Frico FCR-230 Users guide

GB
Instruction for products with software version 1.2. Read this instruction before installation and wiring
i
of the product. This product is BTL listed from
software version 1.2-1-00 (BACnet stack 3.0.4).
Consult documentation in all cases where this symbol
is used, in order to nd out the nature of the potential
hazards and any actions to be taken
INSTRUCTION
FCR-230
FCR230
Room controller for controlling fan-coil units
FCR-230 is a room controller intended for controlling fan-coil heaters/ coolers and thermal actuators or 3-point actuators. Installation is directly on the wall or on an electrical connection box. The fan can be set to one of three speeds. FCR-230 has change-over function and can be used for 2-pipe or 4-pipe systems.
For integration into a system, FCR-230 has communication via
RS485 (Modbus, BACnet or EXOline). The device can be congured
using the application Regio tool (version 1.3-1-05 or later), which can be downloaded from the Regin web site (www.regin.se).
Technical data
Supply voltage 230 V AC ±10 %, 50/60 Hz Power consumption < 3 W
Ambient temperature 0...50°C Ambient humidity Max 90 % RH Storage temperature -20...+70°C Built-in temperature sensor NTC type, range 0...50°C Inputs Refer to connection illustrations and table below Outputs Relays for fan control, 230 V AC, 3 A DO4, DO5 for actuators, Triac, 230 V AC, max. 300 mA Communication RS485: Modbus, EXOline (using automatic detection/switching) or BACnet Modbus 8 bits, 1 or 2 stop bits. Odd, even (FI) or no parity Communication speed 9600, 19200, 38400 bps (EXOline, Modbus and BACnet) or 76800 bps (BACnet only) Terminal blocks Lift type for a maximum cable area 2.1 mm Protection class IP20 Pollution degree 2 Overvoltage category 3 Material casing Polycarbonate, PC Dimensions 102 x 120 x 29 mm
2
Installation
Place the controller in a location that has a temperature representative for
the room. A suitable location is approx. 1.6 m above oor level in a place
with unobstructed air circulation. Depress the locking tab in the upper edge of the controller with a screwdriver. Carefully turn the screwdriver until the bottom plate and the electronics unit are slightly separated (see gure 1). Then use the cutout that becomes visible in the edge of the bottom plate to open the upper
edge completely (see gure 2). Do the same thing in the lower edge of the
controller.
Figure 1 Figure 2
Lift the electronics unit up from the bottom plate. The bottom plate with terminals has a number of hole combinations. Select suitable holes and fasten the bottom plate on the wall or connection box, so that the arrows on the bottom plate point upwards. Do not tighten the screws too hard!
FCR-230
Note: FCR-230 does not indicate fan breakdown or overheating of the heating coil. Therefore, all connections must be made externally. An overheating protection or similar can be used to disconnect the supply
voltage.
Disconnection
FCR-230 should be connected to a switch or circuit breaker in the building installation. This switch should be in close proximity to the controller and within easy reach of the operator, and should be marked as the disconnecting device for the equipment. Always use the circuit breaker to disconnect the controller from the mains supply during maintenance of the fan-coil and actuators.
Settings
Control modes
FCR-230 can control heating and cooling in sequence or be set to seasonal switching between heating and cooling (change-over, see below).
Change-over function
FCR-230 has an input for change-over that automatically resets the output DO4 to operate with heating or cooling function. When the con­troller is used together with a 3-position actuator, output DO5 is also
a󰀨ected by the change-over function in accordance with the above. A
sensor of type PT1000 can be connected to the input and be mounted so that it senses the temperature on the supply pipe to the coil. When the temperature exceeds 28°C, the output function is set to heating and when the temperature drops below 16°C, the output is set to cooling. As an alternative, a potential-free contact can be used. The input function can be set to NO/NC. To ensure satisfactory functioning when using a sensor, the system must have continuous primary circuit circulation. When the change­over function is not used, the input must be left disconnected. When using an electric heater and the change-over function is set to heating, the sequence of operation for FCR-230 will be heating/heat-
ing and DO5 will be activated rst.
If a change-over sensor is not connected, the sequence will be heat­ing/heating. If cooling is to be used in the sequence, parameter 2 (change-over mode) must be changed manually.
Operating mode
There are four di󰀨erent operating modes. Switching between these
modes is performed locally. Comfort: is shown in the display. Heating and cooling have a smaller neutral zone NZC. An occupancy detector can be connected to the DI in order to select between Comfort and Economy. Switching
between Comfort/Economy and O󰀨 can also be done via the On/O󰀨
button. Comfort/Economy is selected via the parameter list.
1
Economy (Standby): “Standby” is shown in the display. The heat­ing and cooling setpoints are freely adjustable. Factory settings: heating=15°C, cooling=30°C. O: The controller does not heat or cool and the fan stops (unless mould protection has been selected or the cool-down function for the electric heater is running, in which case the fan will still run). Window: is shown in the display, the controller is o󰀨 and the fan stops (unless mould protection has been selected or the cool-down function for the electric heater is running, in which case the fan will still run). The window contact is connected to the DI and must be
congured.
Occupancy detection
Parameter 3 determines if the DI is window contact input or occupancy detection input. An occupancy detector can be connected to the DI in order to switch between Comfort and Economy mode.
Setpoint
The setpoint is set using the INCREASE and DECREASE buttons. Parameter 24 determines what is shown in the display. Refer to the parameter list for details.
Setpoint limitation
In parameters 34 and 35, it is possible to set the maximum allowed setpoint increase and decrease respectively. Example: If P35=5 and P34=3, the setpoint can be changed between 17°C and 25°C (see the picture below). The basic setpoint can be changed in parameter 64 (factory setting=22°C).
Figure 3: Example of setpoint limitation
Fan control
The fan can be controlled via FCR-230 with the following modes: Low speed, Medium speed, High speed, Auto. The current fan speed in the Auto mode depends on the heating or cooling demand and the settings for each speed. When using automatic control, ”AUTO” is shown in the display. The number of fan speed steps can be selected via parameter 30.
If the parameter is set to 1, the rst fan speed step will be used for fan
control. Via parameter 31, it is possible to set the fan to the lowest speed level when Auto mode is selected. If this parameter is set to 1, the fan will run
in all operating modes except O󰀨 and Window (unless mould protection is
active or the cool-down function for the electric heater is running, in which case the fan will run in these modes as well).
Manual control of the fan speed
By pressing the fan button, you change the fan speed according to the sequence IàIIàIIIàAUTO. When using manual control, ”MAN” is shown in the display.
If the fan has been congured not to be a󰀨ected by the heating or cooling
demand, ”AUTO” will not be shown when pressing the fan button.
Indications
The display has the following indications: HEAT Heating control COOL Cooling control
The open window symbol is shown if this function has
been congured and a window is open.
OFF The controller does not heat or cool
On/O󰀨 button
By pressing the On/O󰀨 button, FCR-230 will switch between O󰀨 mode
and Comfort/Economy mode.
Parameter list
When the controller is in Comfort mode or Window mode, di󰀨erent param­eter values can be set in a parameter list. Hold the INCREASE and DECREASE buttons depressed simultaneously for about 5 seconds until the Service symbol is displayed and then press the INCREASE button twice. First the display will show parameter 1. Use the INCREASE and DE-
CREASE buttons to scroll between the parameters and press the On/O󰀨
button to select the desired parameter. The parameter number will then be replaced by the parameter value. The value can be changed using the INCREASE and DECREASE buttons. If a button is held depressed the
value will start scrolling, rst slowly and then with increasing speed.
To exit the parameter list and go back to the basic display, press the IN­CREASE button until “EXIT” is shown (one step before parameter 1) and
press the On/O󰀨 button. You can also exit the parameter list by pressing
down the INCREASE and DECREASE buttons simultaneously.
Parameters
The following parameters can be changed in the parameter list.
Nº = parameter number FS = factory setting NO = normally open NC = normally closed
Description FS
1 Control mode:
2=2-pipe system 3=4-pipe system 4=(Electric heater) N/A
2 Change-over mode:
0=Heating control, 1=Cooling control, 2=Automatic change-over depending on analogue temperature sensor or digital input
3 Operating mode when activating digital input 1,
terminal 40/41: 0=Economy mode (occupancy detector)
1=O󰀨 mode (window contact)
4 Mould protection:
0=Not active 1=Active (fan never stops)
5 Neutral zone at Comfort mode (NZC). If the neu-
tral zone is 2 K, the heating setpoint is equal to the setpoint minus 1 and the cooling setpoint is equal
to the setpoint plus 1. 6 Heating setpoint when unoccupied 15°C 7 Cooling setpoint when unoccupied 30°C 8 P-band for the room controller 10 K 9 I-time for the room controller 300 s 10 Not used for this model 11 Switch o󰀨 timer for Comfort mode 0 min 12 Switch on delay for Comfort mode 0 min 13 Sensor connected to AI1, terminal 42/43:
0=Internal sensor, 1=External room sensor 14 Sensor connected to UI1, terminal 43/44:
0=None, 1=Change-over digital, 2=Change-over
analogue 15 Type of digital actuator:
0=Thermal, 1=3-point 16-17Not used for this model
3
0
0
0
0 K
0
0
0
FCR-230
2
Loading...
+ 3 hidden pages