Friax MPC Genesis Series, MPCA 20 Genesis, MPCA 20 C Genesis, MPC Vintage Series, MPCA 20 Vintage Installation Manual

...
R
®
INDUSTRIE France
Installation Manual
MPC Genesis - Vintage
GB-NT-MPCA-0218
Les caractéristiques données dans cette fiche technique peuvent évoluer sans avis préalable, avec les améliorations que "FRIAX Industrie" entend toujours apporter à sa production.
Contents of the package
MPCA
Genesis - Vintage
Thank you for choosing a FRIAX's Monobloc system to control the aging of your wine. Take the me to read this manual. It will help you understand the steps to install and adjust the MPC series.
What is a cellar Monobloc system FRIAX ? The MPC serie is a refrigeraon system specially designed to keep the opmum temperature and humidity at the aging of your wines. The system is composed of three essenals elements which are the evaporator, the condenser unit and the regulaon box. These elements are interconnected by a refrigerant pipe and an electrical connecon.
At the delivery, you must find in your package, your Monobloc, the installaon manual and the accessories describde on page 3. Check package to detect any damage on the carton. Note on the delivery of the carrier all the observaons about the package condion, this could be useful in case of damage. If in doubt contact your dealer. When unpacking check that the material inside the package corresponds to the checklist on the box.
Safety
MPCA
Genesis - Vintage
-Be sure to install the unit in a sheltered place.
-It is advisable to remove the device from its packaging with the help of someone.
-Connect the power supply once the enƟre installaƟon is complete.
Emballage
MPCA
Genesis - Vintage
O pallet dimensions: 750 mm x 490 mm x 510 mm ( P x L x H)
2
H
P
L
Données techniques
MPCA 20 MPCA 20 C
Current heaƟng mode
-
28°C 28°C
4 - 18 °C 4 - 18 °C
Airow outside
MPCA
Genesis - Vintage
Genesis & Vintage
Cooling capacity +6°C
Cooling capacity +12°C
Voltage
Current cooling mode 2,41 A
500 W 500 W
610 W
230 V - 50Hz 230 V - 50 Hz
Genesis
610 W
3,24 A
-
Power consumpƟon 230 W / 1,2 A 230 W / 1.2 A
Airow cellar side
Power cable lenght
Refrigerant
nominal outside temperature
210 m3/h
250 m3/h
1 m 1 m
R290 R290
210 m3/h
250 m3/h
Temperature seƫng range
Weight 45 kg 49 kg
Condensate evaporator tray
No
Yes
MPCA
Accessories
Monobloc FRIAX comes with
- A box with wireless remote, table stand for remote control and two baeries
- A exible drain tube Ø 16 2m length
- A bag containing screws fixing brackets on the air condioner, this leaet and a ng 20/27 for hose Ø 10 on Vintage versions
Genesis - Vintage
3
Dimensions
MPCA
Genesis - Vintage
198 75
285
260
48 42
Regulation LED + synchronization button
Evaporator air inlet
Condenseur air outlet
139
Power Supply
25
204
350
19243
Evaporator air outlet
25326
OperaƟng principal
Cellar
12°C
Evaporator
374
43
Condensor air inlet
567
Outside
28°C
Condenser
4
Installation
MPCA
Genesis - Vintage
260
23
13
5
75
285
43
90 mini
199
Position of the opening in the bottom of the cabinet
75199
285
60
26023
5
Installation
60 mini
MPCA
Genesis - Vintage
60
90
11
480 mini
567
570 between cleat
6
Installation
MPCA
Genesis - Vintage
ConnecƟon of the drain
Only units not equipped with the KBEC opon (condensate evaporaon pan kit) must be connected to a drain.
Connect the drain
Connect the drain tube (Ø 16) to the end
of the elbow with the supplied collar.
7
+
+
-
-
Wirless remote control
MPCA
Genesis - Vintage
Power supply: 2 x 1.5V (AAA) provided
The remote control could be installed in any room. Its maximum range is 100m in a completely open area. This distance could be extremly reduced by thickness of walls and the locaon of the cellar. It is possible to x directly the remote to the unit by using the screw holes on the MPC facade.
80
83
60
26
8
Wireless remote
MPCA
Genesis - Vintage
1
18
19
17
22
2
21
3
4
5
6
8
7
9
%
10
11
12
13
14
15
20
16
Navigation key
Menu key Return
1
Configuration type
2
Key lock indicator
3
Crankcase heater indicator
4
Silent indicator (
5
Heating indicator
EC fan evaporator)
-
OK
Validation key
-Red : heating mode
-Green : cooling mode
-Flashing red : Alarm
12
Radio frequency signal
13
Temperature or humidity indicator (option)
14
Battery charge level indicator
15
°C / °F or humidity (%) unit indicator
16
Speed condensor fan
+
Navigation key
Start key Stand by Stop
6
Cooling indicator
7
Condenser temperature probe
8
Humidifier indicator (
9
Cellar temperature probe
10
Parameter number
11
Setup mode
VINTAGE model
17
Speed evaporator fan
18
Time (12 AM/PM or 24 h)
19
)
existing if EC evaporator fan
20
existing if EC condenser fan
21
Minus for negatives values
22
Lighting control
9
First start
Step I - Set the cellar fan speed
MPCA
Genesis - Vintage
Access to
menu
Even if the screen is blank Press
for 6 seconds
Change the screens with
To exit the menu, press
Parameters Display Handling
Seng the speed evapora­tor fan cellar
Login with
Change the value with or
OK
-
confirm with
OK
Remarks
See below the value set according to the device
+
-For MPC 30 select the value * and conrm.
-For MPC 48 select the value * and conrm.
* For speed value, see the specic installaon instrucons when the appliance is installed outside the cave (mounng OUT) and the evaporator is ducted.
Step II - StarƟng
funcons
Start the unit with the remote control
Shorten the waing period **
Handling
Press for 2 seconds
hold
Views Remarks
or xed or ashing
or becomes xed
The unit starts.
If the icons and are ashing the unit is in standby mode.
The unit starts in heang or cooling mode. If the set is idencal to the tempe­rature of the cellar, the screen shows no opera­on.
10
** It is the preheating of the compressor crankcase heater which avoid any blow of liquid during the rst start. It is preferable to respect this period until its completion
Settings: temperature and humidity *
Step III - Set the cellar temperature and humidity
MPCA
Genesis - Vintage
Seng
Adjust the tempe­rature setpoints and humidity (Vintage Version)
Handling
Press
For 2 seconds
Change the value with or
OK
-
confirm with
Change the value with or
OK
-
+
+
Display Remarks
Displays the current value of the setpoint tempera­ture
Flashing
Displays the value of the desired setpoint tempera­ture
Flashing
Displays the current value
%
Flashing
%
Flashing
of the set point humidity (* Only on Vintage models)
Displays the value of setpoint desired humidity (* Only on Vintage models)
confirm with
* Only on Vintage models
Step IV - Stop the unit
funcons
Stop the unit with the
remote control
Restart the unit with the
remote control
Handling
Press
for 6 seconds
Resume in step II
OK
Returns to the display of measured values in the cellar
Views Remarks
Red LED on unit. The air
condioner is stopped but
the funcon of compres-
sor protecon remains
acve RC**
** If the unit remains o for a long period of time, it is better to stop it this way. This will protect the compressor when restarting
11
User menu
MPCA
Genesis - Vintage
funcons
Display the tempera­ture or humidity of the cellar
Put the fan in the cellar in silent mode
Exit silent mode
Lighng control
Lock the keypad on the remote control
Handling
Press
Press for 2 seconds
Press
Press
5 Seconds
Press
Then simultaneously on
-
-
+
Views Remarks
The display alternately shows the value of the
%
Disappearing
Flashing
Fixed
temperature and humidity (Only available on Vintage model)
The fan switches to low speed for 10 minutes
The fan returns to its normal speed
Lighng on / o
Manipulaon buons no longer possible to change the sengs
Unlock the keypad on the remote control
Pause the remote screen
Out of standby screen
Stop the machine with the remote
Press
Then simultaneously on
Press for 2 seconds
Press for 2 seconds
Press for 6 seconds
Flashing
Disappearing
Buons are accessible to change the sengs
The screen turns o aer a few seconds. The appliance connues to operate
The screen turns on and
%
displays the current values
Red LED on unit. The air condioner stopped but the compressor protecon remains acve RC (crankcase heater)
12
Start the unit with the remote control
defrost mode
Press for 2 seconds
Hold
or xed
The unit starts.
If the lights and are ashing the unit is in standby mode. Starts a manual defrost in addion to the automac defrost all 7 hours
13
User menu
MPCA
Genesis - Vintage
Access to
menu
Even if the screen is blank Press
Parameters Display Handling
Seng the me display. 12 or 24 hours
Login with
Change the value with or
-
confirm with
Login with
Change the value with or
OK
OK
OK
-
Remarks
Switches from 12 h AM / PM display on
+
24
Set hours
+
for 6 seconds
Change the screens with
To exit the menu, press
Seng the me
Seng the temperature unit
confirm with
Change the value with or
OK
-
confirm with
Login with
Change the value with or
OK
OK
-
Minute seng
+
Seng ° C / ° F
+
14
confirm with
OK
13
User menu
MPCA
Genesis - Vintage
Access to
menu
Even if the screen is blank Press
for 6 seconds
Change the screens with
To exit the menu, press
Parameters Screens Manipulations
Calibrang the temperature sensor
Calibraon of humidity probe
Login with
Change the value with or
-
confirm with
Login with
Change the value with or
OK
OK
OK
-
Seng the fan status when the setpoint is reached
confirm with
Login with
Change the value with or
-
confirm with
OK
OK
OK
Remarks
This parameter is set to 0 at the factory. It may be modied only in the case where there would be a dierence
+
between the seng tempera­ture and the real temperature of the cellar.
This parameter is set to 0 at the factory. It may be modied only in the case where there would be a gap between the moisture displayed
+
and the real humi­dity of the cellar. Only available on model Vintage
Lets venlaon at low speed when the air condioner reaches its setpoint temperatures and humidity, to have a permanent air
+
circulaon in the cellar. It is recommended to leave this seng enabled when the evaporator is ducng (version OUT).
14
15
MPCA
Alarms codes
Two types of errors may appear on the wireless remote control.
Type 1 alarm : The Green and red LED on the front panel ashes. A warning message appears on the wireless control and buon flashes when a buon is pressed. The air condioner connues to operate.
Type 2 alarm : The red LED on the front panel ashes. A warning message appears on the wireless control and buon flashes when a buon is pressed. The air condioner does not work anymore. Contact your hardware vendor
Genesis - Vintage
OK
OK
Once the problem is solved, press the Sync buon on the unit or on
Alarm code Error source
AS1c
A SL
Cellar T° sensor
A SH
A SO
AS2c A SL A SH
T° sensor + HR% cellar
(on Vintage model)
AHRH
A SO
AS3c
AS3H
Condenser T° sensor
AS3O
AVEc
AVCc
A rF
Evaporator fan
condenser fan
wireless communicaon
Genesis temperature signal lost
Lower threshold wine cellar temperature
Upper threshold wine cellar temperature
Faulty wine cellar temperature
Vintage temperature signal lost
Lower threshold wine cellar temperature
Upper threshold wine cellar temperature
Upper threshold wine cellar humidity
Faulty wine cellar temperature
Outside unit temperature signal lost
Upper threshold outside unit temperature
Faulty outside unit temperature
Faulty inside unit motor fan Faulty outside unit motor fan
Description
Radio signal lost
OK
Type of error
type 2 type 1 type 1
type 2 type 2 type 1
type 1 type 1 type 2
type 1 type 1 type 1 type 2 type 2 type 1
15
Reset
Genesis & Vintage
How to reset to factory configuraon with te remote controller
Press simultaneously
SPC
+
The reset will change the parameters to their factory value
Restart the unit With the remote
Maintenance
10 Seconds
Set the fan speed, temperature and humidity
Unit starts
Press . For 2 seconds
If symbol or ashes, unit is in stand by mode
Push
Press
unl or
become xed
OK
Maintaining your air condioner cellar
The following maintenance repeated every 6 months operaons will allow your air condio- ner MPC keep its opmal ways to ensure its longevity and your wines.
CAUTION Before any maintenance work, switch o the power supply to the main circuit breaker.
Maintenance of the condenser (hot side) Remove the front cover using an Allen wrench to access the condenser coil air. Use a vacuum cleaner to remove dust. Be careful not to damage the fins.
Maintenance of the evaporator (cold side) Remove the front cover using an Allen wrench to access the evaporator coil air. Use a vacuum cleaner to remove dust. Be careful not to damage the fins.
Remove the condensate tray with a screwdriver, clean it with water then reinstall it
16
Wiring diagram
(Example)
LN
MPCA
Genesis - Vintage
NO
COM
NC
16 A max
blue
L
GND
RC
N
Yellow
PWM1
White
Blue
GND
PWM2
TAC
EVF
CP HGR KCH EVF CDF
L
Blue
N
Black
L
LL L
NNN
Yellow
CDF
L
Blue
White
TAC2
On Vintage
model
POWER Sonde
N
Black
5 x 20
10A GT
cond
L
NN
COM
NC
AUX (light)
T°+HGR
or
L
NO
N
Solenoid valve on vintage series
Crankcase heater
Compressor
Fan
Heater
Temperature sensor
Temperature & humidity sensor on Vintage series
17
Detached pieces
4
2
1
6
3
7
5
Designation Ref. 1 Compressor 30050077 2
Remote
PR20050067 3 Control board PR20050070 4 Light switch 5
Probe °C + HRG%
PR20070008
20050002-20070035
6 Fan PR20080082
Drip tray 40010274
7
Bent hose
PR60010039
Condensate pipe 60010291
18
Manufacturer’s declaration - Compliance with standards
DECLARATION DU FABRICANT
MANUFACTURER’S CERTIFICATE
GB
-SPC-DF-0317
Directeur Général
Managing Director
Eric JACQUOT
DECLARE QUE NOTRE APPAREIL APPARTENANT A UNE DES GAMMES SUIVANTES :
DECLARES THAT THIS MACHINE BELONGING TO ONE OF THE FOLLOWING RANGES:
SPC 30 EVPL (Genesis-Vintage) - SPC 48 EVPL (Genesis-Vintage) - SPC 82 EVPL (Genesis-Vintage) ­SPC 122 EVPL (Genesis-Vintage) - SPC 170 EVPL (Genesis-Vintage) - SPC 230 EVPL (Genesis-Vintage)
SPC 30 EVG / EVI (Genesis-Vintage) - SPC 48 EVG / EVI (Genesis-Vintage) - SPC 82 EVG / EVI (Genesis-Vintage) - SPC 122 EVG / EVI (Genesis-Vintage) - SPC 170 EVG (Genesis-Vintage) - SPC 230 EVG (Genesis-Vintage)
SPC 30 EVA (Genesis-Vintage) – SPC 48 EVA (Genesis-Vintage) – SPC 82 EVA (Genesis-Vintage) – SPC 122 EVA (Genesis-Vintage)
MPC 30 (Genesis-Vintage) – MPC 48 (Genesis-Vintage) - MPCA 30 (Genesis-Vintage)
EST CONFORME:
IS IN CONFO R MITY WITH
- AUX DISPOSITIONS DES DIRECTIVES EUROPEENNES SUIVANTES ET A LEURS MODIFICATIONS :
- THE REQUIREMENTS OF THE FOLLOWING EUROPEAN MEASURES AND THEIR MODIFICATION :
2014/35/EU (Basse Tension),
2014/35/EU
2014/30/EU (Compatibilité électromagnétique),
2014/30/EU (Electromagnetic compatibility),
2014/68/EU (Equipements sous pression),
2014/68/EU (Equipements sous pression),
2011/65/EU (RohS),
2011/65/EU (RohS),
- AUX NORMES SUIVANTES :
- THE FOLLOWINGS STANDARDS :
NF C 15 100 (Installation électriques à basse tension),
NF C 15 100 (Low voltage installation),
EN 60204-1 (Equipement électrique des machines), EN 60204-1 (Electric equipment of machines),
NF EN 378-1 à 4 (Systèmes de réfrigération (…) / Exigences de sécurité et d’environnement), NF EN 378-1 to 4 (Refrigeration Systems(…) / Safety and environmental requirements),
-
AUX REGLEMENT (CE) 2037/2000 SUR LES SUBSTANCES APPAUVRISSANT LA COUCHE D’OZONE
-
THE REGULATION (EC) 2037/2000 CONCERNING OZONE LAYER DEPLETION PRODUCTS
ET QUE LE MARQUAGE A ETE APPOSE SUR LE MATERIEL.
AND THAT THE MARKING HAS BEEN AFFIXED ON UNIT
(Low Voltage),
Tel : +33 (4) 79 34 91 84 – Fax : +33 (4) 79 34 91 85 – info@friax.fr
FRIAX INDUSTRIE - RCS CHAMBERY 477 811 517
ZAC de la Prairie – F73420 VOGLANS