition begins at the evaporator. With a partial restriction, there may be gurgling sounds
at the metering device entrance to the evaporator. The evaporator in a partial restriction could be partially frosted or have an ice ball close to the entrance of the metering device. Frost may continue on the suction line back to the compressor.
Often a partial restriction of any type can be found by feel, as there is a temperature difference from one side of the restriction to the other.
With a complete restriction, there will be no sound at the metering device entrance. An amperage check of the compressor with a partial restriction may show normal current when compared to the unit specifi cation. With a complete restriction the current drawn may be considerably less than normal, as the compressor is running in a deep vacuum (no load.) Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored there.
The following conditions are based primarily on a system in the cooling mode.
41
Page 43
HERMETIC COMPONENTS CHECK
WARNING
BURN HAZARD
Proper safety procedures must be followed, and proper protective clothing must be worn when working with a torch.
Failure to follow these procedures could result in moderate or serious injury.
METERING DEVICE
Capillary Tube Systems
WARNING
CUT/SEVER HAZARD
Be careful with the sharp edges and corners. Wear protective clothing and gloves, etc.
Failure to do so could result in serious injury.
All units are equipped with capillary tube metering devices.
Checking for restricted capillary tubes.
1. Connect pressure gauges to unit.
2. Start the unit in the cooling mode. If after a few minutes of operation the pressures are normal, the check valve
and the cooling capillary are not restricted.
CHECK VALVE
A unique two-way check valve is used on the reverse cycle heat pumps. It is pressure operated and used to direct the ow of refrigerant through a single fi lter drier and to the proper capillary tube during either the heating or cooling cycle.
One-way Check Valve (Heat Pump Models)
NOTE: The slide (check) inside the valve is made of tefl on. Should it become necessary to replace the check valve, place a wet cloth around the valve to prevent overheating during the brazing operation.
3. Switch the unit to the heating mode and observe the gauge readings after a few minutes running time. If the system pressure is lower than normal, the heating capillary is restricted.
4. If the operating pressures are lower than normal in both
the heating and cooling mode, the cooling capillary is restricted.
In the heating mode of operation, high pressure refrigerant enters the check valve from the opposite direction, closing the port (liquid line) to the outdoor coil. The fl ow path of the refrigerant is then through the fi lter drier and heating capillary to the outdoor coil.
Failure of the slide in the check valve to seat properly in either mode of operation will cause fl ooding of the cooling coil. This is due to the refrigerant bypassing the heating or cooling capillary tube and entering the liquid line.
COOLING MODE In the cooling mode of operation, liquid refrigerant from condenser (liquid line) enters the cooling check valve forcing the heating check valve shut. The liquid refrigerant is directed into the liquid dryer after which the refrigerant is metered through cooling capillary tubes to evaporator. (Note: liquid refrigerant will also be directed through the heating capillary tubes in a continuous loop during the cooling mode).
CHECK VALVE OPERATION
In the cooling mode of operation, high pressure liquid enters the check valve forcing the slide to close the opposite port (liquid line) to the indoor coil. Refer to refrigerant fl ow chart. This directs the refrigerant through the fi lter drier and cooling capillary tube to the indoor coil.
42
HEATING MODE
In the heating mode of operation, liquid refrigerant from the indoor coil enters the heating check valve forcing the cooling check valve shut. The liquid refrigerant is directed into the liquid dryer after which the refrigerant is metered through the heating capillary tubes to outdoor coils. (Note: liquid refrigerant will also be directed through the cooling capillary tubes in a continuous loop during the heating mode).
Page 44
REVERSING VALVE DESCRIPTION/OPERATION
WARNING
ELECTRIC SHOCK HAZARD
Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.
The Reversing Valve controls the direction of refrigerant ow to the indoor and outdoor coils. It consists of a pressure-operated, main valve and a pilot valve actuated by a solenoid plunger. The solenoid is energized during the heating cycle only. The reversing valves used in the RAC system is a 2-position, 4-way valve.
The single tube on one side of the main valve body is the high-pressure inlet to the valve from the compressor. The center tube on the opposite side is connected to the low pressure (suction) side of the system. The other two are connected to the indoor and outdoor coils. Small capillary tubes connect each end of the main valve cylinder to the
“A” and “B” ports of the pilot valve. A third capillary is a common return line from these ports to the suction tube on the main valve body. Four-way reversing valves also have a capillary tube from the compressor discharge tube to the pilot valve.
The piston assembly in the main valve can only be shifted by the pressure differential between the high and low sides of the system. The pilot section of the valve opens and closes ports for the small capillary tubes to the main valve to cause it to shift.
NOTE: System operating pressures must be near normal before valve can shift.
43
Page 45
TESTING THE REVERSING VALVE SOLENOID COIL
WARNING
ELECTRIC SHOCK HAZARD
Unplug and/or disconnect all electrical power to the unit before performing inspections, maintenances or service.
Failure to do so could result in electric shock, serious injury or death.
The solenoid coil is an electromagnetic type coil mounted on the reversing valve and is energized during the operation of the compressor in the heating cycle.
1. Turn off high voltage electrical power to unit.
2. Unplug line voltage lead from reversing valve coil.
3. Check for electrical continuity through the coil. If you do not have continuity replace the coil.
4. Check from each lead of coil to the copper liquid line as it leaves the unit or the ground lug. There should be no continuity between either of the coil leads and ground; if there is, coil is grounded and must be replaced.
5. If coil tests okay, reconnect the electrical leads.
6. Make sure coil has been assembled correctly.
NOTE: Do not start unit with solenoid coil removed from valve, or do not remove coil after unit is in operation. This will cause the coil to burn out.
Should the valve fail to shift from coooling to heating, block the air fl ow through the outdoor coil and allow the discharge pressure to build in the system. Then switch the system from heating to cooling.
If the valve is stuck in the heating position, block the air ow through the indoor coil and allow discharge pressure to build in the system. Then switch the system from heating to cooling.
Should the valve fail to shift in either position after increasing the discharge pressure, replace the valve.
Dented or damaged valve body or capillary tubes can prevent the main slide in the valve body from shifting.
If you determing this is the problem, replace the reversing valve.
After all of the previous inspections and checks have been made and determined correct, then perform the “Touch Test” on the reversing valve.
CHECKING THE REVERSING VALVE
NOTE: You must have normal operating pressures before the reversing valve can shift.
WARNING
HIGH PRESSURE HAZARD
Sealed Refrigeration System contains refrigerant and oil under high pressure.
Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.
Failure to follow these procedures could result in serious injury or death.
Check the operation of the valve by starting the system and switching the operation from “Cooling” to “Heating” and then back to “Cooling”. Do not hammer on valve.
Occasionally, the reversing valve may stick in the heating or cooling position or in the mid-position.
When sluggish or stuck in the mid-position, part of the discharge gas from the compressor is directed back to the suction side, resulting in excessively high suction pressure.
Reversing Valve in Heating Mode
44
Page 46
Touch Test in Heating/Cooling Cycle
WARNING
BURN HAZARD
Certain unit components operate at temperatures hot enough to cause burns.
Proper safety procedures must be followed, and proper protective clothing must be worn.
Failure to follow these procedures could result in minor to moderate injury.
6. Protect new valve body from heat while brazing with plastic heat sink (Thermo Trap) or wrap valve body with wet rag.
7. Fit all lines into new valve and braze lines into new valve.
WARNING
EXPLOSION HAZARD
The use of nitrogen requires a pressure regulator. Follow all safety procedures and wear protective safety clothing etc.
The only definite indications that the slide is in the mid­position is if all three tubes on the suction side of the valve are hot after a few minutes of running time.
NOTE: A condition other than those illustrated above, and on Page 44, indicate that the reversing valve is not shifting properly. Both tubes shown as hot or cool must be the same corresponding temperature.
Procedure For Changing Reversing Valve
WARNING
HIGH PRESSURE HAZARD
Sealed Refrigeration System contains refrigerant and oil under high pressure.
Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.
Failure to follow these procedures could result in serious injury or death.
NOTICE
FIRE HAZARD
The use of a torch requires extreme care and proper judgment. Follow all safety recommended precautions and protect surrounding areas with fi re proof materials. Have a fi re extinguisher readily available. Failure to follow this notice could result in moderate to serious property damage.
Failure to follow proper safety procedures could result in serious injury or death.
8. Pressurize sealed system with a combination of R-410A and nitrogen and check for leaks, using a suitable leak detector. Recover refrigerant per EPA guidelines.
9. Once the sealed system is leak free, install solenoid coil
on new valve and charge the sealed system by weighing in the proper amount and type of refrigerant as shown on rating plate. Crimp the process tubes and solder the ends shut. Do not leave Schrader or piercing valves in the sealed system.
NOTE: When brazing a reversing valve into the system, it is of extreme importance that the temperature of the valve does not exceed 250
Wrap the reversing valve with a large rag saturated with water. “Re-wet” the rag and thoroughly cool the valve after each brazing operation of the four joints involved.
The wet rag around the reversing valve will eliminate conduction of heat to the valve body when brazing the line connection.
°F at any time.
1. Install Process Tubes. Recover refrigerant from sealed system. PROPER HANDLING OF RECOVERED REFRIGERANT ACCORDING TO EPA REGULATIONS IS REQUIRED.
2. Remove solenoid coil from reversing valve. If coil is to be reused, protect from heat while changing valve.
3. Unbraze all lines from reversing valve.
4. Clean all excess braze from all tubing so that they will slip into fi ttings on new valve.
5. Remove solenoid coil from new valve.
45
Page 47
COMPRESSOR CHECKS
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before service or installation. Extreme care must be used, if it becomes necessary to work on equipment with power applied.
Heat generated within the compressor shell, usually due to recycling of the motor, is slow to dissipate. It may take anywhere from a few minutes to several hours for the overload to reset.
Checking the Overloads
Failure to do so could result in serious injury or death.
Locked Rotor Voltage (L.R.V.) Test
Locked rotor voltage (L.R.V.) is the actual voltage available at the compressor under a stalled condition.
Single Phase Connections
Disconnect power from unit. Using a voltmeter, attach one lead of the meter to the run “R” terminal on the compressor and the other lead to the common “C” terminal of the com­pressor. Restore power to unit.
Determine L.R.V.
Start the compressor with the volt meter attached; then stop the unit. Attempt to restart the compressor within a couple of seconds and immediately read the voltage on the meter. The compressor under these conditions will not start and will usually kick out on overload within a few seconds since the pressures in the system will not have had time to equalize. Voltage should be at or above minimum voltage of 197 VAC, as specifi ed on the rating plate. If less than minimum, check for cause of inadequate power supply; i.e., incorrect wire size, loose electrical connections, etc.
Amperage (L.R.A.) Test
The running amperage of the compressor is the most important of these readings. A running amperage higher than that indicated in the performance data indicates that a problem exists mechanically or electrically.
Single Phase Running and L.R.A. Test
NOTE: Consult the speci cation and performance section
for running amperage. The L.R.A. can also be found on the rating plate.
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before service or installation. Extreme care must be used, if it becomes necessary to work on equipment with power applied.
Failure to do so could result in serious injury or death.
WARNING
BURN HAZARD
Certain unit components operate at temperatures hot enough to cause burns.
Proper safety procedures must be followed, and proper protective clothing must be worn.
Failure to follow this warning could result in moderate to serious injury.
External Overloads
With power off, remove the leads from compressor terminals. If the compressor is hot, allow the overload to cool before starting check. Using an ohmmeter, test continuity across the terminals of the external overload. If you do not have continuity; this indicates that the overload is open and must be replaced.
Interrnal Overloads
Some model compressors are equipped with an internal overload. The overload is embedded in the motor windings to sense the winding temperature and/or current draw. The overload is connected in series with the common motor terminal.
Select the proper amperage scale and clamp the meter probe around the wire to the “C” terminal of the compressor.
Turn on the unit and read the running amperage on the meter. If the compressor does not start, the reading will indicate the locked rotor amperage (L.R.A.).
Overloads
The compressor is equipped with either an external or internal overload which senses both motor amperage and winding temperature. High motor temperature or amperage heats the overload causing it to open, breaking the common circuit within the compressor.
46
Should the internal temperature and/or current draw become excessive, the contacts in the overload will open, turning off the compressor. The overload will automatically reset, but may require several hours before the heat is dissipated.
Checking the Internal Overload
1. With no power to unit, remove the leads from the compressor terminals.
2. Using an ohmmeter, test continuity between terminals C-S and C-R. If no continuity, the compressor overload is open and the compressor must be replaced.
Page 48
Single Phase Resistance Test
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before service or installation. Extreme care must be used, if it becomes necessary to work on equipment with power applied.
Failure to do so could result in serious injury or death.
the ohmmeter on the lowest scale (R x 1).
from terminals common to run (“C” to “R”).
Add values “C” to “S” and “C” to “R” together and
ur ot trats morf ecnatsiser kcehc Resistance “S” to “R” should equal the total of “C” to “S” and “C” to “R.”
In a single phase PSC compressor motor, the highest
ht ot trats eht morf si ecnatsiser tsehgih txen ehT .)”R“ common connections (“S” to “C”). The lowest resistance is from the run to common. (“C” to “R”) Before replacing a compressor, check to be sure it is defective.
GROUND TEST
Use an ohmmeter set on its highest scale. Touch one lead to the compressor body (clean point of contact as a good connection is a must) and the other probe in turn to each compressor terminal. If a reading is obtained the compressor is grounded and must be replaced.
Check the complete electrical system to the compressor and compressor internal electrical system, check to be certain that compressor is not out on internal overload.
Many compressor failures are caused by the following conditions:
1. Improper air ow over the evaporator.
2. Overcharged refrigerant system causing liquid to be returned to the compressor.
3. Restricted refrigerant system.
4. Lack of lubrication.
tes dna slanimret rosserpmoc eht morf sdael eht evomeR
nommoc slanimret morf retemmho eht fo sdael eht hcuoT retemmho eht fo sdael eht hcuot ,txeN .)”S“ ot ”C“( trats ot
.)”R“ ot ”S“( slanimret n
ot ”S“( snoitcennoc nur eht ot trats eht morf eb lliw eulav e
5. Liquid refrigerant returning to compressor causing oil to be washed out of bearings.
6. Noncondensables such as air and moisture in
the system. Moisture is extremely destructive to a refrigerant system.
7. Capacitor (see page 34).
CHECKING COMPRESSOR EFFICIENCY
The reason for compressor inefciency is normally due to broken or damaged suction and/or discharge valves, reducing the ability of the compressor to pump refrigerant gas.
WARNING
HIGH PRESSURE HAZARD
Sealed Refrigeration System contains refrigerant and oil under high pressure.
Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.
Failure to follow these procedures could result in serious injury or death.
Complete evaluation of the system must be made whenever you suspect the compressor is defective. If the compressor has been operating for sometime, a careful examination must be made to determine why the compressor failed.
This condition can be checked as follows:
1. Install a piercing valve on the suction and discharge or liquid process tube.
2. Attach gauges to the high and low sides of the system.
3. Start the system and run a “cooling or heating perfor mance test.” If test shows:
A. Below normal high side pressure B. Above normal low side pressure C. Low temperature difference across coil
The compressor valves are faulty - replace the compressor.
-
47
Page 49
COMPRESSOR REPLACEMENT
Recommended procedure for compressor replacement
WARNING
RISK OF ELECTRIC SHOCK
Unplug and/or disconnect all electrical power to the unit before performing inspections, maintenances or service.
Failure to do so could result in electric shock, serious injury or death.
1. Be certain to perform all necessary electrical and refrigeration tests to be sure the compressor is actually defective before replacing.
WARNING
HIGH PRESSURE HAZARD
Sealed Refrigeration System contains refrigerant and oil under high pressure.
Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.
Failure to follow these procedures could result in serious injury or death.
2. Recover all refrigerant from the system though the process tubes. PROPER HANDLING OF
RECOVERED REFRIGERANT ACCORDING TO EPA REGULATIONS IS REQUIRED. Do not use
gauge manifold for this purpose if there has been a burnout. You will contaminate your manifold and hoses. Use a Schrader valve adapter and copper tubing for burnout failures.
WARNING
HIGH TEMPERATURES
Extreme care, proper judgment and all safety procedures must be followed when testing, troubleshooting, handling or working around unit while in operation with high temperature components. Wear protective safety aids such as: gloves, clothing etc.
Failure to do so could result in serious burn injury.
3. After all refrigerant has been recovered, disconnect suction and discharge lines from the compressor and remove compressor. Be certain to have both suction and discharge process tubes open to atmosphere.
4. Carefully pour a small amount of oil from the suction stub of the defective compressor into a clean
container.
5. Using an acid test kit (one shot or conventional kit), test the oil for acid content according to the instructions with the kit.
6. If any evidence of a burnout is found, no matter how slight, the system will need to be cleaned up following proper procedures.
7. Install the replacement compressor.
WARNING
EXPLOSION HAZARD
The use of nitrogen requires a pressure regulator. Follow all safety procedures and wear protective safety clothing etc.
Failure to follow proper safety procedures result in serious injury or death.
8. Pressurize with a combination of R-410A and nitrogen
and leak test all connections with an electronic or Halide leak detector. Recover refrigerant and repair any leaks found.
Repeat Step 8 to insure no more leaks are present.
9. Evacuate the system with a good vacuum pump capable of a fi nal vacuum of 200 microns or less. The system should be evacuated through both liquid line and suction line gauge ports. While the unit is being evacuated, seal all openings on the defective compressor. Compressor manufacturers will void warranties on units received not properly sealed. Do not distort the manufacturers tube connections.
CAUTION
FREEZE HAZARD
Proper safety procedures must be followed, and proper protective clothing must be worn when working with liquid refrigerant.
NOTICE
FIRE HAZARD
The use of a torch requires extreme care and proper judgment. Follow all safety recommended precautions and protect surrounding areas with fi re proof materials. Have a fi re extinguisher readily available. Failure to follow this notice could result in moderate to serious property damage.
48
Failure to follow these procedures could result in minor to moderate injury.
10. Recharge the system with the correct amount of refrigerant. The proper refrigerant charge will be found on the unit rating plate. The use of an accurate
measuring device, such as a charging cylinder, electronic scales or similar device is necessary.
Page 50
SPECIAL PROCEDURE IN THE CASE OF MOTOR COMPRESSOR BURNOUT
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before service or installation.
Failure to do so may result in personal injury, or death.
WARNING
HIGH PRESSURE HAZARD
Sealed Refrigeration System contains refrigerant and oil under high pressure.
Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.
Failure to follow these procedures could result in serious injury or death.
WARNING
EXPLOSION HAZARD
The use of nitrogen requires a pressure regulator. Follow all safety procedures and wear protective safety clothing etc.
Failure to follow proper safety procedures result in serious injury or death.
1.
Recover all refrigerant and oil from the system.
Remove compressor, capillary tube and filter drier
2. from the system.
3.
Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent. Use approved ushing agent to remove all contamination from system. Inspect suction and discharge line for carbon deposits. Remove and clean if necessary. Ensure all acid is neutralized.
Reassemble the system, including new drier strainer
4. and capillary tube.
5.
Proceed with step 8-10 on previous page.
ROTARY AND SCROLL COMPRESSOR SPECIAL TROUBLESHOOTING AND SERVICE
Basically, troubleshooting and servicing rotary compres­sors is the same as on the reciprocating compressor with only one main exception:
NEVER, under any circumstances, liquid charge a rotary­compressor through the LOW side. Doing so would cause permanent damage to the new compressor.
49
Page 51
ROUTINE MAINTENANCE
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before inspections, maintenances, or service.
Extreme care must be used, if it becomes necessary to work on equipment with power applied.
Failure to do so could result in serious injury or death.
COILS AND BASE PAN
The indoor coil (evaporator coil), the outdoor coil (condenser coil) and base pan should be inspected periodically (yearly or bi-yearly) and cleaned of all debris (lint, dirt, leaves, paper, etc.). Clean the coils and base pan with a soft brush and compressed air or vacuum. If using a pressure washer, be careful not to bend the aluminium fi n pack. Use a sweeping up and down motion in the direction of the vertical aluminum fi n pack when pressure cleaning coils. Cover all electrical components to protect them from water or spray. Allow the unit to dry thoroughly before reinstalling it in the sleeve.
WARNING
EXCESSIVE WEIGHT HAZARD
Use two people to lift or carry the unit, and wear proper protective clothing.
Failure to do so may result in personal injury.
WARNING
CUT/SEVER HAZARD
Be careful with the sharp edges and corners. Wear protective clothing and gloves, etc.
Failure to do so could result in serious injury.
NOTICE
Units are to be inspected and serviced by qualifi ed service personnel only. Use proper protection on surrounding property. Failure to follow this notice could result in moderate or serious property damage.
NOTICE
Do not use a caustic coil cleaning agent on coils or base pan. Use a biodegradable cleaning agent and degreaser, to prevent damage to the coil and/or base pan.
NOTE: .napesabrosliocnotnegagninaelclioccitsuacaesutonoD
Use a biodegradable cleaning agent and degreaser. The use of harsh c leaning mater ials may lead to deterioration o f the
NOTE: It is e xtremely i mportant t o insure that none of the electrical
and/or electronic parts of the unit get wet. B e sure to cover all electrical components to protect them from water or spray.
BLOWER WHEEL / HOUSING / CONDENSER FAN / SHROUD
Inspect the indoor blower and its housing, evaporator blade, condenser fan blade and condenser shroud periodically (yearly or bi-yearly) and clean of all debris (lint, dirt, mold, fungus, etc.). Clean the blower housing area and blower wheel with an antibacterial / antifungal cleaner. Use a biodegradable cleaning agent and degreaser on condenser fan and condenser shroud. Use warm or cold water when rinsing these items. Allow all items to dry thoroughly before reinstalling them.
ELECTRONIC / ELECTRICAL / MECHANICAL
Periodically (at least yearly or bi-yearly): inspect all control components: electronic, electrical and mechanical, as well as the power supply. Use proper testing instruments (voltmeter, ohmmeter, ammeter, wattmeter, etc.) to perform electrical tests. Use an air conditioning or refrigeration thermometer to check room, outdoor and coil operating temperatures.
AIR FILTER
The air fi lter should be inspected weekly and cleaned if needed by vacuuming with a dust attachment or by cleaning in the sink using warm water and a mild dishwashing detergent. Dry the fi lter thoroughly before reinstalling. Use caution as the coil surface can be sharp.
TO REMOVE, WASH AND REPLACE FILTER
Lower front panel. Use handle on fi lter to fl ex fi lter up and out of retainer. Remove fi lter from unit. Clean lter monthly or more frequently if needed. Refer to accessories section for fi lter options.
50
BLOWER/FAN MOTOR
The motor is permanently lubricated.
Page 52
ROUTINE MAINTENANCE (Continued)
NOTICE
Do not drill holes in the bottom of the drain pan or the underside of the unit. Not following this notice could result in damage to the unit or condensate water leaking inappropriately which could cause water damage to surrounding property.
SLEEVE / DRAIN
Inspect the sleeve and drain system periodically (at least yearly or bi-yearly) and clean of all obstructions and debris. Clean both areas with an antibacterial and antifungal cleaner. Rinse both items thoroughly with water and ensure that the drain outlets are operating correctly. Check the sealant around the sleeve and reseal areas as needed.
DECORATIVE FRONT COVER
Clean the front cover when needed. Use a mild detergent. Wash and rinse with warm water. Allow it to dry thoroughly before reinstalling it in the chassis.
The decorative front and the cabinet can be cleaned with warm water and a mild liquid detergent. Do NOT use solvents or hydrocarbon based cleaners such as acetone, naphtha, gasoline, benzene, etc.
Use a damp (not wet) cloth when cleaning the control area to prevent water from entering the unit, and possibly damaging the electronic control.
CLEARANCES
Inspect the surrounding area (inside and outside) to ensure that the unit’s clearances have not been compromised or altered.
Accumulator
Compressor
Outdoor Grille
Discharge Air
Fresh Air Vent
Reversing Valve
Evaporator Coil
Condenser Coil
Electronic Control
Board
Control Key Pad
Support Bar
Blower Wheel
Air Intake From
Sides and Bottom
Fan/Blower Motor
Base Pan
Sleeve
Air Intake Vents
Fan Blade
Control Key Pad
(User Interface)
Chassis Pull
Out Handle
51
Page 53
ROUTINE MAINTENANCE (Continued)
Standard Filter Cleaning Installation Instructions
STEP 1.
Figure 1
Remove the filter by grabbing it from its handle, lifting it up and swinging it out.
Figure 2
STEP 2. NOTE:
Figure 3
FILTER
FILTER GRIP
STEP 3. Swing the front frame open. Clean the front frame by washing
FILTER GRIP
HANDLE
Figure 4
A
TOP TAB
FRONT FRAME WITH STANDARD MESH FILTER
STEP 4.
STEP 5.
the inside of the front door.
NOTE:
the tab in the frame stops the handle from sliding in, sl3ide the
filter halfway up, tilt it towards the front of you, then gently slide
it up fully. Do not force the handle into the frame.
52
Page 54
ROUTINE MAINTENANCE (Continued)
After Maintenance/Repair Start-up Checklist and Notes
Inspect and ensure that all components and accessories have been
installed properly and that they have not been damaged during the installation progress.
Check the condensate water drain(s) to ensure that they are adequate
for the removal of condensate water, and that they meet the approval of the end user.
Ensure that all installation instructions concerning clearances around
the unit have been adhered to. Check to ensure that the unit air fi lter, indoor coil, and outdoor coil are free from any obstructions.
Ensure that the circuit breaker(s) or fuse(s) and supply circuit wire
size have been sized correctly. If the unit was supplied with a power supply cord, insure that it is stored properly.
Ensure that the entire installation is in compliance with all applicable
national and local codes and ordinances having jurisdiction.
Secure components and accessories, such as a decorative front
cover.
Start the unit and check for proper operation of all components in
each mode of operation.
Instruct the owner or operator of the units operation, and the
manufacturer's Routine Maintenance.
NOTE: A log for recording the dates of maintenance and/or service is
recommended.
Present the owner or operator of the equipment with the name,
address and telephone number of the Authorized Friedrich Warranty Service Company in the area for future reference if necessary.
Heat pumps operate differently
If your unit is a "Y", or heat pump model, there are some things that you will want to be aware of. Some functions of a heat pump differ from your unit when it is used for heating:
It is normal for ice to form on the outdoor coil of the heat pump. 1.
Moisture in the outside air, passing over the coil when very cold, will form ice.
If the outdoor temperature drops below 37° F (3° C), your heat 2.
pump will automatically turn on the electric resistance heat. When the temperature rises to 40° F (4° C), the compressor will resume the heat pump operation. If your unit is a 115 volt model (YS10), it is designed for use in warmer climates and does not have an electrical heat feature, and will not provide adequate heat below 37° F (2.8° C).
CONTROL PANEL BATTERY CHANGE PROCEDURE
Remove the grille, by loosening four (4) captive screws (See Figure 1). Remove one (1) screw on the battery retaining door (See Figure 2). Remove and replace the battery (CR2450). Reinstall the battery retaining door. Align the grille guide pins then tighten the four (4) captive screws. Before closing the grille panel door, check the fi lter. Clean or replace it as necessary.
Figure
Figure 1
NOTE: This is a warm weather appliance
The air conditioner is designed to cool in warm weather when the outside temperature is above 60° F (15.6° C) and below 115° F (46.1° C), so it won't cool a room if it is already cool outside. If you want to cool a room in the spring or fall, select the FAN ONLY air control to Fresh Air. This will bring in a supply of cooler outside air.
mode and set the Fresh Air/Exhaust
Condensation is normal
Air cond itio ners actu all y pum p the hea t an d hum idit y fro m you r ro om to the outside. Humidity becomes water, and your air conditioner will use most of the water to keep the outside coil cool. If there is excessive humidity, there may be excess water that will drip outside. This is normal operation.
Frosting
This usually occurs because of insuf cient airfl ow across the coils, a dirty lter, cool damp weather, or all of these. Set the SYSTEM mode to FAN
ONLY
and the frost will disappear. Setting the thermostat a little warmer
will probably prevent the frosting from recurring.
Noises
All air condition ers make some noise. Friedrich units are designed to oper ate as quietly as possible. An air conditioner mounted in a wall is quieter than one mounted in a window. It is important to ensure that the chassis seal gasket is properly installed (refer to installation instructions).
USE HAND TOOLS
DO NOT OVER TIGHTEN
1. USE HAND TOOLS WHEN INSTALLING AND REMOVING FRONT PANEL.
DO NOT OVERTIGHTEN SCREWS.
2. DISCONNECT POWER AND FOLLOW ALL LABELED WARNINGS WHEN FRONT PANEL IS REMOVED.
Figure
Figure 2
FRR010
Battery type: Lithium, 3 Volts, #CR2450
53
Page 55
Service and Assistance
Before calling for service, please check the “Troubleshooting Tips” section on pages 40 and 41. This may help you to fi nd the answer to your problem, avoid unnecessary service calls, and save you the cost of a service call if the problem is not due to the product itself. If you have checked the “Basic Troubleshooting” section and still need help, it is available as follows:
You can fi nd the n ame o f yo ur l oc al A uth or ize d Se rv ice P rov ider by v isit ing our web site at www.friedrich.com.
If you require further assistance
You can call the Customer Support Call Center at 1-800-541-6645.
Before calling, please make sure that you have the complete model and serial number, and date of purchase of your equipment available. By providing us with this information, we will be better able to assist you.
Our specialists are able to assist you with:
Speci cations and Features of our equipment.
Referrals to dealers, and distributors.
Use and Care Information.
Recommended maintenance procedures.
Installation information.
Referrals to Authorized Service Providers and Parts depots.
Available Accessories
DC-2 Drain Kit – Part No. 01900235
In some inst alla tion s, exce ss cond ensa te w ate r c aus ed by ext re mel y hum id conditions, may result in an undesirable water drip such as on a patio or over an entryway. MODEL DC-2 DRAIN KIT (Part No. 01900-235) can be installed to drain excess condensation to an alternate location.
Carbon Filter Kits
The kits vary depending on the chassis size (small, medium, large). Each kit contains three (3) fi lters.
WCFS – Carbon lter kit for small chassis models. WCFM – Carbon lter kit for medium chassis models. WCFL – Carbon lter kit for large chassis models.
Remote Wall Thermostats
RT4 – Digital wall thermostat hard wired with single speed fan. RT5 – Digital wall thermostat hard wired with a digital display, two fan speed
selection, fi lter check light, temperature limiting, status indicator light, room temperature offset, backlight and battery backup.
Window Installation Kits (Standard in Kühl Models without Heat)
KWIKS – For all ES and YS models. KWIKM – For all EM and YM models. KWIKL – For all EL and YL models.
See www.friedrich.com for additional accessories for your unit.
54
Page 56
ROOM AIR CONDITIONER UNIT PERFORMANCE TEST DATA SHEET
T
JOB NAME________________________________ TECHS NAME____________________________________
DATE: _______________ MODEL:_______________ SERIAL:________________ HOW IS ALL OF THE INSTALLATION? GOOD BAD
YES NO
____ ____ ____ ____ ____ ____ ____ ____
IS A C HAS SIS S E AL GAS KE T INT A LLE D ? IS THE FRESH/EXAUST AIR VENT OPEN? IS A FR IE DR IC H S LEE VE INS TALLED? IS A FR IE DRIC H OU T DO OR GR ILLE INS T ALLE D? IS MA INTE NANC E BE ING P E R FOR MED? ____ ____
If NO
is checked use back of sheet for explanation
ELECTRICAL:
LINE VOLTAGE (STATIC) --------- VOLTS START UP VOLTAGE --------- VOLTS AMPERAGE DRAW --------- AMPS (COOL) AMPERAGE DRAW --------- AMPS (HEAT) COMPRESSOR LOCKED ROTOR AMPS --------- AMPS AMPERAGE DRAW --------- AMPS
INDOOR TEMPE R ATUR ES:
INDOOR AMBIENT TEMPERATURE -------- F RELATIVE HUMIDITY (RH) INDOOR -------- %
DISCHARGE AIR TEMPERATURE (INDOOR) ---------- F --------- F RETURN AIR TEMPERATURE (INDOOR) ---------- F --------- F
C OO L HE AT
OUTDOOR TEMPERATURE :
OUTDOOR AMBIENT TEMPERATURE --------- F RH OUTDOOR --------- %
DISCHARGE AIR TEMPERATURE (OUTDOOR) --------- F ---------- F INTAKE AIR TEMPERATURE (OUTDOOR) --------- F ---------- F
APPLICATION USE ------------------------- ROOM (RESIDENTIAL OR COMMERCIAL)
COOLING OR HEATING
his is a ge neral guide. plea s e cons ult manua l J or M.
AREA W ---------- X L ----------- X H ----------- = SQ/CU/FT ------------
This is a general guide. Please consult manual J or M for exact load calculations.
55
Page 57
)
p
p
p
y
y
p
y
g
q
p
,
p
p
ERROR CODES AND ALARM STATUS
Error
Maintenance
Code
1Flash
2Flash
3Flash
4Flash
5Flash
6 Flash Outdoor Coil > (grater than) 175 F
7Flash
8Log Only
9Log Only
10 Log Only Room Freeze Protection
11 On WallStat Problem or Connection Issue
12 Flash Discharge Air > (greater than) 185 F
ICON
Front Panel Button Stuck For More Than 20 Seconds
Input Voltage Out of Specification (103
- 127 / 187 - 253 Indoor Temperature Sensor is Open or Shorted Indoor Coil Temperature Sensor is
en or Shorted
O
Outdoor Coil Temperature Sensor is Open or Shorted
Indoor Coil < (less than) 30 F for 2 consecutive minutes Unit Cycles > (grater than) 9 Times per hour Unit Cycles < (less than) 3 Times per Hour
Problem Control Board's Action
Continue to monitor for "OPEN" (Unstuck) switch. Do not process switch
ENSURE FRONT COVER DOES NOT DEPRESS BUTTONS
input.
Stop.Open all relays until voltage is back within specs. Resume operation
Set temp to 75°F in COOLING or 68°F in HEATING. Unit continues to o
erate Control Board sets temp to 40°F. Override sensor. Unit Continues to operate. Sets temp to 20°F. Override sensor. Continue operation. Use Elec Heat if available for HEATING. If not available use HEAT PUMP if outdoor temp allows. Shut down for 5 min. Resume operation for 3 min. Continues to monitor. If test fails 3 times, the severity is increased and the unit operation is locked out. Turn compressor off. Run High Fan speed. When coil temp reachs 45°F resume o
Continue operation. Continue to monitor. Take no action. Log Only.
Continue operation. Continue to monitor. Take no action. Log Only.
Only used if Electric Heat is available. Run High Speed and Electric heat until room temp reaches 46°F. Display "FRZ" during operation. Logged Onl Severity 4 error is. Unit operates based on standard input mapping. Severit
Shutdown heat pump and electric heater. Run high fan speed until temp is 100°F. Resume operation. Third occurance in 1 hour locks unit out.
eration after lockout time.
2 error opens all relays. Unit will not operate.
13 Flash Prerssure Limit Switch Open
14 Flash
15 Solid On Heat Pump Error
16 Flash Temperature Beyond Operating Limits
17 Flash
18 Flash Special Test 1 Severity Level 1
19 Flash S
20 Solid On Special Test 3 Severity Level 3
21 OFF
22 OFF, Log Only
23 OFF, Log Only
24 Flash
Log OnlySpecial Test 4 Severity Level 4 Error is Logged Only. Unit operates. Severity 4 keeps unit running.
Key Sequence
Enter Maintenance Menu Press SYSTEM + SCHEDULE + BACK + DISPLAY/ENTER for 6 secs or until double beep sounds() Reset Error Codes & Error History Press  +  for 3 secs or until double beep sounds ( )
Discharge Air Temperature Sensor is O
en or Shorted
Equipment Doesn't Meet Minimum Confi
uration
ecial Test 2 Severity Level 2 Unit operates. Qualified Technical Service required
Outdoor Coil Temperature < 30 F for 2 consecutive Minutes
Frost Protection (for Heat Pump Only Unit- YS10M10)
Outdoor Air Temperature Sensor is O
en or Shorted
If unit is cooling or heat pump on,shut down compressor. Run high fan until switch closes. Resume operation. Third occurance in 1 hour locks unit out.
Override Sensor. Set temp to 75°F. Continue to monitor. Set error code 14 ON. If indoor coil temp < (Lesser than) ambient temp for 3 minutes. Unit uses electric heat to satisf Ambient temp < (less than) 0°F and ambient temp > (greater than) 130°F. Set error code 16 ON. When cleared return unit to normal.
Must have compressor enabled and at least 2 fan speeds
Unit shuts down. Inputs via front panel or t-stat are ignored. Qualified Technical Service re
Error is Logged Only. Unit operates. Severity 3 keeps unit running. Attention is needed
Unit will use electric heat to satisfy heating demands until temp > 45°F. Unit must be a Heat Pum
Unit will run active defrost for a minimum of 6 minutes when Heat Pump run time is greater than 60 minutes and outdoor coil temp is 26 F or less.
Continue with normal operation. Continue to monitor sensor.
Action
heating demand.
uired URGENT
.
56
Page 58
TROUBLESHOOTING TIPS
NOTE:
To more accurately identify the problem, rst check for current maintenance
alerts and their history.
Problem Possible Cause Possible Solution
Unit does not operate.
Unit Trips Circuit Breaker or Blows Fuses.
LCDI Power Cord Trips (Reset Button Pops Out).
Unit Does Not Cool/Heat On And Off Too Frequently.
The unit is turned to the off position,
The LCDI power cord is unplugged.
The LCDI power cord has tripped (Reset button has popped out).
The circuit breaker has tripped or the supply circuit fuse has blown.
There has been a local power
failure.
Other appliances are being used on
the same circuit. An extension cord is being used.
The circuit breaker or time-delay fuse is not of the proper rating.
The LCDI power cord can trip
(Reset button pops out) due to disturbances on your power supply line.
Electrical overload, overheating, or cord pinching can trip (Reset button pops out) the LCDI power cord.
NOTE: A damaged power supply cord must be replaced with a new power supply cord
obtained from the product manufacturer and must not be repaired.
The return/discharge air grille is blocked.
Windows or doors to the outside are
open.
The temperature is not set at a cool
enough/warm enough setting.
The indoor coil or outdoor coil is
dirty or obstructed.
There is excessive heat or moisture (cooking, showers, etc.) in the room.
The temperature of the room you
are trying to cool is extremely hot.
Turn the unit to the on position and raise or
lower temperature setting (as appropriate) to call for operation.
Plug into a properly grounded 3 prong
receptacle. See “Electrical Rating Tables” on pg. 6 for the proper receptacle type for your unit.
Press and release RESET (listen for click;
Reset button latches and remains in) to resume operation.
Reset the circuit breaker, or replace the fuse as
applicable. If the problem continues, contact a licensed electrician.
The unit will resume normal operation once
power has been restored.
The unit requires a dedicated outlet circuit, not
shared with other appliances.
Do NOT use an extension cord with this or any
other air conditioner.
Replace with a circuit breaker or time-delay
fuse of the proper rating. See “Electrical Rating Tables” on pg. 6 for the proper circuit breaker/fuse rating for your unit. If the problem continues, contact a licensed electrician.
Press and release RESET (listen for click; Reset button latches and remains in) to resume normal operation.
Once the problem has been determined and
corrected, press and release RESET (listen for click; Reset button latches and remains in) to resume normal operation.
Ensure that the return and/or discharge air
paths are not blocked by curtains, blinds, furniture, etc.
Ensure that all windows and doors are closed.
Adjust the Temperature control to a cooler or
warmer setting as necessary.
remove obstruction.
Clean the coils, (See Routine Maintenance), or
remove obstruction.
Be sure to use exhaust vent fans while cooking
or bathing and, if possible, try not to use heat producing appliances during the hottest part of the day.
Allow additional time for the air conditioner to
cool off a very hot room.
57
Page 59
TROUBLESHOOTING TIPS (Continued)
Problem Possible Cause Possible Solution
The outside temperature is below 60° F (16° C).
The digital control is set to fan cycling mode.
Unit Does Not Cool/Heat On And Off Too Frequently
(continued).
Unit Runs Too Much.
cooling capacity to match the heat gain of the room.
heating capacity to match the heat loss of the room.
This may be due to an excessive heat load in the room.
It may also be due to an improperly sized unit.
This may be normal for higher
Do not try to operate your air conditioner in the
cooling mode when the outside temperature is below 60° F (16° C). The unit will not cool properly, and the unit may be damaged.
Since the fan does not circulate the room
air continuously at this setting, the room air does not mix as well and hot (or cold) spots may result. Using the continuous fan setting is recommended to obtain optimum comfort levels.
Check the cooling capacity of your unit to
ensure it is properly sized for the room in which it is installed. Room air conditioners are not designed to cool multiple rooms.
Check the heating capacity of your unit. Air
conditioners are sized to meet the cooling load, and heater size is then selected to meet the heating load. In extreme northern climates, room air conditioners may not be able to be used as a primary source of heat.
If there are heat producing appliances in use
in the room, or if the room is heavily occupied, the unit will need to run longer to remove the additional heat.
Be sure to use exhaust vent fans while cooking
or bathing and, if possible, try not to use heat producing appliances during the hottest part of the day.
your new air conditioner may result in the unit running longer than you feel it should. This may be more apparent, if it replaced an
58
You may notice that the discharge
air temperature of your new air conditioner may not seem as cold as you may be accustomed to from older units. This does not, however, indicate a reduction in the cooling capacity of the unit.
compared to older models.
capacity rating (Btu/h) listed on the unit’s rating
Page 60
COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS
Compressor does not run
Fan motor
does not run
Possible Solution
Low voltage
Temperature not set cold enough or room air thermistor inoperative
Compressor hums but cuts off on overload
Open or shorted compressor windings
Open overload Test overload protector & replace if inoperative Open capacitor Test capacitor & replace if inoperative
Inoperative system button
Broken, loose or incorrect wiring
Inoperative system button Test b u tton & r eplace user interface if inoperative Broken, loose or incorrect wiring Refer to applicable wiring diagram Open capacitor Test capacitor & replace if inoperative Fan speed button defective Replace user interface if inoperative
Inoperative fan motor
Check voltage at compressor. 115V & 230V units will operate at 10% voltage variance
Set temperature to lower than ambient position. Test thermistor and replace if inoperative.
Hard start compressor. Direct test compressor. If compressor starts, add starting components
Check for continuity & resistance
Test for continuity in all positions. Replace if inoperative switch or electronic board.
Refer to appropriate wiring diagrams to check wiring. Correct as needed.
Possible Solution
Test fan motor & replace if inoperative (be sure internal overload has had time to reset)
esuaC elbissoP melborP
esuaC elbissoP melborP
Does not cool or
only cools slightly
melborP
Undersized unit Refer to industry standard sizing chart Indoor ambient thermistor open
or shorted Dirty launaM s’renwO ni dednemmocer sa naelC retl
Dirty or restricted condenser or evaporator coil
Poor air circulation Adjust discharge louvers. Use high fan speed Fresh air or exhaust air door open Low capacity - undercharge Check for leak & make repair Compressor not pumping properly
See alarms and replace thermistor if needed.
Use pressure wash or biodegradable cleaning agent to clean
Close doors. Instruct customer on use of this feature
Check amperage draw against nameplate. If not conclusive, make pressure test
esuaC elbissoP Possible Solution
59
Page 61
COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS
Possible Solution esuaC elbissoP melborP
Replace fuse, reset breaker. If repeats, check
Unit does not run
Fuse blown or circuit tripped
Power cord not plugged in Plug it in System button in “OFF” position Set correctly Inoperative system button or open
electronic control board
fuse or breaker size. Check for shorts in unit wiring & components
Test for continuity. Check alarms. Correct as needed.
Evaporator coil
freezes up
Compressor runs
continually & does
not cycle off
Loose or disconnected wiring control board or other components
Dirty launaM s’renwO ni dednemmocer sa naelC retl
Restricted airfl ow
Inoperative thermistor Check alarms. Replace as necessary. Short of refrigerant De-ice coil & check for leak Inoperative fan motor Test fan motor & replace if inoperative Partially restricted capillary tube
Excessive heat load
Restriction in line Refrigerant leak
Compressor relay contacts stuck Remote wall T-stat incorrectly wired Refer to appropriate wiring diagram
Check wiring & connections. Reconnect per wiring diagram
Possible Solution
Check for dirty or obstructed coil. Use pressure wash or biodegradable cleaning agent to clean
De-ice coil. Replace capillary tube.
Possible Solution
Unit undersized. Test cooling performance &
replace with larger unit if needed. See sizing chart. Check for partially iced coil & check
temperature split across coil Find leak and repair.
Check operation of t-stat. Replace if contacts remain closed.
esuaC elbissoP melborP
esuaC elbissoP melborP
60
Electronic control
board does not
turn unit off
Thermistor shorted Replace thermistor or electronic control board
Possible Solution
Compressor relay contacts stuck
Temperature set at coldest point Incorrect wiring Refer to appropriate wiring diagrams
Unit undersized for area to be cooled
Defective thermistor Replace thermistor or electronic control board
Replace electronic control board Turn to higher temp. setting to see if unit
cycles off. If not, replace control board.
Refer to industry standard sizing chart
esuaC elbissoP melborP
Page 62
COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS
Possible Solution esuaC elbissoP melborP
Overload inoperative. Opens too soon
Check operation of unit. Replace overload if system operation is satisfactory
Compressor runs
for short periods
only. Cycles on
overload
Unit does not
turn on
Compressor restarted before system pressures equalized
Low or fl uctuating voltage
Incorrect wiring Refer to appropriate wiring diagram Shorted or incorrect capacitor
Restricted or low air flow through condenser coil or evaporator coil
Compressor running abnormally hot
No power Incorrect wiring Refer to appropriate wiring diagram
Defective thermistor Replace thermistor or electronic control board
Control’s default of 3 minutes wait delay timer inoperative. Replace board.
Check voltage with unit operating. Check for other appliances on circuit. Air conditioner should be in a dedicated circuit for proper voltage & fused separately
Test capacitor and replace if needed. Check for proper fan speed or blocked
coils. Correct as needed. Check for kinked discharge line or restricted
condenser. Refrigerant overcharge. Check amperage, connections.
Possible Solution
Check power supply. Check LCDI plug. Check wire connections. Check if panel is locked.
esuaC elbissoP melborP
Noisy operation
Water leaks into
the room
Possible Solution
Poorly installed Fan blade striking chassis Reposition - adjust motor mount
Compressor vibrating
Improperly mounted or loose cabinet parts refrigerant tubes
Evaporator drain pan overfl owing Clean obstructed drain trough Condensation forming underneath
base pan Poor installation resulting in rain
entering the room
Condensation on discharge grille louvers
Chassis gasket not installed Install gasket, per Installation manual Downward slope of unit is too
steep inward
Refer to Installation Manual for proper installation
Check that compressor grommets have not deteriorated. Check that compressor mounting parts are not missing
Check assembly & parts for looseness, rubbing & rattling pipes, etc.
Possible Solution
Evaporator drain pan broken or cracked. Reseal or replace. No chassis gasket installed. Install chassis gasket
Check installation instructions. Reseal as required
Dirty evaporator coil. Use pressure wash or biodegradable cleaning agent to clean. Environmental phenomena: point supply louvers upward. Put on high fan.
Refer to installation manual for proper installation
esuaC elbissoP melborP
esuaC elbissoP melborP
61
Page 63
COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS
Water “spitting”
into room
Excessive
moisture
Unit
short cycles
Possible Solution
Sublimation: When unconditioned saturated, outside air mixes with conditioned air, condensation forms on the cooler surfaces
Downward pitch of installation is too steep towards back of unit
Restricted coil or dirty fi lter
Insuffi cient air circulation thru area to be air conditioned
Inadequate vapor barrier in building structure, particularly fl oors
Defective thermistor Replace thermistor or electronic control board Unit oversized See sizing chart. Correct as needed.
Chassis seal gasket not sealing or absent causting unit to short cycle
Ensure that foam gaskets are installed in between window panes & in between the unit & the sleeve. Also, ensure that fresh air/exhaust vents (on applicable models) are in the closed position & are in tact
Follow installation instructions to ensure that downward pitch of installed unit is no less than 1/4” & no more than 3/8”
Clean & advise customer of periodic cleaning & maintenance needs of entire unit
Possible Solution
Adjust louvers for best possible air circulation
Advise customer
Possible Solution
Check gasket. Reposition or replace as needed
esuaC elbissoP melborP
esuaC elbissoP melborP
noitisop ”revaSyenoM“ ni etarepO tinu dezisrevO
esuaC elbissoP melborP
Prolonged off
cycles
Outside water
leaks
Restricted coil or dirty fi lter
Defective indoor ambient thermistor or electronic control board
Defective remote wall t-stat
Evaporator drain pan cracked or obstructed
Water in compressor area
Obstructed condenser coil Fan blade/slinger ring improperly
positioned
Clean & advise customer of periodic cleaning & maintenance needs of entire unit
Possible Solution
Check alarms. Replace thermistor or electronic control board
Replace t-stat
Possible Solution
Repair, clean or replace as required Detach shroud from pan & coil. Clean &
remove old sealer. Reseal, reinstall & check Use pressure wash or biodegradable cleaning
agent to clean Adjust fan blade to 1/2” of condenser coil fi n
pack
esuaC elbissoP melborP
esuaC elbissoP melborP
62
Page 64
HEAT / COOL ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS
Possible Solution
Possible Solution
esuaC elbissoPmelborP
Room temperature
uneven
(Heating cycle)
Check error codes. Replace as needed.Bad indoor ambient thermistor Set at higher fan speed.Fan speed too low Close doors, windows, etc.Opened door, windows, etc.
Enable ATSFATSF (room air sampling feature) disabled
Possible SolutionesuaC elbissoPmelborP
Unit will not defrost
(Heat pump
only models)
Replace thermistor.Bad outdoor coil thermistor
• On heat pumps with electric heat: no action needed
• On model YSM10: do not operate below 32°F/ 0°C
• If outdoor air temp is higher than freezing, check reversing valve, electric coil, outdoor thermistor, refrigerant circuits, etc.
• For proper operation: correct as needed
Temperature below 32°F/ 0°C
esuaC elbissoPmelborP
Does not heat
adequately
Exhaust or fresh air door open
Check if operating properly . Instruct customer on proper use of control
Dirty launaM s'renwO ni dednemmocer sa naelCret
l
Unit undersized
Check heat rise across coil. If unit operates effi ciently, check if insulation can be added to attic or walls. If insulation is adequate, recommend additional unit or larger one
Outdoor coil thermistor or electronic control board defective
Heater hi-limit control cycling on & off
Check for adequate fan air across heater. Check for open hi-limit control.
Check alarms (error codes). Replace thermistor or electronic control board.
Shorted or open supplementary heater Do ohmmeter check.
margaid gniriw elbacilppa kcehCgniriw tcerrocnI
63
Page 65
HEAT PUMP ROOM AIR CONDITIONERS: TROUBLE SHOOTING TIPS
noitcAesuaC elbissoPmelborP
Incorrect wiring Refer to applicable wiring diagram Defective solenoid coil Check for continuity of coil
Unit cools when
heat is called for
Reversing valve fails to shift
Inoperative system switch Check for continuity of system switch
Heating capillary tube partially restricted
Cooling adequate,
but heating
Check valve leaking internally
insuffi cient
Reversing valve failing to shift completely; bypassing hot gas
TROUBLESHOOTING CHART - HEAT PUMP
Block condenser coil & switch unit to cooling. Allow pressure to build up in system, then switch to heating. If valve fails to shift, replace valve.
noitcAesuaC elbissoPmelborP
Check for partially starved outer coil. Replace heating capillary tube
Switch unit several times from heating to cooling. Check temperature rise across coil. Refer to specifi cation sheet for correct temperature rise
Denergize solenoid coil, raise head pressure, energize solenoid to break loose. If valve fails to make complete shift, replace valve.
REFRIGERANT SYSTEM DIAGNOSIS - COOLING CYCLE
LOW SUCTION PRESSURE HIGH SUCTION PRESSURE LOW HEAD PRESSURE HIGH HEAD PRESSURE
Low Load Conditions High Load Conditions Low Load Conditions High Load Conditions
Low Air Flow Across High Air Flow Across Refrigerant System Low Air Flow Across Indoor Coil Indoor Coil Restriction Outdoor Coil
Refrigerant System Reversing Valve not Reversing Valve not Overcharged Restriction Fully Seated Fully Seated
Undercharged Overcharged Undercharged Noncondensables (air)
metsyS ni
Moisture in System Defective Compressor Defective Compressor
64
Page 66
HEAT PUMP ROOM AIR CONDITIONERS: TROUBLE SHOOTING TIPS
REFRIGERANT SYSTEM DIAGNOSIS - HEATING CYCLE
LOW SUCTION PRESSURE
Low Airfl ow
Across Outdoor Coil
Refrigerant System
Restriction
Undercharged Overcharged Undercharged
Moisture in System Defective Compressor Defective Compressor
HIGH SUCTION PRESSURE
Outdoor Ambient Too High
for Operation in Heating
Reversing Valve not
Fully Seated
LOW HEAD PRESSURE
Refrigerant System
Restriction
Reversing Valve not
Fully Seated
ELECTRICAL TROUBLESHOOTING CHART - HEAT PUMP
HEAT PUMP
HIGH HEAD PRESSURE
Outdoor Ambient Too High
For Operation In Heating
Low Airfl ow Across
Indoor Coil
Overcharged
Noncondensables (air)
in System
Is Line Voltage
Present at the Solenoid
YES
Is the Solenoid Coil Good?
YES
Reversing Valve Stuck
Replace the Reversing Valve
SYSTEM COOLS WHEN
HEATING IS DESIRED.
NO
NO
Is the Selector Switch
Set for Heat?
Replace the Solenoid Coil
65
Page 67
TROUBLESHOOTING TOUCH TEST CHART: TO SERVICE REVERSING VALVES
NORMAL FUNCTION OF VALVE
VALVE
OPERATING
CONDITION

Normal Cooling
Normal Heating
Valve will not
shift from cool
to heat.
Valve will not
shift from cool
to heat.
Starts to shift
but does not
complete
reversal.
Apparent leap in heat­ing.
Will not shift
from heat to
cool.
14
     
to Compressor
SUCTION TUBE
from Compressor
DISCHARGE TUBE
1 2 3 4 5 6 POSSIBLE CAUSES CORRECTIONS
from Compressor
SUCTION TUBE to
DISCHARGE TUBE
Hot Cool
Hot Cool
COIL
Tube to INSIDE
COIL
Compressor
Tube to INSIDE
Cool
as (2)
Hot
as (1)
COIL
Tube to OUTSIDE
COIL
Tube to OUTSIDE
Hot
*TVB TVB
as (1) Cool
*TVB TVB
as (2)
LEFT Pilot
Capillary Tube
LEFT Pilot
Capillary Tube
RIGHT Pilot
Capillary Tube
RIGHT Pilot
Capillary Tube
* TEMPERATURE OF VALVE BODY
** WARMER THAN VALVE BODY
 
 
MALFUNCTION OF VALVE
Check Electrical circuit and coil
Check refrigeration charge
Hot Cool
Cool, as (2)
Hot,
*TVB Hot Pilot valve okay. Dirt in one bleeder hole.
as (1)
     
Hot Cool
Hot Cool
Warm Cool
Hot Warm Warm Hot *TVB Hot
Cool, as (2)
Cool, as (2)
Cool, as (2)
Hot,
*TVB *TVB Clogged pilot tubes.
as (1)
Hot,
Hot Hot
as (1)
Hot,
*TVB Warm Defective Compressor. Replace compressor
as (1)
Pressure differential too high. Recheck system.
Piston cup leak
Both ports of pilot open. (Back seat port did not close).
Not enough pressure differential at start of stroke or not enough fl ow to maintain pressure differential.
     
Hot Warm Warm Hot Hot Hot Both ports of pilot open.
Valve hung up at mid-stroke. Pumping
     
Hot Hot Hot Hot Hot Hot Both ports of pilot open.
Hot,
Hot,
Hot,
Cool,
*TVB *TVB Piston needle on end of slide leaking.
as (2) Cool,
**WVB **WVB Pilot needle and piston needle leaking.
as (2) Cool,
*TVB *TVB Pressure differential too high.
as (2)
Hot Cool
Hot Cool
Hot Cool
as (1)
as (1)
as (1)
     
Hot,
Hot,
Hot,
Cool,
Hot *TVB Dirt in bleeder hole.
as (2)
Cool,
Hot *TVB Piston cup leak.
as (2)
Cool, as (2)
Cool,
Warm *TVB Defective compressor. Replace compressor
as (2)
Hot Cool
Hot Cool
Hot Cool
Warm Cool
as (1)
as (1)
as (1)
Warm,
as (1)
volume of compressor not suffi cient to maintain reversal.
Clogged pilot tube.
NOTES:
.tiucric lacirtcele riapeR .lioc ot egatlov oN
.lioc ecalpeR .lioc evitcefeD
ael riapeR .egrahc woL
Deenergize solenoid, raise head pressure, reenergize solenoid to break dirt loose. If unsuccessful, remove valve, wash out. Check on air before installing. If no movement, replace valve, add strainer to discharge tube, mount valve horizontally.
Stop unit. After pressures equalize, restart with solenoid energized. If valve shifts, reattempt with compressor running. If still no shift, replace valve.
Raise head pressure, operate solenoid to free. If still no shift, replace valve.
Raise head pressure, operate solenoid to free partially clogged port. If still no shift, replace valve.
Check unit for correct operating pressures and charge. Raise head pressure. If no shift, use valve with smaller port.
evlav ecalpeR .egamad ydoB
Raise head pressure, operate solenoid. If no shift, use valve with smaller ports.
evlav ecalpeR .egamad ydoB toH BVT* toH toH toH toH
Raise head pressure, operate solenoid. If no shift, use valve with smaller ports.
Raise head pressure, operate solenoid. If no shift, replace valve.
Operate valve several times, then recheck. If excessive leak, replace valve.
Operate valve several times, then recheck. If excessive leak, replace valve.
Stop unit. Will reverse during equalization period. Recheck system
Raise head pressure, operate solenoid to free dirt. If still no shift, replace valve.
Raise head pressure, operate solenoid. Remove valve and wash out. Check on air before reinstalling, if no movement, replace valve. Add strainer to discharge tube. Mount valve horizontally.
Stop unit. After pressures equalize, restart with solenoid deenergized. If valve shifts, reattempt with compressor running. If it still will not reverse while running, replace the valve.
.evlav ecalpeR .tolip evitcefeD toH toH
.metsys egrahcer ,k
66
Page 68
ELECTRONIC CONTROL BOARD COMPONENTS IDENTIFICATION
Front
DISCHARGE
Back
Reversing Valve
Battery Compartment
Max Speed
High Speed
Med Speed
Low Speed
Transformer 115/230 Volts
User Interface connector
T-stat Terminals
Transformer voltage Selector Switch 115/230 Volts
Sample board for Kuhl+ unit
67
Page 69
REMOTE WALL THERMOSTAT WIRING DIAGRAMS
LEGEND FOR TSTAT WIRING HARNESS
C Common Terminal GH Call for High Fan
GL Call for Low Fan B Reversing Valve Y Coil for Cooling W Call for Heat R 24 VAC Power From Unit RT5 - Two Speeds Fan T-Stat - Field Provided
-- -- -- Field Wiring
COOL W/O ELECTRIC HEAT
Electronic Control Board
24 VAC Connections
W
R
GH
GL
C
Y
B
GH GL O B Y W RC RH C
RT5 Thermostat
HEAT PUMP WITH ELECTRIC HEAT
Jumper
Wire
GH GL O B Y W RC RH C
HEAT PUMP ONLY AND
Electronic Control Board
24 VAC Connections
COOL WITH ELECTRIC HEAT
Electronic Control Board
24 VAC Connections
W
R
GH
GL
C
Y
B
RT5 Thermostat
Jumper
Wire
68
W
R
GH
GL
C
Y
B
GH GL O B Y W RC RH C
Jumper
Wire
Page 70
KUHL
ELECTRONIC CONTROL
COOL ONLY MODELS
SS08M10A, SS10M10A, SS12M10A, SS14M10A
SS12M30A, SS15M30A
SM18M30A, SM21M30A, SM24M30A
COMPRESSOR
C
OLP
R
S
RED
BLACK
BLUE
BLACK
RED
CAPACITOR BRACKET
GREEN
TO CHASSIS
BLUE
SCHEMATIC
CAPACITOR
C
H
E
R
M
WIRING DIAGRAM
UI HOLDER ELECTRONICS ASY
OD AIR SENSOR OD COIL SENSOR
WHITE
ID COIL SENSOR
L2 or ACN
L1
BLACK
WHITE
DCHRG AIR SENSOR
AMBIENT AIR SENSOR
W O
LL E
N
/Y
E E
N E
R
E
G
R G R O
TO CAPACITOR BRACKET
TO DISPLAY
SUPPLY CORD
F4
BLACK
RELAY F3
BLUE
RELAY
F2
ORANGE
RELAY
RED
F1 RELAY
COMP RELAY
WHITE
O
M
N
A
F
TO INNERWALL/ MOTOR MOUNT
BROWN
N E E R G
MOTOR
L1
CAP
- CAPACITOR
- COMPRESSOR
COMPR
- FAN MOTOR
MTR
OLP
- OVERLOAD PROTECTOR
- USER INTERFACE
UI
- THERMAL FUSE
HLTF- HEATER LIMIT FUSE
4
3
2
1
5
L1
ELECTRONIC CONTROL
L2 OR N
COMP
MAX
F4
HIGH
F3
MEDIUM
F2
LOW
F1
COMPRESSOR
L E G E N D
(115 V)
E
S
U
I
R
T
N
E
F
R
A
E
C
NEUTRAL
L2
(230/208 V)
R
OLP
FAN MTR
S
FAN
COM
CAP
OLP
T
-
THERMISTER
- COMBINATION TERMINAL
- GROUNDED LEAD SYMBOL
- INSULATOR
- HEATER ELEMENT
HTR
C
R
COMPRESSOR
HERM CO M
S
PART NO. REV.
92170000
CAP
04
69
Page 71
KUHL
ELECTRONIC CONTROL
COOL ONLY MODELS
SL28M30A, SL36M30A
COMPRESSOR
C
OLP
R
S
RED
BLACK
BLUE
BLACK
RED
CAPACITOR BRACKET
GREEN
TO CHASSIS
BLUE
SCHEMATIC
SOLID STATE RELAY
2
SSR
1
BLACK
CAPACITOR
M
C
O
H
E
R
M
WIRING DIAGRAM
UI HOLDER ELECTRONICS ASY
OD AIR SENSOR OD COIL SENSOR
WHITE
ID COIL SENSOR
L2 or ACN
L1
BLACK
WHITE
DCHRG AIR SENSOR
AMBIENT AIR SENSOR
W O L L E
N
/Y
E
N
E
E
R
E
G
R G R O
TO CAPACITOR
BRACKET
TO DISPLAY
SUPPLY CORD
F4 RELAY
F3
BLACK
RELAY
BLUE
F2 RELAY
RED
F1 RELAY
WHITE
4
BLUE
3
N
A
F
TO INNERWALL/ MOTOR MOUNT
WHITE
BROWN
N E E R G
COMP RELAY
MOTOR
L1
CAP
- CAPACITOR
- COMPRESSOR
COMPR
- FAN MOTOR
MTR
- OVERLOAD PROTECTOR
OLP UI
- USER INTERFACE
- THERMAL FUSE
HLTF- HEATER LIMIT FUSE
4
3
2
1
L2 OR N
5
L1
COMP
ELECTRONIC CONTROL
HIGH
F3
MEDIUM
F2
LOW
F1
COMPRESSOR
S
U
L E G E N D
(115 V)
R
E
N
T
I
F
R
E
A
C
E
NEUTRAL
L2
(230/208 V)
R
OLP
FAN MTR
S
COM
FAN
CAP
OLP
T
- THERMISTER
- COMBINATION TERMINAL
- GROUNDED LEAD SYMBOL
- INSULATOR
- HEATER ELEMENT
HTR
C
R
COMPRESSOR
HERM
S
92170001
CAP
COM
REV.PART NO.
04
70
Page 72
KUHL+
ELECTRONIC CONTROL
COOL WITH ELECTRIC HEAT MODELS
ES12M33A, ES15M33A
EM18M34A, EM24M34A
COMPRESSOR
C
OLP
R
S
RED
BLUE
BLACK
BLACK
RED
CAPACITOR BRACKET
GREEN
TO CHASSIS
BLUE
SCHEMATIC
HEATER
CAPACITOR
C
H
E
R
M
WIRING DIAGRAM
UI HOLDER ELECTRO NICS ASY
WHITE
OD AIR SENSOR OD COIL SENSOR ID COIL SENSOR
L2 or ACN
L1
BLACK
WHITE
AMBIENT AIR SENSOR
W O L L E
N
/Y
E E
N E
R
E
G
R G R O
TO CAPACITOR BRACKET
DCHRG AIR SENSOR
SUPPLY CORD
TO DISPLAY
RV RELAY
FAN 4 RELAY
FAN 3
BLACK
RELAY
BLUE
FAN 2
ORANGE
RED
M
O
N
A
F
TO INNERWALL/ MOTOR MOUNT
ORANGE
WHITE
BROWN
N E E R G
RELAY
FAN 1 RELAY
HEAT RELAY
HEAT RELAY
COMP RELAY
MOTOR
RED
S
U
E
R
T
N
I
R
E
F
A
C
OLP
E
OLP
C
R
FAN MTR
FAN
S
R
COMPRESSOR
HERM
S
L2
CAP
CAP
(230/208 V)
COM
COM
L1
3
2
1
6
7
5
L1
F2
F1
EH1
EH2
L2 OR N
COMP
MEDIUM
LOW
ELECTRIC HEAT
HL
ELECTRIC HEAT
COMPRESSOR
HTR
TF
HIGH
F3
ELECTRONIC CONTROL
L E G E N D
CAP
- CAPACITOR
- COMPRESSOR
COMPR
- FAN MOTOR
MTR
- OVERLOAD PROTECTOR
OLP
- USER INTERFACEUI
- THERMAL FUSE
TF
- HEATER LIMIT FUSE
HL
T
- THERMISTER
- COMBINATION TERMINAL
- GROUNDED LEAD SY MBOL
- INSULATOR
- HEATER ELEMENT
HTR
PART NO. REV.
92170002
04
71
Page 73
KUHL+
ELECTRONIC CONTROL
COOL WITH ELECTRIC HEAT MODEL
EL36M35A
COMPRESSOR
C
OLP
R
S
BLACK
RED
BLUE
BLACK
RED
CAPACITOR BRACKET
GREEN
TO CHASSIS
BLUE
SCHEMATIC
HE ATER
CAPACITOR
C
H
E
R
M
SOLID STATE RELAY
RED
SOLID STATE RELAY
SSR
BLACK
M
O
N
A
F
SSR
ORANGE
WHITE
BLUE
TO INNERWALL/ MOTO R MOU NT
BLACK
N E E R G
BLACK
BLUE
RED
RED
BLUE
WHITE
BROWN
WIRING DIAGRAM
UI HOLDER ELECTRONICS ASY
WHITE
OUTDOOR AIR SE NSOR
OUTDOOR COIL SE NSOR
INDO OR C OIL SE NS OR
L2 or ACN
L1
BLACK
WHITE
RV RELAY
FAN 4 RELAY
FAN 3 RELAY
FAN 2 RELAY
FAN 1 RELAY
HEAT RELAY
HEAT RELAY
COMP RELAY
MOT OR
W O L L E
N
Y
/
E E
N E
R
E
G
R G
R O
TO CAPACITOR
BRACKET
DSC HRG AIR SENSOR
AMBIE NT AIR S ENS OR
SUPPLY CORD
TO DISP LAY
(115 V)
R
FAN MTR
S
R
S
NEUT RAL
L2
FAN
CAP
HERM
(230/208 V)
COM
COM
CAP
U
R
E
S
N
R
I
T
E
E
C
F
L1
3
2
1
6
MEDIU M
F2
LOW
F1
ELECTRIC HEAT
HL
EH1
ELECTRIC HEAT
HTR
HIGH
F3
A
TF
L2
OLP
C
COMPRESSOR
5
L1

COMP
COMPRESSOR
L E G E N D
T
CAP
- CA PAC ITOR
CO MPR - COMP RE SS OR
- FAN MOT OR
MTR
- OV ER LOA D PR OTE CT OR
OLP
- US ER INTE RF ACE
UI
- TH ER MAL FU SE
TF
- HE ATE R L IMIT FU SE
HL

- THE R MIST ER
- COMB INATION TE RMINAL
- GR OUNDE D LEAD SYMB OL
- INS ULA TOR
- HEATER ELEMENT
HTR
PART NO. 92170007
REV.
00
72
Page 74
KUHL+
ELECTRONIC CONTROL
HEAT PUMP ONLY MODEL
YS10M10A
COMPRESSOR
C
OLP
R
S
RED
BLACK
BLUE
BLACK
RED
CAPACITOR BRACKET
GREEN
TO CHASSIS
BLUE
SCHEMATIC
CAPACITOR
C
H
E
R
M
WIRING DIAGRAM
COIL, SOLENOID
B L U
BLACK
E
BLACK
BLUE
ORANGE
WHITE
M
O
N
A
F
TO INNERWALL/ MOTOR MOUNT
BROWN
N E E R G
UI HOLDER ELECTRONICS ASY
WHITE
OD AIR SENSOR OD COIL SENSOR ID COIL SENSOR
L2 or ACN
L1
BLACK
WHITE
RV RELAY
F4 RELAY
F3 RELAY
F2 RELAY
F1 RELAY
HEAT RELAY
HEAT RELAY
COMP RELAY
RED
MOTOR
DCHRG AIR SENSOR
AMBIENT AIR SENSOR
W O L L E
N
/Y
E E
N E
R
E
G
R G
R O
TO CAPACITOR BRACKET
TO DISPLAY
SUPPLY CORD
NEUTRAL
U
S
E
I
R
T
N
E
F
R
E
C
L1
3
2
1
6
5
L1
L2 OR N
COMP
F2
F1
HP
MEDIUM
LOW
REVERSE CYCLE
COMPRESSOR
HIGH
F3
ELECTRONIC CONTROL
A
R
OLP
FAN MTR
S
FAN
RV
OLP
C
R
COMPRESSOR
HERM
S
L2
CAP
CAP
(115 V)
(230/208 V)
COM
COM
L E G E N D
CAP
- CAPACITOR
- COMPRESSOR
COMPR
- FAN MOTOR
MTR
- OVERLOAD PROTEC TOR
OLP
- USER INTERFACE
UI
- THERMAL FUSE
TF HL
- HEATER LIMIT FUSE
- REVERSING VALVE
T
- THERMISTER
- COMBINATION TERMINAL
- GROUNDED LEAD SYMBOL
- INSULATOR
- HEATER ELEMENT
HTR
92170003
REV.PART NO.
04
73
Page 75
KUHL+
ELECTRONIC CONTROL
HEAT PUMP WITH ELECTRIC HEAT MODELS
YS12M33A, YM18M34A
COMPRESSOR
C
OLP
R
S
RED
BLUE
BLACK
BLACK
RED
CAPACITOR BRACKET
GREEN
TO CHASSIS
BLUE
SCHEMATIC
L1
HEATER
CAPACITOR
C
H
E
R
M
WIRING DIAGRAM
COIL, SOLENOID
B L U
BLACK
E
BLACK
HL
BLUE
ORANGE
N E E R G
HTR
ORANGE
RED
O
M
N
A
F
3
2
1
6
7
EH2
F3
F2
F1
EH1
TO INNERWALL/ MOTOR MOUNT
HIGH
MEDIUM
LOW
ELECTRIC HEAT
ELECTRIC HEAT
UI HOLDER ELECTRONICS ASY
RV RELAY
FAN 4 RELAY
FAN 3 RELAY
FAN 2 RELAY
FAN 1 RELAY
HEAT RELAY
HEAT RELAY
COMP RELAY
WHITE
BROWN
MOTOR
U
S
R
E
I
N
TF
RED
OD AIR SENSOR OD COIL SENSOR ID COIL SENSOR
DCHRG AIR
TO
SENSOR
AMBIENT AIR SENSOR
W O
SUPPLY CORD
L L E
/Y N E E R G
R O
TO CAPACITOR BRACKET
NEUTRAL (115 V)
L2
DISPLAY
(230/208 V)
L2 or ACN
L1
BLACK
WHITE
WHITE
T
E
R
F
A
E
C
N E E R G
R
OLP
FAN MTR
S
FAN
COM
CAP
74
8
5
L1
ELECTRONIC CON TROL
CAP
- CAPACITOR
- COMPRESSOR
COMPR
- FAN MOTOR
MTR
- OVERLOAD PROTECTOR
OLP UITF- USER INTERFACE
- THERMAL FUSE
- HEATER LIMIT FUSE
HL
L2
RV
COMP
REVERSING CYCLE
COMPRESSOR
L E G E N D
RV
OLP
C
R
COMPRESSOR
HERM
S
COM
CAP
- REVERSING VALVE
T
- THERMISTER
- COMBINATION TERMINAL
- GROUNDED LEAD SYMBOL
- INSULATOR
- HEATER ELEMENTHTR
92170004
REV.PART NO.
04
Page 76
KUHL+
ELECTRONIC CONTROL
HEAT PUMP WITH ELECTRIC HEAT MODEL
YL24M35A
COMPRESSOR
C
OLP
R
S
RED
BLACK
BLUE
BLACK
RED
CAPACITOR
BRACKET
GREEN
TO CHASSIS
BLUE
SCHEMATIC
L1
HEATER
CAPACITOR
C
O
H
E
R
M
SOLID STATE RELAY
RED
SOLID STATE RELAY
2
SSR
BLACK
1
M
N
A
F
3
2
1
6
F2
F1
EH1
4
3
F3
2
SSR
1
ORANGE
WHITE
YELLOW
4
3
TO INNERWALL/
MOTOR MOUNT
HIGH
MEDIUM
LOW
ELECTRIC HEAT
HL
ELECTRIC HEAT
BLACK
N E E R G
HTR
BLACK
BLUE
RED
RED
BLUE
WHITE
BROWN
UI HOLDER ELECTRO NICS ASY
RV RELAY
FAN 4 RELAY
FAN 3 RELAY
FAN 2 RELAY
FAN 1 RELAY
HEAT RELAY
HEAT RELAY
COMP RELAY
WHITE
MOTOR
U
E
S
R
N
I
R
T
E
F
A
E
C
TF
WIRING DIAGRAM
OUTDOOR AIR SENSOR
OUTDOOR COIL SENSOR
INDOOR COIL SENSOR
DSCHRG AIR
W O L L E
N
/Y
E E
N E
R
E
G
R G R O
TO CAPACITOR BRACKET
R
FAN MTR
S
SENSOR
AMBIENT AIR SENSOR
SUPPLY CORD
NEUTRAL
L2
FAN
CAP
L2 or ACN
L1
BLACK
WHITE
TO DISPLAY
(115 V)
(230/208 V)
COM
ELECTRONIC CONTROL
SWITCH LOGIC
SWITCH POSITION
OFF HI COOL MED COOL LOW COOL HI HEAT (HP) MED HEAT (HP) LOW HEAT (HP) HI HEAT (EH) MED HEAT (EH) LOW HEAT ( EH) HI FAN MED FAN LOW FAN
12
OOOO
O O O X
0X XO
O
O
O
OX
L1
X = CLOSED O = OPEN
CIRCUIT
3
XXO
XOOO X
OXOO
X
OO
XOO
OXXOO OOOOO OOXOOO OOOOX
7
5
654
7
O
OOO O
OXXOOO
O
O
X
O
X
O
X
XOXOOO
O O O
XX
OOOOOO
L2
RV
COMP
REVERSING CYCLE
COMPRESSOR
CAP
- CAPACITOR
- COMPRESSOR
COMPR
- FAN MOTOR
MTR
- OVERLOAD PROTECTOR
OLP
- USER INTERFACE
UI TF
- THERMAL FUSE
- HEATER
HL
RV
LIMIT FUSE
OLP
C
L E G E N D
T
- THERMISTER
- COMBINATION TERMINAL
- GROUNDED LEAD SYMBOL
- INSULATOR
- HEATER ELEMENT
HTR
R
COMPRESSOR
HERM
S
PART NO. 92170008
CAP
COM
REV.
00
75
Page 77
THERMISTORS’ RESISTANCE VALUES
(This Table Applies to All Thermistors)
76
TEMP
F MIN CENTR MAX MIN MAX
-25 210.889 225.548 240.224 6.50 6.51
-20 178.952 190.889 202.825 6.25 6.25
-15 151.591 161.325 171.059 6.03 6.03
-10 128.434 136.363 144.292 5.81 5.81
-5 108.886 115.340 121.794 5.60 5.60 0 92.411 97.662 102.912 5.38 5.38 5 78.541 82.812 87.083 5.16 5.16
10 66.866 70.339 73.812 4.94 4.94 15 57.039 59.864 62.688 4.72 4.72 20 48.763 51.060 53.357 4.50 4.50 25 41.786 43.654 45.523 4.28 4.28 30 35.896 37.415 38.934 4.06 4.06 31 34.832 36.290 37.747 4.02 4.02 32 33.803 35.202 36.601 3.97 3.97 33 32.808 34.150 35.492 3.93 3.93 34 31.846 33.133 34.421 3.89 3.89 35 30.916 32.151 33.386 3.84 3.84 36 30.016 31.200 32.385 3.80 3.80 37 29.144 30.281 31.418 3.75 3.75 38 28.319 29.425 30.534 3.76 3.77 39 27.486 28.532 29.579 3.67 3.67 40 26.697 27.701 28.704 3.62 3.62 45 23.116 23.931 24.745 3.40 3.40 50 20.071 20.731 21.391 3.18 3.18 55 17.474 18.008 18.542 2.96 2.96 60 15.253 15.684 16.115 2.75 2.75 65 13.351 13.697 14.043 2.53 2.53 66 13.004 13.335 13.666 2.48 2.48 67 12.668 12.984 13.301 2.44 2.44 68 12.341 12.644 12.947 2.39 2.39 69 12.024 12.313 12.603 2.35 2.35 70 11.716 11.993 12.269 2.31 2.31 71 11.418 11.682 11.946 2.26 2.26 72 11.128 11.380 11.633 2.22 2.22 73 10.846 11.088 11.329 2.18 2.18 74 10.574 10.804 11.034 2.13 2.13 75 10.308 10.528 10.748 2.09 2.09 76 10.051 10.260 10.469 2.04 2.04
77 9.800 10.000 10.200 2.00 2.00 78 9.550 9.748 9.945 2.03 2.03 79 9.306 9.503 9.699 2.07 2.07 80 9.070 9.265 9.459 2.10 2.10 81 8.841 9.033 9.226 2.13 2.13 82 8.618 8.809 9.000 2.17 2.17 83 8.402 8.591 8.780 2.20 2.20 84 8.192 8.379 8.566 2.23 2.23 85 7.987 8.172 8.358 2.27 2.27 86 7.789 7.972 8.155 2.30 2.30 87 7.596 7.778 7.959 2.33 2.33 88 7.409 7.589 7.768 2.37 2.37 89 7.227 7.405 7.583 2.40 2.40 90 7.050 7.226 7.402 2.43 2.43 91 6.878 7.052 7.226 2.47 2.47 92 6.711 6.883 7.055 2.50 2.50
93 6.548 6.718 6.889 2.53 2.53 94 6.390 6.558 6.727 2.57 2.57 95 6.237 6.403 6.569 2.60 2.60 96 6.087 6.252 6.417 2.63 2.63 97 5.942 6.105 6.268 2.67 2.67 98 5.800 5.961 6.122 2.70 2.70
99 5.663 5.822 5.981 2.73 2.73 100 5.529 5.686 5.844 2.77 2.77 105 4.912 5.060 5.208 2.93 2.93 110 4.371 4.511 4.651 3.10 3.10 115 3.898 4.030 4.161 3.27 3.27 120 3.482 3.606 3.730 3.43 3.43
INDOOR AIR SENSOR
RESISTENCE (K Ohms)
RESISTANCE
TOLERANCE %
Page 78
Kühl Remote Control
Replacement Remote Control Configuration Instructions
For Use with Kühl
Contents:
Remote Control with Holder
(2) AAA-batteries
Instruction Sheet
(cool only models)
and Kühl +
(cool & heat models)
ATTENTION! – You May Need to Configure The Replacement Remote Control
Please read instructions completely before attempting configuration of the Remote Control. Failure to do so could result in t
Step 1. A. Locate the Model # of your Air Conditioner. B. Identify the prefix (First 2 Letters) of your unit’s model #. C. Look at the chart below and in it, find the prefix of your AC unit’s model #. D. Note the Option # Code (OPT#) next to it and the required action.
display is supposed to show this OPT# Code.
Model Prefix Option Code Required Action
SS, SM OPT 1 None – SL OPT 2 Perform Steps 2 - 5 YS, YM, YL, ES, EM, EL OPT 3 Perform Steps 2 - 5
Step 2. Point the Remote Control at Air Conditioning Unit and then press the Remote Control’s
POWER
Step 3. Once the display on the Air Conditioning Unit is illuminated, check the Option Code
number (OPT#) shown in the display and ensure it matches the OPT# code for your unit
as per the chart above.
OPT1 OPT2
OPT3 Displayed example
he Remote Control not being able to operate the Air Conditioning Unit properly.
The unit’s
Remote Control configured for use with air conditioner
Key once to illuminate the Air Conditioning Unit’s display.
Air Conditioner Unit’s Display
Figure 1
(see example below Fig 1)
77
Page 79
Kühl Remote Control
Step 4 Checking the Remote Control’s OPT # Code With the Remote Control’s display illuminated, press and hold the Remote Control’s
SCHEDULE and the FAN SPEED Keys simultaneously for approximately 6 seconds until
the Remote Control displays its current OPT# Code.
If the OPT# Code is different than the AC Unit’s OPT# Code see instructions below:
Remote Control Remote Control’s OPT# Code
Figure 2
(see example below Fig 2)
Using the Remote Control’s S Increase
or d Decrease Keys, change th e OPT# Code
displayed on the Remote Control to match the OPT # Code shown on the Air
Conditioning Unit’s display
(see examples below)
.
Air Conditioning Unit Display Remote Control Display
Step 5. To save the setting in the Remote Control, press and hold the Remote Control SCHEDULE
and FAN SPEED Key simultaneously for approximately 6 seconds until the displayed configuration number on the Remote Control flashes.
The Remote Control is now configured to work with the air conditioner.
78
Page 80
Kühl User Interface Service Kit
Replacement Instructions
For Use with Kühl (cool only models) and Kühl + (cool and heat models) ATTENTION! - Please read these instructions completely before attempting replacement.
Always unplug the power supply from the power supply receptacle. Contents:
User Interface (UI)
Ribbon Cable
2 – Mounting screws for UI
Instruction Sheet
Step 1. Disconnect ribbon cable by pulling straight out Step 2. Remove 2 –mounting screws securing UI and disconnect ribbon cable Step 3. Remove UI and ribbon cable from handle assembly Step 4. Install new UI using the 2-screws, route new ribbon cable and reattach ribbon cable to UI
and Main control board
Step 5. Verify control operation
Ribbon cable connection
Mounting screws
79
Page 81
INSTRUCTIONS FOR USING COOLING LOAD ESTIMATE
FORM FOR ROOM AIR CONDITIONERS
(AHAM PUB. NO. RAC-1)
A. This cooling load estimate form is suitable for estimating the cooling load for comfort air conditioning installations
which do not require specifi c conditions of inside temperature and humidity.
B. The form is based on an outside design temperature of 95°F dry bulb and 75°F wet bulb. It can be used for areas
in the continental United States having other outside design temperatures by applying a correction factor for the particular locality as determined from the map.
C. The form includes “day” factors for calculating cooling loads in rooms where daytime comfort is desired (such as
living rooms, offi ces, etc.)
D. The numbers of the following paragraphs refer to the corresponding numbered item on the form:
1. Multiply the square feet of window area for each exposure by the applicable factor. The window area is the area of the wall opening in which the window is installed. For windows shaded by inside shades or venetian blinds, use the factor for “Inside Shades.” For windows shaded by outside awnings or by both outside aw­nings and inside shades (or venetian blinds), use the factor for “Outside Awnings.” “Single Glass” includes all types of single thickness windows, and “Double Glass” includes sealed airspace types, storm windows, and glass block. Only one number should be entered in the right hand column for Item 1, and this number should represent only the exposure with the largest load.
2. Multiply the total square feet of all windows in the room by the applicable factor.
3a. Multiply the total length (linear feet) of all walls exposed to the outside by the applicable factor. Doors should
be considered as being part of the wall. Outside walls facing due north should be calculated separately from outside walls facing other directions. Walls which are permanently shaded by adjacent structures should be considered “North Exposure.” Do not consider trees and shrubbery as providing permanent shading. An uninsulated frame wall or a masonry wall 8 inches or less in thickness is considered “Light Construction.” An insulated wall or masonry wall over 8 inches in thickness is considered “Heavy Construction.”
3b. Multiply the total length (linear feet) of all inside walls between the space to be conditioned and any uncondi-
tioned spaces by the given factor. Do not include inside walls which separate other air conditioned rooms.
4. Multiply the total square feet of roof or ceiling area by the factor given for the type of construction most nearly describing the particular application (use one line only.)
5. Multiply the total square feet of fl oor area by the factor given. Disregard this item if the fl oor is directly on the ground or over a basement.
6. Multiply the number of people who normally occupy the space to be air conditioned by the factor given. Use a minimum of 2 people.
7. Determine the total number of watts for light and electrical equipment, except the air conditioner itself, that will be in use when the room air conditioning is operating. Multiply the total wattage by the factor given.
8. Multiply the total width (linear feet) of any doors or arches which are continually open to an unconditioned space by the applicable factor.
NOTE: Where the width of the doors or arches is more than 5 feet, the actual load may exceed the calculated
value. In such cases, both adjoining rooms should be considered as a single large room, and the room air conditioner unit or units should be selected according to a calculation made on this new basis.
9. Total the loads estimated for the foregoing 8 items.
10. Multiply the subtotal obtained in item 9 by the proper correction factor, selected from the map, for the particular locality. The result is the total estimated design cooling load in BTU per hour.
E. For best results, a room air conditioner unit or units having a cooling capacity rating (determined in accordance
with the NEMA Standards Publication for Room Air Conditioners, CN 1-1960) as close as possible to the estimated load should be selected. In general, a greatly oversized unit which would operate intermittently will be much less satisfactory than one which is slightly undersized and which would operate more nearly continuously.
F. Intermittent loads such as kitchen and laundry equipment are not included in this form.
80
Page 82
COOLING LOAD ESTIMATE FORM
HEAT GAIN FROM
1. WINDOWS: Heat gain from the sun.
Northeast East Southeast South Southwest West Northwest North
2. WINDOWS: Heat by conduction
(Total of all windows.) Single glass Double glass or glass block
3. WALLS: (Based on linear feet of wall) a. Outside walls North Exposure Other than North exposure b. Inside Walls (between conditioned and
unconditioned spaces only.)
4. ROOF OR CEILING: (Use one only) a. Roof, uninsulated b. Roof, 1 inch or more insulation c. Ceiling, occupied space above d. Ceiling, insulated, with attic space above e. Ceiling, uninsulated, with attic space above
* These factors are for single glass
only. For glass block, multiply the above factors by 0.5; for double glass or storm windows, multiply the above factors by 0.8.
QUANTITY
___ _sq. ft. ___ _sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft.
____sq. ft. ____sq. ft.
____ ft. ____ ft.
____sq. ft.
____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft.
FACTORS
DAY
No
Shades*
60 80 75
75 110 150 120
0
Light Construction
30 60
Inside
Shades*
Outside
Awnings*
25 40 30 35 45 65 50
0
20 ____ 25 ____ 20 ____ 20 ____ 30 ____ 45 ____ 35 ____
0 ____
14
7
Heavy Construction
30
19
8 3 5
12
BTU/Hr.
(Quantity x Factor)
(Area
X Factor)
____
Use
____
only
____
the
load.
Use only
one.
____ ____ ____ ____ ____
_____ _____
_____ _____
_____
_____ _____ _____ _____ _____
largest
20 30
5. Floor: (Disregard if fl oor is directly on ground or
over a basement.
6. NUMBER OF PEOPLE
7. LIGHTS AND ELECTRICAL EQUIPMENT IN USE
8. DOORS AND ARCHES CONTINUOUSLY OPENED TO UNCONDITIONED SPACE: (TOTAL
LINEAR FEET OF WIDTH.)
9. SUBTOTAL
10. TOTAL COOLING LOAD (BTU per hour to be used
for selection of room air conditioner(s).)
____ Total in Item 9 X ____ (Factor from Map) = ____
____sq. ft.
____
____watts
____ft.
*****
3
600
3
300
*****
_____
_____
_____
_____
_____
81
Page 83
HEAT LOAD FORM
The heat load form on the following page may be used by servicing personnel to determine the heat loss of a conditioned space and the ambient winter design temperatures in which the unit will heat the calculated space.
The upper half of the form is for computing the heat loss of the space to be conditioned. It is necessary only to insert the proper measurements on the lines provided and multiply by the given factors, then add this result for the total heat loss in BTU/Hr./°F.
The BTU/Hr. per °F temperature difference is the 70°F inside winter designed temperature minus the lowest outdoor ambient winter temperature of the area where the unit is installed. This temperature difference is used as the multiplier when calculating the heat loss.
The graph shows the following:
Left Hand Scale Unit capacity BTU/Hr. or heat loss
BTU/Hr.
Bottom Scale Outdoor ambient temperature, base
point.
Heat Pump Model BTU/Hr. capacity heat pump will
deliver at outdoor temperatures.
Following is an example using the heat load form:
A space to be conditioned is part of a house geographically located in an area where the lowest outdoor ambient winter temperature is 40°F. The calculated heat loss is 184 BTU/ Hr./°F.
Subtract 40°F (lowest outdoor ambient temperature for the geographical location) from 70°F (inside design temperature of the unit) for a difference of 30°F. Multiply 184 by 30 for a 5500 BTU/Hr. total heat loss for the calculated space.
On the graph, plot the base point (70°) and a point on the 40°F line where it intersects with the 5500 BTU/Hr. line on the left scale. Draw a straight line from the base point 70 through the point plotted at 40°F. This is the total heat loss line.
Knowing that we have a 5500 BTU/Hr. heat loss, and we expect that our heat pump will maintain a 70°F inside temperature at 40°F outdoor ambient, we plot the selected unit capacity BTU/Hr. of the unit between 35° and 60° on the graph and draw a straight line between these points. Where the total heat loss line and the unit capacity line intersect, read down to the outdoor ambient temperature scale and fi nd that this unit will deliver the required BTU/Hr. capacity to approximately 30°F.
Balance Point Maximum BTU/Hr. heat pump
will deliver at indicated ambient temperature.
82
Page 84
HEATING LOAD FORM
FRIEDRICH ROOM UNIT HEAT PUMPS
BTU/HR PER WALLS: (Linear Feet) °F TEMP. DIFFERENCE 2” Insulation Lin. Ft. x 1.6 Average Lin. Ft. x 2.6
WINDOWS & DOORS (Area, sq. ft.) Single Glass: Sq. Ft. x 1.13 Double Glass: Sq. Ft. x 0.61
INFILTRATION - WINDOWS & DOORS: AVG. Lin. Ft. x 1.0 Loose Lin. Ft. x 2.0
CEILING: (Area, Sq. Ft.) Insulated (6”) Sq. Ft. x 0.07 Insulated (2”) Sq. Ft. x 0.10 Built-up Roof (2” insulated Sq. Ft. x 0.10 Built-up Roof (1/2” insulated) Sq. Ft. x 0.20 No Insulation Sq. Ft. x 0.33
FLOOR: (Area, Sq. Ft.) Above Vented Crawl space Insulated (1:) Sq. Ft. x 0.20 Uninsulated Sq. Ft. x 0.50 * Slab on Ground Lin. Ft. x 1.70 1” Perimeter insulation Lin. Ft. x 1.00 * Based on Linear Feet of outside wall TOTAL HEAT LOSS PER °F BTU/HR/°F
Multiply total BTU/HR/°F X 30 and plot on the graph below at 40°F. Draw a straight line from the 70 base point thru the point plotted at 40°F. The intersection of this heat loss line with the unit capacity line represents the winter design heating load.
83
Page 85
Friedrich Air Conditioning Company
P.O. Box 1540
San Antonio, TX 78295
210.357.4400
www.friedrich.com
ROOM AIR CONDITIONERS
LIMITED WARRANTY
FIRST YEAR
ANY PART: If any part supplied by FRIEDRICH fails because of a defect in workmanship or material within twelve months from date of original
purchase, FRIEDRICH will repair the product at no charge, provided room air conditioner is reasonably accessible for service. Any additional labor cost for removing inaccessible units and/or charges for mileage related to travel by a Service Agency that exceeds 25 miles one way will be the responsibility of the owner. This remedy is expressly agreed to be the exclusive remedy within twelve months from the date of the original purchase.
SECOND THROUGH FIFTH YEAR
SEALED REFRIGERANT SYS TEM : If the Sealed Refrigeration System (de ned for this purpose as the compressor, condenser coil, evaporator
coil, reversing valve, check valve, capillary, fi lter drier, and all interconnecting tubing) supplied by FRIEDRICH in your Room Air Conditioner fails because of a defect in workmanship or material within sixty months from date of purchase, FRIEDRICH will pay a labor allowance and par ts necessary to repair the Sealed Refrigeration System; PROVIDED FRIEDRICH will not pay the cost of diagnosis of the problem, removal, freight charges, and transportation of the air conditioner to and from the Service Agency, and the reinstallation charges associated with repair of the Se aled R efr ige rat ion Sys tem. A ll such cos t will be the sole re spo nsi bil ity of t he own er. T his rem edy is exp res sly agr eed to be the exclusive remedy within sixty months from the date of the original purchase.
APPLICABILITY AND LIMITA TIONS: This warrant y is applicable only to units retained within the Fif ty States of the U.S.A., District of Columbia, and Canada. This warranty is not applicable to:
1. Air fi lters or fuses.
2. Products on which the model and serial numbers have been removed.
3. Products which have defects or damage which results from improper installation, wiring, electrical current characteristics, or maintenance; or caused by accident, misuse or abuse, fi re, fl ood, alterations and/or misapplication of the product and/or units installed in a corrosive atmosphere, default or delay in performance caused by war, government restrictions or restraints, strikes, material shortages beyond the control of FRIEDRICH, or acts of God.
OBT AINING WARRANTY PERFORMANCE: Service will be provided by the FRIEDRICH Authorized Dealer or Service Organization in your area. They are listed in the Yellow Pages. If assistance is required in obtaining warranty performance, write to: Room Air Conditioner Service Manager, Friedrich Air Conditioning Co., P.O. Box 1540, San Antonio, TX 78295-1540.
LIMITATIONS: THIS WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES. Anything in the warranty notwithstanding, ANY IMPLIED WARRANTIES OF FITNESS FOR PARTICULAR PURPOSE AND/OR MERCHANTABILITY SHALL BE LIMITED TO THE DURATION OF THIS EXPRESS WAR RANTY. MANUFACTURER EX PR E S SLY DISCL A IMS AND E XCLUD E S A N Y LIABILI TY FOR CONS EQ U E NT I AL OR INCIDENTAL DAMAGE FOR BREACH OF ANY EXPRESSED OR IMPLIED WARRANTY.
Performance of Friedrich’s Warranty obligation is limited to one of the following methods:
1. Repair of the unit
2. A refund to the customer for the prorated value of the unit based upon the remaining warranty period of the unit.
Providing a replacement unit of equal value3.
The method of fulfi llment of the warranty obligation is at the sole discretion of Friedrich Air Conditioning.
NOTE: Some states do not allow limitations on how long an implied warranty lasts, or do not allow the limitation or exclusion of consequential or
incidental damages, so the foregoing exclusions and limitations may not apply to you.
OTHER: This warranty gives you speci c legal rights, and you may also have other rights which vary from state to state.
PROOF OF PURCHASE: Owner must provide proof of purchase in order to receive any warranty related ser vices.
All service calls for explaining the operation of this product will be the sole responsibility of the consumer. All warranty service must be provided by an Authori zed FRIED RICH Service Agency, unless authorized by FRIEDRICH prior to repairs being made.
(10 - 08)
84
Page 86
TECHNICAL SUPPORT
CONTACT INFORMATION
FRIEDRICH AIR CONDITIONING CO.
Post Offi ce Box 1540 · San Antonio, Texas 78295-1540 4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212 (210) 357-4400 · 877-599-5665 x 846 · FAX (210) 357-4490 Email: tac@friedrich.com www.friedrich.com
Printed in the U.S.A.
Page 87