FRIEDLAND SA3 PLUS Installation & Operating Manual

ZONE 1
1423
56
78
0
ENTER
ESC
ZONE 2 ZONE 3 ZONE 4
TAMPERFIREZONE 6ZONE 5
POWER PART ARM ARM LOW BATT.
9
!
SA3 PLUS
with Telephone Dialler
Installation & Operating Manual
FOREWORD
This Wirefree Alarm System has been designed to meet with the requirements of BS6799 Class 1 for Wireless Alarms. All components are designed and manufactured to provide a high standard of security protection and long, reliable service. No radio operating licence is required for this equipment. The approved radio frequency is not protected from interference, this frequency may also be used by other systems and equipment. The radio devices in this system have been tested by an independent accredited test laboratory for conformity with the R&TTE Directive for radio equipment.
The system is designed for ease of installation using only conventional domestic tools. However, it is essential that the installer reads and fully understands the advice and procedures contained in this manual and plans the system before proceeding with the installation.
During installation, it is important that the procedures described in this manual are followed in sequence.
This manual should be retained in a safe place for future reference.
IMPORTANT
All components, with the exception of the External Solar Siren are suitable for mounting in dry interior locations only.
Tools and Equipment Required:
No.0 Philips Screwdriver No.1 Philips Screwdriver No.2 Philips Screwdriver 5 & 6mm Masonry Drill Bits Drill Small Spirit Level Bradawl
LOCAL AUTHORITY REGULATIONS
Depending on your location within the country, you may be required, by law, to notify the Local Authorities and Police of your new alarm installation.
Local Authority requirements differ from area to area, therefore, we recommend that you contact your Local Borough Environmental Officer to obtain full details of your area's requirements.
SYSTEM SECURITY
This system has been designed to both detect intruders and act as a strong deterrent to would-be intruders when installed correctly.
Please remember that given adequate knowledge and time it is possible to overcome any alarm system and we therefore recommend that an Intruder Alarm is used in conjunction with good physical protection such as security window and door locks.
All units in the system are encoded to operate together using an 8 bit House Code which is configured by the user/installer to provide the unique identification code for your installation. The system House Code can be changed at any time by the user.
IMPORTANT: All units forming part of your alarm system must be set to the same House Code.
The system is operated from the Control Panel or one or more Remote Control units (available as an upgrade accessory). Care should be taken to ensure that the User Access code for the Control Panel does not become known to other people or any Remote Control Unit(s) are not lost, as this will compromise the security of your system. In either event the system house code and User Access code should be changed as soon as possible.
SAFETY
Always follow the manufacturers advice when using power tools; steps, ladders etc. and wear suitable protective equipment (e.g. safety goggles) when drilling holes etc.
Before drilling holes in walls, check for hidden electricity cables and water pipes, the use of a cable/pipe locater maybe advisable if in doubt.
When using ladders, ensure that they are positioned on a firm stable surface at the correct angle and suitably secured before use.
The use of ear defenders is advisable when working in close proximity to the Siren due to the high sound level produced by this device.
CONTENTS
KIT CONTENTS 2
INTRODUCTION AND OVERVIEW
3
System Arming
3 Entry/Exit Delay 3 Zones 3 Zone Lockout 3 Voice Dialler 3 Tamper Protection 4 Jamming Detection 4 Battery Monitoring 4 System House Code 4
PLANNING AND EXTENDING YOUR WIREFREE SOLAR ALARM SYSTEM 5
REMOTE CONTROL 6
General Information 6 Configuring the Remote Contro 6
CONTROL PANEL 7
Positioning the Control Panel 7 Installing the Control Panel 7 Configuring the Control Panel 9 Testing the Control Panel & Remote Control 9
PASSIVE INFRA-RED (PIR) MOVEMENT DETECTORS 10
Positioning the PIR Movement Detectors 10 Installing and Configuring the PIR Movement Detectors 11 Testing the PIR Movement Detectors 12
MAGNETIC CONTACT DETECTORS 12
(Optional Accessory)
Positioning the Magnetic Contact Detectors 13 Installing and Configuring the Magnetic Contact Detectors 13 Testing the Magnetic Contact Detectors 14
EXTERNAL SOLAR SIREN 15
General Information 15 Positioning the Solar Siren 15 Installing and Configuring the Solar Siren 16 Power-up of the Solar Siren 17 Testing the Solar Siren 17
EXTERNAL CONNECTIONS 18
TESTING THE SYSTEM 18
Initial Testing 18 Testing An Installed System 18 Detector Test 18 Hard-Wired Siren Test 19 Siren Test 19 Control Panel LED Test 19 Solar Siren Service Mode 19 Voice Dialler Test 19
FACTORY DEFAULTS 19
Reset Factory Default Conditions 19
PROGRAMMING 20
User Access Code 20 System House Code 20 Instant/Delay Zones 21 Entry/Exit Delay 21 Alarm Duration 21 Part-Arm 21 Zone Lockout 22 Entry/Exit Warning Tone 22 Jamming Detection 22 Hardwired Siren 22 Zone Operating Modes 22 Phone Numbers 23 Alarm Message Play Time 23 Record Alarm Message 24 Replay Alarm Message 24 Call Routing 24 Call Attempts 24 Dial Method 24
OPERATING INSTRUCTIONS 25
Arming The System 25 Disarming The System 25 Personal Attack (PA) Alarm 26 Tamper 26 Siren Service Mode 26 Siren Operating Mode 27 Battery Monitoring 27
MAINTENANCE 28 ALARM RECORD 29 TROUBLE SHOOTING 30 EXTENDING YOUR ALARM SYSTEM 33 COMPONENT SPECIFICATION Back Cover
1
KIT CONTENTS
The Alarm System should contain the following components.
1xExternal Solar Siren 1x6 Zone LED Control Panel
with Telephone Dialler 3xPIR Movement Detectors 1xRemote Control
Also included:
Power Supply Adaptor Telephone Connection Lead Installation & Operating Manual Fixing pack Batteries
IMPORTANT
Please check all items are present BEFORE breaking open the packaging clamshell. No claims for missing parts will be accepted unless the clamshell is unopened and intact.
EXTENDING THE ALARM SYSTEM
The following additional accessories are available to enhance your system and provide further protection and a higher level of security where required.
Component: Product Code
Passive Infra-Red Movement Detector SA433P Magnetic Contact Detector SA433K Remote Control SA433R Remote Keypad SA433KP Additional Solar Siren SA433SS
Full details of these accessories are given on page 33.
2
ZONE 1
1423
56
78
0
ENTER
ESC
#
ZONE 2 ZONE 3 ZONE 4
TAMPERFIREZONE 6ZONE 5
POWER PART ARM ARM LOW BATT.
9
!
External Solar Siren
Control Panel
Remote
Control
PIR Movement
Detector
SYSTEM ARMING
The system has a full ‘Arm’ and a ‘Part-Arm’ mode. Full ARM will arm all zones while the ‘Part-Arm’ mode will only arm the zones that are enabled for ‘Part-Arm’.
For example:
The system could be configured such that during night time, ‘Part-Arm’ would arm only zones protecting the lower floor and outbuildings, leaving the upper floor free for movement without triggering the alarm.
However, when the property is left un-occupied, the full ‘Arm’ mode will arm all zones to protect the entire property, (i.e. upper and lower floors and outbuildings).
ZONES
The system incorporates 6 wirefree Alarm Zones for the connection of the system detectors that are used to independently monitor different areas of the property. In addition to standard intruder protection, each zone may also be configured to operate in one of three other modes:
- ‘Personal Attack’ mode provides 24 hour monitoring
of any Personal Attack (PA) switches incorporated into the system.
- ‘24-hour Intruder’ mode provides 24 hour intruder
protection for areas where continuous monitoring is required, (e.g. gun cupboards).
- ‘Fire’ mode provides 24 hour monitoring of any
Fire/Smoke detectors incorporated into the system.
ENTRY/EXIT DELAY
Each zone can be programmed to be Armed in either Instant or Delay mode.
Usually the zone covering the main entrance door and the route to and from the Control Panel would be configured in Delay mode. This allows time for the user to exit the property after setting the system at the Control Panel or to Disarm the system before an alarm condition is triggered when re-entering the property. The remaining zones would be configured as Instant allowing them to initiate an alarm immediately a detector on the zone is triggered.
Delay Armed zones will not become fully armed until after the Entry/Exit delay period has expired. When a detector on a Delay Armed zone is triggered, an alarm condition will not be triggered until after the Entry/Exit period has elapsed. If the system is not disarmed during the delay period, an alarm condition will occur when the delay period expires.
Instant Armed zones are immediately able to initiate an alarm as soon as the system begins to arm.
ZONE LOCKOUT
If a detector on an active zone is triggered while the system is armed, an alarm condition will occur. After the programmed alarm duration has expired the alarm will stop and the system will automatically reset. Subsequent detectors triggered will again initiate an alarm condition. If a single zone initiates an alarm condition three times then that zone will be ‘Locked Out’ and any further alarm signals from that zone will be ignored until the system is disarmed.
Note: The ‘Zone Lockout’ feature can be disabled if required.
VOICE DIALLER
This system incorporates a telephone voice dialer which is used to call for help and/or notify the user that the system has been triggered and an alarm has occurred.
If the Voice Dialer is enabled and an alarm condition occurs, the system will call for help using your recorded alarm message and up to four telephone numbers. When the telephone voice dialer is activated it will call the first enabled number in the dialing sequence and replay the recorded alarm messages for the configured ‘Play Time’. The recipient must acknowledge the message by pressing the button on their telephone keypad. If the call is unanswered or an acknowledgment signal is not received then the next active number in the dialing sequence will be called. The dialer will continue calling each number in turn until either all numbers in the sequence have been dialed the set number of times or the dialing sequence is cancelled by an acknowledged signal from the recipient.
INTRODUCTION AND OVERVIEW
3
TAMPER PROTECTION
All system devices (except any Remote Control Units) incorporate Tamper protection features to protect against unauthorised attempts to interfere with the device. Any attempt to remove the battery cover from any device (except a Remote Control) or to remove the Solar Siren or Control Panel from the wall will initiate an alarm condition (unless the system is in Test or Programming modes), even if the system is Disarmed.
JAMMING DETECTION
In order to detect any attempts to illegally jam the radio channel used by your alarm system, a special jamming detection function is incorporated into the Control Panel and Solar Siren. If this feature is enabled, and the radio channel is jammed continuously for 30 seconds, when the system is armed, the Solar Siren will emit a pre-alarm series of rapid bleeps for 5 seconds. If the jamming continues for a further 10 seconds or more a full alarm condition will occur. In addition if the system is jammed for more than three periods of 10 seconds in a 5 minute interval, this will also generate a Full Alarm condition. The jamming detection features in the Control Panel and Solar Siren operate independently.
The Jamming Detection circuit is designed to permanently scan for jamming signals. However, it is possible that it may detect other local radio interference operating legally or illegally on the same frequency. If it is planned to operate the jamming detection feature we recommend that the system is monitored for false jamming alarms for at least 2 weeks prior to leaving the Jamming Detection function permanently enabled.
BATTERY MONITORING
In addition to the battery monitor and low-battery indicators in each device, the Control Panel will also indicate a low battery status within any Passive Infra­Red or Magnetic Contact Detector on the system.
SYSTEM HOUSE CODE
In order to prevent any unauthorised attempt to operate or disarm your system, you must configure your system to accept radio signals only from your own system devices. This is done by setting a series of eight miniature (DIP) switches in all devices (except the
Control Panel) to the same ON/OFF combination (the House Code) selected by the user/installer. The Control Panel is then programmed to operate only with devices set to this House Code. All detectors and Remote Control Unit(s) must be configured with the same House Code in order for the system to operate correctly.
Inside the Siren, Detectors and Remote Control Unit is a series of 8 DIP switches.
The House Code is set up by moving each of the 8 switches in each device to the same randomly selected ON/OFF sequence. When setting the DIP switches, ensure that each switch ‘clicks’ fully into position. Use the tip of a ballpoint pen or a small screwdriver to move each switch in turn.
Note: It is recommended that the system House Code is always reset to a code other than the factory default.
4
e.g.
Switch 1 set to the ON position
The following example below shows a typical property incorporating the suggested positions for the External Siren, Control Panel, PIR and Magnetic Detectors for
optimum security. Use this as a guide for your installation in conjunction with the recommendations contained in this manual for planning your intruder alarm system.
Before attempting to install your Alarm System it is important to study your security requirements and plan your installation.
The alarm system may be extended to provide even greater protection by fitting additional PlR Movement Detectors and Magnetic Contact Detectors as required.
PLANNING AND EXTENDING YOUR WIREFREE ALARM SYSTEM
LED Control Panel
Magnetic Contact Detector
Magnetic Contact Detector
External Solar Siren
PIR Movement
Detector
PIR Movement
Detector
Remote Control
SHED
LOUNGE
GROUND FLOOR
GARAGE
KITCHEN
HALL
DINNING
ROOM
PIR Movement Detector
PIR Movement Detector
PIR Movemen
t
Detector
Back Door
ZONE 1
1423
56
78
0
ENTER
ESC
#
ZONE 2 ZONE 3 ZONE 4
TAMPERFIREZONE 6ZONE 5
POWER PART ARM ARM LOW BATT.
9
!
5
*
*
*
Magnetic Contact Detectors available as optional accessories
6
The Remote Control Unit(s) are used to Arm, Part-Arm and Disarm the system.
The Remote Control Unit also incorporates a Personal Attack (PA) switch. Activating the PA switch on the side of the Remote Control will immediately trigger an alarm (unless the Control Panel is in Test or Program Modes) even if the system is disarmed. The alarm can be cancelled by pressing the ’DISARM’ button on the Remote Control or via the Control Panel.
Any number of Remote Control Units can be used with your system, providing they are all coded with the system House Code (DIP switch settings).
The Remote Control is powered by a CR2032 type Lithium cell which under normal conditions will have an expected life in excess of 1 year. Under normal battery conditions the LED on the Remote Control will only illuminate when a button is pressed. However, under low-battery conditions this LED will continue to flash after the button has been released. When this occurs the battery should be replaced as soon as possible.
CONFIGURING THE REMOTE CONTROL
1.
Remove the rear cover by undoing the small screw on the rear of the Remote Control and keeping it safe for later.
2.
Select and record (in the Alarm Record section of this manual) a random combination of ‘ON’ and ‘OFF’ positions for the DIP switches. This will become the system House Code that enables all devices to communicate with the Control Panel.
IMPORTANT:
The House Code for your system
should be changed from the factory default setting.
3.
Ensure that the Jumper Link located immediately below the House Code DIP switches is fitted in position for use with this alarm system.
4.
Insert the battery under the clip ensuring that the
+ terminal faces upwards away from the Circuit
Board.
5. Replace the rear cover and fixing screw. Do not over tighten the screw as this could damage the thread.
Testing the Remote Control:
6. Press the button. The Transmit LED should illuminate while the button is pressed and extinguish within 1 second of releasing the button.
7. Press the and buttons in turn to ensure that the Transmit LED illuminates as before.
REMOTE CONTROL UNIT
Slide up to operate
Transmit LED
Personal Attack
Arm
Part-Arm
Disarm
House Code
DIP Switches
Jumper
Link
Battery Clip
Battery
POSITIONING THE CONTROL PANEL
When choosing a suitable location for the Control Panel, the following points should be considered.
1.
The Control Panel should be located in a position out of sight of potential intruders and in a safe location, but easily accessible for system operation.
2.
The Control Panel should be mounted on a sound flat surface to ensure that the rear tamper switch on the Control Panel is closed when the Panel is mounted. The Control Panel should be mounted at a convenient height of between 1.5 and 2m and in a position where it will be seen each day.
Note: If small children are in the household, a further consideration should be given to keeping the units out of their reach.
3.
It is recommended that the Control Panel should be positioned such that the Exit/Entry tone (emitted by the Control Panel) can be heard from outside the property.
4.
The Control Panel should be mounted within a protected area so that any intruder cannot reach the Control Panel without opening a protected door or passing through an area protected by a PIR movement detector when the system is armed.
5.
The Control Panel must be located within reach of a mains socket.
6.
If the telephone voice dialler is to be used then the Control Panel will need connecting to a convenient telephone point.
7.
Do not locate the Control Unit closer than 1m to any large metallic object, (e.g. mirrors, radiators, etc) as this may affect the radio range of the Control Panel.
INSTALLING THE CONTROL PANEL
1. Undo the two captive fixing screws on top of the panel and open the cover. The cover is hinged along the bottom edge.
2. Unclip and remove the two back-up batteries on either side of the panel.
3. Hold the Control Panel in position on the wall and mark the positions of the four fixing holes. Remove the Panel and drill four 5mm holes and fit the 25mm Wall Plugs.
Note: The wall plugs supplied with the product are not suitable for plasterboard walls, if mounting the Control Panel onto plasterboard use proprietary wall plugs.
CONTROL PANEL
ZONE 1
1423
56
78
0
ENTER
ESC
#
ZONE 2 ZONE 3 ZONE 4
TAMPERFIREZONE 6ZONE 5
POWER PART ARM ARM LOW BATT.
9
!
Zone LEDs
Status LEDs
Keypad
Outside View of Control Panel
7
IMPORTANT: Do not drill the fixing holes with the Control Panel in position; as the resulting dust and vibration may damage the Control Panel’s internal components and invalidate the guarantee.
4. Fit two 18mm No.4 screws into the top holes until almost fully home and hang the Control panel over these screws using the two keyhole slots in the top corners of the panel casing.
5. Route the cable from the Power Supply Unit up behind and on the right hand side of the Control Panel and connect the plug to the DC power socket in the panel. Ensuring that the cable is not trapped between the panel and the wall.
6. Fix the Panel to the wall using two 18mm No.4 screws in the lower two fixing holes in the panel and tighten the upper fixing screws until they just grip the casing. Do not over tighten the fixing screws as this could damage or distort the casing.
7. Ensure that the "Reset" and the "Hard-Wired Siren tamper detect" jumper links are set in the OFF position.
8. Connect battery leads to both back-up batteries and refit batteries.
Battery 1 (left): Red lead to +ve battery terminal
Blue lead to –ve battery terminal
Battery 2 (right): Blue lead to +ve battery terminal
Black lead to –ve battery terminal
IMPORTANT: Take care when connecting battery leads to the batteries as connecting incorrectly could damage the batteries or the Control Panel.
Note: The Power LED may flash to indicate that the unit is being operated from the back-up batteries and that mains supply is not present.
9. Close the lid of the Control Panel and tighten the captive fixing screws.
10.
Plug in and switch ON the Power Supply Unit, (the Power LED should illuminate).
11.
If required, connect the Control Panel to the telephone line using the cable supplied by inserting small RJ11 plug into socket marked LINE located on the bottom edge of the Control Panel.
TAMP GND B+ GND N.C. C N.O. GND V+ OUT GND
Upper Keyhole Fixing Hole
-
ve Terminal
(Black Lead)
+ve Terminal (Blue Lead)
Reset Jumper Link P1
Power Supply Jack Socket
Upper Keyhole
Fixing Hole
+ve Terminal
(Red Lead)
-
ve Terminal (Blue Lead)
Lower Fixing
Hole
External Tamper
Switch Jumper
Link P51
Power Supply Cable Access Hole
Inside View of Control Panel
8
Connect the BT plug on the other end of the lead to an appropriate telephone outlet.
If the cable supplied is not long enough to reach a suitable phone point then it will need extending using a coupler and extension lead (not supplied).
Note: If the Panel Tamper alarm sounds during the installation reset the alarm by pressing:
, ,
on the Control Panel Keypad.
CONFIGURING THE CONTROL PANEL HOUSE CODE
With unit in Standby mode (Power LED only illuminated).
1. Press
, ,
The Control Panel will beep twice and the Arm and Part-Arm LEDs will illuminate. All Zone, Fire and Tamper LEDS will flash.
This puts the Control Panel into programming mode.
2. Press ,
The Zone LEDs 1-6, Fire and Tamper LEDs will illuminate to indicate the current House Code setting with an illuminated LED indicating a setting of "1" in the House Code and LEDs which are OFF indicating a "0".
For Example: A house code of 11110010, will be indicated with zone LEDs 1-4 ON and 5-6 OFF, Fire LED ON and Tamper LED OFF.
3.
The system House Code can be programmed either directly at the Control Panel or via a Remote Control Unit:
At the Control Panel:
a) By pressing buttons 1-8 on the Control Panel,
configure the status LEDs so that they indicate the required house code setting. The LEDs will switch to the opposite state each time the button is pressed.
LED ON = 1, (House Code DIP Switch On/Up) LED OFF = 0, (House Code DIP Switch
Off/Down)
b) Press to save the new setting and return
to programming mode.
c) Press to return to programming mode
without saving.
Using a Remote Control Unit:
a)
With the required House Code already configured, press the button on the Remote Control.
The Control Panel will beep twice to acknowledge the signal.
The Zone, Fire and Tamper LED status will be updated to correspond with the House Code set on the Remote Control and now programmed into the Control Panel.
b) Press to return to programming mode.
4. Press to exit programming mode and return to Standby.
5. Press , ,
The Control Panel will beep and the Arm and Part-Arm LEDs will flash.
This puts the Control Panel into test mode
TESTING THE CONTROL PANEL & REMOTE CONTROL
1. Arm the Panel by pressing the button on the Remote Control.
The Zone LED will illuminate for a few seconds to indicate which zones are being armed. As the entry/ exit delay expires the Control Panel will slowly beep and the Arm LED will flash. Towards the end of the delay the beep rate will increase. When the entry/exit delay is completed the beeping will stop and the Arm LED will stop flashing and be constantly illuminated.
2. Disarm the system by pressing the button on the Remote Control.
The Panel will beep twice and the Arm LED will turn OFF.
3. Activate the Personal Attack switch on the Remote Control.
1
2 3
4
ENTER
1
2 3
4
ENTER
ENTER
ESC
1
2 3
4
ENTER
ENTER
ESC
2
9
Loading...
+ 25 hidden pages