SIRe Advanced Fan Heater Electric
28
GB
Operating modes
Operating modes (without mixing cabinet)
Control is based on the three operating
modes:
•Thermostat/Manualfan
•Thermostat/Automaticfan
•Manual
Thermostat / Manual fan
The thermostat just controls the heating and
the fan runs continually. The fan speed is set
manually. The fan symbol is marked in the
status window, select desired speed with the
rotary dial and confirm. (High speed limit is
step 4 for SE06-15 and step 2 for SE20/30).
When the setpoint value is fallen below by
0.5 K the first heating step is engaged , if the
temperature falls further the next heating step
is engaged, etc. (SE06-15, 20 has 2 heating
steps, SE30 has 3 heating steps).
The difference between the set point value
and the room temperature that controls the
engagement of the Heating step is set under
Heating step diff., see Installer menu > Settings heating > Heating step diff.
Thermostat / Automatic fan
The thermostat controls both the heating and
the fan. The fan speed is set manually in the
status window.
Manual
The fan speed and heating is set manually in
the status window. The heating can be set to 2
or 3 steps. Heating is blocked by the outdoor
temperature, see: [Installer menu > Settings
heating > Outdoor temp. limit]
Operating modes (with mixing cabinet)
The control is based on two operating modes:
Thermostat / Manual fan
Manual
Thermostat / Manual fan
The thermostat just controls the heating and
the fan runs continually. The fan speed is set
manually. The fan symbol is marked in the
status window, select desired speed with the
rotary dial and confirm.
Day mode
In day mode or if no week program is
activated, the fan runs continuously at the
fixed fan control and the damper is open
according to the setting under Day damper
pos.. The heating is controlled in steps via the
room temperature. If the inflow temperature
drops below the set minimum value, heat
connects even if it is sufficiently warm in the
premises.
Night mode
Night time (when the week program is
activated or via external signal for night
reduction) the damper is fully closed or open
according to the setting under Night damper
pos.. The fan is controlled by the room
temperature and the heating is controlled in
steps. When the desired temperature in the
premises has been reached, the fan switches
off and the damper is closed.
Manual
The fan speed and heating is set manually in
the status window. The heating can be set to 2
or 3 steps. Heating is blocked by the outdoor
temperature, see: [Installer menu > Settings
heating > Outdoor temp. limit]