Cabinet Parts Diagram.................................................................................................................. 15
Chassis Parts Diagram ................................................................................................................. 16
Parts List ...................................................................................................................................17-19
2
SPECIFICATIONS
SH14J30B-ASH20J30B-A
BTUH14000/1400019000/18800
E.E.R. - Btu/watt8.0/8.08.5/8.5
Volts230/208230/208
Hertz/Phase60/160/1
Amperes7.8/8.59.9/10.8
Total Watts1750/17502235/2210
Fuse/Breaker Size1520
Fan RPM10951095
Evaporator Air CFM375425
Dehumidification-Pts./hr .4.05.7
Width25-15/16”25-15/16”
Height15-15/16”17-15/16”
Depth27-3/8”27-3/8”
Min. Ext. into Room5-7/8”5-7/8”
Min. Ext to Outside16-15/16”16-15/16”
Net Weight129 Lbs.177 Lbs.
Shipping Weight147 Lbs.199 Lbs.
Maximum Temperature Rating1200 C (2480 F) Ignition Temperature Rating
for Class 1, Division 2, Group D
DISCHARGETEMPSUCTIONDISCHARGEAMPSLOCKEDCHARGE INCHARGE IN
AIRDROP °FROTOR AMPSOUNCESFLUID OZ.
SH14J30B-A
SH14J30B-A
SH20J30B-A
SH20J30B-A
* Rating Conditions: 80° F. Room Air Temperature and 59% Relative Humidity with 95° F. Outside Air Temperature at 40% Relative Humidity.
56.7823.22792967.8432832
8.5
52.8327.1679.52829.8523932
10.4
3
COMPONENT OPERATION AND TESTING
COMPRESSOR WINDING TEST (Figure 2.)
WARNING
DISCONNECT ELECTRICAL POWER TO
THE UNIT BEFORE SERVICING OR
TESTING
COMPRESSORS
Compressors are single phase, 208/230 volt. All
compressor motors are permanent split capacitor
type, using only a running capacitor across the start
and run terminal.
All compressors are internally spring mounted and
externally mounted on rubber isolators.
Line Voltage Overload
The compressor is equipped with an internal line
voltage overload. This overload is embedded in
the windings of the motor to sense the motor
temperature. The overload will open and
disconnect the power to the motor due to high
temperatures caused by:
Remove the compressor terminal box cover and
disconnect the wires from the terminals. Using an
ohmmeter , check continuity across the following:
FIGURE 2 COMPRESSOR WINDING TEST
Testing Procedures
1.Terminal "C" and "S" - no continuity open winding - replace compressor.
2.Terminal "C" and "R" - no continuity open winding - replace compressor.
1.A locked rotor .
2.Excessive running amps.
3.High discharge temperature.
4.Low refrigerant charge.
FIGURE 1 INTERNAL OVERLOAD
LINE BREAK
INTERNAL OVERLOAD
OHMMETER
3.Terminal "R" and "S" - no continuity
open winding - replace compressor.
4. Terminal "C" and the shell of the
compressor – continuity – grounded
motor – replace compressor.
5. Should continuity exist between
terminals "R" and "S", but not between
terminals "C" and "S" and "C" and "R",
the internal overload may be open. If
the compressor is extremely hot, allow
it sufficient time to cool. It may require
as long as one hour for the compressor
to cool sufficiently for the internal
overload to close.
4
GROUND TEST
LED indicates
contacts closed
when lit
Line side
Load side
FAN MOT OR (Figure 4)
Use an ohmmeter set on its highest scale. Touch
one lead to the compressor body (clean point of
contact, as a good connection is a must) and the
other probe in turn to each compressor terminal.
(See Figure 3.) If a reading is obtained, the
compressor is grounded and must be replaced.
FIGURE 3 TYPICAL GROUND TEST
CHECKING COMPRESSOR EFFICIENCY
The reason for compressor inefficiency is
normally due to broken or damaged suction and/
or discharge valves, reducing the ability of the
compressor to pump refrigerant gas.
This condition can be checked as
follows:
1. Install a piercing valve on the suction and
discharge or liquid process tube.
2. Attach gages to the high and low sides of the
system.
3. St art the system and run a "cooling or
heating performance test."
If test shows:
A 230 volt single phase permanent split capacitor
motor is used to drive the evaporator blower and
condenser fan. A running capacitor is wired across
the start and run terminals of the motor .
The motor is totally enclosed and is protected with
a line voltage overload located internally of the
motor. The motor shaft is stainless steel to resist
corrosion.
FIGURE 4 FAN MOT OR
FAN MOTOR – TEST
Disconnect power to the unit.
1. Determine that the capacitor is serviceable.
2. Disconnect the black lead from the circuit
board.
3. Apply "live" test cord leads to the common
terminal of the capacitor and the black lead.
The motor should run at high speed.
SOLID STATE RELAY (Figure 5)
Two 50 amp rated 208/230 volt solid st ate relays
are used to energize the compressor and fan motor .
Terminals 3 and 4 are the 208/230 volt line side.
T erminals 1 and 2 are load side cont acts.
FIGURE 5 SOLID ST A TE RELA Y
A. Below normal high side pressure.
B. Above normal low side pressure.
C. Low temperature difference across the coil.
The compressor valves are faulty replace the compressor .
5
SYSTEM CONTROL SWITCH (Figure 6)
CAPACITOR – TEST
This switch is double pole, single throw. Check for
continuity between terminals 2 and 3, and 5 and 6.
FIGURE 6 SWITCH, ON-OFF
CAPACITOR, RUN
A run capacitor is wired across the auxiliary and
main winding of a single phase permanent split
capacitor motor such as the compressor and fan
motors. A single capacitor can be used for each
motor or a dual rated capacitor can be used for
both.
The capacitor’s primary function is to reduce the
line current while greatly improving the torque
characteristics of a motor. The capacitor also
reduces the line current to the motor by improving
the power factor of the load. The line side of the
capacitor is marked with a red dot and is wired to
the line side of the circuit (see Figure 7.)
FIGURE 7 RUN CAP ACITOR HOOK–UP
COMPRESSOR
FAN
MOTOR
1.Remove the capacitor from the unit.
2. Check for visual damage such as bulges,
cracks, or leaks.
3.For dual rated capacitors, apply an ohmmeter
lead to the common (C) terminal and the other
probe to the compressor (HERM) terminal. A
satisfactory capacitor will cause a deflection
on the pointer, then gradually move back to
infinity.
4. Reverse the leads of the probe and
momentarily touch the capacitor terminals. The
deflection of the pointer should be two times
that of the first check if the capacitor is good.
5.Repeat steps 3 and 4 to check the fan motor
capacitor.
NOTE: A shorted capacitor will indicate a low
resistance and the pointer will move more to the
“0” end of the scale and remain there as long as
the probes are connected. An open capacitor
will show no movement of the pointer when
placed across the terminals of the capacitor.
THERMOSTAT
A cross ambient
thermostat is used
to maintain the
desired comfort level.
The thermostat reacts only
to a change in temperature
at the bulb location.
Important to the
successful operation
of the unit is the position
of the sensing bulb in
relation to the evaporator
(see Figure 8).
FIGURE 8
SENSING BULB
LOCA TION
RED DOT
RUN CAPACITOR
6
RANGE:
Thermostat
(Part No. 618-225-02)
60° F ( ± 2° ) to 90° F( ± 4° )
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.