Frico HP-300, HP-304, HP-305, HP-604, HP-605 Assembly And Operating Instructions Manual

...
Thermocassette
HP
SE
NO
... 4
... 6
GB
DE
... 8
... 10
2
3
Assembly and operating instructions Thermocassette HP-300/304/305/600/604/605
Area of use
The heating panel is intended for the heating of rooms requiring free walls. The panel can be used
for complete heating, or as an additional heater (e.g. over a reception desk or other work place.) There are two ratings: 300 W(593x593x30 mm) and 600 W(1193x593x30 mm). The heating panel provides mainly radiation heating. This implies that to obtain the same experienced temperature it is possible to reduce the air temperature in the room, which saves
energy. Because of the low surface temperature, max 100°C, the heating panel is suitable for rooms with relatively low ceiling height. Thanks to the location, the panel is protected from any physical contact or damage. There is no risk of being burned.
Design
The heating panels are available for 230 and 400 V, which are approved by SEMKO in three versions:
1 . Ceiling model in standard version (IP20).
See fig. 1.
Intended as lay-in panel fpr exposed grid. The 230 V version have cord and socket, which
ensures simple extended connection (max 2100 W from one wall socket. See fig. 2). The 400 V versions are delivered with a cable without plug.
2 . Universal model in splash-proof design
(IP54). See fig. 1.
Intended for other methods of mounting (can also be put in exposed grid). Approved for fire
hazard rooms. The 230 V versions have a cord (without socket). The 400 V versions are delivered with a cable without plug.
a. Screwed to ceiling with accompanying
mounting brackets.
b. Hanging in wire (with accessory
”Wire mounting kit” 74 701 90).
3 . Universal model in flush-proof design (IP55).
See fig. 1.
Identical with 2, but with better protection against water. Delivered with cable without plug.
Mounting
Integrated in ceiling (put in exposed grid). See fig. 3.
1 . Lateral distance to wall shall be at least
50 mm.
2 . Installation, which is to be preceded by an all-
pole switch, must be carried out by an authorized electrician (not applicable to versions with a cord).
3 . Place the cassette in the required ceiling
square. Minimum design height ”H” for dismounting, T-profile 32x15: 150 mm, T-profile 38x24: 200 mm. NOTE! Avoid fixing vertical bars in the T-profile where a heating panel is to be installed. The panel fills out the whole square.
4. Connect the panel.
Bracket mounting. See fig. 4.
1. Mounting height above floor shall be at least
1.8 m, and lateral distance to wall at least 50 mm. When mounting in gypsum board, make sure that the mounting brackets are anchored in the beam behind. During long-term high temperatures the strength of the board is reduced.
2 . Installation, which is to be preceded by an all-
pole switch, must be carried out by an authorized electrician (not applicable to versions with a cord).
3 . Measure, drill and screw the two loose brackets
to the ceiling. Do not tighten the screws yet. It is important that the holes come at right angles, cross measure.
4 . Hook the panel brackets to the ones on the
ceiling (only the side nearest to the connection box). Allow panel to hang vertical.
5. Connect the panel. 6 . Swing up the panel, and adjust the lateral
position of the ceiling mounted brackets.
7 . Swing down the panel and tighten the screws in
the ceiling.
8 . Swing up the panel again and hook the panel
bracket ends in the ceiling brackets. NOTE! Make sure that the brackets do not become unhooked at the other end.
9 . Secure the panel with a screw (enclosed on
delivery) at each hanging point.