FRIEDLAND SA5 Installation And Operating Manual

Installation & Operating Manual
SA5
6 Zone Communicating
Wirefree Alarm System
FOREWORD
All components in this wirefree Alarm System are
The system is designed for ease of installation using only conventional domestic tools. However, it is essential that the installer reads and fully understands the advice and procedures contained in this manual and plans the system before proceeding with the installation.
During installation, it is important that the procedures described in this manual are followed in sequence.
This manual should be retained in a safe place for
future reference.
IMPORTANT
All components are suitable for mounting in dry interior
locations only.
DECLARATION
Friedland hereby declares that this wirefree alarm
system is in compliance with the essential requirements and other relevant provisions of the Radio and Telecommunications Terminal Equipment (R&TTE) directive, 1999/5/EC.
Tools and Equipment Required:
No.0 Philips Screwdriver Drill
No.1 Philips Screwdriver Small Spirit Level No.2 Philips Screwdriver Bradawl 5 & 6mm Masonry Drill Bits
IMPORTANT
Local Authority Regulations And Legislation'.
This alarm system should be installed and operated in
accordance with the requirements of any current local and/or national regulations and legislation. We recommend that you contact your authority to obtain details of any your area's requirements local and/or national regulations.
For example in Belgium, the installation and use of an alarm system including notification by telephone (Voice Dialler) functionality and the optional use of an external siren is controlled by Belgium legislation "KB" of 19/06/2002.
DEVICE RANGE
The quoted range of the system devices (see
component specification on rear cover) is measured in ideal conditions. Any solid object (e.g. walls, ceilings, reinforced PVC doors etc) placed between the transmitter and Receiver Devices and the Chime Unit will reduce the transmission range of the devices.
The amount by which the range will be reduced is dependant upon the nature of the barrier. e.g.
Wall Type Range Reduction
Dry-lined partition wall: 10-30%
Single layer brick wall: 20-40% Double layer brick wall: 30-70% Metal Panel/Radiator: 90-100%
Note: The effect on the range of multiple walls is
cumulative. i.e. if there are two brick walls in the way, the range will be reduced by up to 40% by each wall.
SYSTEM SECURITY
This system has been designed to both detect
intruders and act as a strong deterrent to would-be intruders when installed correctly.
Please remember that given adequate knowledge and time it is possible to overcome any alarm system and we therefore recommend that an Intruder Alarm is used in conjunction with good physical protection such as security window and door locks.
All units in the system are encoded to operate together using an 8 bit House Code which is configured by the user/installer to provide the identification code for your installation. The system House Code can be changed at any time by the user.
The system is operated from one or more Remote Control units and/or the Control Panel. Care should be taken to ensure that your Remote Control Unit(s) are not lost or the User Access Codes for the Control Panel do not become known to other people as this will compromise the security of your system. In either event the system house code and User Access Codes should be changed as soon as possible.
SAFETY
Always follow the manufacturers advice when using
power tools; steps, ladders etc. and wear suitable protective equipment (e.g. safety goggles) when drilling holes etc.
Before drilling holes in walls, check for hidden electricity cables and water pipes, the use of a cable/pipe locater maybe advisable if in doubt.
When using ladders, ensure that they are positioned on a firm stable surface at the correct angle and suitably secured before use.
The use of ear defenders is advisable when working in close proximity to the Siren due to the high sound level produced by this device.
SA5 6 Zone Communicating Wirefree Alarm SystemFriedland
IMPORTANT: All units in your system must be set
to the same House Code which must be changed from the factory supplied setting.
CONTENTS
Page No.
KIT CONTENTS 2
INTRODUCTION AND OVERVIEW 3
Multiple Users 3 System Arming 3 Entry/Exit Delay 3 Zones 3 Zone Lockout 3 Quick Set 4 Final Exit Set Zone 4 Walk Through Zone 4 Omit Zone 4 Event Log 4 Chime 4 Voice Dialler 4 Remote Manager 4 Latch-Key 4 Answer-Phone 5 Voice Memo 5 Remote Phone Access and Control 5 Tamper Protection 5 Jamming Detection 5 Battery Monitoring 5 System House Code 5
PLANNING YOUR ALARM SYSTEM 6
REMOTE CONTROL UNIT 7
General Information 7 Configuring the Remote Control 7
CONTROL PANEL 8
Positioning the Control Panel 8 Installing the Control Panel 8 Configuring the Control Panel House Code 10 Testing the Control Panel & Remote Control 10
PASSIVE INFRA RED (PIR) MOVEMENT DETECTORS 11
Positioning the PIR Movement Detectors 11 Installing and Configuring the PIR
Movement Detectors 12 Testing the PIR Movement Detectors 13
MAGNETIC CONTACT DETECTORS 14
Positioning the Magnetic Contact Detectors 14 Installing and Configuring the
Magnetic Contact Detector 14 Testing the Magnetic Contact Detector 15
EXTERNAL CONNECTIONS 16
Page No.
TESTING THE SYSTEM 17
Initial Testing 17 Testing an Installed System 17
DEFAULT SETTINGS 19
Reset Factory Default Conditions 19
PROGRAMMING 20
Navigating through the Programming Mode Menus 20
Telephone Application Setup 21
Voice Dialler 21 Remote Manager 21 Answer-Phone 21 Latch Key 21
User Setup 21
System Setup 22 Zone Setup 25 Voice Dialler Setup 27 Full Arm Setup 29 Part-Arm 1 Setup 30 Part-Arm 2 Setup 31 Time & Date Setup 32 Latch Key Setup 32 Answer Phone Setup 33 Remote Manager Setup 34
OPERATING INSTRUCTIONS 35
Arming the System 35 Part-Arming the System: Part-Arm 1 35 Part-Arming the System: Part-Arm 2 35 Disarming the System 36 Quick Set 36 Omit Zone 36 Personal Attack (PA) Alarm 36 Tamper 36 Chime 36 Event-Log 37 Leaving a Voice Memo Message 37 Replaying and Deleting Messages
at the Control Panel 37 Remote Phone Access and Control 37 Solar Siren Service and Operating Modes 38 Battery Monitoring 39
MAINTENANCE 40
ALARM RECORD 41
TROUBLE SHOOTING 42
EXTENDING YOUR ALARM SYSTEM 45
COMPONENT SPECIFICATION Back Cover
1SA5
KIT CONTENTS
The Alarm System should contain the following
components.
1xControl Panel 1xRemote Control 1xPIR Movement Detector 1xMagnetic Contact Detector
Also included:
Telephone Connection Lead
Power Supply Adaptor Installation & Operating Manual Fixing pack Batteries
2 SA5
WP1.2-6
Control Panel
6V/1.2Ahr
Sealed lead acid battery
(supplied fitted in
Control Panel)
9V PP3
Alkaline battery
(for PIR Detector)
3V CR2032 Lithium
Coin Cell (for
Remote Control
and Magnetic
Contact Detector)
Magnetic Contact
Detector
Remote Control
PIR Movement
Detector
MULTIPLE USERS
The system allows for up to 6 Users and a Master User
to be configured. This allows the system Event Log to maintain a record of which users have armed and disarmed the system. Each user will have a different Access Code. In addition a 4 second voice recorder facility enables the users name to be recorded for use with the Latch-Key facility.
Only the Master User has access to the programming functions and is able to configure the system.
Note: Any Remote Control Units on the system will be
recorded as User 6.
SYSTEM ARMING
The system has a full ‘Arm’ and a ‘Part-Arm’ mode.
Full ARM will arm all zones while the ‘Part-Arm’ mode will only arm the zones that are enabled for “Part-Arm”.
For example:
The system could be configured such that during night
time, ‘Part-Arm 1’ would arm only zones protecting the lower floor and outbuildings leaving the upper floor free for movement without triggering the alarm.
During the day while the property is occupied ‘Part-Arm 2’ would arm only the zones protecting the outbuildings. However, when the property is left un-occupied, the full ‘Arm’ mode will arm all zones to protect the entire property, (i.e. upper and lower floors and outbuildings).
ENTRY/EXIT DELAY
When the system is armed with the Exit-Delay enabled,
no alarm signal from any detector on an active zone will be able to initiate an alarm until the Exit-Delay has expired. This enables the system to be armed from within the property and allows time for the user to exit the property without triggering an alarm. If the Exit-
Delay is disabled then detectors on active zones will immediately be able to initiate an alarm as soon as the system begins to arm.
The system Exit-Delay may be configured for between 10 to 250 seconds or disabled completely.
If a detector on a zone with its Entry-Delay enabled is triggered, then an alarm condition will not occur until the Entry-Delay period has expired. This allows time for the user to re-enter the property and disarm the system before an alarm condition occurs. Generally only the zones on the main entry route to the property will be configured with an Entry-Delay. The remaining zones would be configured with their Entry-Delay disabled allowing them to immediately initiate an alarm the instant a detector on the zone is triggered.
The Entry-Delay for each zone may be configured for between 10 to 250 seconds or disabled completely.
Note: To conserve power and maximise battery life
the PIR Detector will only detect movement if there has been no movement detected within the previous 2 minutes. Consequently the PIR Detector will not become active until the protected area has been free from movement for more than 2 minutes.
ZONES
The system incorporates 6 wirefree Alarm Zones for
the connection of the system detectors that are used to independently monitor different areas of the property. In addition to standard intruder protection, each zone may also be configured to operate in one of four other modes:
– ‘Personal Attack’ mode provides 24 hour monitoring
of any Personal Attack (PA) switches incorporated into the system.
– ‘24-hour Intruder’ mode provides 24 hour intruder
protection for areas where continuous monitoring is required, (e.g. gun cupboards).
– ‘Fire’ mode provides 24 hour monitoring of any
Fire/Smoke detectors incorporated into the system.
In addition there is the facility to connect 4 hard wired zones to the Control Panel, each of which is fully configurable with the same features as the wirefree zones.
ZONE LOCKOUT
If a detector on an active zone is triggered while the
system is armed an alarm condition will occur. After the programmed alarm duration has expired the alarm
Full Arm
Full Arm Part-Arm
INTRODUCTION AND OVERVIEW
SA5 3
INTRODUCTION
will stop and the system will automatically reset.
Subsequent detectors triggered will again initiate an alarm condition. If a single zone initiates an alarm condition more than three times then that zone will be ‘Locked Out’ and any further alarm signals from that zone will be ignored until the system is disarmed.
Note: The ‘Zone Lockout’ feature can be disabled if
required.
QUICK SET
The system may be fully armed in 5 seconds using the
quick set facility, overriding the programmed exit­delay. This is useful for setting the system at night when the exit-delay warning beep will be silenced after just a few seconds.
FINAL EXIT SET ZONE
Triggering a detector on a Final Exit zone during the
exit-delay will cause the delay to reset to 5 seconds with the system arming 5 seconds later.
WALK THROUGH ZONE
This feature may be used to temporarily disable
detectors on zones covering the route between the main entry door and the Control Panel.
If the system is armed and the property is accessed via the “Entry-Door” zone then the setup entry-delay will operate as normal. However all “Entry-Route “ zones will be disabled to allow free access to the Control Panel to Disarm the system before the entry-delay on the “Entry-Door” zone expires an alarm occurs.
If access is gained via any zone that is not configured as the “Entry-Door” then all zones (including those setup as the “Entry-Route” will operate as normal according to their normal configuration.
Note: The zone configured as the “Entry Door” must be
setup with an Entry-Delay sufficient to reach the Control Panel and Disarm the system. Zones configured as the “Entry Route” should be setup without an Entry-Delay.
OMIT ZONE
A zone may be temporarily omitted when the system is
armed using the Omit feature. When the system is next disarmed any zones set to Omit will be cancelled.
EVENT LOG
The Control Panel incorporates a memory capable of
storing the last 50 system events. This enables the user to see which user has Armed/Disarmed the system and if and when any alarms occurred. The time, date and details of the event type will be recorded for each system event.
CHIME
Chime is a low security facility for use when the system
is Standby mode. If the Chime feature is ON, and a detector on a zone that has its Chime function enabled is triggered, the internal sounder will produce a low volume warning tone. A typical use of the Chime function would be to warn that a door or particular area has been accessed.
VOICE DIALLER
This system incorporates a telephone voice dialler that
is used to call for help and/or notify the user that the system has been triggered and an alarm has occurred.
If the Voice Dialler is enabled and an alarm condition occurs, the system will call for help using your recorded alarm message and up to four telephone numbers. When the telephone voice dialler is activated it will call the first enabled number in the dialling sequence and replay the recorded alarm messages for the configured ‘Play Time’. The recipient must acknowledge the message by pressing the button on their telephone keypad. If the call is unanswered or an acknowledgment signal is not received then the next active number in the dialling sequence will be called. The dialler will continue calling each number in turn until either all numbers in the sequence have been dialled the set number of times or the dialling sequence is cancelled by an acknowledged signal from the recipient.
REMOTE MANAGER
As an alternative to the Voice Dialler the system may
be configured to interface direct with an Alarm Monitoring Service using the Ademco Contact ID communications protocol.
This is an independent service not provided by Novar Friedland.
Note: Remote Manager may not be supported in all
countries. Please refer to enclosed literature, or contact your local help line for availability.
LATCH KEY
When the system is disarmed the Latch-Key facility,
if enabled, will call the first latchkey phone number and replay the user message (recorded under user setup) for the set ‘Play Time’. The recipient must acknowledge the message by pressing the button on their telephone keypad. If the call is unanswered or an acknowledgment is not received then the second latchkey phone number will be called. The voice dialler will continue calling each number in turn until each number has been dialled the set number of times or the sequence is cancelled/acknowledged by the recipient.
SA54
INTRODUCTION
SA5 5
INTRODUCTION
For example, the latchkey facility is useful to inform
parents that a child has returned from school and disarmed the system.
ANSWER PHONE
The Control Panel includes an answer-phone facility.
The answer phone will record and store a maximum of 6 messages with each message being limited to a 30s duration.
Messages may be retrieved either direct from the Control Panel or by dialling into the system from a phone.
VOICE MEMO
In addition it is also possible to record messages at
the Control Panel using the ‘Voice-Memo’ facility. Each voice-memo message is limited to a maximum duration of 30s and counts as an answer phone message.
REMOTE PHONE ACCESS
AND CONTROL
It is possible to dial into the system via the connected
telephone line to interrogate the system status and to have basic control over the system, (e.g. to Arm and Disarm the system). You may also activate the microphone on the control panel to Listen-In to what is happening in the protected property.
Answer phone and Voice-memo messages may also be accessed remotely.
TAMPER PROTECTION
All system devices (except any Remote Control Units)
incorporate Tamper protection features to protect against unauthorised attempts to interfere with the device.
Any attempt to remove the battery cover from any device (except a Remote Control) or to remove the Control Panel from the wall will initiate an alarm condition (unless the system is in Test or Programming modes), even if the system is Disarmed.
JAMMING DETECTION
In order to detect any attempts to illegally jam the radio
channel used by your alarm system, a special jamming detection function is incorporated into the Control Panel and optional Solar Siren. If this feature is enabled, and the radio channel is jammed continuously for 30 seconds, when the system is armed, the Solar Siren will emit a pre-alarm series of rapid beeps for 5 seconds. If the jamming continues for a further 10 seconds or more a full alarm condition will occur. In addition if the system is jammed for more than three
periods of 10 seconds in a 5 minute interval, this will also generate a Full Alarm condition.
The Jamming Detection circuit is designed to permanently scan for jamming signals. However, it is possible that it may detect other local radio interference operating legally or illegally on the same frequency. If it is planned to operate the jamming detection feature we recommend that the system is monitored for false jamming alarms for at least 2 weeks prior to leaving the Jamming Detection function permanently enabled.
Note: The jamming detection features incorporated
into the Control Panel and optional Solar Siren operate independently.
BATTERY MONITORING
All devices powered by non-rechargeable batteries
incorporate a battery level monitoring feature which will warn of a low battery status. In addition the Control Panel will also indicate a low battery status within any Passive Infra-Red or Magnetic Contact Detector on the system. The batteries on any device indicating a low battery status should be replaced immediately.
SYSTEM HOUSE CODE
In order to prevent any unauthorised attempt to
operate or disarm your system, you must configure your system to accept radio signals only from your own system devices. This is done by setting a series of eight miniature (DIP) switches in all devices (except the Control Panel) to the same ON/OFF combination (the House Code) selected by the user/installer. The Control Panel is then programmed to operate only with devices set to this House Code. All detectors and Remote Control Unit(s) must be configured with the same House Code in order for the system to operate correctly.
Note: It is recommended that the system House
Code is always changed to a code other than the factory setting.
SA56
INSTALLATION
Before attempting to install your Alarm System it is
important to study your security requirements and plan your installation.
PIR Movement Detectors are used to protect the main areas of the property, (e.g. lounge, study, hallway and landing). Magnetic Contact Detectors are typically used to protect the main access points to the property, (e.g. front door, back door, patio doors). However, they can also be used to protect other vulnerable doors/windows or access doors to important rooms.
TYPICAL INSTALLATION
The following example below shows typical property
incorporating the suggested positions for the Control Panel, PIR and Magnetic Contact Detectors and optional Solar Siren. Use this as a guide for your installation in conjunction with the detailed positioning requirements for each device provided in the appropriate installation sections in this manual for planning your intruder alarm system.
PLANNING YOUR ALARM SYSTEM
LCD Control Panel
Magnetic Contact Detector
Magnetic Contact Detector
External Solar Siren (Optional)
PIR Movement
Detector
PIR Movement
Detector
Remote Control
SHED
LOUNGE
GROUND FLOOR
GARAGE
KITCHEN
HALL
DINNING
ROOM
PIR Movement Detector
PIR Movement Detector
PIR Movemen
t
Detector
Back Door
SA5 7
INSTALLATION
The system default settings are pre-configured to
provide a basic functional system to suit most typical basic installations:
Zone 1 is configured as a Delay zone with a 30s
entry/exit delay
.
Any detectors covering the main door and the route to the Control Panel should be set on zone 1 only.
Zones 2-6 are configured as INSTANT without any
entry/exit delay.
The system has a 3 minute alarm duration.
Zone Lockout is enabled.
PART-ARM 1 is configured to operate with detectors
on zones 1 to 4 only. Detectors on zones 5 & 6 are inactive in Part-Arm 1.
PART-ARM 2 is OFF
All other system features, (e.g. telephone dialler,
answer phone, Latch-Key, Chime etc) are OFF or not programmed.
REMOTE CONTROL UNIT
The Remote Control Unit(s) are used to Arm, Part-Arm
and Disarm the system.
The Remote Control Unit also incorporates a Personal Attack (PA) switch. Activating the PA switch on the side of the Remote Control will immediately initiate a Full Alarm condition whether the system is Armed or Disarmed. The alarm can be cancelled by pressing the ’DISARM’ button on the Remote Control or via the Control Panel.
Any number of Remote Control Units can be used with your system, providing they are all coded with the system House Code.
The Remote Control is powered by a CR2032 type Lithium cell which under normal conditions will have an expected life in excess of 1 year. Under normal battery conditions the LED on the Remote Control will only illuminate when a button is pressed. However, under low-battery conditions this LED will continue to flash after the button has been released. When this occurs the battery should be replaced as soon as possible.
CONFIGURING THE REMOTE
CONTROL
1. Remove the rear cover by undoing the small screw
on the rear of the Remote Control.
2. Select and record a random combination of ‘ON’ and ‘OFF’ positions for the DIP switches. This will be the system House Code that enables all elements of your transmitters to communicate with the Control Panel.
IMPORTANT: The House Code for your system
should be changed from the factory default setting.
Slide up to operate
Transmit LED
Personal Attack
Disarm
Arm
Part-Arm
IMPORTANT:
All system components must be set to the same
House Code.
As soon as installation is complete
- The default Master User Access Code (1234) for the Control Panel should be changed to your own code that only you know.
- User Access Codes 1-6 for the Control Panel should be changed to your own codes that only the relevant system user knows.
- The system Time and Date must be configured.
3. Ensure that the jumper link located immediately
below the House Code DIP switches is fitted in position for use with this alarm system.
4. Insert the battery under the clip ensuring that the + terminal faces upwards away from the PCB.
5.
Replace the rear cover and fixing screw. Do not over tighten the screw as this could damage the thread
.
CONTROL PANEL
Outside View of Control panel
POSITIONING THE CONTROL PANEL
When choosing a suitable location for the Control
Panel, the following points should be considered.
1.
The Control Panel should be located in a position out of sight of potential intruders and in a safe location, but easily accessible for system operation.
2.
The Control Panel should be mounted on a sound flat surface to ensure that the rear tamper switch on the Control Panel is closed when the Panel is mounted. The Control Panel should be mounted at a convenient height of between 1.5 and 2m and in a position where it will be seen each day.
Note: If small children are in the household, a
further consideration should be given to keeping the units out of their reach.
3. It is recommended that the Control Panel should be positioned such that the Exit/Entry tone (emitted by the Control Panel) can be heard from outside the property.
4. The Control Panel should be mounted within a protected area so that any intruder cannot reach the Control Panel without opening a protected door or passing through an area protected by a PIR movement detector when the system is armed.
5. The Control Panel must be located within reach of a mains socket.
6.
If the telephone based functionality is to be used then the Control Panel will need connecting to a convenient telephone point.
Note: It is recommended that the telephone
connection lead is not extended beyond 5m before connecting to a telephone master or secondary outlet.
7. Do not locate the Control Unit closer than 1m to any large metallic object, (e.g. mirrors, radiators, etc.) as this may affect the radio range of the Control Panel.
INSTALLING THE CONTROL PANEL
1. Undo the two captive fixing screws on top of the
panel and open the cover. The cover is hinged along the bottom edge
2. Unclip and remove the two back-up batteries on either side of the panel.
3. Hold the Control Panel in position on the wall and mark the positions of the four fixing holes. Remove the Panel and drill four 5mm holes and fit the 25mm Wall Plugs.
Note: The wall plugs supplied with the product
are not suitable for plasterboard walls, if mounting the Control Panel onto plasterboard use appropriate wall plugs.
IMPORTANT: Do not drill the fixing holes with the
Control Panel in position as the resulting dust and vibration may damage the Control Panel’s internal components and invalidate the guarantee.
8 SA5
INSTALLATION
House Code
Dip Switches
Jumper Link
Battery Clip
Battery
LCD Display Window
Status Indicator LED
s
Keypad
SA5 9
INSTALLATION
4. Fit two 18mm No.4 screws into the top holes until
almost fully home and hang the Control panel over these screws using the two keyhole slots in the top corners of the panel casing.
5. Feed the connection plug and cable from the Power Supply Unit into the Control Panel from the rear through the cable entry hole below the battery on the right of the panel and connect the plug to the DC power socket. Ensure that the cable is not trapped between the panel and the wall.
6. Fix the Panel to the wall using two 18mm No.4 screws in the lower two fixing holes in the panel and tighten the upper fixing screws until they just grip the casing. Do not over tighten the fixing screws as this could damage or distort the casing.
7. Ensure that the "Reset" and the "Hard-Wired Siren tamper detect" jumper links are set in the OFF position.
8. Connect battery leads to both back-up batteries and refit batteries.
Battery 1 (left): Red lead to
+ve battery
terminal Blue lead to –ve battery
terminal
Battery 2 (right): Blue lead to +ve battery
terminal Black lead to –ve battery
terminal
IMPORTANT: Take care when connecting battery
leads to the batteries as connecting incorrectly could damage the batteries or the Control Panel.
Note: The Power LED may flash to indicate that
the unit is being operated from the back-up batteries and that mains supply is not present.
9. If fitted, remove the plastic film covering the LCD display and on the display window on the cover.
10. Close the lid of the Control Panel and tighten the captive fixing screws.
11. Plug in and switch ON the Power Supply Unit, (the Power LED should illuminate).
Upper Keyhole Fixing Hole
– ve Terminal (Black Lead)
+ ve Terminal (Blue Lead)
Reset Jumper Link P1
Power Supply Jack Socket
Upper Keyhole
Fixing Hole
+ ve Terminal
(Red Lead)
– ve Terminal
(Blue Lead)
Lower Fixing
Hole
External Tamper
Switch Jumper
Link P51
Power Supply Cable Access Hole
T1 T2 GND T3 T4 N.C. CN.O.GNDGND BUZ BUTTAMP GND B+ V+ OUT GND
Inside View of Control Panel
10 SA5
INSTALLATION
12. If required, connect the Control Panel to the
telephone line using the cable supplied by inserting small RJ11 plug into socket marked LINE located on the bottom edge of the Control Panel. If the cable supplied is not long enough to reach a suitable phone point then it will need extending using a coupler and extension lead (not supplied).
Note: If the Panel Tamper alarm sounds during the
installation reset the alarm by pressing:
, ,
on the Control Panel keypad.
CONFIGURING THE CONTROL PANEL
HOUSE CODE
With unit in Standby mode (Power LED only
illuminated).
1. Press , ,
‘1. USER SETUP’ will be displayed.
This puts the Control Panel into programming mode.
2. Use the and buttons to scroll through the menu until ‘2. SYSTEM SETUP’ is displayed
and press .
‘2-1 Learn House Code’ will be displayed.
3. Press .
The current House code setting will be displayed.
4. The new system House Code can be programmed either directly at the Control Panel or via a Remote Control Unit.
At the Control Panel:
Press buttons 1-8 on the Control Panel to
configure the display so that the required house code is displayed on the screen. As each button is pressed the corresponding digit in the house code will change to the opposite state, (“0” or “1”).
1=House Code DIP Switch On/Up
0=House Code DIP Switch Off/Down
Using a Remote Control:
With the required House Code already
configured on the Remote Control, press
.
The Control Panel will beep twice to acknowledge the signal. The display will change to show the received house code on lower line of the display beneath the corresponding DIP switch numbers (1-8).
5.
Press to save the new setting.
6.
Press , to return to Standby mode.
TESTING THE CONTROL PANEL
& REMOTE CONTROL
1. Press , ,
to put the system into Test mode.
‘TEST MODE – WALK TEST’ will be displayed.
2. Press to activate Walk Test.
‘Walk Test Waiting…’ will be displayed.
3. Press the buttons on the Remote Control in turn, as each button is pressed the Control Panel will beep and display the function of the button being pressed on the screen.
4. Test the range of the Remote Control by pressing the ‘DISARM’ button on the Remote Control from in and around the property and from all locations where you plan to install detectors. Check that the Control Panel acknowledges the signal from the Remote Control each time the ‘DISARM’ button is pressed.
5. Press to return to the top level menu of TEST MODE.
User Access Code
1 234
ENTER
User Access Code
1 234
ENTER
Master User Access Code
1 234
ENTER
ENTER
ENTER
ENTER
ESC
ESC
ESC
ENTER
PASSIVE INFRA RED (PIR)
MOVEMENT DETECTORS
PIR detectors are designed to detect movement in a
protected area by detecting changes in infra-red radiation levels caused for example when a person moves within or across the devices field of vision. If movement is detected an alarm signal will be generated, (if the system is armed). PIR detectors will also detect animals, so ensure that pets are not permitted access to areas fitted with Passive Infra Red Movement Detectors when the system is armed.
The Detector incorporates a tamper protection feature to protect against attempts to interfere with the device. If the battery cover is removed, an alarm will immediately occur at any time.
The Detector also incorporates a sensitivity adjustment feature to compensate for situations where the detector may be affected by environmental changes, (e.g. insects, air temperature, etc).
To conserve power and maximise battery life the PIR detector will only detect movement if there has been no movement detected within the previous 2 minutes.
The PIR Detector is powered by a PP3 Alkaline battery which under normal conditions will have an expected life in excess of 1 year. When the battery level drops, with the PIR in normal operation mode and the battery cover fitted, the LED behind the detection window will flash. When this occurs the battery should be replaced as soon as possible. (Note: in normal operation with the LED behind the lens will not flash on detection of movement).
Any number of PIR Movement Detectors can be used with your system, providing they are all coded with the system House Code and are mounted within effective radio range of the Control Panel.
POSITIONING THE PIR MOVEMENT
DETECTORS
The recommended position for a PIR Movement
Detector is in the corner of a room mounted at a height between 2 and 2.5m. At this height, the detector will have a maximum range of up to 12m with a field of view of 110°.
Detection Zone Pattern for PCB in position 5
The Position of the PCB inside the PIR can be set to 5
different positions to adjust the range of the detection pattern created by the PIR. Setting the PCB in position 3 will reduce the range to approximately 9m, with position 1 providing a range of approximately 6m. The recommended position setting for the PCB is in position 5.
When considering and deciding upon the mounting position for the detector the following points should be considered to ensure trouble free operation:
Do not position the detector facing a window or
where it is exposed to or facing direct sunlight. PIR Movement Detectors are not suitable for use in conservatories.
Do not position the detector where it is exposed to
draughts.
Do not position the detector directly above a heat
source, (e.g. fire, radiator, boiler, etc).
Where possible, mount the detector in the corner of
the room so that the logical path of an intruder would cut across the fan detection pattern. PIR detectors respond more effectively to movement across the device than to movement directly towards it.
Do not position the detector in a position where it is
subject to excessive vibration.
INSTALLATION
SA5 11
2m - 2.5m
23416785910
Detector Range (metres)
5m
110° 180°
10m
3m
INSTALLATION
12 SA5
Ensure that the position selected for the PIR
detector is within effective range of the Control Panel, (refer to "Testing the Control Panel & Remote Control").
Note: When the system is Armed, pets should not be
allowed into an area protected by a PIR Detector as their movement would trigger the PIR and trigger an alarm.
Note: DO NOT fix the detector to metalwork or locate
the unit within 1m of metalwork (i.e. radiators, water pipes, etc) as this could affect the radio range of the Device.
INSTALLING AND CONFIGURING THE
PIR MOVEMENT DETECTORS
Ensure that the system is in Test mode, (see page 15).
1. Undo and remove the fixing screw from the
bottom edge of the PIR. Carefully pull the bottom edge of the detector away from the rear cover and then slide down to release the top clips.
2. Carefully drill out the required mounting holes in the rear cover using a 3mm drill according to whether the unit is being mounted in a corner or against a flat wall.
3. Using the rear cover as a template, mark the positions of the fixing holes on the wall.
4. Fix the rear cover to the wall using the two 18mm No.4 screws and 25mm wall plugs, (a 5mm hole will be required for the wall plugs). Do not over­tighten the fixing screws as this may distort or damage the cover.
Note: The wall plugs supplied with the product
are not suitable for plasterboard walls, if mounting
the Detector Panel onto plasterboard use appropriate wall plugs.
5. Configure the House Code for the PIR Detector by setting DIP switches 1-8 of SW2 to the same ON/OFF combination as the House Code DIP switches in all other system devices.
6. Configure the alarm zone which the detector will operate on by setting DIP switches 1-3 of SW3 as follows:
DIP 1 DIP 2 DIP 3 Zone 1 OFF OFF OFF Zone 2 OFF OFF ON Zone 3 OFF ON OFF Zone 4 OFF ON ON Zone 5 ON OFF OFF Zone 6 ON OFF ON
e.g. To configure the detector to operate on Zone 3 set DIP switches 1, 2 and 3 of SW3 as follows:
7. DIP 4 of SW3 is used to configure the PIR Detector for walk test mode, which allows the operation of the detector to be checked during installation without triggering a Full Alarm.
ON Walk Test mode OFF Normal operation
Note: On initial installation the detector should be
configured into Walk-Test mode ready for testing.
8. To select the required sensitivity, set DIP 5 of SW3 as follows:
ON HIGH Sensitivity OFF LOW Sensitivity
Note: The recommended setting is HIGH.
However, in cases of extreme environmental problems or if unexplained false alarms are experienced, it may be necessary to set the sensitivity to LOW. Setting the device to LOW sensitivity will require a greater amount of movement in order to trigger the device.
9. Connect the PP3 Alkaline battery to the battery clip. The LED behind the lens will rapidly flash for approximately 2-3 minutes until the PIR has
Mounting
Hole
Positions
Fixing Screw
Rear Cover
ON
1 2 3 4 5
INSTALLATION
SA5 13
stabilised. The LED will then stop flashing and turn OFF.
Note: If the device is configured in Walk Test
mode (i.e. DIP 4 of SW3 ON) then the LED will flash upon detection of movement after the warm up period has expired.
10. Check that the detector PCB is located and set in the correct position to give the detection zone pattern required.
To adjust the PCB position simply slide it up or down ensuring that the location legs are aligned with the required position number marked on the board.
PCB Position Detection Range
16m 39m 5 12m
11. Refit the PIR detector to the rear cover by offering the detector up to the rear cover and locate the clips in the top edge into the rear cover. Push the lower edge of the detector into place and refit the fixing screw in the bottom edge of the PIR to secure in position. Do not over-tighten the fixing screws as this may damage the casing.
TESTING THE PIR MOVEMENT
DETECTORS
Ensure that the system is in Test mode, (see page 17).
Ensure that the PIR is configured in Walk Test mode, (i.e.
DIP 4 of SW3 ON) and mounted in position on the wall.
Allow 2-3 minutes for the detector to stabilise before commencing testing.
1. Use the and buttons to scroll through the menu until ‘WALK TEST’ is displayed and
press .
‘Walk Test Waiting…’ will be displayed.
2. Walk into and move slowly around the protected area, each time the detector senses movement the LED behind the lens will flash. In addition, the Control Panel will beep to indicate that the alarm signal has been received and the identity of the zone that the detector is configured for will be displayed.
If necessary adjust the detection range by changing the mounting position of the PCB within the PIR housing.
Note: In normal operation, the LED behind the
PIR lens will not flash on movement detection, (unless the battery is low).
3.
Remove the back cover of the PIR detector. The Control panel should beep and display "Accessory Tamper" to show that the detector's tamper switch has been activated.
4.
Press to return to the top level menu of TEST MODE.
5. Reconfigure the PIR Detector for Normal operation mode by setting DIP4 of SW3 to OFF and refit in position.
Note: When the detector is fully installed i.e. battery
cover is refitted, to conserve power and maximise battery life the PIR detector will only detect movement if there has been no movement detected within the previous 2 minutes.
Dip Switches
(SW2 and SW3)
PCB Board
(slides up and down to adjust position)
5 4 3 2 1
PCB Position Indicator
(positions 1-5)
O
N
1
2
3
4
5
6
7
8
O
N
1
2
3
4
5
S
W
3
S
W
2
ENTER
ESC
Loading...
+ 33 hidden pages