FRIEDLAND Wirefree AlarmInterface Module Installation And Operating Instructions Manual

Wirefree Alarm
Interface Module
Installation and Operating Instructions
These instructions should be read in conjunction with your Alarm System Installation and Operating Manual and the Smoke Alarm instructions, the
should be retained for future reference.
DECLARATION
Friedland hereby declares that this wirefree Alarm Interface Module is in compliance with the essential requirements and other relevant provisions of the R&TTE directive, 1999/5/EC.
INTRODUCTION
This Interface Module is designe d for use with Friedland Wirefree Intruder Alarm systems incorporating a suitable Control Panel and operating at 433MHz only .
When the connected Smoke Alarm activates, the Interface Module provides a link to the alarm system that will generate an alarm on your security system.
POSITIONING THE INTERFACE MODULE AND SMOKE ALARM
The Smoke Alarm and Interface Module are suitable for mounting in dry interior lo cat ions on ly.
The Smoke Alarm must be positioned according to the guidelines stated in its instruction manual.
In addition, the Interface Module must be mounted within the specified radio range of 50m to the Control Panel. Don’t forget to allow for any obstructions in between that may reduce this range. Take care not to position the device directly onto, behind or very close to metalwork, as this could affect the operating range of your system.
Note: If using the interconnect feature on the smoke alarm then only one Alarm Interface Module should be connected to a single Smoke Alarm only.
1 Wiref
ree Alarm Interface Module
CONFIGURING THE INTERFACE MODULE AND SMOKE ALARM
Configuration
Switches
Configuring the Interface Module:
1) Remove the rear cover by inserting a small coin between the front and back covers and gently twisting.
The procedures described in this section should be undertaken on a table to ensure that the Interface Module and Smoke
A
larm are correctly setup and operating before fixing the devices in position on the ceiling.
Inside the Interface Module are two jumper links and a series of twelve 3-position switches. These are used to configure the device for use with the Smoke Alarm and your alarm system.
2) Jumper link S1 must be connected across pins marked “G” and “C”.
Terminal Block
Tamper Switch
Jumper S1
3 ) Jumper Link S2 must be fitted
in position across the pins.
4 ) Set switches 1-8 to the same
alarm system house code as configured into all other alarm system devices.
House Code Interface Remote Control
setting DIP switch DIP switch
+ 1 On / Up
-0 Off / Down
Jumper S2
For example; an alarm system house code of 1101 0011 will
Wirefree Alarm Interface Module 2
Loading...
+ 7 hidden pages